Instruction Manual Supplement
D104227X012
IECEx Hazardous Area Approvals
DVC2000 Digital Valve Controller
July 2017
Fisher
™
FIELDVUE™ DVC2000 Digital Valve
Controller
Hazardous Area Classifications and Special Instructions for “Safe
Use” and Installations in Hazardous Locations
Certain nameplates may carry more than one approval, and each approval may have unique installation/wiring
requirements and/or conditions of “safe use”. These special instructions for “safe use” are in addition to, and may
override, the standard installation procedures. Special instructions are listed by approval.
Note
This information supplements the nameplate markings affixed to the product and the DVC2000 quick start guide (D103203X012
and instruction manual (D103176X012
Always refer to the nameplate itself to identify the appropriate certification.
), available from your Emerson sales office, Local Business Partner, or Fisher.com.
)
WARNING
Failure to follow these conditions of “safe use” could result in personal injury or property damage from fire or explosion, or
area re‐classification.
Conditions of Certification
Intrinsically Safe
This equipment shall be connected in accordance with the manufacturer's installation instructions (drawing GE14581,
figure 2) to intrinsic safety barriers that satisfy the following parameters for each set of terminals.
Main 4-20 mA: Ui = 30 V, Ii = 130 mA, Pi = 1W, Li = 0.55 mH, Ci = 10.5 nF
XMTR circuit: Ui = 28 V, Ii = 100 mA, Pi = 1W, Li = 0 mH, Ci = 5 nF
Limit Switch 1 (LS1): Ui = 16 V, Ii = 76 mA, Pi = 1W, Li = 0 mH, Ci = 5 nF
Limit Switch 2 (LS2): Ui = 16 V, Ii = 76 mA, Pi = 1W, Li = 0 mH, Ci = 5 nF
Refer to figure 1 for a typical DVC2000 IECEx approval nameplate.
www.Fisher.com

DVC2000 Digital Valve Controller
July 2017
Figure 1. Typical IECEx Nameplate
Instruction Manual Supplement
D104227X012
2

Instruction Manual Supplement
D104227X012
Figure 2. IECEx Installation Drawing GE14581
DVC2000 Digital Valve Controller
July 2017
INSTALLATION MUST BE IN ACCORDANCE WITH THE NATIONAL WIRING PRACTICES OF THE
COUNTRY IN USE.
BARRIERS MUST BE CONNECTED PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.
INTRINSICALLY SAFE APPARATUS MAY BE CONNECTED TO ASSOCIATED
APPARATUS NOT SPECIFICALLY EXAMINED IN SUCH COMBINATION. THE CRITERIA
FOR INTERCONNECTION IS THAT THE VOLTAGE (Ui) AND THE CURRENT (Ii) OF THE
INTRINSICALLY SAFE APPARATUS MUST BE EQUAL TO OR GREATER THAN THE
VOLTAGE (Uo) AND CURRENT (Io) DEFINED BY THE ASSOCIATED APPARATUS. IN
ADDITION, THE SUM OF THE MAXIMUM UNPROTECTED CAPACITANCE (Ci) AND
INDUCTANCE (Li) OF EACH INTRINSICALLY SAFE APPARATUS, AND THE
HAZARDOUS LOCATION NON‐HAZARDOUS LOCATION
INTERCONNECTING WIRING, MUST BE LESS THAN THE ALLOWABLE
CAPACITANCE (Co) AND INDUCTANCE (Lo) DEFINED BY THE
ASSOCIATED APPARATUS. IF THESE
ZONE 0, GROUP IIC
CRITERIA ARE MET, THEN THE COMBINATION MAY BE CONNECTED.
FORMULASUi > Uo
Ii > Io
Ci + Ccable < Co
Li + Lcable < Lo
Pi > Po
ENTITY PARAMETERS FOR EACH I.S. CIRCUIT ARE AS FOLLOWS:
CIRCUIT
XMTR
MAIN
LS1
LS2
VMax (Ui)
28Vdc
30Vdc
16Vdc
16Vdc
IMAX(Ii)
100mA
130mA
76mA
76mA
Ci
5nF
10.5nF
5nF
5nF
Li
0 mH
0.55 mH
0 mH
0 mH
PMAX
1W
1W
1W
1W
DVC2000
WHERE MULTIPLE I.S. CIRCUITS ARE USED:
S EACH I.S. CIRCUIT MUST BE SHIELDED TWISTED PAIR CABLE.
S I.S. CIRCUITS MUST ENTER ENCLOSURE VIA CONDUIT ENTRIES
AS SPECIFIED IN DETAIL 1.
S CABLE INSULATION AND SHIELD MUST EXTEND TO WITHIN PARTITIONED
AREA (SEE DETAIL 1).
S XMTR, LS1, AND LS2 CIRCUITS ARE OPTIONAL.
RESISTANCE BETWEEN BARRIER GROUND AND EARTH GROUND MUST BE LESS THAN ONE OHM.
IF HAND‐HELD COMMUNICATOR OR MULTIPLEXOR IS USED, IT MUST BE APPROVED
WITH ENTITY PARAMETERS AND INSTALLED PER THE MANUFACTURER'S CONTROL DRAWING.
GE14581‐C
WARNING
THE APPARATUS ENCLOSURE CONTAINS ALUMINUM
AND IS CONSIDERED TO CONSTITUTE A POTENTIAL
RISK OF IGNTION BY IMPACT OR FRICTION. CARE
MUST BE TAKEN DURING INSTALLATION AND USE TO
PREVENT IMPACT OR FRICTION.
XMTR
MAIN
LS1
LS2
DETAIL 1
I.S. APPROVED
BARRIER
I.S. APPROVED
BARRIER
I.S. APPROVED
BARRIER
I.S. APPROVED
BARRIER
XMTR
MAIN
LS1
LS2
PARTITIONED AREA
Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance
of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
FIELDVUE and Fisher are marks owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. Emerson
Automation Solutions, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their
respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not
to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are
governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such
products at any time without notice.
Emerson Automation Solutions
Marshalltown, Iowa 50158 USA
Sorocaba, 18087 Brazil
Cernay, 68700 France
Dubai, United Arab Emirates
Singapore 128461 Singapore
www.Fisher.com
E 2017 Fisher Controls International LLC. All rights reserved.
3