Instruction Manual Supplement
D104227X012
IECEx Hazardous Area Approvals
DVC2000 Digital Valve Controller
July 2017
Fisher
™
FIELDVUE™ DVC2000 Digital Valve
Controller
Hazardous Area Classifications and Special Instructions for “Safe
Use” and Installations in Hazardous Locations
Certain nameplates may carry more than one approval, and each approval may have unique installation/wiring
requirements and/or conditions of “safe use”. These special instructions for “safe use” are in addition to, and may
override, the standard installation procedures. Special instructions are listed by approval.
Note
This information supplements the nameplate markings affixed to the product and the DVC2000 quick start guide (D103203X012
and instruction manual (D103176X012
Always refer to the nameplate itself to identify the appropriate certification.
), available from your Emerson sales office, Local Business Partner, or Fisher.com.
)
WARNING
Failure to follow these conditions of “safe use” could result in personal injury or property damage from fire or explosion, or
area re‐classification.
Conditions of Certification
Intrinsically Safe
This equipment shall be connected in accordance with the manufacturer's installation instructions (drawing GE14581,
figure 2) to intrinsic safety barriers that satisfy the following parameters for each set of terminals.
Main 4-20 mA: Ui = 30 V, Ii = 130 mA, Pi = 1W, Li = 0.55 mH, Ci = 10.5 nF
XMTR circuit: Ui = 28 V, Ii = 100 mA, Pi = 1W, Li = 0 mH, Ci = 5 nF
Limit Switch 1 (LS1): Ui = 16 V, Ii = 76 mA, Pi = 1W, Li = 0 mH, Ci = 5 nF
Limit Switch 2 (LS2): Ui = 16 V, Ii = 76 mA, Pi = 1W, Li = 0 mH, Ci = 5 nF
Refer to figure 1 for a typical DVC2000 IECEx approval nameplate.
www.Fisher.com

DVC2000 Digital Valve Controller
July 2017
Figure 1. Typical IECEx Nameplate
Instruction Manual Supplement
D104227X012
2