Fisher Installation Guide: 1098-EGR, 1098H-EGR | Fisher Manuals & Guides

Installation Guide English – February 2016
Types 1098-EGR and 1098H-EGR
Introduction
This installation guide provides instructions for installation, startup and adjustment. To receive a copy of the instruction
manual, contact your local Sales Ofce or view a copy at www.sherregulators.com. For further information refer
to: Types 1098-EGR and 1098H-EGR Instruction Manual, form 5084, D100339X012.
P.E.D. Categories
This product may be used as a safety accessory with pressure equipment in the following Pressure Equipment
Directive 97/23/EC categories. It may also be used outside of the Pressure Equipment Directive using sound
engineering practice (SEP) per table below.
PRODUCT SIZE CATEGORY
DN 25 / NPS 1 SEP
DN 50, 80, 100, 150, 200 x 150 or 300 x 150 /
II
Specications
Body Sizes and End Connection Styles
See Table 1
Main Valve Maximum Inlet Pressure
27.6 bar / 400 psig or body rating limit whichever is lower
Maximum Pilot Supply Pressure
41.4 bar / 600 psig
Outlet Pressure Ranges
(1)
See Table 2
Actuator Sizes and Maximum Pressures
See Table 3
Maximum and Minimum Differential Pressures
See Table 4
Temperature Capabilities
(1)
Nitrile (NBR): -29 to 82°C / -20 to 180°F Fluorocarbon (FKM): -18 to 149°C / 0 to 300°F,
except water is limited to -18 to 93°C / 0 to 200°F
Ethylenepropylene (EPDM): -29 to 135°C / -20 to 275°F
(1)
(1)
(1)
(1)
If the regulator vents uid or a leak
develops in the system, it indicates that
service is required. Failure to take the
regulator out of service immediately may create a hazardous condition.
Personal injury, equipment damage or
leakage due to escaping uid or bursting of
pressure-containing parts may result if this regulator is overpressured or is installed where service conditions could exceed the
limits given in the Specications section,
or where conditions exceed any ratings of the adjacent piping or piping connections.
To avoid such injury or damage, provide pressure-relieving or pressure-limiting devices (as required by the appropriate code, regulation, or standard) to prevent service conditions from exceeding limits.
Additionally, physical damage to the regulator could result in personal injury
and property damage due to escaping uid.
To avoid such injury and damage, install the regulator in a safe location.
Clean out all pipelines before installation of the regulator and check to be sure the regulator has not been damaged
or has collected foreign material during shipping. For
NPT bodies, apply pipe compound to the external pipe
threads. For anged bodies, use suitable line gaskets and
approved piping and bolting practices. Install the regulator
in any position desired, unless otherwise specied, but be sure ow through the body is in the direction indicated by the arrow on the body.
Note
It is important that the regulator be installed so that the vent hole in the spring case is unobstructed at all times. For outdoor installations, the regulator should be located
away from vehicular trafc and positioned
so that water, ice and other foreign materials cannot enter the spring case through the vent. Avoid placing the regulator beneath eaves or downspouts and be sure it is above the probable snow level.
Installation
WARNING
!
Overpressure Protection
The recommended pressure limitations are stamped on the regulator nameplate. Some type of overpressure protection is needed if the actual inlet pressure
Only qualied personnel should install
or service a regulator. Regulators should be installed, operated and maintained in accordance with international and applicable codes and regulations, and Emerson Process Management Regulator Technologies, Inc. instructions.
exceeds the maximum operating outlet pressure rating. Overpressure protection should also be provided if the
regulator inlet pressure is greater than the safe working pressure of the downstream equipment.
Regulator operation below the maximum pressure
limitations does not preclude the possibility of damage from external sources or debris in the line. The regulator should be inspected for damage after any overpressure condition.
1. The pressure/temperature limits in this Installation Guide and any applicable standard or code limitation should not be exceeded.
www.sherregulators.com
D100339XUS2
Types 1098-EGR and 1098H-EGR
Table 1. Body Sizes and End Connection Styles
BODY SIZE
DN NPS
25, 50 1, 2 NPT, CL125 FF or CL250 RF NPT, CL150 RF, CL300 RF, CL600 RF, BWE, SWE or PN 16/25/40
80, 100, 150 3, 4, 6 CL125 FF or CL250 RF CL150 RF, CL300 RF, CL600 RF, BWE or PN 16/25/40
200 x 150, 300 x 150 8 x 6, 12 x 6 - - - - CL150 RF, CL300 RF, CL600 RF or BWE
Table 2. Outlet Pressure Ranges
PILOT TYPE
6351
6352
6353
(1)
6354L
(2)
6354M
6354H
61L 61LD 61LE
61H 0.69 to 4.48 10 to 65
61HP
Y600AM
1. Without diaphragm limiter.
2. With diaphragm limiter.
CAST IRON STEEL OR STAINLESS STEEL
OUTLET (CONTROL) PRESSURE RANGE
bar psig
0.21 to 1.38
0.34 to 2.41
2.41 to 6.90
35 mbar to 0.14 bar
0.14 to 0.69
0.21 to 2.76
2.41 to 8.62
5.86 to 13.8
12.1 to 15.2
13.8 to 20.7
17 mbar to 0.1 bar
0.07 to 0.34
0.14 to 0.69
0.34 to 1.03
0.69 to 1.38
1.03 to 3.10
2.41 to 6.90
6.90 to 20.7
10 to 20 mbar 17 to 40 mbar 37 to 83 mbar
0.83 to 0.17
0.17 to 0.31
0.31 to 0.48
35 to 100
14 in. w.c. to 2 psig
35 to 125
85 to 200 175 to 220 200 to 300
7 in. w.c. to 2 psig
10 to 20
15 to 45
35 to 100 100 to 300
4 to 8 in. w.c.
7 to 16 in. w.c.
15 in. w.c . to 1.2 psig
1.2 to 2.5
2.5 to 4.5
3 to 20 5 to 35
2 to 10 3 to 40
1 to 5 2 to 10 5 to 15
4.5 to 7
Table 3. Actuator Sizes and Maximum Pressures
ACTUATOR OUTLET (CONTROL) PRESSURE EMERGENCY CASING PRESSURE
Type Size bar psig bar psig
1098
30
40 (standard)
70
6.90
5.17
3.45
100
75 50
7.93
5.65
4.48
1098H 30 24.1 350 27.6 400
Table 4. Maximum and Minimum Differential Pressures for Main Valve Selection
MAXIMUM ALLOWABLE
BODY SIZE
SPRING PART
NUMBER
SPRING
COLOR
DIFFERENTIAL
PRESSURE
(1)
DN NPS bar psig bar psig bar psig bar psig
14A9687X012 Green 4.1 60 0.24 3.5 0.17 2.5 0.07 1
25 1
14A9680X012 Blue 8.6 125 0.34 5 0.21 3 0.10 1.5
14A9679X012 Red 27.6
(3)
400
14A6768X012 Yellow 1.4 20 - - - - - - - - 0.14 2 0.07 1
50 2
14A6626X012 Green 4.1 60 0.28 4 0.21 3 0.10 1.5
14A6627X012 Blue 8.6 125 0.41 6 0.34 5 0.14 2
14A6628X012 Red 27.6
(3)
400
14A6771X012 Yellow 1.4 20 - - - - - - - - 0.17 2.5 0.07 1
80 3
14A6629X012 Green 4.1 60 0.34 5 0.28 4 0.14 2
14A6630X012 Blue 8.6 125 0.55 8 0.41 6 0.17 2.5
14A6631X012 Red 27.6
(3)
400
14A6770X012 Yellow 1.4 20 - - - - - - - - 0.25 3.5 0.09 1.3
100 4
14A6632X012 Green 4.1 60 0.69 10 0.34 5 0.17 2.5
14A6633X012 Blue 8.6 125 0.90 13 0.55 8 0.21 3
14A6634X012 Red 27.6
(3)
400
15A2253X012 Yellow 1.4 20 - - - - - - - - 0.42 6 0.15 2.2
150, 200 x 150
or 300 x 150
1. Maximum inlet pressure is equal to set pressure plus maximum differential.
2. Requires special 6300 Series pilot construction without integral check valve and with external Type 1806H 2.8 bar d / 40 psid check valve.
3. Should not exceed the body rating limit. Use this pressure value or the body rating limit, whichever is lower.
6, 8 x 6
or 12 x 6
14A9686X012 Green 4.1 60 0.90 13 0.66 9.5 0.28 4
14A9685X012 Blue 8.6 125 1.3 19 0.97 14 0.41 6
15A2615X012 Red 27.6
(3)
400
MINIMUM DIFFERENTIAL PRESSURE REQUIRED FOR FULL STROKE
Size 30 Actuator Size 40 Actuator Size 70 Actuator
(3)
0.48 7 0.34 5 0.17 2.5
(3)
0.76 11 0.69 10 0.21 3
(3)
0.97 14 0.76 11 0.28 4
(3)
1.5 22 0.90 13 0.34 5
(3)
1.9
(2)
(2)
28
1.3 19 0.55 8
115
82 65
2
Types 1098-EGR and 1098H-EGR
Startup
The regulator is factory set at approximately the midpoint of the spring range or the pressure requested, so an initial adjustment may be required to give the desired results. With proper installation completed and relief
valves properly adjusted, slowly open the upstream and downstream shutoff valves.
21
27
Adjustment
To change the outlet pressure, remove the closing cap or
loosen the locknut and turn the adjusting screw clockwise to increase outlet pressure or counterclockwise to decrease outlet pressure. Monitor the outlet pressure with
a test gauge during the adjustment. Replace the closing cap or tighten the locknut to maintain the desired setting.
Taking Out of Service (Shutdown)
WARNING
!
To avoid personal injury resulting from sudden release of pressure, isolate the regulator from all pressure before attempting disassembly.
Parts List
Type EGR Parts List (Figure 1)
Key Description
1 Valve Body
2 Body Flange 3 Cap Screw or Stud Bolt
4 Gasket
5 Travel Indicator Fitting
6 O-ring Retainer 7 Travel Indicator Stem O-ring 8 Travel Indicator Hex Nut 9 Spring 10 Travel Indicator Stem 11 Cage 12 Port Seal 13 Seat Ring 14 Piston Ring 15 Upper Seal 16 Valve Plug 17 Cage O-ring 18 Travel Indicator Scale 19 Travel Indicator Protector 20 Plug O-ring
21 Travel Indicator Fitting or Indicator Plug O-ring 22 Travel Indicator Flange Nut
23 E-ring
24 Drive Screw 25 Flow Arrow 26 Body Rating Plate (not shown)
27 Indicator Plug 28 Spring Seat
29 Hex Nut (not shown)
31 Pipe Plug 32 Travel Stop
33 NACE Tag (not shown) 34 Tag Wire (not shown) 35 Fitting
36 Back-up Ring 37 O-ring 38 Pipe Plug
35A3167
19
INDICATOR PLUG ASSEMBLY
10
37
7
21
6
3
2
24
26
14
15
9
16 13 12
11
25
24
COMPLETE CAST IRON
FULL-CAPACITY MAIN VALVE ASSEMBLY
Figure 1. Type EGR Main Valve Assembly
18
22
8
35
36
5
31
4
20
23
28
17
1
3
Loading...