Fisher Instruction Manual: Fisher 846 Current-to-Pressure Transducers Manuals & Guides

Instruction Manual
D102005X012
846 Transducer
Fisher™ 846 Current-to-Pressure Transducer
May 2022
Contents
Introduction
Scope of Manual 2.............................
Description 2.................................
Educational Services 5.........................
Installation 6..................................
Hazardous Area Classifications and Special
Instructions for Safe‐Use and Installation
in Hazardous Locations 7.....................
Mounting 8..................................
Pressure Connections 8........................
Supply Pressure 10.........................
Output Pressure 14........................
Electrical Connections 14.......................
Venting Ports 15..............................
Signal Interruption 15..........................
Calibration 16..................................
Standard Performance:
Full Range Input, Direct Action 18.............
Multirange Performance:
Full Range Input, Direct Action 18.............
Standard Performance:
Split Range Input, Direct Action 19.............
4 to 12 mA Input Signal 19..................
12 to 20 mA Input Signal 19.................
Standard Performance:
Full Range Input, Reverse Action 20............
Multirange Performance:
Full Range Input, Reverse Action 20............
Standard Performance:
Split Range Input, Reverse Action 21...........
4 to 12 mA Input Signal 21..................
12 to 20 mA Input Signal 21.................
Transporting the Module Final Assembly 22.......
Principle of Operation 22........................
Electronic Circuit 22...........................
Magnetic Actuator 23..........................
Pilot Stage 23.................................
Booster Stage 24..............................
Troubleshooting 25.............................
Diagnostic Features 25.........................
Stroke Port 25.............................
Figure 1. Fisher 846 Current‐to‐Pressure Transducer
X0234
Remote Pressure Reading (RPR) 25...........
Using a Frequency Counter to read the
RPR Signal 25.........................
In‐service Troubleshooting 26...................
Troubleshooting in the Shop 29.................
Maintenance 31................................
Module Final Assembly 32......................
Removing the Module Final Assembly 34......
Replacing the Module Final Assembly 35.......
Electronic Circuit Board 36......................
Remote Pressure Reading (RPR) Jumper 36.....
Range Jumper 37..........................
Action 37.................................
Removing the Electronic Circuit Board 37......
Replacing the Electronic Circuit Board 38......
Pilot/Actuator Assembly 38.....................
Action 38.................................
Removing the Pilot/Actuator Assembly 39.....
Replacing the Pilot/Actuator Assembly 39.....
Module Subassembly 40........................
Terminal Compartment 40.....................
Exhaust and Stroke Port Screens 41..............
Parts 42......................................
www.Fisher.com
846 Transducer
May 2022
Instruction Manual
D102005X012
Introduction
Scope of Manual
This instruction manual provides installation, operating, calibration, maintenance, and parts ordering information for Fisher 846 current‐to‐pressure transducers. Refer to separate manuals for instructions covering equipment used with the transducers.
Do not install, operate or maintain an 846 current‐to‐pressure transducer without being fully trained and qualified in valve, actuator, and accessory installation, operation, and maintenance. To avoid
personal injury or property damage, it is important to carefully read, understand, and follow all of the contents of this manual, including all safety cautions and warnings. If you have any questions about
these instructions, contact your Emerson sales office
Description
The 846 current‐to‐pressure transducer, shown in figure 1, accepts an electrical input signal and produces a proportional pneumatic output. Typically, 4 to 20 mA is converted to 0.2 to 1.0 bar (3 to 15 psi). Models are available in direct or reverse action and field‐selectable for full or split range inputs. Refer to the Calibration section for more information on input/output combinations.
before proceeding.
The most common application of the transducer is to receive an electrical signal from a controller and produce a pneumatic output for operating a control valve actuator or positioner. The 846 may also be used to produce a signal for a pneumatic receiving instrument.
The 846 is an electronic I/P transducer. It has a single electronic circuit board, as shown in figure 2. The circuit contains a solid‐state pressure sensor that monitors output pressure and is part of an electronic feedback network. The self‐correcting ability provided by the sensor/circuit combination allows the transducer to produce a very stable and responsive output signal.
All active mechanical and electrical components of the 846 are incorporated into a single, field‐replaceable module called the module final assembly, shown in figure 2. The module final assembly contains the electronic circuit board, pilot/actuator assembly, and booster stage. The module final assembly is easily removed by unscrewing the module cover. Its design minimizes parts and reduces the time required for repair and troubleshooting.
The terminal compartment and module compartment are separated by a sealed compartment wall. This multi‐compartment housing also protects the electronics from contaminants and moisture in the supply air.
Specifications
WARNING
This product is intended for a specific range of pressures, temperatures, and other application specifications. Applying different pressure, temperature and other service conditions could result in a malfunction of the product, property damage or personal injury.
Specifications for the 846 transducer are listed in table 1.
2
Instruction Manual
D102005X012
Table 1. Specifications
846 Transducer
May 2022
Input Signal
Standard Performance:
4 to 20 mA DC, 4 to 12 mA DC, or 12 to 20 mA DC. Field adjustable split ranging.
Multirange Performance:
4 to 20 mA DC. Consult factory for split range input
Equivalent Circuit
See figure 3
Output Signal
(1)
Standard Performance:
(Consult factory for split range output)
Direct Action (Minimum span of 6 psi)
Typical outputs: 0.2 to 1.0 bar (3 to 15 psi). Rangeability between 0.1 and 1.2 bar (1 and 18 psi)
Reverse Action (Minimum span of 11 psi)
Typical outputs: 1.0 to 0.2 bar (15 to 3 psi) Rangeability between 1.2 and 0.1 bar (18 and 1 psi)
Multirange Performance: Direct Action (Minimum span of 6 psi)
Typical outputs: 0.2 to 1.9 bar (3 to 27 psi), 0.4 to 2 bar (6 to 30 psi), and 0.3 to 1.7 bar (5 to 25 psi) Rangeability between 0.03 and 2.3 bar (0.5 and 33 psi)
Reverse Action (Minimum span of 11 psi)
Typical outputs: 1.9 to 0.2 bar (27 to 3 psi), 2 to
0.4 bar (30 to 6 psi), and 1.7 to 0.3 bar (25 to 5 psi) Rangeability between 2.3 and 0.03 bar (33 and
0.5 psi)
Supply Pressure
(2)
Standard Performance: 1.2 to 1.6 bar (18 to 24 psi) Multirange Performance:
(3)
0.2 bar (3 psi)
greater than the maximum
calibrated output pressure
Maximum: 2.4 bar (35 psi)
Per ISO 8573-1
Maximum particle density size: Class 7 Oil content: Class 3 Pressure Dew Point: Class 3 or at least 10°C less than
the lowest ambient temperature expected
Output Air Capacity
(4)
Standard: 6.4 m3/hr (240 scfh) at 1.4 bar (20 psi) supply pressure
3
Multirange: 9.7 m
/hr (360 scfh) at 2.5 bar
(35 psig) supply pressure
Maximum Steady‐State Air Consumption
(4)
0.3 m3/hr (12 scfh) at 1.4 bar (20 psi) supply pressure
Temperature Limits
(2)
Operating: -40 to 85_C (-40 to 185_F)
Storage :-40 to 93_C (-40 to 200_F)
Humidity Limits
0 to 100% condensing relative humidity
Performance
(5)
Note: The performance of all 846 I/Ps is verified using computer automated manufacturing systems to ensure that every unit shipped meets its performance specifications
Accuracy: $0.30% of output span
Linearity, Hysteresis, and Repeatability: $0.3% of
span.
Temperature Effect (total effect including zero and span): $0.07%/_C (0.045%/_F) of span
Supply Pressure Medium
Clean, dry air
Per ISA Standard 7.0.01
A maximum 40 micrometer particle size in the air system is acceptable. Further filtration down to 5 micrometer particle size is recommended. Lubricant content is not to exceed 1 ppm weight (w/w) or volume (v/v) basis. Condensation in the air supply should be minimized
Vibration Effect: $0.3% of span per g during the following conditions: 5 to 15 Hz at 4 mm constant displacement 15 to 150 Hz at 2 g. 150 to 2000 Hz at 1 g. per SAMA Standard PMC 31.1, Sec. 5.3, Condition 3, Steady State
Shock Effect: $0.5% of span, when tested per SAMA Standard PMC 31.1, Sec. 5.4.
Supply Pressure Effect: Negligible
-Continued-
3
846 Transducer
May 2022
Table 1. Specifications (continued)
Instruction Manual
D102005X012
Performance (continued)
(5)
Electromagnetic Interference (EMI): Tested per IEC 61326‐1:2013. Meets emission levels for Class A equipment (industrial locations) and Class B equipment (domestic locations). Meets immunity requirements for industrial locations (Table A.1 in the IEC specification document). Immunity performance is shown in table 2.
Leak Sensitivity
3
4.8 m
/hr (180 scfh) downstream leakage.
(4)
: Less than 1.0% of span for up to
Overpressure Effect: Less than 0.25% of span for
misapplication of up to 7.0 bar (100 psi) supply pressure for less than 5 minutes to the input port.
Reverse Polarity Protection: No damage occurs from reversal of normal supply current (4 to 20 mA) or from misapplication of up to 100 mA.
Connections
Supply Air, Output Signal, and Output Gauge: 1/4‐18 NPT internal connection Electrical: 1/2‐14 NPT internal conduit connection
Adjustments
Zero and Span: screwdriver adjustments located in terminal compartment.
Remote Pressure Reading (RPR) Jumper selectable, ON or OFF, if unit includes option
Frequency Range: 0 to 10,000 Hz Amplitude: 0.4 to 1.0 V
p‐p
Required Operating Voltage with Remote pressure Reading Off
Min. 6.0 V (at 4 mA) Max. 7.2 V (at 20 mA)
Electrical Classification
Pollution Degree 4
Hazardous area: CSA C/US—Intrinsically Safe, Explosion-proof,
Non-Incendive
FM—Intrinsically Safe, Explosion-proof, Non-Incendive ATEX—Intrinsically Safe, Flameproof, Type n IECEx—Intrinsically Safe, Flameproof Electrical Housing:
Tropicalization (Fungus test per MIL-STD-810)
CSA C/US—Type 4X FM—Type 4X ATEX—IP66 IECEx—IP66
(6)
(6)
Other Classifications/Certifications
CUTR— Customs Union Technical Regulations (Russian, Kazakhstan, Belarus, and Armenia)
ESMA— Emirates Authority for Standardization and Metrology - ECAS-Ex (UAE)
INMETRO— National Institute of Metrology, Quality, and Technology (Brazil)
KTL— Korea Testing Laboratory (South Korea) CCC— China Compulsory Compliance NEPSI— National Supervision and Inspection Centre
for Explosion Protection and Safety of Instrumentation (China)
PESO CCOE— Petroleum and Explosives Safety Organization - Chief Controller of Explosives (India)
Contact your Emerson sales office
for
classification/certification specific information
Required Operating Voltage with Remote Pressure Reading On
Min 6.4 V (at 4 mA) Max. 8.2 V (at 20 mA)
4
Construction Materials
Housing: Low‐copper aluminum with polyurethane paint, or 316 stainless steel
O‐Rings: Nitrile, except silicone for sensor O‐rings.
-continued-
Instruction Manual
D102005X012
Table 1. Specifications (continued)
846 Transducer
May 2022
Options
Declaration of SEP
Fisher 67CFR filter regulator, supply and output gauges or tire valve remote pressure reading, module cover with multiple stroke ports, stainless steel housing, or stainless steel mounting bracket.
Fisher Controls International LLC declares this product to be in compliance with Article 3 paragraph 4 of the PED Directive 2014/68/EU. It was designed and manufactured in accordance with Sound
Altitude Rating
Up to 2000 meters (6562 feet)
Weight
Aluminum: 2.9 kg (6.5 lb) excluding options Stainless Steel: 6.7 kg (14.8 lb) excluding options
NOTE: Specialized instrument terms are defined in ANSI/ISA Standard 51.1 - Process Instrument Terminology.
1. Metric calibration also available.
2. The pressure/temperature limits in this document, and any applicable standard or code limitation should not be exceeded.
3. 0.14 bar (2 psi) for a 2.3 bar (33 psi) output.
4. Normal m
5. Reference Conditions: 4.0 to 20 mA DC input, 0.2 to 1.0 bar (3 to 15 psi) output, and 1.4 bar (20 psi) supply pressure.
6. ATEX and IECEx Flameproof — IP66 per CSA Letter of Attestation.
3
/hr—Normal cubic meters per hour (0_C and 1.01325 bar, absolute). Scfh—Standard cubic feet per hour (60_F and 14.7 psia).
Engineering Practice (SEP) and cannot bear the CE marking related to PED compliance.
However, the product may bear the CE marking to indicate compliance with other applicable European Community Directives.
Table 2. EMC Immunity Performance Criteria
Port Phenomenon Basic Standard Test Level Performance Criteria
Electrostatic discharge (ESD) IEC 61000‐4‐2
Enclosure
I/O signal/control
Specification limit = ±1% of span
1. A = No degradation during testing. B = Temporary degradation during testing, but is self‐recovering.
Radiated EM field IEC 61000‐4‐3
Burst (fast transients) IEC 61000‐4‐4 1 kV A Surge IEC 61000‐4‐5 1 kV (line to ground only, each) B
Conducted RF IEC 61000‐4‐6
4 kV contact 8 kV air
80 to 1000 MHz @ 10V/m with 1 kHz AM at 80% 1400 to 2000 MHz @ 3V/m with 1kHz AM at 80% 2000 to 2700 MHz @ 1V/m with 1kHz AM at 80%
150 kHz to 8 MHz at 3 Vrms B 8 MHz to 80 MHz at 3 Vrms A
(1)
A
A
Educational Services
Emerson Automation Solutions Educational Services - Registration Phone: +1-800-338-8158 Email: education@emerson.com emerson.com/mytraining
5
846 Transducer
May 2022
Instruction Manual
D102005X012
Figure 2. Transducer Modular Construction
TERMINAL COMPARTMENT COVER
TERMINAL BLOCK
MODULE HOUSING
ELECTRONIC CIRCUIT BOARD
MODULE FINAL ASSEMBLY
Figure 3. Equivalent Circuit
846
6 V DC
50 OHMS
POWER SUPPLY
NOTE: THE 846 IS NOT A CONSTANT RESISTOR IN SERIES WITH AN INDUCTOR. IT IS BETTER MODELED IN THE LOOP AS A 50 OHM RESISTOR IN SERIES WITH A 6‐VOLT DC VOLTAGE DROP WITH NEGLIGIBLE INDUCTANCE.
A6325
MODULE COVER
A6643
Installation
WARNING
To avoid personal injury or property damage from the sudden release of pressure or air:
D Always wear protective clothing, gloves, and eyewear when performing any installation operations.
D Disconnect any operating lines providing air pressure, electric power, or a control signal to the actuator. Be sure the
actuator cannot suddenly open or close the valve.
D Use bypass valves or completely shut off the process to isolate the valve from process pressure. Relieve process pressure
on both sides of the valve.
D Use lock‐out procedures to be sure that the above measures stay in effect while you work on the equipment.
D Check with your process or safety engineer for any additional measures that must be taken to protect against process
media.
6
Instruction Manual
D102005X012
846 Transducer
May 2022
NOTICE
Do not use sealing tape on pneumatic connections. This instrument contains small passages that may become obstructed by detached sealing tape. Thread sealant paste should be used to seal and lubricate pneumatic threaded connections.
This section presents information on installing the 846 current‐to‐pressure transducer. Figures 4, 5, 6, and 8 can be used as references for instructions contained in this section.
When a control valve is ordered with an 846 transducer specified to be mounted on the actuator, the factory‐mounted transducer is connected to the actuator with the necessary tubing and calibrated to the specifications on the order.
If the transducer is purchased separately for mounting on a control valve already in service, all the necessary mounting parts are furnished, if ordered. This includes the appropriate bracket for attaching the unit to an actuator boss (with tapped holes) or for attaching it to the diaphragm casing.
If preferred, mounting parts can be supplied for mounting the transducer on a 51 mm (2‐inch) diameter pipestand, a flat surface, or a bulkhead.
Transducers also can be ordered separately for mounting on a control valve assembly already in service. The transducer may be ordered with or without mounting parts. Mounting parts include the appropriate bracket and bolts for attaching the unit to an actuator boss (with tapped holes) or for attaching it to the diaphragm casing.
Hazardous Area Classifications and Special Instructions for “Safe Use” and Installation in Hazardous Locations
Refer to the following instruction manual supplements for approval information.
D CSA Approval Information for Fisher 846 Current-to-Pressure Transducers (D104218X012
D FM Approval Information for Fisher 846 Current-to-Pressure Transducers (D104219X012
D ATEX Approval Information for 846 Current-to-Pressure Transducers (D104220X012
D IECEx Approval Information for 846 Current-to-Pressure Transducers (D104221X012
D INMETRO Approval Information for Fisher 846 Current-to-Pressure Transducers (D103623X012
D NEPSI Approval Information for Fisher 846 Current-to-Pressure Transducers (D103618X012
All documents are available from your Emerson sales office other approval/certification information.
or Fisher.com. Contact your Emerson sales office for all
)
)
)
)
)
)
7
846 Transducer
May 2022
Instruction Manual
D102005X012
Mounting
Note
This unit will vent to the atmosphere through the stroke port in the module cover and the exhaust port, located under the nameplate. Do not remote vent this unit.
The transducer is designed for mounting on a control valve, 51 mm (2‐inch) diameter pipestand, wall, or panel. Figures 5, 6, 7, and 8 show recommended mounting configurations. The mounting positions shown allow any moisture buildup in the terminal compartment to drain to the signal wire conduit entrance. Any moisture in the pilot stage area will be expelled through the stroke port without affecting pilot stage operation. In applications with excessive moisture in the supply air, vertical mounting allows the most effective drainage through the stroke port.
NOTICE
Do not mount the transducer with the terminal compartment cover on the bottom as moisture, or any corrosive elements in the plant atmosphere, may accumulate in the terminal compartment or pilot stage, resulting in transducer malfunction.
Mounting is accomplished with an optional universal mounting bracket. Before mounting the transducer, note the following recommendations:
D Ensure that all bolts are fully tightened. The recommended torque is 22 NSm (16 lbfSft).
D Bolts that connect to the transducer and to a valve actuator should have the lock washer placed directly beneath the
bolt head and the flat washer placed between the lock washer and bracket. All other bolts should have the lock washer next to the nut, and the flat washer placed between the lock washer and bracket.
D Do not mount the transducer in a location where foreign material may cover the stroke port or exhaust port. See the
descriptions of the stroke port and exhaust port later in this section.
Pressure Connections
NOTICE
Do not use sealing tape on pneumatic connections. This instrument contains small passages that may become obstructed by detached sealing tape. Thread sealant paste should be used to seal and lubricate pneumatic threaded connections.
As shown in figure 4, all pressure connections are 1/4‐18 NPT internal connections. Use 9.5 mm (3/8‐inch) outside diameter tubing for the supply and output connections.
8
Instruction Manual
D102005X012
Figure 4. Typical Dimensions and Connection Locations (Aluminum Construction Shown)
129
(5.07)
119
STROKE PORT
(4.68)
MODULE COVER WITH
MULTIPLE PORTS
NAMEPLATE
MOUNTING BOLT HOLES 5/16‐18 (3)
59
(2.31)
846 Transducer
May 2022
CONDUIT CONNECTION 1/2 ‐ 14 NPT
OUTPUT PORT 1/4 ‐ 18 NPT
EXHAUST PORT UNDERNEATH NAMEPLATE
35
(1.38)
29
(1.13)
29
(1.16)
COVER REMOVAL
OUTPUT GAUGE PORT 1/4‐18 NPT
TEST PINS
WIRING CONNECTION
NOTE: REFER TO FIGURE 8 FOR TRANSDUCER DIMENSIONS WITH ATEX / IECEx FLAMEPROOF CERTIFICATIONS
B2473‐1
POSITIVE NEGATIVE INTERNAL GROUND
110
(4.33)
102
(4.00)
O‐RING GROOVE FOR FILTER REGULATOR
SUPPLY PORT 1/4‐18 NPT
5/16‐18 (2)
mm
(INCHES)
9
846 Transducer
May 2022
Instruction Manual
D102005X012
Supply Pressure
WARNING
Severe personal injury or property damage may occur from process instability if the instrument supply medium is not clean, dry air. While use and regular maintenance of a filter that removes particles larger than 40 micrometers in diameter will suffice in most applications, check with an Emerson field office and industry instrument air quality standards if you are unsure about the proper amount or method of air filtration or filter maintenance.
The supply medium must be clean, dry air that meets the requirements of ISA Standard 7.0.01 or ISO 8573-1. An output span of 0.2 to 1.0 bar (3 to 15 psi) requires a nominal supply pressure of 1.4 bar (20 psi) and a flow capacity not less than 6.4 normal m
For multirange performance units with higher output spans, the supply pressure should be at least 0.2 bar (3 psi) greater than the maximum calibrated output pressure.
The air supply line can be connected to the 1/4‐18 NPT supply port, or to the supply port of a filter‐regulator mounted directly to the transducer. Figures 5, 6, 7, and 8 show the installation options.
3
/hr (240 scfh).
Figure 5. Typical Dimensions with Fisher 67CFR Filter/Regulator and Gauges
215 COVER REMOVAL CLEARANCE
NOTE:  1  THE MOUNTING POSITIONS SHOWN ALLOW ANY MOISTURE BUILDUP IN THE TERMINAL COMPARTMENT TO DRAIN TO THE SIGNAL WIRE CONDUIT ENTRANCE. DO NOT MOUNT THE TRANSDUCER WITH THE TERMINAL COMPARTMENT COVER ON THE BOTTOM; MOISTURE MAY ACCUMULATE IN THE TERMINAL COMPARTMENT OR PILOT STAGE, PREVENTING PROPER TRANSDUCER OPERATION. THE VERTICAL MOUNT IS MOST EFFECTIVE FOR MOISTURE DRAINAGE IN WET APPLICATIONS.
14B7361‐D A6626-3
67
(2.62)
78
(3.08)
156
(6.15)
(8.48)
CENTERLINE OF ACTUATOR
YOKE MOUNTED
6
(0.25)
FOR PROPER MOISTURE DRAINAGE THIS END MUST BE UP
191
(7.51)
MODULE COVER REMOVAL CLEARANCE
1
13
(0.50)
FOR ATEX/IECEx FLAMEPROOF UNITS: BOLT ENGAGEMENT NOT TO EXCEED
137
12.9 mm (0.51 INCHES).
(5.38)
5/16‐18 BOLTS
mm
(INCH)
10
Instruction Manual
D102005X012
Figure 6. Typical Transducer Mounting with Universal Mounting Bracket
846 Transducer
May 2022
ADDITIONAL ADAPTER PLATE PART NUMBER 03311‐0318‐0001 REQUIRED FOR I/P WITH STAINLESS STEEL HOUSING
U BOLT
5/16‐18 x 5/8 BOLTS
ADAPTER PLATE (SEE DETAIL “B”)
(1.61)
VERTICAL MOUNT
MOUNTING BRACKET (SEE DETAIL “A”)
FOR PROPER MOISTURE DRAINAGE, THIS END MUST BE UP
5/16‐18 HEX NUT (4 PLACES)
41
3
2‐INCH PIPESTAND MOUNTING
FOR ATEX/IECEx FLAMEPROOF UNITS: BOLT ENGAGEMENT NOT TO EXCEED 8.8 mm (0.35 INCHES). 5/16‐18 BOLT HOLES
1
MOUNTING BRACKET (SEE DETAIL “A”)
ADAPTER PLATE (SEE DETAIL “B”)
FOR ATEX/IECEx FLAMEPROOF UNITS: BOLT ENGAGEMENT NOT TO EXCEED
8.1 mm (0.32 INCHES). 5/16‐18 BOLT HOLES
2
HORIZONTAL MOUNT
FOR PROPER MOISTURE DRAINAGE, THE I/P MUST BE MOUNTED ON TOP OF THE PIPE
ADDITIONAL ADAPTER PLATE PART NUMBER 03311‐0318‐0001 REQUIRED FOR I/P WITH STAINLESS STEEL HOUSING
5/16‐18 x 3/4 BOLTS (4 PLACES)
5/16‐18 x 3/4 BOLTS (4 PLACES)
MOUNTING BRACKET (SEE DETAIL “A”)
FOR PROPER MOISTURE DRAINAGE, THIS END MUST BE UP
1
1
GE06214 SHT 3
BOLT HOLES FOR STAINLESS
STEEL CONSTRUCTION (COVERLOCK SHOWN)
GE06214 SHT 2
BOLT HOLES FOR ALUMINUM
CONSTRUCTION (COVERLOCK SHOWN)
NOTES:  1  THE MOUNTING POSITIONS SHOWN ALLOW ANY MOISTURE BUILDUP IN THE TERMINAL COMPARTMENT TO DRAIN TO THE SIGNAL WIRE CONDUIT ENTRANCE. DO NOT MOUNT THE TRANSDUCER WITH THE TERMINAL COMPARTMENT COVER ON THE BOTTOM; MOISTURE MAY ACCUMULATE IN THE TERMINAL COMPARTMENT OR PILOT STAGE, PREVENTING PROPER TRANSDUCER OPERATION. THE VERTICAL MOUNT IS MOST EFFECTIVE FOR MOISTURE DRAINAGE IN WET APPLICATIONS.  2  IF MOUNTED ON HORIZONTAL PIPE, THE I/P MUST BE ON TOP OF THE PIPE FOR PROPER MOISTURE DRAINAGE.  3  THIS DIMENSION IS 44 (1.74) FOR STAINLESS STEEL HOUSING.
14B7332 19B9484‐B E0786
32
(1.25)
WALL/PANEL MOUNTING
(ALUMINUM HOUSING)
mm (INCH)
11
846 Transducer
May 2022
Figure 6. Typical Transducer Mounting with Universal Mounting Bracket (continued)
Instruction Manual
D102005X012
4 X 10 (0.375)
(1.18)
5 X 10 (0.375)
U‐BOLT SLOTS 19 (0.75)
30
29
(1.13)
38
(1.50)
(3.50)
29
(1.16)
(2.312)
59
89
(.89)
23
89
(3.50)
FOR ALUMINUM HOUSING, ALIGN 3 HOLES WITH I/P HOUSING
DETAIL “A” MOUNTING BRACKET
29
(1.125
57
(2.25)
U‐BOLT SLOTS 19 (0.75)
FOR STAINLESS STEEL HOUSING, ALIGN 4 HOLES WITH I/P HOUSING
38
(1.50)
29
(1.125
57
(2.25)
2 X 10 (0.375)
03311-0318
4 X 5 (0.188)
2 X 10 (0.375)
DETAIL “B” ADAPTER PLATE
4 X 5 (0.188)
mm (INCH)
ADDITIONAL ADAPTOR PLATE (PART NUMBER 03311‐0318‐0001)
REQUIRED FOR I/P WITH STAINLESS STEEL HOUSING
NOTES:
1. ATTACH THE BRACKET SHOWN IN DETAIL “A” TO THE TRANSDUCER
2. ATTACH THE ADAPTER PLATE SHOWN IN DETAIL “B” TO THE VALVE OR PIPE.
3. CONNECT THE TWO PIECES.
34B4990‐C 34B5000‐B E0787
The mounting boss for the air supply connection contains two 5/16‐18 UNC tapped holes that are 2‐1/4 inches apart. The tapped holes allow direct connection (integral mount) of a 67CFR filter‐regulator, if desired. When the filter‐regulator is factory mounted, the mounting hardware consists of two 5/16‐18 x 3‐1/2 inch stainless steel bolts and one O‐ring. When the filter‐regulator is field mounted, the mounting hardware consists of two 5/16‐18 x 3‐1/2 inch stainless steel bolts, two spacers (which may or may not be required) and two O‐rings (of which only one will fit correctly into the housing O‐ring groove and the other may be discarded). This is due to the fact that the current housing has been slightly modified from its original design, hence, the additional hardware (if needed) when field mounting the 67CFR filter‐regulator.
12
Instruction Manual
D102005X012
Figure 7. Typical Transducer Dimensions with Gauges
846 Transducer
May 2022
81
(3.2)
9
(0.36)
14B7332‐D E0776
49
(1.92)
(2.83)
OUTPUT GAGE
72
SUPPLY GAGE
FILTER‐ REGULATOR
67CFR 14‐18 NPT SUPPLY CONN
Figure 8. Transducer Dimensions with ATEX / IECEx Flameproof Certifications
EXTERNAL EARTHING CONNECTION, SST TERMINAL CLAMP AND SLOTTED M5 SCREW AND SPLIT RING WASHER
1/4‐18 NPT OUTLET CONN PLUGGED WHEN GAUGE NOT FURNISHED
mm
(INCH)
B2465
COVER LOCK
INTERNAL HEX DRIVE ROUND HEAD SCREW (3 mm)
TERMINAL COMPARTMENT COVER
4.75
(121)
162
(6.38)
3.62 (92)
HOUSING
129
(5.07)
MODULE COVER
121
(4.75)
mm
(INCH)
13
846 Transducer
May 2022
Instruction Manual
D102005X012
Output Pressure
Connect the output signal line to the transducer at the output port. The output port is 1/4‐18 NPT, as shown in figure
4. The output gauge port can be used as an alternate signal port. If the gauge port is used as a signal port, a threaded plug must be installed in the output port.
The output gauge port allows connection of an output gauge to provide local output signal indication. The output gauge port is 1/4‐18 NPT. If an output gauge is not specified, a threaded plug is shipped with the transducer. The plug must be installed in the output gauge port when the port is not used.
Electrical Connections
WARNING
Personal injury or property damage could result from fire or explosion. In explosive atmospheres, remove power and shut off the air supply to the I/P unit before attempting to remove the terminal compartment cover or module cover. Failure to do so could result in an electrical spark or explosion.
Personal injury or property damage could result from an uncontrolled process. Perform the steps in the WARNING at the beginning of the Installation section before removing the module cover to ensure the process is properly controlled. Unscrewing the module cover removes power from the electronics and opens the supply and output air passages to atmosphere resulting in an output signal of 0.0 psi.
NOTICE
Excessive current can damage the transducer. Do not connect an input current of more than 100 mA to the transducer.
Note
For North American explosion‐proof applications, 846 transducers have been designed so that a conduit seal is not required. For all other applications install the product per local, regional, or national code, rules, and regulations.
WARNING
Select wiring and/or cable glands that are rated for the environment of use (such as hazardous location, ingress protection, and temperature). Failure to use properly rated wiring and/or cable glands can result in personal injury or property damage from fire or explosion.
Signal wiring is brought to the terminal compartment through a 1/2‐14 NPT housing conduit connection, shown in figure 4. Where condensate is common, use a conduit drip leg to help reduce liquid buildup in the terminal compartment and avoid shorting of the input signal. Electrical connections are made at the terminal block. Internal and external grounding lugs are provided to facilitate a separate ground when required. The internal ground is shown in figure 4, and the external grounding lug is shown in figure 8.
14
Loading...
+ 30 hidden pages