Bulletin LP - 7: R622E / R652E
Types R622E and R652E 2-PSI (0,14 bar)
Service Regulators
Introduction
The Types R622E and R652E 2-PSI (0,14 bar) service
regulators are Underwriters Laboratories listed regulators
designed for Two PSI (0,14 bar) LP-Gas systems.
The units are installed downstream from a rst-stage
regulator to reduce an inlet pressure of 10 psig (0,69
bar) to a nominal 2 psig (0,14 bar) outlet pressure. The
2 PSIG (0,14 bar) LP-Gas is supplied to a line regulator
located inside the building. In most cases a manifold
is used with corrugated stainless steel tubing (CSST)
as well as other acceptable piping materials for routing
to the line regulator. The Type R622E incorporates the
standard straight-through body while the Type R652E is
designed for back mount installations. Both units have
white closing caps for easy identication of the 2 psig
(0,14 bar) setting. Screened drip-lip vents are oriented
over the inlet as standard.
Features
• 20-Year Recommended Replacement Life — The
Types R622E and R652E are designed using rugged
time proven design concepts with enhancements to the
corrosion resistance and durability of materials, both materials, bothmaterials, both
internally and externally. With proper installation and
periodic inspection and maintenance the Types R622E
and R652E designs have a 20 Year Recommended
Replacement Life. In some environmental conditions
earlier replacement may be required.
• Improved Regulations — Fisher’s large molded
fabric-reinforced diaphragm and spring assisted vent
stabilizer deliver accurate, stable regulation.
Figure 1. Type R622E and R652E 2-PSI Service Regulators
• Superior Overpressure Protection — The
combination of a high capacity relief valve and large
vent provide overpressure protection which exceeds
UL standards.
• Inlet Screen — Fisher’s stainless steel inlet screen
reduces the amount of debris entering the regulator.
• Easy System Checks — 1/8 inch NPT inlet and
outlet gauge taps oriced to a number 54 drill size are
easily accessible for gas system checks.
• Positive Drainage — When installed properly
with the spring case pointed down the Fisher Positive
Drainage design allows any moisture formed in the
spring case to drain out eliminating the problems with
corrosion and freezing of the water in the spring case.
TYPE R622E
January 2004
TYPE R652E
Table 1. Ordering Information
TYPE
NUMBER
R622E-BCH 1,250,000 1/2 inch x 1/2 inch FNPT
R622E-DCH 1,500,000
R652E-DFH 1,400,000
1. Capacities are based on 10 psig (0,69 bar) inlet pressure and 20% droop.
CAPACITY BTU/HR
PROPANE
(1)
CONNECTIONS
INLET x OUTLET
3/4 inch x 3/4 inch FNPT
www.FISHERregulators.com/lp
OUTLET ADJUSTMENT
SETTING
2 psig
(0,14 bar)
OUTLET PRESSURE
RANGE
1 to 2.2 psig
(0,07 to 0,15 bar)
D450137T012
Bulletin LP - 7: R622E / R652E
Table 2. Selected Capacities for Type R622E/R652E Second-Stage Regulators
OUTLET PRESSURE SETTING,
SPRING RANGE
2 psig
(0,14 bar) setting,
1 to 2.2 psig
(0,07 to 0,15 bar)
1. Capacities are based on 20 inch w.c. (50,00 mbar) droop.
INLET PRESSURE,
PSIG (bar)
10 (0,69) 1,460 1,680 1,500
3/4-14 NPT
SCREENED VENT
1/8-27 NPT
INLET AND OUTLET
GAUGE TAPS
1/2 OR 3/4 NPT
INLET FITTING
5 (0,34) 930 1,030 930
3.63
(92)
1/2-Inch (DN 15) Body 3/4-Inch (DN 20) Body 3/4-Inch (DN 20) Body
4.45
(113)
TYPE R622E
CAPACITIES IN THOUSANDS BTU/HR PROPANE
Type R622E Type R652E
5.25
(134)
5.01
(127)
7.46
(189)
6.11
(155)
5.56
(141)
3.01
(76)
5.41
1.11
(28,2)
(137)
1/2 OR 3/4 NPT
OUTLET
TAPPED FOR 1/4-20
MOUNTING SCREWS
(1)
3/4-14 NPT
SCREENED
VENT
3/4 NPT
INLET FITTING
1/8-27 NPT
INLET AND
OUTLET
GAUGE TAPS
5.41
(137)
6.41
(165)
1.63
(41,4)
3/4 NPT
OUTLET
5.71
(145)
TYPE R652E
Figure 4. Types R622E and R652E Dimensions Inches (mm)
Fisher and Fisher Regulators are marks owned by Fisher Controls International, LLC. The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are the
property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, expressed
or implied, regarding the products or services described herein or their use or applicability. We reserve the right to modify or improve the designs or specications of such products at any time
without notice.
Fisher does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any Fisher product remains solely with
the purchaser.
Emerson Process Management
Fisher Controls International, LLC.
P.O. Box 8004
McKinney, Texas 75070, USA
Telephone: 1 (800) 558-5853
Telephone: 1 (469) 293-4201
©Fis her Cont rols Interna tio nal, LLC., 2003, 2004; All R igh ts Reserv ed
www.FISHERregulators.com/lp