Failure to follow these instructions or to properly install and maintain this equipment could result in an explosion, fire
and/or chemical contamination causing property damage and personal injury or death.
Jeon regulators must be installed, operated and maintained in accordance with federal, state and local codes, rules and
regulations and Emerson Process Management Regulator Technologies, Inc. instructions.
If the regulator vents gas or a leak develops in the system, service to the unit may be required. Failure to correct trouble
could result in a hazardous condition.
Installation, operation and maintenance procedures performed by unqualified personnel may result in improper
adjustment and unsafe operation. Either condition may result in equipment damage or personal injury. Call qualified
personnel when installing, operating and maintaining the RB Series regulating system.
2
2
Page 3
RB Series Regulating System
1. Introduction
RB Series (wall-mountable) regulating box can be deployed for natural gas distribution system in the residential or in the commercial
market segment. It can be used for gas services including natural gas, manufactured gas and liqueed petroleum gas, etc.
The basic types include Types RB, RBT, RBQ and RBQT.
R X □ / 0.4□□
Internal codes (RB, RBT, RBQ and RBQT)
Structure types (A - 1+0; B - 1+1; C - 2+0). See Table 1 for dimensions.
Maximum inlet pressure (MPa)
Rated ow
Gas Regulator Box
Figure 1. RB Series Regulating System
Box Body
RB1+0
Backplate
Connecting Bolt
RBQ1+0
RBT1+0
Figure 2. RB Series Parts
Box Body
2. Technical Data and Features
Inlet Pressure Range (P1)
Outlet Pressure Range (P2)
Regulating Accuracy : Up to AC 5
Lockup Accuracy: Up to SG 10
Slam-shut Accuracy: Up to AC5
Temperature Capability
Body Size and End Connection: See Table 1
(1)
: 0.02 to 0.4 MPa / 2.9 to 58.0 psig
(1)
: 1.5 to 30 KPa / 0.22 to 4.35 psig (See Table 2 for available spring ranges)
(1)
: -20 to 60°C / -4 to 140°F
Filtration Module
Regulator Module
Pressure Measuring
Nipple
Connecting bolt
Outlet Ball Valve
Inlet Ball Valve
RB1+1
RB2+0
RBQT1+0
Box Body
Bellow
Features:
•Modular design
•Filter system
•Automatic overpressure micro relief
•High-accuracy 2-stage regulator
•Designed for ease of operation and maintenance
•“Loose” inlet/outlet flange connections
•Automatic overpressure shut off
1. The pressure/temperature limits in this Manual and any applicable standard or code limitation for valve should not be exceeded.
3
3
Page 4
RB Series Regulating System
Table 1. RB Series Body Size and End Connection
STRUCTURAL
MODEL
RB
RBT
RBQ
RBQT
Type RBT is added with bypass connection ports based on RB1+0, with G threaded connection.
Type RBQT is added with bypass connection ports based on RBQ1+0, with quick-action coupling acc. to GB/T 5860 or ISO 7241-1.
Note: If you have demands for products with nominal ow higher than 100 SCMH or other special requirements, please contact Emerson Process Management Regulator Technologies Inc.
authorized agent or sales company.
TYPE
1+025/402525
1+050/80/100254010
1+125/40252535
1+150/80/100254043
2+025/40252535
2+050/80/100254043
1+025/402525151513
1+050/80/1002540152516
1+0252525
1+050/80/100505016
1+0252525151515
1+050/80/1005050152520
NOMINAL
FLOW,
SCMH
INLET
FLANGE,
DN
OUTLET
FLANGE,
DN
BYPASS
INLET,
DN
N/AN/A
N/AN/A
BYPASS
OUTLET,
DN
NET WEIGHT
OF REGULATOR
BOX, kg
9
12
CENTER DISTANCE OF
INLET AND OUTLET
FLANGES, mm
155
280/3001+040404014
3001+0404040151518
according to
HG20592 PN16
3. Structure and Principle of Operation
RB Series regulator box consists of inlet and outlet ball valves, ltration module, regulator module and box body (see Figures 1
and 2). The regulator module includes shut off, 1st stage regulation, 2nd stage regulation and micro relief.
Regulator operational concept (See Figure 3): After the gas had gone through the rst stage regulator and had stabilized the
intermediate pressure, it will then go through the second stage regulator. The second stage regulator will reduce the pressure
to the desired outlet pressure, P2.
When P2 meets the relief set pressure, the relief valve will open to release the sudden increase in pressure caused by environmental
temperature uctuations or other factors. This is to prevent “false shutoff” or accidental trip by the slam-shut valve when there
is a sudden erratic increase in pressure and to maintain the pressure at the setpoint, P2.
When the slam-shut valve registered P2 is higher than the set pressure, the latching mechanism is released and the spring will
assist to close speedily and to seal tightly the slam-shut orice with the pad. This will cut off the ow in the valve and prevent
damages to downstream equipment.
Upon correcting the cause of overpressure, pull and latch the reset bar to allow normal ow operation again.
FLANGE
STANDARD
Flange
connection
dimensions
Figure 3. RB Series Operational Schematic
FIRST STAGE ORIFICE
FIRST STAGE
REGULATOR
FIRST STAGE
DIAPHRAGM
INLET PRESSURE
OUTLET PRESSURE
ATMOSPHERIC PRESSURE
INTERMEDIATE PRESSURE
4
4
SLAM-SHUT PAD
SLAM-SHUT
VALVE
SLAM-SHUT
RESET BAR
FILTRATION MODULE
FILTER
ELEMENT
FILTER CAP
SECOND STAGE
REGULATOR
REGULATOR
ADJUSTMENT
SCREW CAP
RELIEF
ADJUSTMENT NUT
SECOND STAGE
ORIFICE PAD
RELIEF
VALVE
REGULATOR
CAP
Page 5
RB Series Regulating System
4. Selection of Spring
Table 2. Regulator Spring Selection
RANGE OF PRESSURE, kPaWIRE DIAMETER OF SPRING, mmSPRING CODECOLOR
1.5 to 3.32.5JJJJ86CXT01Galvanized
3.0 to 6.02.5JJJJ86CXT02Yellow
6.0 to 10.02.8JJJJ86CXT03Red
9.0 to 15.03.0JJJJ86CXT13Black
15.0 to 22.03.5ERAA15524A0Blue
22.0 to 30.03.5ERAA15525A0White
Table 3. Shut-off Selection
RANGE OF PRESSURE, kPaWIRE DIAMETER OF SPRING, mmSPRING CODECOLOR
2.5 to 5.01.2JJJJ86CXT06Galvanized
5.0 to 10.01.5JJJJ86CXT07Yellow
9.0 to 15.02.0JJJJ86CXT08Red
15.0 to 26.02.2ERAA15381A0Blue
26.0 to 40.02.5ERAA15382A0White
!
WARNING
To avoid personal injury, property damage or equipment damage caused by bursting of pressure containing parts or
explosion of accumulated gas, never adjust the control spring to produce an outlet pressure higher than the upper limit
of the outlet pressure range for that particular spring. If the desired outlet pressure is not within the range of the control
spring, install a spring of the proper range.
5. Flow Chart (SCMH)
Table 4. Flow Chart (SCMH)
NOMINAL FLOW
25102227282930
40122442434445
50142852535455
80214080808080
1003055100120120120
0.020.050.10.20.30.4
INLET PRESSURE, MPa
Notes:
• The values shown above are the ow capacity at 3 kPa outlet pressure setting. For the other outlet pressure setting, there
is a very small difference of actual ow capacity.
• Flow capacity are based on 0.61 specic gravity, Natural Gas. If other media is used, multiply the shown data by: 1.17 for
manufactured gas; 0.55 for butane; 0.63 for propane; 0.78 for air; 0.79 for nitrogen.
!
WARNING
Installation, operation and maintenance performed by non-qualified personnel may result in unsafe operation,
equipment damage or personal injury. Call a qualified personnel when installing, operating and maintaining the unit.
6. Installation
The regulator installation and usage must only be carried out by qualied and trained personnel. Otherwise, please contact the
company. The company will not be responsible for any consequences due to non-standard operations/compliance of usage.
1. Install the regulator in ambient temperature, away from sources of re and away from vibrations.
2. Check if the pressure in the pipeline is within the pressure range stated on the regulator nameplate.
3. Make sure that the ow direction of the pipeline matches the arrow stamped on the regulator body.
4. Purge and clean the pipeline before installation.
5. Install the inlet and outlet pipeline end connections 155 mm / 6.10 in. apart (from center to center of pipes). Recommended
pipeline end connections shall be ≥1.2 m / 3.94 ft. above ground level. The ange connection face levelling height tolerance
is 3 mm / 0.12 in.; exceeding this will cause leakage or damage to the regulator. Do not use exceedingly strong force while
connecting the ange ends. Sequentially, tighten the inlet anges before tightening the outlet anges. (Please see Figure
5 for the installation dimensions.)
6. Place a suitable cubage between the regulator and any quick alternating pressure equipment (e.g., burner or solenoid
valve) to prevent any “false shutoff”.
Note: Remove the regulator when the pipeline is undergoing pressure test or purging to avoid damaging the regulator.
5
5
Page 6
RB Series Regulating System
E
H
G
F
G
Figure 4. Slam-Shut Valve Position
FULLY OPENFULLY CLOSE
Figure 5. Installation Dimensions
A
20
R5
Inlet Ball
Valve
230
DC
Types: RB/RBT/RBQ/RBQT
B
Structural Type: 1+0
Outlet Ball
Valve
A
DC
B
F
G
Outlet Ball
Valve
20
E
F
H
R5
230
10
Inlet Ball
Valve
E
H
Type: RB
Structural Types: 1+1 and 2+0
Table 5. Installation Dimensions of RB Series of Regulator Box
TYPE
RB1+0all310409515519424332784
RB1+1all323408515534550069084
RB2+0all323408515534550069084
RBT1+0all323407415522530038284
RBQ
RBQT1+0all4701138730027030038284
6
6
STRUCTURAL
TYPE
1+0all4551138730019424332784
1+0all4351138728019424332784
NOMINAL
FLOW
ABCDEFGH
Page 7
RB Series Regulating System
Figure 6. Outlet Pressure Setting Adjustment
Figure 7. Slam-Shut Setting Adjustment
7. Usage
1. Commissioning Procedure
1. Ensure that the slam-shut valve is in the open position; use the handle to open slightly the outlet ball valve. See Figure 4.
2. Slowly turn the handle counterclockwise to open the ball valve.
3. Momentarily stop until the ow stabilizes.
4. Fully open the ball valve when ow stabilizes.
2. Setting the Outlet Pressure
1. Slowly turn the adjustment screw cap to the desired pressure. (Turning clockwise will increase the outlet pressure while
turning counterclockwise will decrease the outlet pressure.) See Figure 6.
2. Ensure that the setpoint is within the spring pressure range or it may damage the regulator.
Note: While the regulator is in operation, do not open the test port valve as it will increase the downstream pressure.
3. Setting the Slam-Shut Pressure
1. Slowly turn the adjustment nut with the handle to adjust and set the desired slam-shut set pressure. (Turning clockwise will
increase the set pressure while turning counterclockwise will decrease the set pressure.)
2. Determine the set pressure from the test port valve.
3. Ensure that both inlet and outlet ball valves are in close positions before taking the measurements, then vent the gas inside
the regulator. For safety, as a rule of thumb, the slam-shut module set pressure should not be more than 1.5 times the
regulator setpoint.
4. Unscrew the regulator adjustment cap (see Figure 3) if the user would need to vent the pressure of the regulator.
5. Use a size 14 wrench to turn the adjustment nut. (Turning clockwise will increase the setpoint while turning counterclockwise
will decrease the setpoint.) Vent pressure is recommended to be 1.3 times of regulator operating pressure.
Note: Calibrate the slam-shut set pressure by turning the adjustment nut but make sure that it is done when the spring is at the
most relaxed spring length, then slowly compress it to the desired set pressure.
4. Reset the Slam-Shut Valve
1. Check the root cause that activated the valve to shut off.
2. Close the inlet ball valve such that it only allows a small ow into the regulator for a build-up inlet pressure.
3. Close the outlet ball valve such that it only allows a small ow through the regulator (or completely close the regulator outlet valve
and slightly open the test port valve to allow a small outlet ow).
4. Pull the “Reset Bar” until a small ow through the regulator is achieved and maintain the ow at that.
5. Wait until the pressure is balanced before and after the slam-shut valve. However, if there is resistance while pulling the “Reset
Bar”, stop pulling. If the regulator does not work normally, close both the inlet and outlet ball valves and diagnose the root cause
of the problem. If the regulator operates normally, pull the “Reset Bar” (there shall be no resistance while pulling) until it is latched
on again.
7
7
Page 8
RB Series Regulating System
6. Slowly open the inlet and outlet ball valves, respectively. After troubleshooting, reset the slam-shut valve, then slightly open
the outlet ball valve and then the inlet ball valve and observe if the regulator is back to normal operation. If the regulator
resumes normal operation, fully open both the inlet and outlet ball valves.
Notes:
• Do not attempt to reset the slam-shut valve with fully open inlet and outlet ball valves. Doing so may cause personal injury
and damage to the regulator.
• RB Series regulating box has OPSO shut-off protection. If need UPSO shut-off protection, please contact an authorized agent
or sales company authorized by Emerson Process Management Regulator Technologies Inc.
8. Maintenance
1. General maintenance
1. Ensure that the inlet and outlet ball valves are in close position before any maintenance of the regulator is carried out. Verify
also that the slam-shut valve is in the open position.
2. Open the test port valve to relieve the pressure in the regulator. Make sure not to damage the diaphragm orices and other
components of the regulator while disassembling and assembling.
3. While assembling the moveable parts, ensure that the parts remain functional.
4. After re-installation of the valve, restore the regulator to the required setpoint prior to maintenance.
5. Ensure all end connections are tightly sealed and without leakage.
Our company provides training for maintenance personnel. For further enquiries, please contact our company’s service
department or authorized representatives.
2. Routine maintenance
Routine Maintenance checks should be done by the user’s managing department for regulators. The duration in between the
checks should be determined by the user depending on the weather and usage parameters to ensure safe operations:
1. Use a gas detection equipment (or do “bubble check”) to detect any leakage.
2. Check the readings on the pressure gauge for the corresponding outlet pressure.
3. Clean the externals of the regulator.
3. Regular maintenance
Maintenance content: selective checks depending on the actual situation.
1. Regular operational pressure check:
a. Connect a pressure gauge at the test port of the regulator.
b. Open the test port valve and then slowly close the regulator outlet ball valve.
c. Wait for 3 minutes and record the reading on the gauge.
d. Check if the pressure reading is within the operational range. If the reading falls within the operational range, there is no
need to proceed to the next steps of the maintenance instructions.
Figure 8. Box Cover Removal
BOX COVER
BACK OF BOX
Figure 9. Slam-Shut Parts
RESET BAR NUT
SLAM-SHUT BONNET
RESET SHAFT
ADJUSTMENT NUT
CLAMPING NUT
SLAM-SHUT
DIAPHRAGM
SLAM-SHUT
LOWER CASE
SLAM-SHUT
BOX BRACKET
8
8
ORIFICE PAD
BALL BEARING
Page 9
Figure 10. First Stage Regulator Parts
PRESS AND HOLD
RB Series Regulating System
FIRST STAGE
REGULATOR COVER
BALANCING SHAFT
FIRST STAGE
DIAPHRAGM
CONNECTION
SHAFT
2. Slam-shut valve set pressure check:
a. Close the inlet and outlet ball valves and vent the regulator pressure.
b. Allow pressure to ow into the test port (while it is open).
c. Observe if the pressure when the slam-shut tripped is the desired set pressure.
3. Replace consumable parts: Valve and orice pads, diaphragms, O-rings and other elastomer parts.
4. Clean the lter element.
9. Assembly and Disassembly Points to Note
A. Removing the Box cover (See Figure 8):
1. Unlock and swing open the cover by 90°.
2. Lift up the cover to remove it.
B. Removing the filter element (See Figure 3):
1. Vent pressure out of the regulator.
2. Use a size 4 hex-key to remove the screws and the lter cap. (Note: Be careful of the spring inside springing out when the
cap is detached.)
3. Pull the ring attached on the lter and pull out the lter element.
C. Removing Slam-Shut parts (See Figure 9):
1. Use the tools provided to turn the adjustment nut until it is levelled with the bonnet.
2. Use a size 4 hex-key to remove the screws and the slam-shut module.
3. Unscrew the reset bar nut.
4. As shown in Figure 9, lift open the slam-shut bonnet (take note of the 5 ball bearings that will fall out) and remove the
reset bar.
5. Use a spring collar tool (JB/T3411.47) to remove Φ7 spring collar on the orice pad and thus removing the orice pad.
(During the process of removing the parts, ensure that the reset bar is not bent due to excessive applied force.)
6. Use a size 9 wrench to loosen the clamping nut to remove the diaphragm.
D. Removing the First Stage Regulator Orifice Pad:
1. Do Step “C” to remove the slam-shut module.
2. Use a size “A” spring collar tool (place it into the holes and turn it counterclockwise) to remove the rst stage regulator
orice pad.
9
9
Page 10
RB Series Regulating System
E. Removing the First Stage Regulator diaphragm (See Figure 10):
1. Unscrew the bolts and screws with a size 13 wrench (GB/T4388) that connect the ends of the inlet and outlet ball valves.
2. Remove the regulator.
3. Do Step “D” to remove the rst stage regulator orice pad.
4. Remove the diaphragm assembly.
5. Use a size 17 wrench to loosen the balancing shaft and connection shaft and then remove the diaphragm.
6. While reassembling, apply downward pressure onto the cover and screw in all the screws slightly before tightening them.
Ensure that the entire diaphragm is NOT displaced out of the cover before completely tightening all the screws.
F. Removing the Second Stage Regulator diaphragm (See Figure 11):
1. Unscrew the adjustment screw ap.
2. Use a size 4 wrench to unscrew the surrounding nuts and bolts.
3. Open the bonnet and remove the diaphragm. Altogether, hold onto the diaphragm and the components of the second
stage regulator while removing them from the body of the regulator.
4. Use a size 14 wrench to unscrew the second stage diaphragm nut and remove the diaphragm.
G. Removing the Second Stage Regulator Orifice Pad (See Figures 12 and 13):
1. After completing step “F”, use a Phillips screw driver to unscrew 2x M3 screws that are holding the Lever in its position.
2. Remove the lever.
3. Use the special tool to unscrew the regulator cap.
4. Remove the second stage orice pad assembly.
5. Use a Phillips or at screw driver to unscrew the M5 screws holding the second stage orice pad assembly; remove the
orice pad.
6. During the reassembly of the second stage regulator, rst assemble the orice pad assembly, then put the lever in its place
and screw back the M3 screws to hold it in position.
7. Hold onto the orice pad to let the lever return to the lifted position while placing the diaphragm back to its original position
in the body.
8. Follow the diagram below (Figure 13) and adjust until the rectangular slot faces are in the direction shown and slot the lever
back onto the diaphragm attachment.
9. Place back the bonnet and tighten it with nuts and bolts.
10. Clean all the parts before placing them back into the regulator body.
11. Apply the appropriate grease onto all the seal tight elements (O-rings, diaphragm, etc.) and contact surfaces before placing
them back into the regulator body.
Figure 11. Second Stage Regulator Parts
10
10
ADJUSTMENT CAP
SECOND STAGE BONNET
SECOND STAGE COMPONENTS
Page 11
Figure 12. Second Stage Regulator Orice Pad Removal
RB Series Regulating System
Figure 13. Rectangular Spot Positioning
RECTANGULAR
SLOT
SHAFT
LEVER
M3 BOLT
SECOND STAGE ORIFICE
PAD ASSEMBLY
REGULATOR CAP
RECTANGULAR
SLOT
Table 6. Troubleshooting Guide
ISSUECAUSEREMEDY
• Inlet pressure is low.
Low operating outlet pressure
Regulator is in close position
but pressure increases
Regulator fully opens • Regulator main spring is undersized. • Replace the main spring.
Slam-shut valve doesn’t work
Slam-shut instability
Cannot reset the slam-shut valve • Differential pressure is exceedingly high. • Close inlet and outlet valves, then open the test port valve.
• Downstream ow capacity demand exceeds the
regulator capacity.
• The lter is blocked.
• First stage regulator diaphragm is damaged.
• Orice pad is worn out.
• Orice is jammed due to impurities or orice is damaged.
• Slam-shut diaphragm is damaged.
• Sensing port is blocked.
• Slam-shut spring is oversized.
• Spring setting is wrong.
• Latching mechanism has high resistance due to friction.
Table 7. Spare Parts Package of RB Series of Regulator Box
Service T: +86 28 85366930 or +86 28 85360000 Ext. 1613
PressureManagement.AP@emerson.com
www.emerson.com
Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use
or maintenance of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the
purchaser and end user.
Jeon is a mark owned by one of the businesses of Emerson Automation Solutions. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not
to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales
are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specications of
such products at any time without notice.
Emerson Process Management
Chennai Ltd
Plot No. 5, 6, 7 and 8 Self Help Industrial Estate
Keelkattalai, Chennai, India - 600117
T +91 44 4903 4405
F +91 44 4903 4400
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.