Fisher RB Series Regulating System (Asia Pacific Only) Manuals & Guides

Page 1
Instruction Manual
D103251X012
December 2018
RB Series
Regulating System
Page 2
RB Series Regulating System
1. Introduction ........................................................3
2. Technical Data and Features ..........................................3
3. Structure and Principle of Operation ...................................4
4. Selection of Spring ..................................................5
5. Flow Chart (SCMH) ..................................................5
6. Installation .........................................................5
7. Usage .............................................................7
8. Maintenance .......................................................8
9. Assembly and Disassembly Points to Note ..............................9
10. Ordering Guide ................................................... 12
!
WARNING
Failure to follow these instructions or to properly install and maintain this equipment could result in an explosion, fire and/or chemical contamination causing property damage and personal injury or death.
Jeon regulators must be installed, operated and maintained in accordance with federal, state and local codes, rules and regulations and Emerson Process Management Regulator Technologies, Inc. instructions.
If the regulator vents gas or a leak develops in the system, service to the unit may be required. Failure to correct trouble could result in a hazardous condition.
Installation, operation and maintenance procedures performed by unqualified personnel may result in improper adjustment and unsafe operation. Either condition may result in equipment damage or personal injury. Call qualified personnel when installing, operating and maintaining the RB Series regulating system.
2
2
Page 3
RB Series Regulating System
1. Introduction
RB Series (wall-mountable) regulating box can be deployed for natural gas distribution system in the residential or in the commercial
market segment. It can be used for gas services including natural gas, manufactured gas and liqueed petroleum gas, etc.
The basic types include Types RB, RBT, RBQ and RBQT.
R X / 0.4
Internal codes (RB, RBT, RBQ and RBQT) Structure types (A - 1+0; B - 1+1; C - 2+0). See Table 1 for dimensions. Maximum inlet pressure (MPa)
Rated ow
Gas Regulator Box
Figure 1. RB Series Regulating System
Box Body
RB1+0
Backplate
Connecting Bolt
RBQ1+0
RBT1+0
Figure 2. RB Series Parts
Box Body
2. Technical Data and Features
Inlet Pressure Range (P1)
Outlet Pressure Range (P2)
Regulating Accuracy : Up to AC 5
Lockup Accuracy: Up to SG 10
Slam-shut Accuracy: Up to AC5
Temperature Capability
Body Size and End Connection: See Table 1
(1)
: 0.02 to 0.4 MPa / 2.9 to 58.0 psig
(1)
: 1.5 to 30 KPa / 0.22 to 4.35 psig (See Table 2 for available spring ranges)
(1)
: -20 to 60°C / -4 to 140°F
Filtration Module
Regulator Module
Pressure Measuring Nipple
Connecting bolt
Outlet Ball Valve
Inlet Ball Valve
RB1+1 RB2+0
RBQT1+0
Box Body
Bellow
Features:
•Modular design
•Filter system
•Automatic overpressure micro relief
•High-accuracy 2-stage regulator
•Designed for ease of operation and maintenance
•“Loose” inlet/outlet flange connections
•Automatic overpressure shut off
1. The pressure/temperature limits in this Manual and any applicable standard or code limitation for valve should not be exceeded.
3
3
Page 4
RB Series Regulating System
Table 1. RB Series Body Size and End Connection
STRUCTURAL
MODEL
RB
RBT
RBQ
RBQT
Type RBT is added with bypass connection ports based on RB1+0, with G threaded connection. Type RBQT is added with bypass connection ports based on RBQ1+0, with quick-action coupling acc. to GB/T 5860 or ISO 7241-1.
Note: If you have demands for products with nominal ow higher than 100 SCMH or other special requirements, please contact Emerson Process Management Regulator Technologies Inc. authorized agent or sales company.
TYPE
1+0 25/40 25 25
1+0 50/80/100 25 40 10
1+1 25/40 25 25 35
1+1 50/80/100 25 40 43
2+0 25/40 25 25 35
2+0 50/80/100 25 40 43
1+0 25/40 25 25 15 15 13
1+0 50/80/100 25 40 15 25 16
1+0 25 25 25
1+0 50/80/100 50 50 16
1+0 25 25 25 15 15 15
1+0 50/80/100 50 50 15 25 20
NOMINAL
FLOW,
SCMH
INLET
FLANGE,
DN
OUTLET
FLANGE,
DN
BYPASS
INLET,
DN
N/A N/A
N/A N/A
BYPASS
OUTLET,
DN
NET WEIGHT
OF REGULATOR
BOX, kg
9
12
CENTER DISTANCE OF
INLET AND OUTLET
FLANGES, mm
155
280/3001+0 40 40 40 14
3001+0 40 40 40 15 15 18
according to
HG20592 PN16
3. Structure and Principle of Operation
RB Series regulator box consists of inlet and outlet ball valves, ltration module, regulator module and box body (see Figures 1
and 2). The regulator module includes shut off, 1st stage regulation, 2nd stage regulation and micro relief.
Regulator operational concept (See Figure 3): After the gas had gone through the rst stage regulator and had stabilized the
intermediate pressure, it will then go through the second stage regulator. The second stage regulator will reduce the pressure to the desired outlet pressure, P2.
When P2 meets the relief set pressure, the relief valve will open to release the sudden increase in pressure caused by environmental
temperature uctuations or other factors. This is to prevent “false shutoff” or accidental trip by the slam-shut valve when there
is a sudden erratic increase in pressure and to maintain the pressure at the setpoint, P2.
When the slam-shut valve registered P2 is higher than the set pressure, the latching mechanism is released and the spring will
assist to close speedily and to seal tightly the slam-shut orice with the pad. This will cut off the ow in the valve and prevent
damages to downstream equipment.
Upon correcting the cause of overpressure, pull and latch the reset bar to allow normal ow operation again.
FLANGE
STANDARD
Flange connection dimensions
Figure 3. RB Series Operational Schematic
FIRST STAGE ORIFICE
FIRST STAGE REGULATOR
FIRST STAGE DIAPHRAGM
INLET PRESSURE
OUTLET PRESSURE
ATMOSPHERIC PRESSURE
INTERMEDIATE PRESSURE
4
4
SLAM-SHUT PAD
SLAM-SHUT VALVE
SLAM-SHUT RESET BAR
FILTRATION MODULE
FILTER ELEMENT
FILTER CAP
SECOND STAGE REGULATOR
REGULATOR ADJUSTMENT SCREW CAP
RELIEF ADJUSTMENT NUT
SECOND STAGE ORIFICE PAD
RELIEF VALVE
REGULATOR CAP
Page 5
RB Series Regulating System
4. Selection of Spring
Table 2. Regulator Spring Selection
RANGE OF PRESSURE, kPa WIRE DIAMETER OF SPRING, mm SPRING CODE COLOR
1.5 to 3.3 2.5 JJJJ86CXT01 Galvanized
3.0 to 6.0 2.5 JJJJ86CXT02 Yellow
6.0 to 10.0 2.8 JJJJ86CXT03 Red
9.0 to 15.0 3.0 JJJJ86CXT13 Black
15.0 to 22.0 3.5 ERAA15524A0 Blue
22.0 to 30.0 3.5 ERAA15525A0 White
Table 3. Shut-off Selection
RANGE OF PRESSURE, kPa WIRE DIAMETER OF SPRING, mm SPRING CODE COLOR
2.5 to 5.0 1.2 JJJJ86CXT06 Galvanized
5.0 to 10.0 1.5 JJJJ86CXT07 Yellow
9.0 to 15.0 2.0 JJJJ86CXT08 Red
15.0 to 26.0 2.2 ERAA15381A0 Blue
26.0 to 40.0 2.5 ERAA15382A0 White
!
WARNING
To avoid personal injury, property damage or equipment damage caused by bursting of pressure containing parts or explosion of accumulated gas, never adjust the control spring to produce an outlet pressure higher than the upper limit of the outlet pressure range for that particular spring. If the desired outlet pressure is not within the range of the control spring, install a spring of the proper range.
5. Flow Chart (SCMH)
Table 4. Flow Chart (SCMH)
NOMINAL FLOW
25 10 22 27 28 29 30
40 12 24 42 43 44 45
50 14 28 52 53 54 55
80 21 40 80 80 80 80
100 30 55 100 120 120 120
0.02 0.05 0.1 0.2 0.3 0.4
INLET PRESSURE, MPa
Notes:
• The values shown above are the ow capacity at 3 kPa outlet pressure setting. For the other outlet pressure setting, there is a very small difference of actual ow capacity.
Flow capacity are based on 0.61 specic gravity, Natural Gas. If other media is used, multiply the shown data by: 1.17 for
manufactured gas; 0.55 for butane; 0.63 for propane; 0.78 for air; 0.79 for nitrogen.
!
WARNING
Installation, operation and maintenance performed by non-qualified personnel may result in unsafe operation, equipment damage or personal injury. Call a qualified personnel when installing, operating and maintaining the unit.
6. Installation
The regulator installation and usage must only be carried out by qualied and trained personnel. Otherwise, please contact the
company. The company will not be responsible for any consequences due to non-standard operations/compliance of usage.
1. Install the regulator in ambient temperature, away from sources of re and away from vibrations.
2. Check if the pressure in the pipeline is within the pressure range stated on the regulator nameplate.
3. Make sure that the ow direction of the pipeline matches the arrow stamped on the regulator body.
4. Purge and clean the pipeline before installation.
5. Install the inlet and outlet pipeline end connections 155 mm / 6.10 in. apart (from center to center of pipes). Recommended
pipeline end connections shall be ≥1.2 m / 3.94 ft. above ground level. The ange connection face levelling height tolerance
is 3 mm / 0.12 in.; exceeding this will cause leakage or damage to the regulator. Do not use exceedingly strong force while
connecting the ange ends. Sequentially, tighten the inlet anges before tightening the outlet anges. (Please see Figure
5 for the installation dimensions.)
6. Place a suitable cubage between the regulator and any quick alternating pressure equipment (e.g., burner or solenoid
valve) to prevent any “false shutoff”.
Note: Remove the regulator when the pipeline is undergoing pressure test or purging to avoid damaging the regulator.
5
5
Page 6
RB Series Regulating System
E
H
G
F
G
Figure 4. Slam-Shut Valve Position
FULLY OPEN FULLY CLOSE
Figure 5. Installation Dimensions
A
20
R5
Inlet Ball Valve
230
D C
Types: RB/RBT/RBQ/RBQT
B
Structural Type: 1+0
Outlet Ball Valve
A
D C
B
F
G
Outlet Ball Valve
20
E
F
H
R5
230
10
Inlet Ball Valve
E
H
Type: RB
Structural Types: 1+1 and 2+0
Table 5. Installation Dimensions of RB Series of Regulator Box
TYPE
RB 1+0 all 310 40 95 155 194 243 327 84
RB 1+1 all 323 40 85 155 345 500 690 84
RB 2+0 all 323 40 85 155 345 500 690 84
RBT 1+0 all 323 40 74 155 225 300 382 84
RBQ
RBQT 1+0 all 470 113 87 300 270 300 382 84
6
6
STRUCTURAL
TYPE
1+0 all 455 113 87 300 194 243 327 84
1+0 all 435 113 87 280 194 243 327 84
NOMINAL
FLOW
A B C D E F G H
Page 7
RB Series Regulating System
Figure 6. Outlet Pressure Setting Adjustment
Figure 7. Slam-Shut Setting Adjustment
7. Usage
1. Commissioning Procedure
1. Ensure that the slam-shut valve is in the open position; use the handle to open slightly the outlet ball valve. See Figure 4.
2. Slowly turn the handle counterclockwise to open the ball valve.
3. Momentarily stop until the ow stabilizes.
4. Fully open the ball valve when ow stabilizes.
2. Setting the Outlet Pressure
1. Slowly turn the adjustment screw cap to the desired pressure. (Turning clockwise will increase the outlet pressure while turning counterclockwise will decrease the outlet pressure.) See Figure 6.
2. Ensure that the setpoint is within the spring pressure range or it may damage the regulator.
Note: While the regulator is in operation, do not open the test port valve as it will increase the downstream pressure.
3. Setting the Slam-Shut Pressure
1. Slowly turn the adjustment nut with the handle to adjust and set the desired slam-shut set pressure. (Turning clockwise will increase the set pressure while turning counterclockwise will decrease the set pressure.)
2. Determine the set pressure from the test port valve.
3. Ensure that both inlet and outlet ball valves are in close positions before taking the measurements, then vent the gas inside
the regulator. For safety, as a rule of thumb, the slam-shut module set pressure should not be more than 1.5 times the regulator setpoint.
4. Unscrew the regulator adjustment cap (see Figure 3) if the user would need to vent the pressure of the regulator.
5. Use a size 14 wrench to turn the adjustment nut. (Turning clockwise will increase the setpoint while turning counterclockwise
will decrease the setpoint.) Vent pressure is recommended to be 1.3 times of regulator operating pressure.
Note: Calibrate the slam-shut set pressure by turning the adjustment nut but make sure that it is done when the spring is at the
most relaxed spring length, then slowly compress it to the desired set pressure.
4. Reset the Slam-Shut Valve
1. Check the root cause that activated the valve to shut off.
2. Close the inlet ball valve such that it only allows a small ow into the regulator for a build-up inlet pressure.
3. Close the outlet ball valve such that it only allows a small ow through the regulator (or completely close the regulator outlet valve and slightly open the test port valve to allow a small outlet ow).
4. Pull the “Reset Bar” until a small ow through the regulator is achieved and maintain the ow at that.
5. Wait until the pressure is balanced before and after the slam-shut valve. However, if there is resistance while pulling the “Reset Bar”, stop pulling. If the regulator does not work normally, close both the inlet and outlet ball valves and diagnose the root cause of the problem. If the regulator operates normally, pull the “Reset Bar” (there shall be no resistance while pulling) until it is latched
on again.
7
7
Page 8
RB Series Regulating System
6. Slowly open the inlet and outlet ball valves, respectively. After troubleshooting, reset the slam-shut valve, then slightly open the outlet ball valve and then the inlet ball valve and observe if the regulator is back to normal operation. If the regulator resumes normal operation, fully open both the inlet and outlet ball valves.
Notes:
Do not attempt to reset the slam-shut valve with fully open inlet and outlet ball valves. Doing so may cause personal injury
and damage to the regulator.
• RB Series regulating box has OPSO shut-off protection. If need UPSO shut-off protection, please contact an authorized agent
or sales company authorized by Emerson Process Management Regulator Technologies Inc.
8. Maintenance
1. General maintenance
1. Ensure that the inlet and outlet ball valves are in close position before any maintenance of the regulator is carried out. Verify
also that the slam-shut valve is in the open position.
2. Open the test port valve to relieve the pressure in the regulator. Make sure not to damage the diaphragm orices and other
components of the regulator while disassembling and assembling.
3. While assembling the moveable parts, ensure that the parts remain functional.
4. After re-installation of the valve, restore the regulator to the required setpoint prior to maintenance.
5. Ensure all end connections are tightly sealed and without leakage.
Our company provides training for maintenance personnel. For further enquiries, please contact our company’s service
department or authorized representatives.
2. Routine maintenance
Routine Maintenance checks should be done by the user’s managing department for regulators. The duration in between the checks should be determined by the user depending on the weather and usage parameters to ensure safe operations:
1. Use a gas detection equipment (or do “bubble check”) to detect any leakage.
2. Check the readings on the pressure gauge for the corresponding outlet pressure.
3. Clean the externals of the regulator.
3. Regular maintenance
Maintenance content: selective checks depending on the actual situation.
1. Regular operational pressure check:
a. Connect a pressure gauge at the test port of the regulator.
b. Open the test port valve and then slowly close the regulator outlet ball valve.
c. Wait for 3 minutes and record the reading on the gauge.
d. Check if the pressure reading is within the operational range. If the reading falls within the operational range, there is no
need to proceed to the next steps of the maintenance instructions.
Figure 8. Box Cover Removal
BOX COVER
BACK OF BOX
Figure 9. Slam-Shut Parts
RESET BAR NUT
SLAM-SHUT BONNET
RESET SHAFT
ADJUSTMENT NUT
CLAMPING NUT
SLAM-SHUT DIAPHRAGM
SLAM-SHUT LOWER CASE
SLAM-SHUT
BOX BRACKET
8
8
ORIFICE PAD
BALL BEARING
Page 9
Figure 10. First Stage Regulator Parts
PRESS AND HOLD
RB Series Regulating System
FIRST STAGE REGULATOR COVER
BALANCING SHAFT
FIRST STAGE DIAPHRAGM
CONNECTION SHAFT
2. Slam-shut valve set pressure check:
a. Close the inlet and outlet ball valves and vent the regulator pressure.
b. Allow pressure to ow into the test port (while it is open).
c. Observe if the pressure when the slam-shut tripped is the desired set pressure.
3. Replace consumable parts: Valve and orice pads, diaphragms, O-rings and other elastomer parts.
4. Clean the lter element.
9. Assembly and Disassembly Points to Note
A. Removing the Box cover (See Figure 8):
1. Unlock and swing open the cover by 90°.
2. Lift up the cover to remove it.
B. Removing the filter element (See Figure 3):
1. Vent pressure out of the regulator.
2. Use a size 4 hex-key to remove the screws and the lter cap. (Note: Be careful of the spring inside springing out when the
cap is detached.)
3. Pull the ring attached on the lter and pull out the lter element.
C. Removing Slam-Shut parts (See Figure 9):
1. Use the tools provided to turn the adjustment nut until it is levelled with the bonnet.
2. Use a size 4 hex-key to remove the screws and the slam-shut module.
3. Unscrew the reset bar nut.
4. As shown in Figure 9, lift open the slam-shut bonnet (take note of the 5 ball bearings that will fall out) and remove the reset bar.
5. Use a spring collar tool (JB/T3411.47) to remove Φ7 spring collar on the orice pad and thus removing the orice pad. (During the process of removing the parts, ensure that the reset bar is not bent due to excessive applied force.)
6. Use a size 9 wrench to loosen the clamping nut to remove the diaphragm.
D. Removing the First Stage Regulator Orifice Pad:
1. Do Step “C” to remove the slam-shut module.
2. Use a size “A” spring collar tool (place it into the holes and turn it counterclockwise) to remove the rst stage regulator orice pad.
9
9
Page 10
RB Series Regulating System
E. Removing the First Stage Regulator diaphragm (See Figure 10):
1. Unscrew the bolts and screws with a size 13 wrench (GB/T4388) that connect the ends of the inlet and outlet ball valves.
2. Remove the regulator.
3. Do Step “D” to remove the rst stage regulator orice pad.
4. Remove the diaphragm assembly.
5. Use a size 17 wrench to loosen the balancing shaft and connection shaft and then remove the diaphragm.
6. While reassembling, apply downward pressure onto the cover and screw in all the screws slightly before tightening them.
Ensure that the entire diaphragm is NOT displaced out of the cover before completely tightening all the screws.
F. Removing the Second Stage Regulator diaphragm (See Figure 11):
1. Unscrew the adjustment screw ap.
2. Use a size 4 wrench to unscrew the surrounding nuts and bolts.
3. Open the bonnet and remove the diaphragm. Altogether, hold onto the diaphragm and the components of the second stage regulator while removing them from the body of the regulator.
4. Use a size 14 wrench to unscrew the second stage diaphragm nut and remove the diaphragm.
G. Removing the Second Stage Regulator Orifice Pad (See Figures 12 and 13):
1. After completing step “F”, use a Phillips screw driver to unscrew 2x M3 screws that are holding the Lever in its position.
2. Remove the lever.
3. Use the special tool to unscrew the regulator cap.
4. Remove the second stage orice pad assembly.
5. Use a Phillips or at screw driver to unscrew the M5 screws holding the second stage orice pad assembly; remove the orice pad.
6. During the reassembly of the second stage regulator, rst assemble the orice pad assembly, then put the lever in its place
and screw back the M3 screws to hold it in position.
7. Hold onto the orice pad to let the lever return to the lifted position while placing the diaphragm back to its original position
in the body.
8. Follow the diagram below (Figure 13) and adjust until the rectangular slot faces are in the direction shown and slot the lever back onto the diaphragm attachment.
9. Place back the bonnet and tighten it with nuts and bolts.
10. Clean all the parts before placing them back into the regulator body.
11. Apply the appropriate grease onto all the seal tight elements (O-rings, diaphragm, etc.) and contact surfaces before placing
them back into the regulator body.
Figure 11. Second Stage Regulator Parts
10
10
ADJUSTMENT CAP
SECOND STAGE BONNET
SECOND STAGE COMPONENTS
Page 11
Figure 12. Second Stage Regulator Orice Pad Removal
RB Series Regulating System
Figure 13. Rectangular Spot Positioning
RECTANGULAR SLOT
SHAFT
LEVER
M3 BOLT
SECOND STAGE ORIFICE PAD ASSEMBLY
REGULATOR CAP
RECTANGULAR SLOT
Table 6. Troubleshooting Guide
ISSUE CAUSE REMEDY
• Inlet pressure is low.
Low operating outlet pressure
Regulator is in close position
but pressure increases
Regulator fully opens • Regulator main spring is undersized. • Replace the main spring.
Slam-shut valve doesn’t work
Slam-shut instability
Cannot reset the slam-shut valve • Differential pressure is exceedingly high. • Close inlet and outlet valves, then open the test port valve.
• Downstream ow capacity demand exceeds the regulator capacity.
• The lter is blocked.
• First stage regulator diaphragm is damaged.
• Orice pad is worn out.
• Orice is jammed due to impurities or orice is damaged.
• Slam-shut diaphragm is damaged.
• Sensing port is blocked.
• Slam-shut spring is oversized.
• Spring setting is wrong.
• Latching mechanism has high resistance due to friction.
Table 7. Spare Parts Package of RB Series of Regulator Box
TYPE STRUCTURAL TYPE NOMINAL FLOW
RB 1+0 All JJJJ86BX050 1 RB 1+1 All JJJJ86BX050 2
RB 2+0 All JJJJ86BX050 2 RBT 1+0 All JJJJ86BX050 1 RBQ 1+0 All JJJJ86BX061 1
RBQT 1+0 All JJJJ86BX061 1
• Increase the inlet pressure.
• Correct the size of the regulator.
• Clean the lter.
• Replace the diaphragm.
• Replace the orice pad.
• Clean or replace the orice.
• Replace diaphragm.
• Clean sensing port.
• Replace slam-shut spring with the right spring size.
• Calibrate the setpoint.
• Clean the latching mechanism.
ORDERING NUMBER OF
SPARE PARTS PACKAGE
QTY PER EACH
11
11
Page 12
10. Ordering Guide
RB 25 B1 C4 F1 EB1
Typ e
RB RBT RBQ RBQT
Flow Rate
25 40 50 80 100
Regulating
B1 (15 to 33 mbar) B2 (30 to 60 mbar) B3 (60 to 100 mbar) B4 (90 to 150 mbar) B5 (150 to 220 mbar) B6 (220 to 300 mbar)
Slam Shut Spring Selection
C4 (25 to 50 mbar) C5 (50 to 100 mbar) C6 (90 to 150 mbar) C7 (150 to 240 mbar) C8 (240 to 400 mbar)
Structure
N/A 1+0 B1 1+1
(Only for Type RB)
C1 2+0
(Only for Type RB)
Center Distance
None Default
(RB/RBT=155 mm, RBQ/RBQT=300 mm)
F1 280 mm
Nameplate Manual and Manual Language E English None Simplied
Chinese
Emerson Process Management Asia Pacific Pte Ltd
1 Pandan Crescent
Singapore 128461 T: +65 6777 8211 F: +65 6770 8028
FISHER JEON Gas Equipment (Chengdu) Co., Ltd
No. 9, Wukedong 2nd Road, Wuhou Science Technic Park, Chengdu, 610045, P.R. China T: +86 28 85360000 F: +86 28 85371201
Service T: +86 28 85366930 or +86 28 85360000 Ext. 1613
PressureManagement.AP@emerson.com
www.emerson.com
Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Jeon is a mark owned by one of the businesses of Emerson Automation Solutions. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales
are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specications of
such products at any time without notice.
Emerson Process Management Chennai Ltd
Plot No. 5, 6, 7 and 8 Self Help Industrial Estate
Keelkattalai, Chennai, India - 600117 T +91 44 4903 4405 F +91 44 4903 4400
Loading...