Instruction Manual Supplement
D103469X012
FIELDVUE Instruments
Using Fisher™ FIELDVUE™ HART® Digital Valve
April 2017
Controllers with the Smart Wireless THUM
™
Adapter and a HART Interface Module (HIM)
HART communicating FIELDVUE digital valve controllers can be used in conjunction with a HART Interface Module
(HIM) and a Smart Wireless THUM adapter from Emerson Automation Solutions (figure 1). This combination allows
multiple analog signals into a control system via the HIM and remote access to diagnostics with the THUM adapter.
The Smart HART Loop Interface and Monitor from Moore Industries (shown in figure 2), and ValveLink
AMS Suite: Intelligent Device Manager can be used with the THUM adapter to implement this solution.
Note
A THUM adapter should not be used with a FIELDVUE digital valve controller firmware 4 and lower in burst mode. Since the HIM is a
HART Master and polls the FIELDVUE digital valve controller, burst mode is not required.
If the HIM replaces a device that requires the digital valve controller to be in burst mode, be sure to disable burst mode in the
digital valve controller.
Figure 1. Smart Wireless THUM Adapter from Emerson and Moore Industries HART Loop Monitor
™
software or
WIRELESS THUM ADAPTER INSTALLED ON
DVC6200 DIGITAL VALVE CONTROLLER
www.Fisher.com
HART LOOP INTERFACE AND MONITOR (HIM)

FIELDVUE Instruments
April 2017
Instruction Manual Supplement
D103469X012
Figure 2. Example of FIELDVUE DVC6200 SIS Digital Valve Controller Installed with a Moore Industries HART Loop
Monitor, the Smart Wireless Thumb Adapter and the Smart Wireless Gateway
FIELDVUE DVC6200 SIS
Digital Valve Controller
HART
Digital
Communication
Smart HART Loop
Interface and Monitor
WirelessHART
Communications
Smart Wireless
THUM Adapter
4‐20 mA Valve Control Signal
with Superimposed
HART Digital Signal
Valve 90% Open
Valve Full Open
Valve Travel
Output Pressure
®
Relay #1
Relay #2
4-20 mA
4-20 mA
Ethernet
Communication
S
S
Control
System
AMS Device
Manager
ValveLink
Software
PC
Smart Wireless Gateway
Installation and Configuration Considerations
Refer to figures 2 and 3 for installation examples.
The HIM should be configured as the Primary Master and the THUM adapter as the Secondary Master. Both devices will
be transparent on the loop and poll the digital valve controller.
The HIM updates about 2 times per second. The THUM adapter updates as configured by the user and allows
communications with ValveLink software and AMS Device Manager.
2