Fisher IM Supplement: HART Field Device Specification - FIELDVUE DLC3010 Digital Level Controller (Supported Product) Manuals & Guides

Instruction Manual Supplement
D104329X012
HARTr Field Device Specification
DLC3010 Digital Level Controller
May 2022
Fisher
FIELDVUE™ DLC3010 Digital Level
Controller (Supported Product)
HART 5
Contents
Introduction 2.................................
Scope 2......................................
Purpose of this document 2.....................
Abbreviations and definitions 2..................
Reference Documentation 3....................
Device Identification 3..........................
Product Overview 3............................
Product Interfaces 4............................
Process Interface 4............................
Process Temperature Interface 4.................
Electronics Temperature Interface 5..............
Host interface 5...............................
HART Digital Interface 5........................
Local Interfaces, Jumpers and Switches 5..........
Device Variables 6..............................
Dynamic Variables 7............................
Status Information 7............................
Universal Commands 8..........................
Common-Practice Commands 18.................
Device Specific Commands 27....................
Tables 38.....................................
Performance 45................................
Annex A: Compatibility Checklist 48...............
Annex B: Default Configuration 48................
Annex C DLC3010 Parameters as part of a Rosemount
Gateway 50...............................
1410/1420 WirelessHARTr
04 1 8
W7977-2
www.Fisher.com
Product removed from sale April 2022
DLC3010 Digital Level Controller
May 2022
Instruction Manual Supplement
D104329X012
Introduction
Scope
The Fisher DLC3010 digital level controller targeted compliance with HART Protocol Revision 5.2. Additionally, an effort was made to provide support for the proposed revision 5/6 compatibility rules. This document provides all the device-specific features and HART communications protocol implementation details. The functionality of this field device is described sufficiently to allow its proper application in a process and its complete support in HART-capable host applications.
Purpose of this document
This document provides a description of the field device from a HART Communication perspective. Additional product information can be found in the DLC3010 product literature, available from your Emerson sales office
Who should use this document
.
The information contained herein is intended for use as a technical reference for HART-capable host application developers, systems integrators, and knowledgeable end-users. It also provides functional specifications (e.g., commands, enumerations, and performance requirements) used during field device development, maintenance, and testing. Users of this document must be fully trained in HART Protocol requirements and terminology.
Abbreviations and definitions
Additional Device Status
Byte An 8bit unsigned integer
Common Table <n> A reference to a table in HCF_SPEC-183 (FCG TS20183) Common Tables Specification
Configuration Variables
Device Variable
DLC DLC3010 digital level controller product
Dynamic Variable
Enumeration A pre-defined set of values or text
Float IEEE 754 floating point format
HART Highway Addressable Remote Transducer
LCD Liquid Crystal Display
Lift-Off Voltage
Status information returned by Command 48
Variables which represent nonvolatile values of manufacturinginitialized data or userspecified configuration information. These variables cannot be accessed via Universal or Common Practice Commands.
Uniquely defined data items within a field device, containing process-related information. They are assigned consecutive code numbers starting with zero.
A Device Variable mapped to a slot in the set of HART commands that support potential analog channels in the device. Only the first slot is required to have an associated analog channel.
Minimum supply voltage required at device terminals to guarantee correct behavior, (including HART communication), during both normal operation and while indicating a malfunction
2
Instruction Manual Supplement
D104329X012
NVM Non-volatile memory
Packed
RTD Resistance Temperature Detector
STO
Word A 16bit unsigned integer
Uint <n> Unsigned integer with bit length n
Packed ASCII, a special form of characters defined by HART in which four 6bit ASCII characters are packed into three bytes
Slave Time Out. The time allowed for a slave device to begin its transmission, defined in HCF_SPEC-081 (FCG TS20081) and tested in HCF_TEST-001 section 7.24 DLL024.
Reference Documentation
DLC3010 Digital Level Controller
May 2022
HART Smart Communications Protocol Specification Revision 5.0; a group of documents specifying the HART Communication Protocol, physical layers, and Data Link Layers as defined by the FieldComm Group
FIELDVUE DLC3010 Digital Level Controller Instruction Manual, D102748X012
FIELDVUE DLC3010 Digital Level Controller Quick Start Guide, D103214X012
Industrial Platinum Resistance Thermometers and Platinum Temperature Sensors, IEC 60751, International Electrotechnical Commission
.
Device Identification
Manufacturer Name Fisher Controls Model Name(s) DLC3010
Manufacture ID Code 19 (13 Hex) Device Type Code 04 (04 Hex)
HART Protocol Revision 5.2 Device Revision 1
Number of Device Variables 5 (effectively 3, as variables 0, 1 and 2 cannot coexist)
Physical Layers Supported FSK (Bell 202 Current)
Physical Device Category Transmitter (two-wire), Non-DC-isolated Bus Device
Product Overview
DLC3010 digital level controllers are used with level sensors to measure liquid level, level of the interface between two liquids, or liquid specific gravity (density). Changes in level or specific gravity exert a buoyant force on a displacer, which rotates the torque tube shaft. This rotary motion is applied to the digital level controller, transformed to an electrical signal and digitized. The digital signal is compensated and processed per user configuration requirements, and converted to a 4-20 mA analog electrical signal. The resulting current output signal is sent to an indicating or final control element. The name plate is located on the top of the DLC3010 assembly and indicates the model name, individual product serial number, and any applicable third party approvals.
3
DLC3010 Digital Level Controller
May 2022
Instruction Manual Supplement
D104329X012
Product Interfaces
Process Interface
Primary Variable Sensor Interface
DLC3010 digital level controllers mount on a wide variety of caged and cageless 249 level sensors. Mounting adaptors are available to allow using them on other manufacturers' displacer type level sensors. The field device is provided with a lever that carries a set of magnets across a Hall-Effect sensor to transform angular position into voltage. The lever is coupled to the buoyancy sensor’s pilot shaft by a clamping bolt and nut. Nominal design rotation of the buoyancy sensor for a full span change of water level at room temperature is 4.4_. To best utilize the accuracy of the transmitter, the amount of input rotation used should be close to this range. For applications that would develop a very small proportional band with standard hardware, (e.g., interface level measurements where the difference between the densities of the two phases is quite small), custom sensor configurations may be specified to improve the mechanical gain.
The available lever travel in the digital level controller is approximately ±6_ from the neutral or ‘locked’ position. This allows right- or left-hand-mounted sensors to be used with out mechanical changes to the transmitter. It also allows the digital level controller to be used with sensors having mechanical gain slightly higher than nominal by physically coupling at the center of sensor travel instead of at the lowest process condition.
249 LEVEL SENSOR
DLC3010 DIGITAL LEVEL CONTROLLER
Process Temperature Interface
An external 100 Ohm Platinum RTD of 2-wire or 3-wire configuration may be installed to provide process temperature instrumentation. The terminals for the RTD are in the lower bank of the instrument terminal box, and are labeled “Rs”, “R1”, and “R2”, from left to right. “Rs” and “R1” are used for the two wires from the same node of a 3-wire RTD, and must be shorted with a jumper when a two-wire RTD is employed. Refer to the Instruction Manual for additional installation details. When the RTD is installed, configured, and calibrated, and a table of density versus temperature is entered by the user, this input will be used to drive density compensation for the level calibration. If the RTD is not installed, the compensation tables can also be driven by a manually-entered value of process temperature. To disable the density temperature-compensation, the compensation table length is reduced to 1 element.
4
Instruction Manual Supplement
D104329X012
DLC3010 Digital Level Controller
May 2022
The process temperature value derived from the RTD may be checked against user-defined alarm thresholds to indicate when the sensor is operating outside of recommended temperature limits.
Electronics Temperature Interface
An internal temperature sensor mounted near the Hall Sensor is utilized to drive factory-configured temperature compensation for magnetic flux and Hall-effect sensitivity variations. It may also be checked against user-defined alarm thresholds to indicate when the transmitter is operating outside of recommended temperature limits.
Host interface
Analog Output: Primary Variable
When available terminal voltage is above the Lift-Off Voltage, the DLC3010 acts as the current source in a twowire 4to20 mA current loop (in pointtopoint mode) or draws 4 mA fixed current (in multidrop mode). This output is provided in the DLC3010’s terminal box at two terminals marked “+” and “”. Refer to the Quick Start Guide for connection details. In point-to-point mode, the digital value of the primary variable is mapped to the 4-20 mA signal by the Range Values.
Direction Value (% Range) Value (mA or V)
Saturation Limits
Alarm Indication
Maximum Current 22.5 mA
Multi-Drop Current Draw 4.0 mA
Lift-Off Voltage 12 V.
* User must select one or the other of the alarm indication outputs with a hardware jumper. They are mutually exclusive.
High PV > +103.13% 20.5 mA Low PV < -1.25% 3.8 mA High* 22.5 mA Low* 3.7 mA
HART Digital Interface
When available terminal voltage is above the Lift-Off Voltage, the DLC3010 can communicate digitally via Bell 202 FSK HART protocol. This interface is available at test clips in the DLC3010’s terminal box on the two terminals marked “+” and “”, or across any convenient impedance on the loop that is sufficient to meet the HART signaling requirements. Refer to the Quick Start Guide for connection details.
Local Interfaces, Jumpers, and Switches
Local Displays
A removable Liquid Crystal Display (LCD) assembly is provided. It displays PV %Range on a circular “bar-graph”, and different combinations of digital information such as PV %Range, PV in engineering units, Process Temperature, etc. Display symbols or text are provided for:
D Write-lock (key symbol)
D Display numeric field overflow (OFLOW)
D Hardware failure (Hdwr FL)
5
DLC3010 Digital Level Controller
May 2022
Instruction Manual Supplement
D104329X012
Local Jumpers
A fail-mode jumper is provided on the lower face of the LCD assembly (on the upper right quadrant of the electronics module when the LCD is not used). This jumper is internal to the electronics compartment and may only be accessed by removing the main cover. It allows the user to select either the High or Low alarm indication documented in the table above. Only one alarm indication value can be made available during operation. The fault conditions that trigger the alarm are documented in table 2a.
Device Variables
These variables represent measurements taken by the device (see table 5), and are all in float format. Their values are not directly exposed by any standard HART command. However, they are the set of internal variables from which the Dynamic Variables are selected. Only one of the Liquid Level, Interface Level, or Liquid Density measurements may be computed in a given configuration, so assigning one of these to PV sets up the structure of the measurement algorithm. Temperature variable selections are permanently allocated to SV and TV slots, so their indices are used primarily for units processing. Process temperature is only functional as TV if the RTD is installed, otherwise it is a fixed parameter entered by the user.
Device Variable 0 - Liquid Level
When Liquid Level is assigned as PV, the process value is derived from the measured rotation of the sensor’s torque tube by using calibration data to convert the change in rotation to a force measurement, then applying displacer weight, displacer volume, and fluid density configuration data to convert force to liquid level. This variable is not computed when it is not assigned as PV.
Device Variable 1 - Interface Level
When the Interface Level is assigned as PV, the process value is derived from the measured rotation of the sensor’s torque tube by using calibration data to convert the change in rotation to a force measurement, then applying displacer weight, displacer volume, upper fluid density, and lower fluid density configuration data to convert force to interface level. This variable is not computed when it is not assigned as PV.
Device Variable 2 – Liquid Density
When the Liquid Density is assigned as PV, the process value is derived from the measured rotation of the sensor’s torque tube by by using calibration data to convert the change in rotation to a force measurement, then applying weight and volume configuration data to convert force to fluid density. This variable is not computed when it is not assigned as PV.
Device Variable 3 – Process Temperature
When an RTD installed in the process fluid is wired to the device and assigned as the Process Temperature Source, the Process Temperature variable is derived from the measured resistance of the RTD via a table related to IEC 60751. A 60-second lag, factory calibration, and user offset adjustments are applied to the signal before reporting.
When “Manual Entry” is assigned as the Process Temperature Source, this variable simply reports a fixed user-entered value.
Device Variable 4 – Electronics Temperature
This variable is derived from the voltage drop across a semiconductor junction in a chip mounted in the transducer housing. A 60-second lag and factory or user offset adjustments are applied to the signal before reporting.
6
Instruction Manual Supplement
D104329X012
DLC3010 Digital Level Controller
May 2022
Dynamic Variables
Three Dynamic Variables are implemented. The PV is user-selectable to one of the first three Device Variables via Command 51.
Default Meaning Units
PV* SV Instrument Temperature See table 6 TV Process Temperature See table 6 FV Not Used N/A
* User selectable
Liquid Level See table 6
Status Information
Device Status
The Field Device Status Byte (see table 2a) is the only status byte defined in the HART 5 protocol. The order and meaning of each of the eight bits within the byte are fixed by the protocol. This byte is one of the status bytes included with each HART response. It is not part of the Command 48 data.
Extended Device Status
This byte was not defined in the HART 5 specification, so it is not supported.
Additional Status Integrity Bytes
Three Additional Status bytes providing details of internal monitor states are returned in the Command 48 response. Refer to table 2b for definitions of the bits.
7
DLC3010 Digital Level Controller
May 2022
Instruction Manual Supplement
Universal Commands
The following HART 5.0 Universal Commands are implemented in the DLC3010 firmware:
Command 0: Read Unique HART Identifier Command 1: Read Primary Variable Command 2: Read PV Current and Percent Range Command 3: Read Dynamic Variables and PV Current Command 6: Write Polling Address Command 11: Read Unique Identifier with Tag Command 12: Read Message Command 13: Read Tag, Descriptor, Date Command 14: Read PV Sensor Info Command 15: Read PV Output Info Command 16: Read Final Assembly Number Command 17: Write Message Command 18: WriteTag, Descriptor, Date
D104329X012
Note
At HART 5, Commands 38 and 48 were in the Common Practice group.
Any command can return any of the following response codes:
0 No command specific errors 5 Incorrect Byte Count 8 Warning - value written was truncated (write commands only) 32 Busy
In addition, some commands may return additional error codes. See the “Command Specific Response Codes” part of the command description for additional codes. One of the error codes associated with writing data to the instrument is:
7 In Write Protect Mode
A more complete list is available in table 1. All commands will check for the required number of data bytes and return Incorrect Byte Count if too few bytes are received. If too many bytes are received for the given command, the extra bytes are ignored. This is the behavior defined by the HART specification, which allows for command expansion with backward compatibility. If additional bytes are added to any command, an older instrument will still accept the command with only the original bytes used and will ignore any of the additional bytes.
8
Instruction Manual Supplement
D104329X012
DLC3010 Digital Level Controller
May 2022
Command 0: Read Unique Identifier
Returns identity information about the field device in HART 5 identity format, including: Device Type, revision levels, and Device ID. This command is implemented by a field device in both Short and Long Frame Formats. Command 0 is the only command that may respond to a short frame address. The Device Type Code will be returned in the expanded three-byte format. ("254", Manufacturer Identification Code, Manufacturer's Device Type Code). The combination of Manufacturer Identification Code, Manufacturer's Device Type Code, and Device Identification Code make up the Unique Identifier required for the Extended Frame Format of the Data Link Layer.
Byte Format Description Returned Value
Request Data bytes
None
0 Enum Expansion code “254” 254
1 Enum Manufacturer Identification code [Common Table 8] 19
2 Enum Manufacturer's Device Type code [Common Table 1] 4
3 Uint8
4 Uint8
5 Uint8
6 Uint8 Software revision level of this device 8
7.7-7.3 Uint5
7.2-7.0 Enum Physical Signaling Code [Common Table 10] 0
8 Bits Flags [Common Table 11] 0
9-11 Uint24 (Unique) Device Identification Number
Code Class Description
Number of preambles required for master to slave request, including those required for message detection
Revision level of the universal command document implemented by this device. Levels 254 and 255 are reserved.
Revision level of the device - specific document implemented. Levels 254 and 255 are reserved
Hardware revision level. Does not necessarily trace component changes
5
5
1
1
Response Codes
6
Error Device-Specific Command Error
9
DLC3010 Digital Level Controller
May 2022
Command 1: Read Primary Variable
The Primary Variable is returned along with its Units Code.
Byte Format Description
Instruction Manual Supplement
D104329X012
Request Data Bytes
Response Data Bytes
Response Codes
None
0 Enum Primary Variable Units (table 6, DLC3010 Unit Codes)
1-4 Float Primary Variable
Code Class Description
6 8
16
Error Device-Specific Command Error
Warning Update Failure
Error Access Restricted
Command 2: Read Loop Current and Percent of Range
The Loop Current should match the current that would be measured by a milliammeter in series with the field device. The actual implementation reports the commanded value driving the output Digital to Analog converter.
The Percent of Range signal follows the PV as mapped by URV and LRV in normal operation. However, the value reported by Command 2 in the DLC3010 at firmware 8 is derived from the current command, thus reflecting saturation limits and alarm values, instead of following PV out to Sensor Limits.
Byte Format Description Returned Value
Request Data Bytes
Response Data Bytes
None
0-3 Float Primary Variable Loop Current (milliamperes)
4-7 Float Primary Variable Percent of Range (%)
Response Codes
10
Code Class Description
6 8
Error
Warning
Device-Specific Command Error Update Failure
Instruction Manual Supplement
D104329X012
DLC3010 Digital Level Controller
May 2022
Command 3: Read Dynamic Variables and Loop Current
The Loop Current should match the current that would be measured by a milliammeter in series with the field device. The actual implementation reports the commanded value driving the output Digital to Analog converter.
The remaining Response Data include the PV with its Units Code, Process Temperature and Electronics Temperature with Temperature Units Codes.
Byte Format Description Returned Value
Request Data Bytes
Response Data Bytes
Response Codes
None
0-3 Float Primary Variable Loop Current (mA)
4 Enum Primary Variable Units Code (table 6)
5-8 Float Primary Variable
9 Enum Secondary Variable Units Code (table 6)
10-13 Float Secondary Variable (Electronics Temperature)
14 Enum Tertiary Variable Units Code (table 6)
15-18 Float Tertiary Variable (Process Temperature)
19 Enum Not Used
20-23 Float Not Computed NaN
Code Class Description
6 8
Error Device-Specific Command Error
Warning Update Failure
250
11
DLC3010 Digital Level Controller
May 2022
Instruction Manual Supplement
D104329X012
Command 6: Write Polling Address
This is a Data Link Layer Management Command.
This command writes the Polling Address to the field device. The address is used to control the Primary Variable Analog Output and provide a means of device identification in Multidrop installations.
The Primary Variable Analog Output responds to the applied process only when the Polling Address of the device is set to 0. When the address assigned to a device is in the range from 1 through 15, the Analog Output is Not Active and does not respond to the applied process. While the Analog Output is Not Active, the Analog Output is set to its minimum; the Transmitter Status Bit #3, Primary Variable Analog Output Fixed, is set; and the Upscale/Downscale Alarm is disabled. If the Polling Address is changed back to 0, the Primary Variable Analog Output will become Active and respond to the applied process.
In the HART 5 specification, no Read Command was provided for Polling Address. A Device-Specific Command is used to acquire its value for display in the interface.
Byte Format Description
0 Uint8 Polling Address
Request Data bytes
Response Data Bytes
Response Codes
0 Analog Output Active
1 – 15 Analog Output Not Active
16 - 255 Invalid
0 Uint8 Polling Address
0 Analog Output Active
1 – 15 Analog Output Not Active
16 - 255 Invalid
Code Class Description
2 Error Invalid Selection 5 6 7
Error Too Few Data Bytes Received Error Device-Specific Command Error Error In Write-Protect Mode
12
Instruction Manual Supplement
D104329X012
DLC3010 Digital Level Controller
May 2022
Command 11: Read Unique Identifier Associated with Tag
This command returns the Expanded Device Type code, revision levels, and Device Identification Number from a device containing the requested Tag. This command is unique in that no response will be made unless the Tag matches that of the device.
The Device Type Code will always be returned in expanded 3-byte format: "254", Manufacturer Identification Code, Manufacturer's Device Type code.
Byte Format Description Returned Value
Request Data bytes
Response Data Bytes
Response
Codes
0-5
0 Enum Device Type Code for Expansion 254
1 Enum Manufacturer Identification Code 19
2 Enum Device Type Code 4
3 Uint8
4 Uint8
5 Uint8
6 Uint8 Software revision level of this device 8
7.7-7.3 Uint5
7.2-7.0 Enum3 Physical Signaling Code [Common Table 10] 0
8 Bits Flags [Common Table 11] 0
9-11 Uint24 Device Identification Number
Code Class Description
6 Error Device-Specific Command Error
Packed Tag
Number of Preambles required for request from Master to Slave, including those required for message detect
Revision Level of the Universal Command Specification implemented by this device
Revision level of the device - specific document implemented.
Hardware revision level. Does not necessarily trace component changes
5
5
1
1
13
DLC3010 Digital Level Controller
May 2022
Command 12: Read Message
This command reads a user-defined message contained within the device.
Byte Format Description
Instruction Manual Supplement
D104329X012
Request Data bytes
Response Data Bytes
Response Codes
None
023 Packed Message String
Code Class Description
6 Error Device-Specific Command Error
Command 13: Read Tag, Descriptor, Date
This command reads the tag, descriptor, and date contained within the device.
Byte Format Description
Request Data bytes
Response Data Bytes
Response Codes
None
05 Packed Tag
617 Packed Descriptor
1820 Uint8[3] Date; Respectively: day, month, year – base year (1900)
Code Class Description
6 Error Device-Specific Command Error
14
Instruction Manual Supplement
D104329X012
DLC3010 Digital Level Controller
May 2022
Command 14: Read Primary Variable Sensor Information
Reads the Primary Variable Sensor Serial Number, Primary Variable Sensor Limits/Minimum Span Units Code, Primary Variable Upper Sensor Limit, Primary Variable Lower Sensor Limit, and Primary Variable Minimum Span for the sensor. The Primary Variable Sensor Limits and Minimum Span Units will be the same as the Primary Variable Units.
Note
The sensor serial number is not applicable to the DLC3010 and is set to “0”.
3 bytes (2^24 = 16,777,216 ) were insufficient to code Fisher serial numbers, which have passed the 17,000,000 mark, and may also contain non-numeric elements. We have created a device-specific variable to hold the displacer serial number
Byte Format Description Returned Value
Request Data bytes
Response Data Bytes
Response Codes
None
02 Uint24 Not used in DLC3010 - Sensor Serial Number 000000
3 Enum Sensor Limits and Minimum Span Units Code From Cmd 44
Level Offset plus 120% of
47 Float Upper Sensor Limit
displacer length, or a density of
1.5 SGU Level Offset minus 20% of
811 Float Lower Sensor Limit
displacer length, or a density of
0.1 SGU Closest usable spacing
between upper/lower range
1215 Float Minimum Span
values before accuracy issues need to be considered, 25% of displacer length or a density difference of 0.25 SGU.
Code Class Description
6 Error Device-Specific Command Error
15
DLC3010 Digital Level Controller
May 2022
Instruction Manual Supplement
D104329X012
Command 15: Read Primary Variable Output Information
This command reads the Instrument alarm selection code (condition of the hardware jumper), units code for the PV range variables, upper and lower range values, PV damping value, and private label distributor code. This command has the HART 5 structure, 1 byte shorter than the HART 7 version.
Byte Format Description
Request Data
None
bytes
0 Enum Hardware Alarm Selection Code (Ignore)
1 Enum
2 Enum
PV Transfer Function Code
PV Upper and Lower Range Value Units Code, refer to table 6.
(2)
(1)
36 Float PV Upper Range Value
Response Data Bytes
710 Float PV Lower Range Value
1114 Float PV Damping Value (units of seconds)
15 Enum Write Protect Code (0=Not Protected, 1=Protected)
16 Enum Private Label Distributor Code, refer to table 3
Code Class Description
Response Codes
1. The enumeration assignments for Alarm Selection Code in the DLC3010 do not comply with the definition in HCF_SPEC-183 Common Tables Specification, Table 6. Therefore, it is not referenced in DD menus, and the associated data item is handled by a device-specific command and variable.
2. The value of Transfer Function Code in the DLC3010 was inadvertently hard-coded to ‘1’ during development. The DD uses a post-read action to reset it to the correct value of ‘0’, but it must be ignored when accessed outside of the DD.
6 Error Device-Specific Command Error
Command 16: Read Final Assembly Number
This command reads a 24-bit user-defined identification number from the device.
Request Data bytes
Response Data Bytes
Response Codes
16
Byte Format Description
None
02 Uint24 Final Assembly Number
Code Class Description
6 Error Device-Specific Command Error
Instruction Manual Supplement
D104329X012
DLC3010 Digital Level Controller
Command 17: Write Message
This command allows you to write a 24-character informational message into the device.
Byte Format Description
May 2022
Request Data bytes
Response Data Bytes
Response Codes
023 Packed
023 Packed Message String
Code Class Description
5 Error Too few data bytes 6 Error Device Specific command error 7 Error In write protect mode
Message string
Command 18: Write Tag, Descriptor, Date
This command writes the tag, descriptor, and date into the device.
Byte Format Description
05 Packed Tag Request Data bytes
Response Data Bytes
Response Codes
617 Packed Descriptor
1820 Uint8[3] Date; Respectively: day, month, year – base year (1900)
05 Packed Tag
617 Packed Descriptor
1820 Uint8[3] Date; Respectively: day, month, year – base year (1900)
Code Class Description
5 Error Too few data bytes 6 Error Device Specific command error 7 Error In write protect mode
Command 19: Write Final Assembly Number
This command writes the user-defined final assembly number into the device.
Byte Format Description
Request Data bytes
Response Data Bytes
Response Codes
02 Uint24 Final Assembly Number
02 Uint24 Final Assembly Number
Code Class Description
5 Error Too few data bytes 6 Error Device Specific command error 7 Error In write protect mode
17
Loading...
+ 37 hidden pages