Failure to follow these instructions or
to properly install and maintain this
equipment could result in an explosion
and/or re causing property damage and
personal injury or death.
Fisher® regulators must be installed,
operated, and maintained in accordance
with federal, state, and local codes,
rules and regulations, and Emerson
Process Management Regulator
T echnologies, inc. instructions.
For LP-gas service, an approved
regulator (such as one listed by UL)
should be used or approved by the
authority Having Jurisdiction. The
installation in most states, must comply
with nFPa 58 standard.
if the regulator vents gas or a leak
develops in the system, service to the unit
may be required. Failure to correct trouble
could result in a hazardous condition.
Call a gas service person to service
the unit. Only a qualied person must
install or service the regulator.
introduction
Scope of the Manual
This manual provides instructions for the installation,
adjustment, maintenance, and parts ordering information
for the Type R622 pressure reducing regulator.
Product Description
Type R622 direct-operated, spring-loaded regulators
provide economical pressure reducing control in
a variety of residential, commercial, and industrial
applications. These regulators can be used with
natural, manufactured, or liqueed petroleum gases and
have the same inlet and outlet pressure capabilities.
In addition, Type R622 regulators have internal relief
across the diaphragm to help minimize overpressure.
Any outlet pressure above the start-to-discharge point
of the nonadjustable relief valve spring moves the
diaphragm off the relief valve seat, allowing excess
pressure to bleed out through the screened spring
case vent.
Specications
The Specications section lists operating conditions
and other specications of the Type R622 regulator.
Information specic to a regulator’s construction is
stamped on the nameplate.
Principle of Operation
Refer to Figure 2. When downstream demand
decreases, the pressure under the diaphragm
increases. This pressure overcomes the regulator
setting (which is set by a spring). Through the action
of the pusher post assembly, lever, and valve stem,
the valve disk moves closer to the orice and reduces
gas ow. If demand downstream increases, pressure
under the diaphragm decreases. Spring force
pushes the pusher post assembly downward and the
valve disk moves away from the orice. Type R622
regulators include an internal relief valve used to help
minimize overpressure. Any outlet pressure above
ORiFiCE
Figure 2. Type R622 Operational Schematic
STEM
the start-to-discharge point of the non-adjustable
relief spring moves the diaphragm off of the relief
seat, allowing excess pressure to discharge through
the vent.
installation
Personal injury, equipment damage,
or leakage due to escaping gas or
bursting of pressure-containing parts
might result if these regulators are
overpressured or installed where
service conditions could exceed the
limits for which the regulators were
designed, or where conditions exceed
any ratings of the adjacent piping or
piping connections. To avoid such
injury or damage, provide pressurerelieving or pressure-limiting devices
(as required by the appropriate code,
regulation or standard) to prevent
service conditions from exceeding
those limits.
additionally, physical damage to a
regulator could cause personal injury
and property damage due to escaping
LEVER
WaRning
!
3
Page 4
Type R622
gas. To avoid such injury and damage,
install the regulator in a safe location.
a regulator may vent some gas to the
atmosphere in hazardous or ammable
gas service, vented gas might accumulate
and cause personal injury, death or
property damage due to re or explosion.
Vent a regulator in hazardous gas service
to a remote, safe location away from
air intakes or any hazardous location.
The vent line must be protected against
condensation or clogging.
Before installing the regulator, check for damage
which might have occurred in shipment. Also check
for dirt or foreign matter which may have accumulated
in the regulator body or in the pipeline. Apply pipe
compound to the external threads of the pipeline and
install the regulator so that the ow is in the direction
of the arrow cast on the side of the body. The
diaphragm actuator assembly can be rotated to any
position relative to the body, in 90° increments.
Do not install the regulator in a location where there
can be excessive water accumulation, such as directly
beneath a downspout or in an undrained pit.
To obtain the maximum ow capacities or other
performance characteristics, the length of pipe from the
regulator outlet to the meter—or for the rst 18-inches
(457 mm), whichever is closer—should have no bends
and should be the same size as the regulator outlet.
Replace the regulator if water gets into the spring case
or the lower casing of the regulator.
Type R622 regulators have a spring case vent
(3/4 NPT) which is screened to prevent insects or
foreign material from entering.
TO aPPLianCE
VEnT aSSEMBLY
VEnT LinE
BaSEMEnT
B2497
Figure 3. Typical Vent Line Installation
precautions apply to vent assemblies as the integral
regulator vents described previously.
A program of regular inspection of the vent opening
should be established to see that it has not become
plugged by foreign material. On some installations,
such as in areas of heavy snowfall, it may be
necessary to install the regulator beneath a protective
hood. If other protection is provided from the elements,
the vent should be pointing or sloping down sufciently
to allow any condensate to drain. Also check the
regulator periodically for external or internal corrosion.
Overpressure Protection
WaRning
!
CaUTiOn
You are advised to use new vent piping
because defective threads on the relief
vent piping may interfere with the venting
assembly if the piping obstructs the
movement of the vent apper.
On indoor installations, the vent should be piped
outside the building, see Figure 3. Remove the screen
from the regulator vent connection and connect vent
piping from that connection to the outdoors. Vent
piping should be as large in diameter as practical, be
as short as possible, and have a minimum number
of bends and elbows. Install a weather and insect
resistant vent assembly on the outside end of the
pipe, such as a Type Y602. The same installation
4
Some type of overpressure protection
is needed if actual inlet pressure can
exceed the outlet pressure rating.
Overpressuring any portion of this
equipment above the limits given in the
Specication section and table 1 may
cause damage to regulator parts, leaks
in the regulator, or personal injury due to
bursting of pressure-containing parts or
explosion of accumulated gas.
Type R622 regulators provide internal relief that limits
the total outlet pressure build-up over setpoint. This
internal relief may be adequate for most application,
if not, provide additional pressure relief or a pressurelimiting device downstream. Regulators should be
inspected for damage after any overpressure condition.
Page 5
Type R622
Startup
WaRning
!
To avoid personal injury or property
damage due to explosion or damage to
regulator or downstream components
during startup, release downstream
pressure to prevent an overpressure
condition on the diaphragm of
the regulator.
in order to avoid an overpressure
condition and possible equipment
damage, pressure gauges should
always be used to monitor pressures
during startup.
1. Check to see that all appliances are turned off.
2. Slowly open the upstream shutoff valve.
3. Slowly open the downstream shutoff valve
4. Check all connections for leaks.
5. Make nal control spring adjustments according to
the adjustment procedures.
6. Light the appliance pilots.
adjustment
To increase the outlet pressure setting of the regulator,
the adjusting screw (key 23, Figure 5) must be turned
clockwise. This requires removal of the closing cap
(key 31, Figure 5). To reduce the outlet pressure
setting, turn the adjusting screw counterclockwise.
A pressure gauge should always be used to monitor
downstream pressure while adjustments are being
made. Do not adjust the spring to produce an outlet
pressure setting above the limit identied on the
information label. If the required pressure setting is not
within the range of the spring being used, substitute
with the correct spring, see Table 1. When changing
the spring, also change the range identied on the
information label to indicate the actual pressure range
of the spring in use. After the spring adjustment has
been completed, replace the closing cap.
Shutdown
WaRning
!
To avoid personal injury or property
damage due to explosion or damage to
regulator or downstream components
during shutdown, release downstream
pressure to prevent an overpressure
condition on the regulator diaphragm.
Installation arrangements may vary, but in any
installation it is important that the valves be
opened or closed slowly. These steps apply to the
typical installation.
1. Slowly close the downstream shutoff valve.
2. Slowly close the upstream shutoff valve.
3. Open vent valves downstream of the regulator.
4. Open vent valves upstream of the regulator.
Maintenance
WaRning
!
avoid personal injury or damage to
property from sudden release of pressure
or uncontrolled gas or other process
uid. Before starting to disassemble,
isolate the regulator from all pressure and
cautiously release trapped pressure from
the regulator. Use gauges to monitor
inlet, loading and outlet pressures while
releasing these pressures.
These procedures are for gaining access to the
diaphragm, valve disk and orice. All pressure must be
released from the diaphragm actuator assembly before
the following steps can be performed.
While using the following procedures, refer to Figure 5
for key number locations.
Diaphragm and Disk Replacement
1. Remove the closing cap (key 31) and adjusting
screw (key 23).
2. Remove the spring case machine screws (key 4) out
of the spring case (key 25), and remove the spring
case and control spring (key 22).
3. Lift the diaphragm assembly slightly, and slide it
away from the lever (key 27), so that the pusher
post (key 18) releases the lever.
4. Remove the diaphragm assembly (key 17). Examine
the diaphragm assembly , replace if necessary.
5. Reassemble in the reverse order of the above
procedures. Place the diaphragm assembly into
position in the body (key 1), being sure the pusher
post is properly hooked on the lever (key 27).
Rotate the diaphragm so that the diaphragm and
lower casing holes align. Check the diaphragm
for proper orientation. Tighten the spring case
machine screws (key 4) to 15 to 30-inch-pounds
(2 to 4 N•m).
6. To remove the disk follow steps 1 through 4.
7. Remove screws (key 4).
5
Page 6
Type R622
8. Remove lever (key 27)
9. Remove stem assembly (key 28)
10. Remove disk (key 33) from stem assembly
(key 28). Examine the disk. If it is nicked, cut, or
otherwise damaged, the disk should be replaced.
11. Put together in reverse order.
Inlet Screen and Orice Replacement
1. Remove the regulator from line.
2. Remove machine screws (key 4).
3. Remove inlet O-ring (key 5). Lubricate a new inlet
O-ring and place on inlet tting (key 3).
4. Remove inlet screen (key 13). Clean and/or
replace the inlet screen, if necessary.
5. Install the inlet screen (key 13) and inlet tting
(key 3). Then install and tighten the machine
screws (key 4) to 15 to 30-inch-pounds-force (2 to
4 N•m).
6. To replace the orice, follow steps 1 through 4,
and then remove orice (key 24) from body.
Examine the seating edge of the orice. If it is
nicked or rough, it should be replaced. Treat the
external threads of the new orice with lubricant
before reassembling, tightening to 15 to
20-inch-pounds (2 to 3 N•m) of torque.
7. Install the inlet screen (key 13) and inlet tting
(key 3). Then install and tighten the machine
screws (key 4) to 15 to 30-inch-pounds-force
(2 to 4 N•m).
Parts Ordering
The type number, orice size, spring range, and date
of manufacture are located on the spring case. Always
provide this information in any correspondence with
your local Sales Ofce regarding replacement parts
or technical assistance. If construction changes are
made in the eld, be sure that the information label is
also changed to reect the most recent construction.
Parts List
Key Description Part number
1 Body, Aluminum T80567T0GY2
2 Pipe Plug, Carbon steel (2 required) 1D8293T0022
3 Inlet Fitting, Aluminum T21176T0BK2
4 Machine Screw, Carbon Steel (12 required) T13526T0012
5 O-Ring, Nitrile (NBR) T14431T0012
13 Inlet Screen, 18-8 Stainless steel T14436T0012
16 Relief Spring, 302 Stainless steel T13612T0012
17 Diaphragm T21163T0012
18 Pusher Post, Acetal T40653T0012
19 Lower Spring Seat, Zinc-plated steel T14396T0012
20 Relief Spring Retainer, 18-8 Stainless steel T13613T0012
22 Spring, Zinc-plated steel See Table 1
23 Adjusting Screw, Delrin
For use with inches w.c. springs T21186T0012
For use with psig spring T21202T0012
is a mark owned by E.I. du Pont de Nemours and Co.
6
Page 7
POSiTiOn 1
38
13
4
24
33
282930
27181
2
4
4142
17
19
16
2022
23
3125
26
5
3
VEnT OVER inLET
POSiTiOn 2POSiTiOn 4
Type R622
T80577
Figure 4. Vent Location
POSiTiOn 3
VEnT OVER OUTLET
T80577
Figure 5. Type R622 Regulator Assembly
7
Page 8
Type R622
2
4142
Figure 5. Type R622 Regulator Assembly (continued)
industrial Regulators
Emerson Process Management
Regulator Technologies, inc.
USA - Headquarters
McKinney, Texas 75069-1872 USA
Tel: 1-800-558-5853
Outside U.S. 1-972-548-3574
Asia-Pacic
Shanghai, China 201206
Tel: +86 21 2892 9000
Europe
Bologna, Italy 40013
Tel: +39 051 4190611
Middle East and Africa
Dubai, United Arab Emirates
Tel: +971 4811 8100
For further information visit www.emersonprocess.com/regulators
The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are the property of their prospective owners. Fisher is a mark owned by Fisher Controls, Inc., a
business of Emerson Process Management.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or
guarantees, express or implied, regarding the products or services described herein or their use or applicability. We reserve the right to modify or improve the designs or specications of such
products at any time without notice.
Emerson Process Management does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any Emerson
Process Management product remains solely with the purchaser.
natural gas Technologies
Emerson Process Management
Regulator Technologies, inc.
USA - Headquarters
McKinney, Texas 75069-1872 USA
Tel: 1-800-558-5853
Outside U.S. 1-972-548-3574
Asia-Pacic
Singapore, Singapore 128461
Tel: +65 6777 8211
Europe
Bologna, Italy 40013
Tel: +39 051 4190611
Gallardon, France 28320
Tel: +33 (0)2 37 33 47 00
TESCOM
Emerson Process Management
Tescom Corporation
USA - Headquarters
Elk River, Minnesota 55330-2445 USA
Tel: 1-763-241-3238
Europe
Selmsdorf, Germany 23923
Tel: +49 (0) 38823 31 0