Fisher Instruction Manual: C831 Series Internal Valves | Fisher Manuals & Guides

Instruction Manual MCK-1185
March 2010
C831 Series Internal Valves
WARNING
!
re and/or chemical contamination
causing property damage and personal injury or death.
Fisher equipment must be installed, operated, and maintained in accordance with federal, state, and local codes and Fisher instructions.
Only personnel trained in the proper procedures, codes, standards, and regulations of the applicable industrial service should install and service this equipment.
C831 Series
The internal valve must be closed except during product transfer. A line break downstream of a pump may not actuate
the excess ow valve. If any break
occurs in the system or if the excess
ow valve closes, the system should be
shut down immediately.
Introduction
Scope of Manual
This manual covers instructions for the C831 Series 2 and 3-inch Class 300 Raised Face Flange internal valves.
These valves are serialized for the service specied with
the order. The valves can be used on other compressed
gases, but the user should check with the factory to
make sure the valve materials are suitable for the intended service.
Description
The valves are typically used on the inlets and outlets of transport trucks and on large stationary storage tanks.
Figure 1. C831 Series
Specications
The Specications table lists specications for C831 Series
internal valves.
DOT Internal Self-Closing Stop Valve Requirement —U.S. Department of Transportation (DOT) regulations
49CFR§178.337-8(a)(4) require each liquid or vapor discharge outlet on cargo tanks (except for cargo tanks used to transport chlorine, carbon dioxide, refrigerated liquid, and
certain cargo tanks certied prior to January 1, 1995) to be tted with an internal self-closing stop valve. Fisher’s “C” series internal valves comply with the internal self-closing
stop valve requirement under the DOT regulations.
D450090T012
R
www.FISHERregulators.com/lp
C831 Series
Specications
Body Size and End Connection Style
Inlet: 2 or 3-inch
Class 300 ANSI Raised Face Flanged
Outlet: 2 or 3-inch
Class 300 ANSI Raised Face Flanged
Number of Outlets
C831 Series: 2 (side and straight through)
Maximum Allowable Inlet Pressure
500 psig (34,5 bar) WOG
Excess Flow Springs
2-Inch Size: 85, 110 and 160 GPM
(322, 416, 605 l/min) water
3-Inch Size: 110, 145,175, 270, and 345 GPM
(416, 549, 662, 1022, 1306 l/min) water
Temperature Capabilities
-20° to 150°F (-29° to 66°C)
O.D AND THICKNESS TO SUIT CONTAINER
C
TANK CONNECTION FLANGES - DIMENSIONS ARE IN INCHES (mm)
300 LB ANSI RF FLANGE
2-inch
3-inch
A-BOLTING
DBC NO. Size
5.0 8
(127)
6.62 8
(168)
45°
SPECIFICATIONS
E B
A
Figure 2
B RF C RF D E
5/8
3.62
(15,9)
(92)
3/4
5.75
(19,0)
(146)
D MAX
0.06 (1,5)
0.06 (1,5)
1.45
(36,8)
1.50 (38)
2.46
(62,5)
4.62
(117)
INCH (mm)
MATING
FLANGE O.D.
6.50 (165)
8.25 (210)
1 (25,4)
MINIMUM
3/4-IO UNC
Approximate Weight
2-Inch: 20 pounds (9 kg) 3-Inch: 32 pounds (14 kg)
Construction Materials
Stainless Steel: Lever, Cam, Disc Holder, Springs,
Hexagon Head Cap Screws, Cotter Pin, Stub Shaft, Stem, Washers, Drive Screw, Plug Holder, Stop Tube, Body, Gland, Web, Pins, Screws, Bolts, Nut
Washer, Spring Seat, Disc Retainer, Disc Holder, and Retainer
Plated Steel: Nameplate, Drive Pin Polyurethane: Rod Wiper PTFE or Filled PTFE: Gland Packing, Liner Brushing,
Washer, Wear Plug
Nitrile (Standard Construction): Disc and O-Rings Other Disc and O-Ring Trim Material Available from Factory: TFE, Neoprene, Ethylene Propylene,
Viton, and Kalrez
Keep piping from the valve outlet to the pump full size and
as short as possible with a minimum number of bends.
Reduction in pipe size to suit smaller pump inlets should be made as close to the pump as possible using forged
reducers (swage nipples) or venturi tapers rather than bushings. This assures minimum ow resistance and efcient pump operation.
The valves have a break off section below the inlet ange which is intended to permit the lower valve body
to shear off in an accident, leaving the valve seat in the tank. The break off section is designed for container
installations and will probably not provide shear protection if the valve is installed in a pipeline.
A hydrostatic relief valve does not need to be installed
adjacent to the valve since the internal valve relieves excessive line pressure into the tank.
Installation
Note
Installer must furnish 8 stud bolts,
8 ange nuts, and spiral wound gaskets
as these parts are not supplied with the internal valves.
Coat both sides of the spiral wound gaskets with Dow Corning #111 silicone grease or equivalent. An appropriately sized tank ange, see Figure 2, must be
installed in the tank. The internal valve can then be installed in the tank and outlet piping attached to the internal valve.
2
Selectively Filling Manifolded Tanks
Fisher internal valves provide positive shutoff only in one direction, from out of the tank to downstream of the valve. The internal valves are designed to allow gas to ow into a tank when the downstream line pressure exceeds tank pressure. If you want to selectively ll one or more of the other tanks in a tank manifold system, you must place a positive shutoff valve downstream of the internal valve, otherwise, all tanks will be lled at the same time and at
about the same rate.
C831 Series
Actuators
The remote operating control system for the valve is extremely important, and it must be installed to conform with the applicable codes. DOT MC331, for example, most generally applies for trucks.
Fisher offers both cable controls and air cylinder systems to operate the C831 Series internal valves. It may also be possible to use cable controls from other
manufacturers or to fabricate a linkage mechanism.
Any control system requires thermal protection (fuse
links) at the valve, at the remote control point and, if
necessary, near the hose connections. The instruction manuals for Fisher Controls actuator systems show how
to install the fuse links.
Installation instructions on Fisher Types P650, P163A, and P164A cable controls, are in Form MCK-1083. Air cylinder actuator installation is covered in Form MCK-1137. Type P340 latch/remote release instructions
are on Form MCK-2048.
The operating linkage must allow the operating lever to move from the fully closed position to within 2° of the fully open position. The linkage should not apply strong force to the lever past the fully open position or the valve could
be damaged.
CAUTION
The internal valve’s closing spring is not designed to overcome drag in the control linkage in order to close the valve. Depending upon the control system used, an external spring (such as Fisher drawing number 1K4434) or positive closing linkage may be needed. Be sure the control system is installed to prevent binding that could cause the valve to stick in the open position.
Excess Flow Operation
Likewise, if the internal valve is installed on a stationary tank or in the related downstream piping system, the integral excess ow valve can provide protection against
an unintentional release of hazardous materials in the
event that a pump or piping attached directly to the internal valve is sheared off before the rst valve, pump, or tting downstream of the internal valve, provided that the ow of product through the internal valve reaches the rated ow specied by Fisher.
!
EXPLOSION HAZARD
Restrictions incorporated in the discharge system of a bobtail truck or transport or of a stationary tank (due to pumps, pipe and hose length and dimensions, branching, elbows, reductions in pipe diameter, or a
number of other in-line valves or ttings),
low operating pressure as a result of ambient temperature, or a partially closed valve downstream from the integral excess
ow valve, can restrict the rate of ow
through the internal valve below the level necessary to actuate the integral excess
ow valve. Therefore, DO NOT USE the excess ow function of the internal valve
for the purpose of providing protection against the discharge of hazardous materials in the event of a rupture of hose or piping at a point in the discharge system
downstream from the rst valve, pump, or tting downstream of the internal valve.
The internal valve is designed with an internal bleed feature for equalization of
pressure. After the integral excess ow
valve closes, the leakage through the bleed must be controlled or a hazard can be created. For this reason the operator must be familiar with the closure controls for the internal valve and must close the internal valve immediately after the
integral excess ow valve closes.
The internal valve contains an excess ow function, or “integral excess ow valve”, that will close when the ow exceeds the ow rating established by Fisher. Fisher’s integral excess ow valve installed on a bobtail truck or
transport can provide protection against the discharge of hazardous materials during an unloading operation of a bobtail truck or transport in the event that a pump or
piping attached directly to the internal valve is sheared off before the rst valve, pump, or tting downstream of
the internal valve, provided that the cargo tank pressure
produces a ow rate greater than the valve’s excess ow rating.
Failure to follow this warning could result in serious personal injury or property damage
from a re or explosion.
DOT Passive Shutdown Equipment Requirement —DOT regulations 49CFR§173.315(n)(2) require certain
cargo tanks transporting propane, anhydrous ammonia and other liqueed compressed gases to be equipped with passive emergency discharge control equipment that will automatically shut off the ow of product without human intervention within 20 seconds of an unintentional release caused by complete separation of a delivery hose. The design for each passive shutdown system
3
Loading...
+ 5 hidden pages