Instruction Manual Supplement
D103395X012
June 2009
DVC6000 SIS
Supplement to Fisherr FIELDVUEr DVC6000
SIS Series Digital Valve Controllers for
Safety Instrumented System (SIS) Solutions
Instruction Manual
Control and Safety Valve Diagnostics Unleashed: Enable
Valve Alert Reporting on Non-Smart Communicating Systems
WARNING: This instruction manual supplement is not intended to be used as a
stand-alone document. It must be used in conjunction with the following manuals:
FisherR FIELDVUEr DVC6000 Series Digital Valve Controllers for Safety Instrumented System
(SIS) Solutions Instruction Manual (D103230X012) and
The appropriate Safety Manual for FIELDVUER DVC6000 SIS Series Digital Valve Controllers for
Safety Instrumented System (SIS) Solutions (0-20 mA or 0-24 VDC [D103035X012] or 4-20 mA
[D103294X012]).
It may also be helpful to reference the Instruction Manual Supplement for HART
Communicating FisherR FIELDVUER Instruments—Using FIELDVUER Instruments with the Smart
HARTR Loop Interface and Monitor (HIM) (D103263X012).
Failure to use this application guide in conjunction with above referenced manuals could result
in personal injury or property damage. If you have any questions regarding these instructions
or need assistance in obtaining any of these documents, contact your Emerson Process
Management sale office.
R
www.Fisher.com

Instruction Manual Supplement
DVC6000 SIS
June 2009
Introduction
FIELDVUE instrumentation provides NO EQUAL diagnostics capabilities that clearly differentiate Fisher control
valve packages from other control valve packages. However, end-users often do not have a HART or
fieldbus-capable control system that enables them to get the benefit of FIELDVUE diagnostic capabilities.
There are two easy ways to unleash the power of valve diagnostics in such an environment:
Wireless—the THUMr adapter, or
Hardwiring—using HART to analog converters
This document provides a hardwiring technical solution, using the Smart HART Loop Interface and Monitor
(HIM) from Moore Industries, shown in figure 1, that will enable conventional analog control system users to
benefit from FIELDVUE diagnostic capabilities.
Figure 1. Moore Industries HARTr Loop Monitor
2