Fisher RPE Electric Pilot Heater Instruction Manual Manuals & Guides

Instruction Manual D103694X012
September 2018
Electric Pilot Heater
SUMMARY
Introduction ......................................................................... 1
Characteristics .................................................................... 2
Labelling ............................................................................ 2
Dimensions and Weights ................................................... 2
Installation .......................................................................... 3
Commissioning .................................................................. 4
Maintenance ...................................................................... 4
Spare Parts ........................................................................ 5
Type RPE
Declaration of Conformity ................................................... 6
WARNING
!
Failure to follow these instructions or to properly install and maintain this equipment
could result in an explosion and/or re
causing property damage and personal injury or death.
Fisher™ electric pilot heater must be installed, operated and maintained in accordance with federal, state and local codes, rules and regulations and Emerson Process Management Regulator Technologies, Inc. instructions.
If the electric pilot heater vents gas or leak develops in the system, service to the unit may be required. Failure to correct trouble could result in a hazardous condition.
Call a gas service person to service the unit.
Only qualied person must install or service
the device.
Figure 1. Type RPE
Product Description
The electric pilot heater Type RPE is used for reheating gas supplying pressure reducing regulator pilots to avoid the inconveniences caused by freezing which occurs during large pressure drops and/or low ambient temperatures.
A “regulator bottom” version exists.
The Type RPE consists of :
• An explosion-proof junction box
• A thermometer pocket containing the heating element and a probe
INTRODUCTION
Scope of the Manual
This manual provides installation, startup, maintenance and parts ordering information for the electric pilot heater Type RPE.
• A heater tube (not present on “regulator bottom” version)
• A thermostat in charge of temperature regulation
The Type RPE is in conformity with the Directive for
Equipment or protective system intended for use in
potentially explosive atmospheres 2014/34/UE.
It is classied under group II, category 2.
190
Ø 90
Ø 78
230
Type RPE
CHARACTERISTICS
Table 1. Electric Pilot Heater Type RPE Characteristics
OPERATING PRESSURE
Heater tube
Thermometer pocket
ELECTRICAL MATERIAL FOR EXPLOSIVE ATMOSPHERES
Group according to directive 2014/34/UE Group II
Category according to directive 2014/34/UE Category 2
Protection Ex db IIC T2 Gb
Certicate CML 18 ATEX 1081
Power supply 230 V 50-60 Hz
Power consumption 140 W
Recommended operating temperature 0 to 30 °C
Max. allowable admitted temperature 60 °C
RECOMMENDED THERMOSTAT SETTINGS
Selector for temperature A range 0/30
Adjustment for B setting 30
Differential selector C 2
PS 100 bar max.
Materials
Heater tube Steel
Thermometer pocket Steel
TEMPERATURE MEASUREMENT
Interchangeable thermic probe 10 kΩ
HEATER
Two interchangeable heating cartridges 280 W - 230 V
Connected in series 140 W
TEMPERATURE REGULATION RANGE
Thermostat - 30 to + 90 °C
POWER SUPPLY
Power relay
PROTECTION
Thermostat 2 A
Power relay 2 A
FLUID
st
and 2nd family according to EN437.
Gas 1
The gas must be non corrosive, clean and dry.
I max
U
2 A 250 V~
Junction box Aluminum
LABELLING
Figure 2. Electric Pilot Heater Type RPE Label
DIMENSIONS AND WEIGHTS
Heater only : 1,4 kg Heater + heating element: 4,5 kg
2
Figure 3. Electric Pilot Heater Type RPE Dimensions and Weights
P
A
B
C
2
2
4
Type RPE
INSTALLATION
Figure 4. Type RPE Electric Pilot Heater Installation
Assembly
Electrical pilot heater (with heating element)
The Type RPE is assembled with the vertical thermometer pocket axe using the xing part supplied with the regulator actuator bolt.
N
2A 2A
123456789
1 2 3
030
4
5
6
230 V 50-60 Hz
-30 0
30
90
60
10
A1 12
3
A2 34
123456
Figure 5. Assembly on Symmetrical DIN Rail
Electrical Connections
Electrical
Type
RPE box: Packing gland 3/4” NPT for cable
snap-on.
Electrical wiring: Customer (according to Figure 5)
Recommended wiring: U-1000 RVFV, according to
2
NF C32-322, type class 2.5, conductors 1,5 mm
.
Note: the electrical terminals 4 and 6 of the thermostat (key 2) must be shunted to cut off supply in the case of rupture of the thermal probe (key 5).
Note: the electrical terminals 2 and 3 of the Type RPE connector block (key 4) must be shunted so that the heating elements (key 6) are connected in series.
Note: the thermostat (key 2) and the power relay (key 3) must be protected by 2A fuses (protection against short-circuit of the heating elements).
Note: the thermostat (key 2) and the power relay (key 3) are assembled on a symmetrical DIN rail.
Regulator bottom electrical heater
The Type RPE is assembled on the regulator bottom with 4
xing screws M8 x 20.
The Type RPE can be installed in an explosive risk zone.
The thermostat and power relay must be installed in an non-explosive risk zone.
Pneumatic Connections
The Type RPE is to be installed between the pilot lter and
the pre-expansion relay.
Inlet/Outlet: 1/4” NPT - tube 8/10 (regardless of the
gas ow).
Figure 6. Type RPE Regulator Bottom Electrical Heater Installation
3
Type RPE
WARNING
!
Personal injury or equipment damage, due to bursting of pressure-containing part may result if this device is overpressured or is installed where service conditions could exceed the limits given in the Characteristics section and on the appropriate nameplate or where conditions exceed any rating of the adjacent piping or piping connections.
To avoid such injury or damage, provide pressure-relieving or pressure-limiting devices to prevent service conditions from exceeding those limits.
Also, be sure the installation is in compliance with all applicable codes and regulations.
Additionally, physical damage to the device can cause personal injury and property damage due to bursting of pressure containing parts.
To avoid such injury and damage, a possible approach could be e.g. install the device in a safe location.
All interventions on the equipment should only be performed by qualied and trained personnel.
COMMISSIONING
WARNING
!
All interventions on the equipment should only be performed by qualied and trained personnel.
Preliminary Verications
Thermostat start-up positions
• Temperature range selector (A) - 0/30 °C
• Adjustment of the temperature setting (B) - 30
• Differential selector (C) - 2
Position before commissioning
• Pilot feeding valve
Closed
Commissioning
• Pilot feeding valve
Open slowly
The equipment is commissioned.
The thermometer pocket’s axis is to be installed vertically.
A support must be used to avoid pressure force on the regulator’s body.
No modication should be made to the
structure of the equipment (drilling, grinding, soldering...).
Verify that the inlet side is protected by an appropriate device(s) to avoid exceeding the limits of utilization (PS,TS).
Verify that the limits of utilization correspond to the appropriate operation conditions.
The equipment should not receive any type of shock.
Fire, seismic and lightning are not taken into consideration in standard regulators.
If required, a special product selection
and/or specic calculations may be supplied according to specic requirement.
MAINTENANCE
WARNING
!
To avoid personal injury or property damage from sudden release of pressure, isolate the electric pilot heater Type RPE from the pressure system and release all pressure from the main valve before performing maintenance operations.
Servicing Check
Recommended frequency
• Once a year minimum.
Verication
• Probe, heating cartridges.
Replacement
The user should verify or carry out a protection adapted to the environment.
4
• In case of visible wear and/or tear in these parts, replace them.
Type RPE
Precautions Before Disassembly
• Close the pilot feeding valve.
• Bleed of the pressure from the heater tube.
• Switch off the power supply.
Disassembly
• Unscrew the junction box’s cover (key 10).
• Unscrew the M3 screw (key 9) and carefully take out the screw (key 9), the nut (key 8), the washer (key 7) and the O-ring (key 6).
• Pull out the heating cartridges (key 5) and the probe (key 4) and check for wear and/or tear.
SPARE PARTS
WARNING
!
If the Type RPE electric pilot heater was on before this operation, heating cartridges may be hot. If it is the case, wait until cool off before doing the maintenance operation.
• If a replacement is needed, unscrew the screw from the terminal block related to the element to change, take off the element and put a new one in the same terminals.
Reassembly
• Perform above operations in reverse order.
• Lightly lubricate heating cartridges before putting them back in the thermometer pocket.
1
4 5
6
7
8
9
2
3
10
Figure 7. Electric Pilot Heater Type RPE Schematic
Table 2. Type RPE Electric Pilot Heater Spare Parts
KEY DESCRIPTION QTY REFERENCE
- Type RPE+Thermostat+Relay 1 FA197519X12
2 (Figure 6) Thermostat 1 FA461328X12
- Relay 2 FA461330X12
4 (Figure 7) Probe 1 FA461363X12
5 (Figure 7) Heating cartridge 2 FA461365X12
5
Type RPE
DECLARATION OF CONFORMITY
We declare that the electrical heaters, Type RPE, are aimed to put on the market for usage in explosive atmospheres and that they apply to the following:
- articles of the directive 2014/34/UE
- norms: • EN 60079-0: 2012
• EN 60079-1: 2014
Issue 0
11 Description
Electric heater type RPE 180 985.
- The heater is to:
- Maintain a minimum temperature in the body of a regulator in ‘ zero flow’ to assist start up.
- Maintain a minimum temperature in the control circuit of a press ure regulator.
- Options:
- Electric pilot heater (with heating pot).
- Regulator bottom electric heater (without heating pot). The temperature regulation is carried out through a relay, by a pro be HAGER type EK083 and
through a multi-range thermostat HAGER type EK 186 set to max imum 60°C (or equival The thermowell of the RPE is constantly bathing in the non-flam mable gas. Around the RPE, an
explosive atmosphere may occur, when:
- Opening of a valve,
- Opening of a vent,
- Leakage at a sealed connection.
If the sensor is switched off, the heating elements are switched off. The RPE can operate in the absence of gas circulation.
The thermowell is be mounted vertically.
Rating: 230 VAC – 280 W- 50/60 Hz
The heater is fitted with a ¾ NPT flameproof cable gland.
12 Certificate history and evaluation reports
Issue Date Associated report Notes
0 06 Apr 2018 R11598A/00 Issue of prime certificate
Note: Drawings that describe the equipment or component are liste d in the Annex.
13 Conditions of manufacture
The following conditions are required of the manufacturing pr ocess for compliance with the certification.
13.1 Where the product incorporates certified parts or safety critical c omponents the manufacturer shall ensure that any changes to those parts or components do not affect the compliance of the certified product that is the subject of this certificate.
14 Special Conditions for Safe Use (Conditions of Certifica
None.
This certificate shall only be copied 2 of 2 Version: 7.0 Approval: Approved in its entirety and without change
www.CMLEx.com
CML 18ATEX11081
ent).
tion)
3 avenue Victor Hugo, CS80125 28008 CHARTRES Cedex France
II 2 G
th Article 17 of Directive
th the following
EU Type Examination Certificate CML 18ATEX1081 Issue 0
1 Equipment inten ded for use in Potentially Explosive Atmospheres Directive 2014/34/EU
2 Equipment Elect ric Heater Type RPE 180 985
3 Manufacturer FRANCEL SAS [Brand name FISHER]
4 Address Business Park
5 The equipm ent is specified in the description of this certificate and the documents to which it
refers.
6 Certification Man agement Limited, Unit 1 Newport Business Park, New Port Road, Ellesmere
Port CH65 4LZ, UK, Notified Body Number 2503, in accordance wi 2014/34/EU of the European Parliament and of the Council, dated 26 February 2014, certifies that this equipment has been found to comply with the Ess ential Health and Safety Requirements relating to the design and construction of equipm ent intended for use in potentially explosive atmospheres given in Annex II to the Direc tive.
The examination and test results are recorded in the conf idential reports listed in Section 12.
7 If an ‘X’ suff ix appears after the certificate number, it indicates that the equipment is subject to
conditions of safe use (affecting correct installation or safe use) . These are specified in Section 14.
8 This EU T ype Examination certificate relates only to the design and construction of the
specified equipment or component. Further requirements of Directive 2014/34/EU Article 13 apply to the manufacture of the equipment or component an d are separately certified.
9 Compliance with the Essential Health and Safety Requirements, with the exception of those
listed in the confidential report, has been demonstrated throug h compliance wi documents:
The equipment shall be marked with the following:
10
Ex db IIC T2 Gb
Ta = -20°C to +40°C
This certificate shall only be copied 1 of 2 H M Amos MIET in its entirety and without change Technical Manager www.CMLEx.com
Figure 8. Examination Certicates
6
Certificate Annex
Certificate Number CML 18ATEX1081
Equipment Electric heater Type RPE 180 985
Manufacturer FRANCEL SAS [Brand na me FISHER]
The following documents describe the equipment or component d efined in this certificate:
Issue 0
Drawing No Sheets
DT 028 1 to 33 0 06 Apr 2018 DOCUMENTATION TECHNIQUE
142364 1 of 1 A 06 Apr 2018 DO IGT DE GANT
142365 1 of 1 A 06 Apr 2018 MAM ELON REPRIS
ATEX-FA180985 1 of 1 -/- 06 A pr 2018 RECHAUFFEUR ELECTRIQUE
FA180985 1 of 1 BB 06 Apr 2018 RECHAUFFEUR ELECTRIQUE
D103706XFR2 1 to 4 -/- 06 Apr 2018 NOTICE T ECHNIQUE
FA142388 1 to 3 CE 06 Apr 2018 IDENTIFICATION PLAT E RPE INDEX
Rev. Approved
date
Title
Type RPE
This certificate shall only be copied 1 of 1 Version: 7.0 Approval: Approved in its entirety and without change
www.CMLEx.com
Figure 8. Examination Certicates (continue)
7
Type RPE
Webadmin.Regulators@emerson.com
Fisher.com
Facebook.com/EmersonAutomationSolutions
LinkedIn.com/company/emerson-automation-solutions
Twitter.com/emr_automation
Emerson Automation Solutions
Americas McKinney, Texas 75070 USA T +1 800 558 5853
Asia Pacic
Singapore 128461, Singapore T +65 6770 8337
+1 972 548 3574
Europe Bologna 40013, Italy T +39 051 419 0611
Francel SAS, 3 Avenue Victor Hugo,CS 80125, Chartres 28008, France SIRET 552 068 637 00057 APE 2651B, N° TVA : FR84552068637, RCS Chartres B 552 068 637, SAS capital 534 400 Euro
Middle East and Africa
Dubai, United Arab Emirates T +971 4 811 8100
D103694X012 © 2017, 2018 Emerson Process Management Regulator Technologies, Inc. All rights reserved. 09/18. The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are the property of their prospective owners. Fisher™ is a mark owned by Fisher Controls International LLC, a business of Emerson Automation Solutions.
The contents of this publication are presented for information purposes only, and while effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available on request. We reserve the right to modify or improve the
designs or specications of our products at any time without notice.
Emerson Process Management Regulator Technologies, Inc does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any Emerson Process Management Regulator Technologies, Inc. product remains solely with the purchaser.