Installation, Pneumatic and Electrical Connections,
and Initial Configuration3.....................
Scope of Manual3..............................
Conventions Used in this Manual3................
Description4..................................
Specifications4................................
Related Documents8...........................
Educational Services9...........................
Section 2 Wiring Practices10.............
Control System Requirements10.................
HART Filter10................................
Voltage Available10...........................
Compliance Voltage11........................
Auxiliary Terminal Wiring Length Guidelines13....
Maximum Cable Capacitance12.................
Local Control Panel14...........................
Installaton14.................................
Electrical Connections14.......................
Section 3 Configuration16...............
Guided Setup16...............................
Manual Setup16...............................
Mode and Protection18........................
Instrument Mode18.......................
Write Protection18........................
Instrument19................................
Identification19...........................
Serial Numbers19.........................
Units19..................................
Terminal Box19...........................
Spec Sheet20.............................
Edit Instrument Time20....................
X0079
Travel/Pressure Control20......................
End Point Pressure Control20................
Characterization21........................
Dynamic Response22......................
Travel Cutoffs22..........................
Tuning22....................................
Travel Tuning22...........................
Integral Settings26........................
Valve and Actuator26..........................
SIS/Partial Stroke Test29.......................
Partial Stroke Test Parameters29.............
Partial Stroke Parameters30.................
PST Abnormal Criteria32...................
PST Abort Criteria33.......................
PST Prohibited33..........................
SIS Options34............................
Solenoid Valve Test34.........................
Instrument Configuration35................
SOV Test Parameters35....................
SOV Test Alerts36.........................
Outputs36...................................
Output Terminal Configuration36............
Switch Configuration36....................
HART Variable Assignments37..............
Transmitter Output37.....................
Burst Mode37............................
Alert Setup38.................................
Change to HART 5 / HART 738....................
June 2022
www.Fisher.com
DVC6200 SIS Digital Valve Controller
June 2022
Instruction Manual
D103557X012
Contents (continued)
Section 4 Calibration39.................
Calibration Overview39.........................
Travel Calibration40...........................
Auto Calibration40........................
Manual Calibration41......................
Pushbutton Calibration42..................
Sensor Calibration43..........................
Pressure Sensors43........................
Analog Input Calibration44.................
Relay Adjustment45...........................
Double‐Acting Relay45.....................
Single‐Acting Relays46.....................
PST Calibration47.............................
SOV Test Calibration47........................
Section 5 Device Information, Alerts and
Diagnostics48.........................
Overview48...................................
Status & Primary Purpose Variables48............
Device Information48.........................
Service Tools49................................
Device Status49..............................
Alert Record49...............................
Alert Reporting49.............................
Deadband Principle of Operation53..............
Diagnostics55................................
Stroke Valve55............................
Partial Stroke Test55.......................
Demand Mode Tests56.....................
Solenoid Valve Health Monitoring60.........
Variables60...................................
Section 6 Maintenance and
Troubleshooting62.....................
Replacing the Magnetic Feedback Assembly63......
Module Base Maintenance63.....................
Tools Required63.............................
Component Replacement64....................
Removing the Module Base64..................
Replacing the Module Base65...................
Submodule Maintenance66......................
I/P Converter66...............................
Printed Wiring Board (PWB) Assembly68..........
Pneumatic Relay69............................
Spool Valve70................................
Seal Retainer71...............................
Gauges, Pipe Plugs or Tire Valves72..............
Terminal Box72................................
Removing the Terminal Box73..................
Replacing the Terminal Box73...................
Troubleshooting74.............................
Checking Voltage Available74....................
Restart Processor74............................
DVC6200 SIS Technical Support Checklist77........
Section 7 Parts78......................
Parts Ordering78...............................
Parts Kits78...................................
PWB Assembly78.............................
Parts List80...................................
Housing80...................................
Common Parts80.............................
Module Base80...............................
I/P Converter Assembly80......................
Relay80.....................................
Spool Valve80................................
Terminal Box81...............................
Feedback Connection Terminal Box81............
Pressure Gauges, Pipe Plugs, or Tire
Valve Assemblies81.........................
DVC6215 Feedback Unit81.....................
HART Filter81................................
Line Conditioner81............................
Appendix A Principle of Operation92......
HART Communication92........................
DVC6200 SIS Digital Valve Controller92............
Appendix B Device Communicator
Menu Tree97........................
Glossary107...........................
Index115.............................
2
Instruction Manual
D103557X012
Section 1 Introduction
Installation, Pneumatic and Electrical Connections,
and Initial Configuration
Introduction
June 2022
Refer to the DVC6200 Series Quick Start Guide (D103556X012) for DVC6200 SIS
installation, connection, and initial configuration information. If a copy of the quick
start guide is needed scan or click the QR code at the right, contact your Emerson
sales office or visit our website at Fisher.com.
Scan or click
to access
field support
Scope of Manual
This instruction manual is a supplement to the DVC6200 Series Quick Start Guide (D103556X012) and Safety manual
(D103601X012
materials, custom setup information, maintenance procedures, and replacement part details.
Note
The information included in this instruction manual also applies to the DVC6200 SIS High Cv. Specifications, setup information,
maintenance procedures, and replacement part details unique to the DVC6200 SIS High Cv are noted.
This instruction manual describes using an Emerson DeviceCommunicator to set up and calibrate the instrument. You
can also use Fisher ValveLink
using ValveLink software with the instrument refer to ValveLink software help or documentation.
Note
DVC6200 SIS High Cv requires ValveLink software 13.6 or higher to set up, configure, and calibrate the instrument.
) that ship with every instrument. This instruction manual includes product specifications, reference
™
software to setup, calibrate, and diagnose the valve and instrument. For information on
Do not install, operate, or maintain a DVC6200 SIS digital valve controller without being fully trained
and qualified in valve, actuator, and accessory installation, operation, and maintenance. To avoid
personal injury or property damage, it is important to carefully read, understand, and follow all of the
contents of this manual, including all safety cautions and warnings. If you have any questions about
these instructions, contact your Emerson sales office before proceeding.
Conventions Used in this Manual
Navigation paths and fast‐key sequences are included for procedures and parameters that can be accessed using the
Device Communicator.
Refer to Appendix B for Device Communicator menu trees.
Note
Fast-key sequences are only applicable to the 475 Field Communicator. They do not apply to the Trex
™
Device Communicator.
3
Introduction
June 2022
Fast -key sequences are not applicable to the DVC6200 SIS High Cv. ValveLink software 13.6 or higher is required to set up and
calibrate a DVC6200 SIS High Cv.
Figure 1‐1. FIELDVUE DVC6200 SIS Digital Valve Controller Mounted on a Bettis Quarter-Turn Actuator
X0079
Instruction Manual
D103557X012
Description
DVC6200 SIS digital valve controllers (figure 1‐1) are HART communicating, microprocessorbased
currenttopneumatic instruments. The DVC6200 SIS digital valve controller has three fundamental functions.
1. Modulate a pneumatic output to a valve actuator in response to a demand signal from a logic solver to move the
valve to a safe state.
2. Perform periodic tests on a valve assembly to exercise the mechanical components that are prone to sticking.
3. Continuously monitor the health of the valve and report alerts.
Specifications
WARNING
Refer to table 1‐1 for specifications. Incorrect configuration of a positioning instrument could result in the malfunction of
the product, property damage or personal injury.
Specifications for DVC6200 SIS digital valve controllers are shown in table 1‐1. Specifications for the Device
Communicator can be found in the Device Communicator quick start guide
.
4
Instruction Manual
D103557X012
Table 1‐1. Specifications
Introduction
June 2022
Available Mounting
J Sliding‐stem linear applications
J Quarter‐turn rotary applications
J Integral mounting to Fisher rotary actuators
J Integral mounting to Fisher 657/667 or GX
actuators
DVC6200 SIS digital valve controllers can also be
mounted on other actuators that comply with
IEC 60534‐6‐1, IEC 60534‐6‐2, VDI/VDE‐3845, and
NAMUR mounting standards
Mounting the instrument vertically, with the vent at
the bottom of the assembly, or horizontally, with the
vent pointing down, is recommended to allow
drainage of moisture that may be introduced via the
instrument air supply
Communication Protocol
J HART 5 or J HART 7
Input Signal
Point-to-Point
Analog Input Signal: 4‐20 mA DC, nominal
Minimum Voltage Available at Instrument Terminals
must be 9.5 VDC for analog control, 10 VDC for HART
communication
Minimum Control Current: 4.0 mA
Minimum Current w/o Microprocessor Restart: 3.5 mA
Maximum Voltage: 30 VDC
Overcurrent protected
Reverse Polarity protected
Multi-Drop
Instrument Power: 11 to 30 VDC at 10 mA
Reverse Polarity protected
Supply Pressure
(1)
Minimum Recommended
DVC6200 SIS w/Low Bleed Relay
0.3 bar (5 psig) higher than maximum
actuator requirements
(
DVC6200 SIS High Cv (HCv1, HCv2, HCv3)
2)
2.8 bar (40 psig) required
Maximum: 10.0 bar (145 psig) or maximum pressure
rating of the actuator, whichever is lower
‐continued‐
Medium: Air or Natural Gas
Supply medium must be clean, dry and noncorrosive
Per ISA Standard 7.0.01
A maximum 40 micrometer particle size in the air
system is acceptable, however, the DVC6200 SIS
High Cv requires a maximum 5 micrometer particle
size. Further filtration down to 5 micrometer particle
size for other applications is recommended as well.
Lubricant content is not to exceed 1 ppm weight
(w/w) or volume (v/v) basis. Condensation in the air
supply should be minimized
Per ISO 8573-1
Maximum particle density size: Class 7
Oil content: Class 3
Pressure Dew Point: Class 3 or at least 10_C less than
the lowest ambient temperature expected
Output Signal
Pneumatic Output: up to full supply pressure
Maximum Span: 9.5 bar (140 psig)
Action: Double, Single Direct, or Single Reverse
Note: HCv3 is only available for Single Direct action
Electronic Output
Integral 4‐20 mA Position Transmitter:
J
(3)
4‐20 mA output, isolated
Supply Voltage: 8‐30 VDC
Reference Accuracy: 1% of travel span
Safety Accuracy: 5% of travel span
The position transmitter meets the requirements of
NAMUR NE43; selectable to show failure high
( > 22.5 mA) or failure low (< 3.6 mA). Fail high only
when the positioner is powered.
J Integral Switch:
One isolated switch, configurable throughout the
calibrated travel range or actuated from a device
alert
Off State: 0 mA (nominal)
On State: up to 1 A
Supply Voltage: 30 VDC maximum
Reference Accuracy: 2% of travel span
Safety Accuracy: 5% of travel span
5
Introduction
June 2022
Table 1‐1. Specifications (continued)
Steady State Air Consumption
DVC6200 SIS w/Low Bleed Relay
At 1.4 bar (20 psig) supply pressure:
0.056 normal m
At 5.5 bar (80 psig) supply pressure:
0.184 normal m
3
/hr (2.1 scfh), average
3
/hr (6.9 scfh), average
DVC6200 SIS High Cv:
At 3.4 bar (50 psig) supply pressure
HCv1
Pressurized: 0.033 normal m
Vented: 0.129 normal m
HCv2
Pressurized: 0.039 normal m
Vented normal: 0.173 m
3
HCv3
Pressurized: 0.144 normal m
Vented: 0.179 normal m
Meets EN 61326‐1:2021
Immunity‐Industrial locations per Table 2 of the
EN 61326‐1 standard. Performance is
shown in table 1‐2 below.
Emissions-Class A
ISM equipment rating: Group 1, Class A
Vibration Testing Method
Tested per ANSI/ISA S75.13.01 Section 5.3.5
(4)(5)
(6)
:
3
/hr (1.25 scfh)
3
/hr (4.82 scfh)
3
/hr (1.49 scfh)
/hr (6.48 scfh)
3
/hr (5.38 scfh)
3
/hr (6.70 scfh
(4)(5)
(5)
(1)(7)
Instruction Manual
D103557X012
Input Load Impedance
An equivalent impedance of 500 ohms may be used.
This value corresponds to 10V @ 20 mA.
Ignition-proof, Non-Incendive
ATEX— Intrinsically Safe, Flameproof, Type n,
Dust by intrinsic safety
IECEx— Intrinsically Safe, Flameproof, Type n,
Dust by intrinsic safety and enclosure
Auxiliary Terminal Contact: Nominal Electrical
Rating 5 V, <1 mA; It is recommended that the
switch be sealed or have gold plated contacts to
avoid corrosion
Electrical Housing
CSA— Type 4X, IP66
FM— Type 4X, IP66
ATEX— IP66
IECEx— IP66
Other Classifications/Certifications
Lloyds Register— Marine Type Approval
CML— Certification Management Limited (Japan)
CUTR— Customs Union Technical Regulations
(Russia, Kazakhstan, Belarus, and Armenia)
ESMA— Emirates Authority for Standardization and
Metrology - ECAS-Ex (UAE)
INMETRO— National Institute of Metrology, Quality,
and Technology (Brazil)
KOSHA— Korean Occupational Safety & Health
Agency (South Korea)
KTL— Korea Testing Laboratory (South Korea)
CCC— China Compulsory Certification
NEPSI— National Supervision and Inspection Centre
for Explosion Protection and Safety of
Instrumentation (China)
PESO CCOE— Petroleum and Explosives Safety
Organisation - Chief Controller of Explosives (India)
‐continued‐
6
Instruction Manual
D103557X012
Table 1‐1. Specifications (continued)
Introduction
June 2022
Other Classifications/Certifications (continued)
SANS— South Africa National Standards
Contact your Emerson sales office
for
classification/certification specific information
IEC 61010 Compliance Requirements
Power Source: The loop current must be derived from
a separated extra‐low voltage (SELV) power source
Environmental Conditions: Installation Category I
Connections
DVC6200 SIS w/Low Bleed Relay:
Supply Pressure: 1/4 NPT internal and integral pad for
mounting Fisher 67CFR regulator
Recommended tubing size at least equal to port
connection size
Minimum inside diameter required
HCv1: 7.11 mm (0.28 inch)
HCv2: 11.7 mm (0.46 inch)
HCv3: 16.5 mm (0.65 inch)
Electrical: 1/2 NPT internal or M20
Actuator Compatibility
Sliding-Stem Linear
Linear actuators with rated travel between 6.35 mm
(0.25 inch) and 606 mm (23.375 inches)
Quarter‐Turn Rotary
Rotary actuators with rated travel between
45 degrees and 180 degrees
(9)
Weight
Aluminum
DVC6200 SIS w/Low Bleed Relay: 3.5 kg (7.7 lbs)
DVC6200 SIS High Cv: 6.5 kg (14.3 lbs)
J Supply and output pressure gauges or tire valves
J Integral mounted filter regulator
J Standard Bleed Relay J Remote mount
trip
J
LCP100 local control panel J LCP200 local control
panel
J Fisher LC340 line conditioner J Stainless
steel
J DVC6200 SIS High Cv
(10)
J Energize to
(11)(12)
Declaration of SEP
Fisher Controls International LLC declares this
product to be in compliance with Article 4 paragraph
3 of the PED Directive 2014/68/EU. It was designed
and manufactured in accordance with Sound
Engineering Practice (SEP) and cannot bear the CE
marking related to PED compliance.
However, the product may bear the CE marking to
indicate compliance with other applicable European
Community Directives.
NOTE: Specialized instrument terms are defined in ANSI/ISA Standard 51.1 – Process Instrument Terminology.
1. The pressure/temperature limits in this document and any other applicable code or standard should not be exceeded.
2. HCv1: 1.2 Cv spool valve, needs a minimum 8 inch diameter cylinder/ diaphragm.
2. HCv2: 3.2 Cv spool valve, needs a minimum 12 inch diameter cylinder or 220 inch
2. HCv3: 6.2 Cv spool valve, needs a minimum 12 inch diameter cylinder or 220 inch
3. The electronic output is available with either the position transmitter or the switch.
4. Normal m
5. Values at 1.4 bar (20 psig) based on single‐acting direct relay; values at 5.5 bar (80 psig) based on double‐acting relay.
6. The Quad O steady-state consumption requirement of 6 scfh can be met by a DVC6200 SIS with low bleed relay A option, when used with up to 4.8 bar (70 psi) supply
of Natural Gas at 16_C (60_F). The 6 scfh requirement can be met by low bleed relay B and C when used with up to 5.2 bar (75 psi) supply of Natural Gas at 16_C (60_F).
7. Temperature limits vary based on hazardous area approval. Lower temperature limit for CUTR Ex d approval with fluorosilicone elastomers is -53_C (-63.4_F).
8. Not applicable for travels less than 19 mm (0.75 inch) or for shaft rotation less than 60 degrees. Also not applicable for digital valve controllers in long-stroke applications
over 4-inch.
9. Rotary actuators with 180 degree rated travel require a special mounting kit; contact your Emerson sales office for kit availability.
10. An integral mounted filter regulator is not available with the DVC6200 SIS High Cv.
11. 4‐conductor shielded cable, 18 to 22 AWG minimum wire size, in rigid or flexible metal conduit, is required for connection between base unit and feedback unit.
Pneumatic tubing between base unit output connection and actuator has been tested to 91 meters (300 feet). At 15 meters (50 feet) there was no performance
degradation. At 91 meters there was minimal pneumatic lag.
12. The position monitor (transmitter or switch) with the remote mount construction is not safety certified.
3
/hour – Normal cubic meters per hour at 0_C and 1.01325 bar, absolute. Scfh – Standard cubic feet per hour at 60_F and 14.7 psia.
2
diaphragm area.
2
diaphragm area.
7
Introduction
June 2022
Instruction Manual
D103557X012
Table 1‐2. EMC Summary Results—Immunity
PortPhenomenonBasic StandardTest Level
Electrostatic discharge (ESD)IEC 61000‐4‐2
Enclosure
I/O signal/control
Performance criteria: +/- 1% effect.
1. A = No degradation during testing. B = Temporary degradation during testing, but is self‐recovering.
2. Supplementary immunity testing performed from 1.4 GHz to 10 GHz to meet EN 61326-1:2021 requirements.
Radiated EM fieldIEC 61000‐4‐3
Rated power frequency
magnetic field
BurstIEC 61000‐4‐41 kVA
SurgeIEC 61000‐4‐51 kVB
Conducted RFIEC 61000‐4‐6150 kHz to 80 MHz at 3 VrmsA
IEC 61000‐4‐830 A/m at 50/60HzA
4 kV contact
8 kV air
80 to 1000 MHz @ 10V/m with 1 kHz AM at 80%
1400 to 2000 MHz @ 3V/m with 1 kHz AM at 80%
2000 to 2700 MHz @ 1V/m with 1 kHz AM at 80%
2700 to 6000 MHz @ 10V/m with 1 kHz AM at 80%
(2)
Performance
Criteria
A
A
(1)
Related Documents
This section lists other documents containing information related to the DVC6200 SIS digital valve controller. These
documents include:
D Bulletin 62.1:DVC6200 SIS FIELDVUE DVC6200 SIS Digital Valve Controller (D103555X012
D Bulletin 62.1:DVC6200(S1) FIELDVUE DVC6200 Digital Valve Controller Dimensions (D103543X012
)
)
D Bulletin 62.1:Digital Valve Controller - Fisher FIELDVUE Digital Valve Controller Product Selection (D104363X012
D FIELDVUE DVC6200 Series Quick Start Guide (D103556X012
D CSA Hazardous Area Approvals - DVC6200 Series Digital Valve Controllers (D104203X012
D FM Hazardous Area Approvals - DVC6200 Series Digital Valve Controllers (D104204X012
D ATEX Hazardous Area Approvals - DVC6200 Series Digital Valve Controllers (D104205X012
D IECEx Hazardous Area Approvals - DVC6200 Series Digital Valve Controllers (D104206X012
D FIELDVUE DVC6200 SIS Safety Manual (D103601X012
D HART Field Device Specification for FIELDVUE DVC6200 SIS (D103638X012
)
)
)
)
)
)
)
D Monitoring Health of External Solenoid Valve (SOV) with FIELDVUE DVC6200 SIS Digital Valve Controllers
(D104028X012
D Partial Stroke Test using 475/375 Field Communicator (D103320X012
D Partial Stroke Test using ValveLink Software (D103641X012
)
)
)
)
D Pre-Commissioning Installation / Setup Guidelines using ValveLink Software (D103285X012
D Bulletin 62.1:LCP200 (D104313X012
D Fisher LCP200 Instruction Manual (D104296X012
8
)
)
)
Instruction Manual
D103557X012
D Bulletin 62.1:LCP100 (D103604X012)
Introduction
June 2022
D Fisher LCP100 Instruction Manual (D103272X012
D Fisher LC340 Instruction Manual (D102797X012
D Fisher HF340 Filter Instruction Manual (D102796X012
D AMS Trex Device Communicator User Guide
D ValveLink Software Help or Documentation
All documents are available from your Emerson sales office or at Fisher.com.
There are several parameters that should be checked to ensure the logic solver or control system is compatible with
the DVC6200 SIS digital valve controller.
HART Filter / Line Conditioner
Depending on the logic solver or control system and operational mode of the DVC6200 SIS digital valve controller, a
line conditioner or HART filter may be required.
Operational Mode
4-20 mA
Point-to-Point Loop
24 VDC
Multi-Drop Loop
Control System
or Logic Solver
PROVOX™, RS3™,
DeltaV
™, Ovation™
All OthersConsult Sales OfficeNo
AllNoYes
HART Filter
Required?
NoNo
Line Conditioner
Required?
The HF340 HART filter and LC340 Line Conditioner are passive devices that are inserted in the field wiring of the HART
loop. A filter or line conditioner is normally installed near the field wiring terminals of the system I/O (see figure 2‐1).
Its purpose is to effectively isolate the system output from modulated HART communication signals and raise the
impedance of the system to allow HART communication. For more information, refer to the HF340 HART filter
(D102796X012
) or LC340 Line Conditioner (D102797X012) instruction manual.
Voltage Available
The voltage available at the DVC6200 SIS digital valve controller must be at least 10 VDC. The voltage available at the
instrument is not the actual voltage measured at the instrument when the instrument is connected. The voltage
measured at the instrument is limited by the instrument and is typically less than the voltage available.
As shown in figure 2‐1, the voltage available at the instrument depends upon:
D The logic solver or control system compliance voltage
D if a line conditioner filter or intrinsic safety barrier is used, and
D the wire type and length.
The compliance voltage is the maximum voltage at the logic solver or control system output terminals at which the
system can produce maximum loop current.
The voltage available at the instrument may be calculated from the following equation:
Voltage Available = [Compliance Voltage (at maximum current)] - [line conditioner/filter voltage drop] - [total cable
resistance maximum current] - [barrier resistance x maximum current].
The calculated voltage available should be greater than or equal to 10 volts DC.
10
Instruction Manual
D103557X012
Figure 2‐1. Determining Voltage Available at the Instrument
Wiring Practices
June 2022
COMPLIANCE VOLTAGE
CONTROL
SYSTEM
+
-
LINE CONDITIONER
OR HART FILTER
(if used)
INTRINSIC SAFETY
BARRIER
(if used)
Calculate Voltage Available at the Instrument as follows:
Logic solver or control system compliance voltage
– Line conditioner or filter voltage drop (if used)
1
TOTAL LOOP
CABLE RESISTANCE
Example Calculation
18.5 volts (at 21.05 mA for Honeywell TDC2000)
– 2 volts
R
VOLTAGE
AVAILABLE AT THE
+
INSTRUMENT
-
– Intrinsic safety barrier resistance (if used) x maximum loop current– 2.55 volts (121 ohms x 0.02105 amps)
– Total loop cable resistance x maximum loop current
= Voltage available at the instrument
2
– 1.01 volts (48 ohms x 0.02105 amps for
1000 feet of Belden 9501 cable)
= 15.49 volts, available—if safety barrier (2.55 volts)
is not used
NOTES:
Obtain filter voltage drop. The measured drop will be different than this value. The measured filter voltage drop
1
depends upon control system output voltage, the intrinsic safety barrier (if used), and the instrument. See note 2.
The voltage available at the instrument is not the voltage measured at the instrument terminals. Once the instrument is
2
connected, the instrument limits the measured voltage to approximately 8.0 to 9.5 volts.
Compliance Voltage
If the compliance voltage of the logic solver or control system is not known, perform the following compliance voltage
test.
1. Disconnect the field wiring from the system and connect equipment as shown in figure 2‐2 to the system terminals.
Figure 2‐2. Voltage Test Schematic
kW POTENTIOMETER
1
VOLTMETER
CIRCUIT
UNDER
TEST
A6192‐1
MILLIAMMETER
11
Wiring Practices
June 2022
Instruction Manual
2. Set the system to provide maximum output current.
3. Increase the resistance of the 1 kW potentiometer, shown in figure 2‐2, until the current observed on the
milliammeter begins to drop quickly.
4. Record the voltage shown on the voltmeter. This is the compliance voltage.
D103557X012
Contact your Emerson sales office
for specific parameter information relating to your control system.
Maximum Cable Capacitance
The maximum cable length for HART communication is limited by the characteristic capacitance of the cable.
Maximum length due to capacitance can be calculated using the following formulas:
Length(ft) = [160,000 - C
Length(m) = [160,000 - C
where:
160,000 = a constant derived for FIELDVUE instruments to ensure that the HART network RC time constant will be no
greater than 65 μs (per the HART specification).
C
C
= the capacitance of the control system or HART filter
master
= the capacitance of the cable used (see table 2‐1)
cable
The following example shows how to calculate the cable length for a Foxboro
of 50, 000 pF and a Belden 9501 cable with characteristic capacitance of 50pF/ft.
Length(ft) = [160,000 - 50,000pF] [50pF/ft]
Length = 2200 ft.
The HART communication cable length is limited by the cable characteristic capacitance. To increase cable length,
select a wire with lower capacitance per foot. Contact your Emerson sales office for specific information relating to
your control system.
master
master
(pF)] [C
(pF)] [C
cable
cable
(pF/ft)]
(pF/m)]
t
I/A control system (1988) with a C
master
Table 2‐1. Cable Characteristics
pF/Ft
(1)
Capacitance
Cable Type
BS5308/1, 0.5 sq mm61.02000.0220.074
BS5308/1, 1.0 sq mm61.02000.0120.037
BS5308/1, 1.5 sq mm61.02000.0080.025
BS5308/2, 0.5 sq mm121.94000.0220.074
BS5308/2, 0.75 sq mm121.94000.0160.053
BS5308/2, 1.5 sq mm121.94000.0080.025
BELDEN 8303, 22 awg63.0206.70.0300.098
BELDEN 8441, 22 awg83.22730.0300.098
BELDEN 8767, 22 awg76.82520.0300.098
BELDEN 8777, 22 awg54.91800.0300.098
BELDEN 9501, 24 awg50.01640.0480.157
BELDEN 9680, 24 awg27.590.20.0480.157
BELDEN 9729, 24 awg22.172.50.0480.157
BELDEN 9773, 18 awg54.91800.0120.042
BELDEN 9829, 24 awg27.188.90.0480.157
BELDEN 9873, 20 awg54.91800.0200.069
1. The capacitance values represent capacitance from one conductor to all other conductors and shield. This is the appropriate value to use in the cable length calculations.
2. The resistance values include both wires of the twisted pair.
12
Capacitance
pF/m
(1)
Resistance
Ohms/ft
(2)
Resistance
Ohms/m
(2)
Instruction Manual
D103557X012
Wiring Practices
June 2022
Auxiliary Terminal Wiring Length Guidelines
The Auxiliary Input Terminals of a DVC6200 SIS can be used with an LCP100 local control panel or a locally‐mounted
switch for initiating a partial stroke test. Some applications require that the switch or local control panel be installed
remotely from the DVC6200 SIS.
The length for wiring connected to the Auxiliary Input Terminals is limited by capacitance. For proper operation of the
Auxiliary Input Terminals capacitance should not exceed 100,000 pF. As with all control signal wiring, good wiring
practices should be observed to minimize adverse effect of electrical noise on the Aux Switch function.
Example Calculation: Capacitance per foot or per meter is required to calculate the length of wire that may be
connected to the Aux switch input. The wire should not exceed the capacitance limit of 100,000 pF. Typically the wire
manufacturer supplies a data sheet which provides all of the electrical properties of the wire. The pertinent parameter
is the highest possible capacitance. If shielded wire is used, the appropriate number is the “Conductor to Other
Conductor & Shield” value.
Example — 18AWG Unshielded Audio, Control and Instrumentation Cable
Manufacturer's specifications include:
Nom. Capacitance Conductor to Conductor @ 1 KHz: 26 pF/ft
Nom. Conductor DC Resistance @ 20 Deg. C: 5.96 Ohms/1000 ft
Max. Operating Voltage - UL 200 V RMS (PLTC, CMG),150 V RMS (ITC)
Allowable Length with this cable = 100,000pF /(26pF/ft) =3846 ft
Example — 18AWG Shielded Audio, Control and Instrumentation Cable
Manufacturer's specifications include:
Nom. Characteristic Impedance: 29 Ohms
Nom. Inductance: .15 μH/ft
Nom. Capacitance Conductor to Conductor @ 1 KHz: 51 pF/ft
Nom. Cap. Cond. to other Cond. & Shield @ 1 KHz 97 pF/ft
Allowable Length with this cable = 100,000pF /(97pF/ft) = 1030 ft
The AUX switch input passes less than 1 mA through the switch contacts, and uses less than 5 V, therefore, neither the
resistance nor the voltage rating of the cable are critical. Ensure that switch contact corrosion is prevented. It is
generally advisable that the switch have gold‐plated or sealed contacts.
13
Wiring Practices
June 2022
Instruction Manual
D103557X012
Local Control Panel
Fisher LCP100 and LCP200 local control panels are used to manually open and close a safety shutdown valve.
The LCP100 provides a manual reset feature as well as a button for initiating a partial stroke test.
The LCP200 can be configured to auto or manual reset after a trip. It also offers a smart auto reset configuration which
requires a manual reset for locally initiated trips but auto reset for all other trips. It includes trip and reset push buttons
to provide a corresponding change in the state of the associated single pole double throw (SPDT) relay. The trip and
reset relays can be used as input to initiate Trip or Reset action in the logic solver. Additionally, it includes a button for
initiating a partial stroke test.
Installation
Both LCP100 and LCP200 local control panels have mounting holes for on‐site mounting of the device.
Notes
A mounting kit is available to use when replacing an LCP100 with the LCP200. Contact your Emerson sales office
obtaining this kit.
The local control panel must be installed so that the wiring connections are on the bottom to prevent accumulation of moisture
inside the box.
LCP100: When installing the LCP100 cover tighten the screws evenly in a criss‐cross pattern to a torque of 2.8 N•m (25 lbf•in) to
help ensure the cover is properly installed.
LCP200: When installing the terminal cover on the LCP200, use a 4 mm hex key to tighten the screws evenly in a criss‐cross pattern
to a torque of 8.7 N•m (77 lbf•in) +/- 10%, to help ensure the cover is properly installed. Apply silicone lubricant to the terminal
box O-ring.
for information on
Electrical Connections
WARNING
Select wiring and/or cable glands that are rated for the environment of use (such as hazardous location, ingress protection,
and temperature). Failure to use properly rated wiring and/or cable glands can result in personal injury or property damage
from fire or explosion.
Wiring connections must be in accordance with local, regional, and national codes for any given hazardous area approval.
Failure to follow the local, regional, and national codes could result in personal injury or property damage from fire or
explosion.
LCP100 protection and wiring methods are defined in table 2‐2. Refer to the LCP100 instruction manual
(D103272X012
Wiring configurations for the LPC200, based on installation requirements, are defined in table 2‐3. Refer to the LCP200
instruction manual (D104296X012)
local control panel.
Documents are available from your Emerson sales office or at Fisher.com.
14
) for installation wiring diagrams, as well as all other information on the LCP100 local control panel.
for installation wiring diagrams, as well as all other information on the LCP200
Instruction Manual
D103557X012
Table 2‐2. Fisher LCP100 Protection and Wiring Methods
LCP100 Protection MethodLCP100 Power Source
DVC6200 SIS then LCP100
Ex e mb [ib] IIC
Ex tb IIIC
Ex ic IIC
Ex tb IIIC
Ex ia IIB
Ex tb IIIC
LOOP
LCP100 then DVC6200 SIS
24 VDCDVC6200 SIS then LCP100
DVC6200 SIS then LCP100
LOOP
LCP100 then DVC6200 SIS
24 VDCDVC6200 SIS then LCP100
DVC6200 SIS then LCP100
LOOP
LCP100 then DVC6200 SIS
Wiring Order from
Logic Solver
Wiring Practices
June 2022
DVC6200 SIS Mode
(Current or Voltage)
Point-to-Point
Multi-Drop
Point-to-Point
Multi-Drop
Point-to-Point
Multi-Drop
Point-to-Point
Multi-Drop
Point-to-Point
Multi-Drop
Point-to-Point
Multi-Drop
Point-to-Point
Multi-Drop
Point-to-Point
Multi-Drop
Table 2‐3. Fisher LCP200 Wiring Configurations
LCP200 Power SourceSystem OutputDVC6200 SIS Mode (Current or Voltage)
LOOP
24 VDC External Power
Note
Factory default for the DIP switch power selector is 24VDC.
8-20 mAPoint-to-Point
24 VDCMulti-Drop
4-20 mAPoint-to-Point
24 VDCMulti-Drop
15
Configuration
June 2022
Instruction Manual
D103557X012
Section 3 Configuration
Note
Fast-key sequences are only applicable to the 475 Field Communicator. They do not apply to the Trex Device Communicator.
Fast -key sequences are not applicable to the DVC6200 SIS High Cv. ValveLink software 13.6 or higher is required to set up,
configure, and calibrate a DVC6200 SIS High Cv.
Guided Setup
Device CommunicatorConfigure > Guided Setup (2‐1)
To quickly setup the instrument, the following procedures will guide you through the process.
Device Setup is used to configure the unique parameters for the valve, actuator, instrument and accessory
construction. After Device Setup is complete, proceed with Auto Calibration.
Auto Calibration is used to establish the limits of physical travel. During this process, the valve will fully stroke from
one travel extreme to the other. There are three calibration options to choose from:
d Autocalibrate – Standard runs the full calibration process (recommended).
d Autocalibrate – Without Biases establishes the travel end points, but does not adjust the Minor Loop Feedback
bias. This is for advanced use when manually setting the biases for large actuators.
dAdvanced Settings allows additional custom configuration of calibration parameters. This is for advanced use
when calibrating large actuators.
Manual Setup33
Manual Setup allows you to configure the digital valve controller to your application. Table 3‐1 lists the default settings
for a standard factory configuration. You can adjust actuator response, set the various modes, alerts, ranges, travel
cutoffs and limits. You can also restart the instrument and set the protection.
Refer to table 3‐2 for possible configurations for a digital valve controller operated by a 4‐20 mA input current
(point‐to‐point mode), and table 3‐3 for possible configurations for a digital valve controller operated by a 0‐24 VDC
power supply (multi‐drop mode).
1. The settings listed are for standard factory configuration. DVC6200 SIS instruments can also be ordered with custom configuration settings. Refer to the order requisition
for custom settings.
2. Adjust to bar, kPa, or Kg/cm
2
if necessary.
Integral Deadzone
Low Bleed Relay
HCv1, HCv2, HCv3
1. In these configurations, the DVC6200 SIS is used as a diagnostic device, the safety function is provided by other devices in the pneumatic loop, e.g. a solenoid valve.
Open
Close
Open
(1)
(1)
24 VDCOpen100%100%
24 VDCOpen100%100%
24 VDCClose0%0%
24 VDCClose0%0%
Less Common Application
Common Application
Common Application
Less Common Application
Mode and Protection
Device CommunicatorConfigure > Manual Setup > Mode and Protection (2‐2‐1)
Instrument Mode
There are two instrument modes for the DVC6200 SIS; In Service or Out of Service. In Service is the normal operating
mode such that the instrument follows the 420 mA or 24 VDC control signal. Out of Service is required in some cases
to modify configuration parameters, calibrate, or to run diagnostics.
Note
Some changes that require the instrument to be taken Out Of Service will not take effect until the instrument is placed back In
Service or the instrument is restarted.
Write Protection
There are two Write Protection modes for the DVC6200 SIS: Not Protected or Protected. Protected prevents
configuration and calibration changes to the instrument. The default setting is Not Protected. Write Protection can be
changed to Protected remotely. However, to change Write Protection to Not Protected, you must have physical access
to the instrument. The procedure will require you to press a button ( ) on the terminal box as a security measure.
Follow the prompts on the Device Communicator display to configure the following Instrument parameters:
Identification
DHART Tag—A tag name up to 8 characters is available for the instrument. The HART tag is the easiest way to
distinguish between instruments in a multi‐instrument environment. Use the HART tag to label instruments
electronically according to the requirements of your application. The tag you assign is automatically displayed
when the Device Communicator establishes contact with the digital valve controller at power‐up.
D HART Long Tag (HART Universal Revision 7 only)—A tag name up to 32 characters is available for the instrument.
D Description provides a separate electronic label allowing for additional instrument identification.
D Message—Enter any message with up to 32 characters. Message provides the most specific user‐defined means for
identifying individual instruments in multi‐instrument environments.
DPolling Address—If the digital valve controller is used in point‐to‐point operation, the Polling Address is 0. When
several devices are connected in the same loop, such as for split ranging, each device must be assigned a unique
polling address. The Polling Address is set to a value between 0 and 63 for HART 7 and 0 and 15 for HART 5. To
change the polling address the instrument must be Out Of Service. For the Device Communicator to be able to
communicate with a device whose polling address is not 0, it must be configured to automatically search for all or
specific connected devices.
Serial Numbers
D Instrument Serial Number—Enter the serial number on the instrument nameplate, up to 12 characters.
D Valve Serial Number—Enter the serial number for the valve in the application with up to 12 characters.
Units
D Pressure Units—Defines the output and supply pressure units in either psi, bar, kPa, or kg/cm2.
D Temperature Units—Degrees Fahrenheit or Celsius. The temperature measured is from a sensor mounted on the
digital valve controller's printed wiring board.
D Analog Input Units—Permits defining the Analog Input Units in mA or percent of 4-20 mA range.
Terminal Box
DCalibration (CAL) Button—This button is near the wiring terminals in the terminal box and provides a quick means to
autocalibrate the instrument. The button must be pressed for 3 to 10 seconds. Autocalibration will move the valve
through the full range of travel whether the Instrument Mode is In Service or Out of Service. However, if the Write
Protection is Protected, this button will not be active. To abort, press the button again for 1 second. The calibration
button is disabled by default.
19
Configuration
June 2022
DAuxiliary Terminal Action—These wire terminals can be configured to initiate a partial stroke test upon detection of
a short across the (+) and (-) terminals. The terminals must be shorted for 3 to 10 seconds. Alternatively, the
auxiliary terminals can be configured to support the local control panel.
Instruction Manual
D103557X012
Spec Sheet
The Spec Sheet provides a means to store the entire control valve specifications on board the DVC6200 SIS.
Edit Instrument Time
Permits setting the instrument clock. When alerts are stored in the alert record, the record includes the time and date.
The instrument clock uses a 24‐hour format.
Travel/Pressure Control
Device CommunicatorConfigure > Manual Setup > Travel/Pressure Control (2‐2-3)
End Point Pressure Control (EPPC)
DEPPC Enable—Select Yes or No. End Point Pressure Control allows the digital valve controller to pull back from
saturation of the pneumatic output after reaching the travel extreme. Rather than having the instrument provide
full supply pressure (saturation) continuously at the travel extreme, the digital valve controller switches to an End
Point Pressure Control where the output pressure (pressure controller set point) to the actuator is maintained at the
EPPC Set Point. Because the digital valve controller is actively controlling the pressure and not allowed to reach a
dormant or saturated state, it is constantly testing its own pneumatic system. If there is an output pressure
deviation, for example, the instrument will issue an alert. To ensure there is an alert when an output pressure
deviation occurs, setup the alert as described under Pressure Deviation Alert.
DEPPC Set Point—Used in conjunction with End Point Pressure Control, End Point Pressure Control Set Point allows
the user to select a pressure to be delivered by the instrument at the travel extreme. For a fail‐closed valve, this
pressure must be sufficient to maintain the fully open position. For a fail‐open valve, this pressure (which is
automatically set to supply pressure) must be sufficient to fully close the valve and maintain its rated shutoff
classification. For double‐acting spring return actuators, this is the differential pressure required to either maintain
the fully open or fully closed position, depending on the valve and actuator configuration. For a double‐acting
actuator without springs with a fail‐close valve, this is 95% of the supply pressure.
DEPPC Saturation Time—End Point Pressure Control Saturation Time is the time the digital valve controller stays in
hard cutoff before switching to pressure control. Default is 45 seconds.
DEnd Point Pressure Control Tuning—These are the tuning parameters that the instrument uses while in end point
pressure control. The tuning set letters correspond with the travel control tuning sets (e.g. if tuning set C is
appropriate for travel control, it is also appropriate for pressure control). However, note that the individual values
may be different between travel and pressure control.
20
Instruction Manual
D103557X012
Configuration
June 2022
Characterization
Input Characterization defines the relationship between the travel target and ranged set point. Ranged set point is the
input to the characterization function. If the zero power condition equals closed, then a set point of 0% corresponds to
a ranged input of 0%. If the zero power condition equals open, a set point of 0% corresponds to a ranged input of 100%.
Travel target is the output from the characterization function.
To select an input characterization, select Input Characterization from the Characterization menu. You can select from
the three fixed input characteristics shown in figure 3‐1 or you can select a custom characteristic. Figure 3‐1 shows the
relationship between the travel target and ranged set point for the fixed input characteristics, assuming the Zero
Power Condition is configured as closed.
You can specify 21 points on a custom characteristic curve. Each point defines a travel target, in % of ranged travel, for
a corresponding set point, in % of ranged set point. Set point values range from -6.25% to 106.25%. Before
modification, the custom characteristic is linear.
Figure 3‐1. Travel Target Versus Ranged Set Point, for Various Input Characteristics (Zero Power Condition = Closed)
125
100
Travel Target, %
0
-25
-250125100
Ranged Set Point, %
Input Characteristic = Linear
125
100
125
100
Travel Target, %
0
-25
-250125100
Ranged Set Point, %
Input Characteristic = Equal Percentage
A6535‐1
Travel Target, %
0
-25
-250125100
Ranged Set Point, %
Input Characteristic = Quick Opening
21
Configuration
June 2022
Custom Characterization
To define a custom input character, from the Characterization menu select Custom Characterization. Select the point
you wish to define (1 to 21), then enter the desired set point value. Press Enter then enter the desired travel target for
the corresponding set point. When finished, select point 0 to return to the Characterization menu.
With input characterization you can modify the overall characteristic of the valve and instrument combination.
Selecting an equal percentage, quick opening, or custom (other than the default of linear) input characteristic
modifies the overall valve and instrument characteristic. However, if you select the linear input characteristic, the
overall valve and instrument characteristic is the characteristic of the valve, which is determined by the valve trim
(i.e., the plug or cage).
Instruction Manual
D103557X012
Dynamic Response
DSP Rate Open is the maximum rate (% of valve travel per second) at which the digital valve controller will move to
the open position regardless of the rate of input current change. A value of 0 will deactivate this feature and allow
the valve to stroke open as fast as possible.
DSP Rate Close is the maximum rate (% of valve travel per second) at which the digital valve controller will move to
the close position regardless of the rate of input current change. A value of 0 will deactivate this feature and allow
the valve to stroke close as fast as possible.
DSet Point Filter Time (Lag Time) slows the response of the digital valve controller. A value ranging from 0.2 to 10.0
can be used for noisy or fast processes to improve closed loop process control. Entering a value of 0.0 will
deactivate the lag filter.
Travel Cutoffs
D Hi Cutoff Select—When selected the Travel Target is set to 123% when the Travel exceeds the Hi Cutoff Point.
D Hi Cutoff Point is the point within the calibrated travel range above which the cutoff is in effect. When using cutoffs,
a Cutoff Hi of 50% is recommended to ensure valve goes fully open.
D Lo Cutoff Select—When selected the Travel Target is set to 23% when the Travel is below the Lo Cutoff Point.
D Lo Cutoff Point is the point within the calibrated travel range below which the cutoff is in effect. When using cutoffs,
a Cutoff Lo of 50% is recommended to help ensure maximum shutoff seat loading.
Changes to the tuning set may cause the valve/actuator assembly to stroke. To avoid personal injury and property damage
caused by moving parts, keep hands, tools, and other objects away from the valve/actuator assembly.
22
Instruction Manual
D103557X012
Configuration
June 2022
DTravel Tuning Set
There are eleven tuning sets to choose from. Each tuning set provides a preselected value for the digital valve
controller gain settings. Tuning set C provides the slowest response and M provides the fastest response.
Table 3‐4 lists the proportional gain, velocity gain, and minor loop feedback gain values for preselected tuning sets.
Table 3‐5 lists the proportional gain and velocity gain values for preselected tuning sets for the DVC6200 SIS High Cv.
Table 3‐4. Gain Values for Preselected Travel Tuning
Sets
Tuning
Set
C
D
E
F
G
H
I
J
K
L
M
X
(Expert)
Proportional GainVelocity Gain
Pneumatic Relay
4.4
4.8
5.5
6.2
7.2
8.4
9.7
11.3
13.1
15.5
18.0
User AdjustedUser AdjustedUser Adjusted
3.0
3.0
3.0
3.1
3.6
4.2
4.85
5.65
6.0
6.0
6.0
Minor Loop
Feedback Gain
35
35
35
35
34
31
27
23
18
12
12
In addition, you can specify Expert tuning and
individually set the proportional gain, velocity gain,
and minor loop feedback gain. Individually setting or
changing any tuning parameter or running
Stabilize/Optimize will automatically change the
tuning set to X (expert).
Table 3‐5. Gain Values for Preselected Travel Tuning
Sets - DVC6200 SIS High Cv
Tuning SetProportional GainVelocity Gain
HCv1
C
D
E
F
G
H
I
J
K
L
M
X (Expert)User AdjustedUser Adjusted
C
D
E
F
G
H
I
J
K
L
M
X (Expert)User AdjustedUser Adjusted
1.7
2.3
2.9
3.4
4.0
4.6
5.2
5.8
6.3
6.9
7.5
HCv2 and Hcv3
2.5
3.3
4.0
4.8
5.5
6.3
7.0
7.8
8.5
9.3
10.0
40
36
33
32
31
30
29
29
28
28
27
37
34
32
31
31
30
30
29
29
29
28
Note
Use Expert tuning only if standard tuning has not achieved the desired results.
Stabilize/Optimize, or Performance Tuner in ValveLink software, may be used to achieve the desired results more rapidly than
manual Expert tuning.
Table 3‐6 provides tuning set selection guidelines using Fisher and Baumann actuators. Table 3‐7 provides tuning set
selection guidelines for Bettis actuators for use with the DVC6200 SIS High Cv. These tuning sets are only
recommended starting points. After you finish setting up and calibrating the instrument, you may have to select either
a higher or lower tuning set to get the desired response.
DProportional Gain for the travel control tuning set. Changing this parameter will also change the tuning set to
Expert.
D Velocity Gain for the travel control tuning set. Changing this parameter will also change the tuning set to Expert.
D MLFB Gain is the minor loop feedback gain for the travel control tuning set. Changing this parameter will also
change the tuning set to Expert.
23
Configuration
June 2022
Table 3‐6. Actuator Information for Initial Setup
Actuator
Manufacturer
Fisher
Baumann
NOTE: Refer to figure table 3‐8 for feedback connection (magnet assembly) information.
1. X = Expert Tuning. Proportional Gain = 4.2; Velocity Gain = 3.0; Minor Loop Feedback Gain = 18.0
2. Travel Sensor Motion in this instance refers to the motion of the magnet assembly.
3. Values shown are for Relay A and C. Reverse for Relay B.
Actuator
Model
585C & 585CR
657
667
1051 & 1052
1061
1066SR
2052
3024C
GX
Air to Extend
Air to RetractTowards the top of the instrument
Rotary
Actuator SizeActuator Style
25
50
60
68, 80
100, 130
30, 30i
34, 34i, 40, 40i
45, 45i, 50, 50i
46, 46i, 60, 60i, 70,
70i & 80‐100
30, 30i
34, 34i, 40, 40i
45, 45i, 50, 50i
46, 46i, 60, 60i, 70,
70i, 76, 76i & 80‐100
20, 30
33
40
60, 70
30
40
60
68, 80, 100, 130
20
27, 75
1
2
3
30, 30E
34, 34E, 40, 40E
45, 45E
225
750K
1200M
16
32
54
10
25
54
Piston Dbl w/ or w/o
Spring. See actuator
instruction manual
and nameplate.
Spring & Diaphragm
Spring & Diaphragm
Spring & Diaphragm
(Window‐mount)
Piston Dbl
w/o Spring
Piston Sgl w/Spring
Spring & Diaphragm
(Window‐mount)
Spring & Diaphragm
Spring & Diaphragm
Spring & Diaphragm
Starting Tuning Set
(Pneumatic Relay)
Instruction Manual
D103557X012
Travel Sensor Motion
Relay A or C
E
I
J
L
M
H
K
L
M
H
K
L
M
H
I
K
M
J
K
L
M
G
L
H
J
M
E
H
K
(1)
X
C
E
H
E
H
J
Away from the top of the instrument
Towards the top of the instrument
Away from the top of the instrument
Depends upon pneumatic connections. See
description for Travel Sensor Motion
Mounting StyleTravel Sensor Motion
Away from the top of the instrument
For Po operating mode (air opens):
Towards the top of the instrument
For P
Away from the top of the instrument
Air to Open
Towards the top of
the instrument
Away from the top of the instrument
User Specified
A
B
C
D
operating mode (air closes):
s
Towards the top of the
Towards the top of the
Specify
(2)
(3)
Away from the top of
the instrument
instrument
instrument
Away from the top of
the instrument
Air to Close
Away from the top of
the instrument
DIntegral Enable—Yes or No. Enable the integral setting to improve static performance by correcting for error that
exists between the travel target and actual travel. Travel Integral Control is enabled by default.
DIntegral Gain—Travel Integral Gain is the ratio of the change in output to the change in input, based on the control
action in which the output is proportional to the time integral of the input.
24
Instruction Manual
D103557X012
Table 3‐7. Actuator Information for Initial Setup - DVC6200 SIS High Cv
During Stabilize/Optimize the valve may move, causing process fluid or pressure to be released. To avoid personal injury
and property damage caused by the release of process fluid or pressure, isolate the valve from the process and equalize
pressure on both sides of the valve or bleed off the process fluid.
Stabilize/Optimize permits you to adjust valve response by changing the digital valve controller tuning. During this
routine, the instrument must be out of service; however, the instrument will respond to setpoint changes.
If the valve is unstable select decrease response for a more conservative setting. If the valve response is sluggish, select
increase response for a more aggressive setting. When finished select Done.
25
Configuration
June 2022
Instruction Manual
D103557X012
Integral Settings
Note
Use the Integral Dead Zone and Integrator Limit values automatically selected during setup for the DVC6200 SIS High Cv.
DIntegral Dead Zone—A window around the Primary Setpoint in which integral action is disabled. This feature is used
to eliminate friction induced limit cycles around the Primary Setpoint when the integrator is active. The Dead Zone
is configurable from 0% to 2%, corresponding to a symmetric window from 0% to +/-2% around the Primary
Setpoint. Default value is 0.25%. Default value for the DVC6200 SIS High Cv is 0.75%.
DIntegrator Limit—The Integrator Limit provides an upper limit to the integrator output. The high limit is configurable
from 0 to 100% of the I/P drive signal. Default value for the DVC6200 SIS High Cv 50%.
Valve and Actuator
Device CommunicatorConfigure > Manual Setup > Valve and Actuator (2‐2‐5)
Valve Style—Enter the valve style, rotary or sliding‐stem
Actuator Style—Enter the actuator style, spring and diaphragm, piston double‐acting without spring, piston
single‐acting with spring, or piston double‐acting with spring.
Feedback Connection—Refer to table 3‐8 for Feedback Connection options. Choose the assembly that matches the
actuator travel range.
Note
As a general rule, do not use less than 60% of the magnet assembly travel range for full travel measurement. Performance will
decrease as the assembly is increasingly subranged.
The linear magnet assemblies have a valid travel range indicated by arrows molded into the piece. This means that the hall sensor
(on the back of the DVC6200 SIS housing) has to remain within this range throughout the entire valve travel. The linear magnet
assemblies are symmetrical. Either end may be up.
Table 3‐8. Feedback Connection Options
Magnet Assembly
SStem #74.2-70.17-0.28-
SStem #198-190.32-0.75-
SStem #2520-250.76-1.00-
SStem #3826-381.01-1.50-
SStem #5039-501.51-2.00-
SStem #11051-1102.01-4.125-
SStem #210110-2104.125-8.25
SStem #1 Roller 210 8.2560-90_
RShaft Window #1--60-90_
RShaft Window #2--60-90_
RShaft End Mount--60-90_
mmInchDegrees
Travel Range
26
Instruction Manual
D103557X012
Configuration
June 2022
Relay Type—There are three categories of relays that result in combinations from which to select.
Relay Type: The relay type is printed on the label affixed to the relay body.
A = double‐acting or single‐acting
B = single‐acting, reverse
C= single‐acting, direct
Special App: This is used in single‐acting applications where the “unused” output port is configured to read the
pressure downstream of a solenoid valve.
Lo Bleed: The label affixed to the relay body indicates whether it is a low bleed version.
HCv1 = Single-acting direct/ reverse acting or double-acting
HCv2 = Single-acting direct/ reverse acting or double-acting
HCv3 = Single-acting direct
Zero Power Condition—The position of the valve (open or closed) when the electrical power to the instrument is
removed. Zero Power Condition (ZPC) is determined by relay type, as shown in figure 3‐2.
Figure 3‐2. Zero Power Condition
A
Relay Type
Single‐Acting Direct
(Relay A, C, HCv1, HCv2, HCv3)
Double‐Acting
(Relay A, HCv1, HCv2)
B
Single‐Acting Reverse
(Relay B, HCv1, HCv2)
Loss of Electrical Power
Port A pressure to zero.
Port A pressure to zero.
Port B pressure to full supply.
Port B pressure to full supply.
X077-SIS
Travel Sensor Motion
WARNING
If you answer YES to the prompt for permission to move the valve when determining travel sensor motion, the instrument
will move the valve through a significant portion of its travel range. To avoid personal injury and property damage caused
by the release of process fluid or pressure, isolate the valve from the process and equalize pressure on both sides of the
valve or bleed off the process fluid.
Select Clockwise/Toward Bottom, or Counterclockwise/Toward Top. Travel Sensor Motion establishes the proper
travel sensor rotation. For quarter‐turn actuators determine rotation by viewing the rotation of the magnet assembly
from the back of the instrument.
Note
Travel Sensor Motion in this instance refers to the motion of the magnet assembly. Note that the magnet assembly may be
referred to as a magnetic array in user interface tools.
DFor instruments with Relay A or C, or direct-acting HCv1, HCv2, HCv3: If increasing air pressure at output A causes
the magnet assembly to move down or the rotary shaft to turn clockwise, enter CW/To Bottom Inst. If it causes the
magnet assembly to move up, or the rotary shaft to turn counterclockwise, enter CCW/To Top Inst.
27
Configuration
June 2022
Instruction Manual
D103557X012
DFor instruments with Relay B or reverse-acting HCv1, HCv2: If decreasing air pressure at output B causes the magnet
assembly to down, or the rotary shaft to turn clockwise, enter CW/To Bottom Inst. If it causes the magnet assembly
to move up, or the rotary shaft to turn counterclockwise, enter CCW/To Top Inst.
Maximum Supply Pressure
Enter the maximum supply pressure that is required to fully stroke the valve. For DVC6200 SIS High Cv the supply
pressure must be between 2.8 bar (40 psig) and 10 bar (145 psig).
Port A Pressure Limit
In single acting direct only applications, the instrument will limit the output pressure to the actuator from Port A.
When this pressure limit is exceeded the device will go to the no air state.
NOTICE
This is a firmware controlled feature that requires loop power to the instrument. If loop power is lost, or there is an
electronic or firmware failure, the protection feature will not remain in effect.
Output Pressure Limit Enable enables/disables the Port A Pressure Limit feature.
Note
There is an associated alert available with this feature. See the Port A Overpressurized alert in the Alert Setup section.
A partial stroke test is the process of taking the valve from the normal end to a target position at a preconfigured ramp
rate before returning to the normal end while gathering data. The data is analyzed to evaluate the condition of the
valve assembly against a set of user defined thresholds. A partial stroke test is only run if everything is normal in the
instrument. A safety demand signal will always take precedence over a partial stroke test.
Partial Stroke Test Parameters
Test Start Point defines the normal (not tripped) end of valve travel. The valve must be at this end for a PST to be
initiated. Setting this value to Not Configured will disable partial stroke tests.
Travel Hi Hi defines, in percent (%) of calibrated travel, the point above which the valve is considered to have reached
the high end.
Travel Lo Lo defines, in percent (%) of calibrated travel, the point below which the valve is considered to have reached
the low end.
Pause Time is the time between the outgoing and incoming strokes of the test. The default value is 5 seconds. The
outgoing stroke is from the normal end to the PST target and the incoming stroke is the return stroke to normal. See
figure 3‐3.
High Friction Breakout Pressure indicates that the breakout required a higher force than configured by the user. Refer
to figure 3‐3.
29
Configuration
June 2022
Instruction Manual
D103557X012
Low Friction Breakout Pressure indicates that the breakout required a lower force than configured by the user. Refer to
figure 3‐3.
Action On a Failed Test defines if the valve should step or ramp back on a failed stroke test.
Auto Test Interval is the interval of time in days between valve stroke tests that are automatically executed by the
digital valve controller, subject to the device being powered up. A value of 0 disables this feature.
Partial Stroke Parameters
Minimum Travel Movement is the percentage of total span that the valve moves away from its normal operating end
of travel towards its tripped end of travel during the test. The default value is 10%; default for DVC6200 SIS High Cv is
20%.
Short Duration PST, when enabled the incoming stroke is initiated as soon as the travel reaches the minimum travel
movement. Refer to figure 3‐4 for a time series representation of this parameter.
Figure 3‐4. Time Series Representation of Short Duration PST
NORMAL
TRAVEL
1
2
3
BREAKOUT
TIMEOUT
RETURN
LEAD
EARLY
TURNAROUND
SHORT DURATION PST
ENABLED
REDUCED
PST TIME
TIME
TRAVEL
NORMAL
OUTGOING
RAMP RATE
1
2
SHORT DURATION PST
1 MINIMUM TRAVEL MOVEMENT
2 TRAVEL TARGET MOVEMENT
3 MAX. ALLOWABLE TRAVEL
INCOMING
RAMP RATE
RETURN
LEAD
TIME
PAUSE TIME
DISABLED
Outgoing Ramp Rate is the rate at which the valve will move during the Outgoing stroke of the Partial Stroke test. The
default value is 0.25%/second.
Incoming Ramp Rate is the rate at which the valve will move during the Incoming stroke of the Partial Stroke test. The
default value is 0.25%/second.
Return Lead defines the percent (%) change in setpoint to overcome the hysteresis in the valve assembly. The error
between setpoint and actual error is added to this percent change. For example, if the Return Lead is set at 0.5% and
there is a 1% error this will be set at 1.5%
Breakout Timeout is the user configured amount of time before which the valve must leave the normal end during a
PST.
30
Loading...
+ 94 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.