Fisher IM Supplement: IECEx Hazardous Area Approvals-FIELDVUE DVC2000 Digital Valve Controller Manuals & Guides

Instruction Manual Supplement
D104227X012
IECEx Hazardous Area Approvals
DVC2000 Digital Valve Controller
July 2017
Fisher
FIELDVUE™ DVC2000 Digital Valve
Controller
Hazardous Area Classifications and Special Instructions for “Safe Use” and Installations in Hazardous Locations
Certain nameplates may carry more than one approval, and each approval may have unique installation/wiring requirements and/or conditions of “safe use”. These special instructions for “safe use” are in addition to, and may override, the standard installation procedures. Special instructions are listed by approval.
Note
This information supplements the nameplate markings affixed to the product and the DVC2000 quick start guide (D103203X012 and instruction manual (D103176X012
Always refer to the nameplate itself to identify the appropriate certification.
), available from your Emerson sales office, Local Business Partner, or Fisher.com.
)
WARNING
Failure to follow these conditions of “safe use” could result in personal injury or property damage from fire or explosion, or area re‐classification.
Conditions of Certification
Intrinsically Safe
This equipment shall be connected in accordance with the manufacturer's installation instructions (drawing GE14581, figure 2) to intrinsic safety barriers that satisfy the following parameters for each set of terminals.
Main 4-20 mA: Ui = 30 V, Ii = 130 mA, Pi = 1W, Li = 0.55 mH, Ci = 10.5 nF
XMTR circuit: Ui = 28 V, Ii = 100 mA, Pi = 1W, Li = 0 mH, Ci = 5 nF
Limit Switch 1 (LS1): Ui = 16 V, Ii = 76 mA, Pi = 1W, Li = 0 mH, Ci = 5 nF
Limit Switch 2 (LS2): Ui = 16 V, Ii = 76 mA, Pi = 1W, Li = 0 mH, Ci = 5 nF
Refer to figure 1 for a typical DVC2000 IECEx approval nameplate.
www.Fisher.com
DVC2000 Digital Valve Controller
July 2017
Figure 1. Typical IECEx Nameplate
Instruction Manual Supplement
D104227X012
2
Instruction Manual Supplement
D104227X012
Figure 2. IECEx Installation Drawing GE14581
DVC2000 Digital Valve Controller
July 2017
INSTALLATION MUST BE IN ACCORDANCE WITH THE NATIONAL WIRING PRACTICES OF THE COUNTRY IN USE.
BARRIERS MUST BE CONNECTED PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.
INTRINSICALLY SAFE APPARATUS MAY BE CONNECTED TO ASSOCIATED
APPARATUS NOT SPECIFICALLY EXAMINED IN SUCH COMBINATION. THE CRITERIA FOR INTERCONNECTION IS THAT THE VOLTAGE (Ui) AND THE CURRENT (Ii) OF THE INTRINSICALLY SAFE APPARATUS MUST BE EQUAL TO OR GREATER THAN THE VOLTAGE (Uo) AND CURRENT (Io) DEFINED BY THE ASSOCIATED APPARATUS. IN ADDITION, THE SUM OF THE MAXIMUM UNPROTECTED CAPACITANCE (Ci) AND INDUCTANCE (Li) OF EACH INTRINSICALLY SAFE APPARATUS, AND THE
HAZARDOUS LOCATION NON‐HAZARDOUS LOCATION INTERCONNECTING WIRING, MUST BE LESS THAN THE ALLOWABLE CAPACITANCE (Co) AND INDUCTANCE (Lo) DEFINED BY THE ASSOCIATED APPARATUS. IF THESE
ZONE 0, GROUP IIC
CRITERIA ARE MET, THEN THE COMBINATION MAY BE CONNECTED. FORMULASUi > Uo
Ii > Io Ci + Ccable < Co Li + Lcable < Lo Pi > Po
ENTITY PARAMETERS FOR EACH I.S. CIRCUIT ARE AS FOLLOWS:
CIRCUIT
 XMTR  MAIN  LS1  LS2
VMax (Ui)
28Vdc 30Vdc 16Vdc 16Vdc
IMAX(Ii)
100mA 130mA 76mA 76mA
Ci
5nF
10.5nF 5nF 5nF
Li
0 mH
0.55 mH 0 mH 0 mH
PMAX
1W 1W 1W 1W
DVC2000
WHERE MULTIPLE I.S. CIRCUITS ARE USED:
S EACH I.S. CIRCUIT MUST BE SHIELDED TWISTED PAIR CABLE. S I.S. CIRCUITS MUST ENTER ENCLOSURE VIA CONDUIT ENTRIES
AS SPECIFIED IN DETAIL 1.
S CABLE INSULATION AND SHIELD MUST EXTEND TO WITHIN PARTITIONED
AREA (SEE DETAIL 1).
S XMTR, LS1, AND LS2 CIRCUITS ARE OPTIONAL.
RESISTANCE BETWEEN BARRIER GROUND AND EARTH GROUND MUST BE LESS THAN ONE OHM.
IF HAND‐HELD COMMUNICATOR OR MULTIPLEXOR IS USED, IT MUST BE APPROVED
WITH ENTITY PARAMETERS AND INSTALLED PER THE MANUFACTURER'S CONTROL DRAWING.
GE14581‐C
WARNING
THE APPARATUS ENCLOSURE CONTAINS ALUMINUM AND IS CONSIDERED TO CONSTITUTE A POTENTIAL RISK OF IGNTION BY IMPACT OR FRICTION. CARE MUST BE TAKEN DURING INSTALLATION AND USE TO PREVENT IMPACT OR FRICTION.
XMTR
MAIN
LS1
LS2
DETAIL 1
I.S. APPROVED BARRIER
I.S. APPROVED BARRIER
I.S. APPROVED BARRIER
I.S. APPROVED BARRIER
XMTR
MAIN
LS1
LS2
PARTITIONED AREA
Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
FIELDVUE and Fisher are marks owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. Emerson Automation Solutions, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.
Emerson Automation Solutions
Marshalltown, Iowa 50158 USA Sorocaba, 18087 Brazil Cernay, 68700 France Dubai, United Arab Emirates Singapore 128461 Singapore
www.Fisher.com
E 2017 Fisher Controls International LLC. All rights reserved.
3
Loading...