Fisher IM Supplement: HART Field Device Specification - DVC6000 and DVC6200 HW1 Digital Valve Controllers Manuals & Guides

Instruction Manual Supplement
D103649X012
HARTR Field Device Specification
DVC6000 Digital Valve Controller
December 2020
Fisher
FIELDVUE™ DVC6000 and DVC6200 HW1
HART Revision Device Type Device Revision Firmware Revision
HART 5 03
* Also applicable to DVC6200 HW1, Device Revision 2, Firmware 10 & 11
Introduction 2.................................
Product Overview 2............................
Purpose of this document 2.....................
Abbreviations and definitions 2..................
Reference Documentation 3....................
Device Identification 3..........................
Product Interfaces 4............................
Control Valve Interface 4.......................
Host interface 4...............................
Touch-Up Calibration 4.........................
Internal Jumpers And Switches 5.................
Write Protection 5.............................
Firmware Upgrade 5...........................
Dynamic Variables 6............................
Device Variables 6..............................
Status Information 7............................
Device Status 7...............................
Universal Commands 8..........................
CommonPractice Commands 13.................
Supported Commands 13......................
Device-Specific Commands 22....................
Burst Mode 22................................
Catch Device Variable 22.......................
Performance 22................................
Annex A Compatibility Checklist 23................
Annex B DVC6000 Parameters as part of a Rosemount
Gateway 24...............................
1410/1420 WirelessHARTr
1 2, 3, 4, 5, 6 2 7, 9, 10*, 11*
Note
This document does not include the DVC6000 AC product (Device Type 1307) which only supports Device Specific HART Commands and not Universal or Common Practice Commands.
Product removed from sale October 2013
www.Fisher.com
DVC6000 Digital Valve Controller
December 2020
Instruction Manual Supplement
D103649X012
Introduction
Product Overview
The FIELDVUE DVC6000 digital valve controller is designed to control the pneumatic actuator of a process control valve. It receives a current signal from a host and uses instrument air supply to create a metered pressure output signal to the pneumatic actuator. Movement of the actuator as it positions the process control valve is measured by the DVC6000 travel sensor as its primary feedback. The name plate is located on the bottom side of the DVC6000 master module assembly and indicates the model name, individual product serial number, and any applicable third party approvals.
Purpose of this document
This specification is designed to be a technical reference for HART capable host application developers, system integrators and knowledgeable end-users. It also provides functional specifications (e.g., commands, enumerations and performance requirements) used during field device development, maintenance and testing. This document assumes the reader is familiar with HART Protocol requirements and terminology. Additional product information is available in the DVC6000 product literature, available from your Emerson sales office.
Abbreviations and definitions
AR Alert Record
Configuration Variables
Device Variable
Enumeration A pre-defined set of values or text.
MV Measured Variable, a physical input to the instrument.
NV
Point
PS1 The PORT A output pressure which increases with increasing drive signal.
PS2 The PORT B output pressure which decreases with increasing drive signal.
PST Partial Stroke Test, a limited form of ramped valve diagnostic.
Byte An 8bit unsigned integer.
Word A 16bit unsigned integer.
Float Refers to the IEEE 754 floating point format.
Packed ASCII
Standard Span Format
Variables which represent nonvolatile values of manufacturinginitialized data or userspecified configuration information. These variables cannot be enumerated via Command 54 and as such stand on their own with no associated units or range information.
Measured variables that are exposed to HART and can be enumerated using Command 54. Generally there are variables whose ID is in the range of 0 to 10 and are associated with units codes, status, and range values.
Named Variable – a logical point inside the device, hardmapped to a given MV as the source of NV data.
A term that applies to diagnostic data packets. It is defined as a collection of periodically sampled variables captured at a single instant in time. It does not include the “Monitor” point.
A special form of characters defined by HART in which 6bit ASCII characters are packed into byte data.
A proprietary 16bit integer format for numerical values used by some of this device’s Device Specific commands.
2
Instruction Manual Supplement
D103649X012
DVC6000 Digital Valve Controller
December 2020
Reference Documentation
HART Smart Communications Protocol Specification Revision 5; a group of documents specifying the HART Communication Protocol, physical layers, and Data Link Layers as defined by the HART Communications Foundation.
DVC6000 (Supported)
Fisher FIELDVUE DVC6000 Digital Valve Controller Instruction Manual (D102794X012)
DVC6000 SIS (Supported)
Fisher FIELDVUE DVC6000 SIS Digital Valve Controller Instruction Manual (D103230X012)
DVC6200 HW1 (Supported)
Fisher FIELDVUE DVC6200 Series Digital Valve Controllers Quick Start Guide (D103556X012)
Fisher FIELDVUE DVC6200 HW1 Digital Valve Controller Instruction Manual (D103409X012
)
Device Identification
Manufacturer Name Fisher Controls Model Name(s) DVC6000
Manufacture ID Code 19 (13 Hex) Device Type Code 03 (03 Hex)
HART Protocol Revision 5 Device Revision 1 or 2
User Selectable HART Revision
between HART 5 and HART 7
Number of Device Variables 12
Physical Layers Supported FSK
Physical Device Category Valve Positioner
No
3
DVC6000 Digital Valve Controller
December 2020
Instruction Manual Supplement
D103649X012
Product Interfaces
Control Valve Interface
The DVC6000 digital valve controller is mechanically attached to the valve’s actuator by means of a mounting bracket. The control valve's position is conveyed to the travel sensor of the DVC6000 digital valve controller by means of the feedback bracket attached to the actuator’s stem and the rotating travel sensor.
MOUNTING BRACKET
CAP SCREW, FLANGED
BIAS
SPRING
A7024 ‐2
MOUNTING ADAPTER
FEEDBACK ARM TORSION SPRING
CAP SCREW, HEX SOCKET
MOUNTING BRACKET
FEEDBACK ARM ASSEMBLY
CAP SCREW, HEX HEAD
ARM ASSEMBLY PIN
ARM ASSEMBLY
MACHINE SCREW
SHIELD
ADJUSTMENT ARM
CONNECTOR ARM
CAP SCREW
PLAIN WASHER
29B1674‐A
Pneumatic tubing connected to the DVC6000 brings instrument supply air to the DVC6000 and takes controlled output air from the DVC6000 to the actuator. Pressure sensors in the DVC6000 measure these pressure signals and present them as device variables.
Host interface
The input to the DVC6000 can either be twowire 4to20 mA current loop (in pointtopoint mode) or 24 VDC (in multidrop mode). This input is connected in the DVC6000’s terminal box on two terminals marked “LOOP +” and “LOOP ”. Refer to the DVC6000 quick start guide for connection details.
Touch-Up Calibration
Shorting of the AUX terminals in the terminal box provides a quick means to autocalibrate the travel of the instrument. The terminals must be shorted for 3 to 5 seconds. Autocalibration will move the valve through the full range of travel whether the Instrument Mode is In Service or Out of Service. However, if the Write Protection is Protected, this button will not be active. To abort, press the button again for 1 second. The calibration function of the AUX terminals is disabled by default.
4
Instruction Manual Supplement
D103649X012
DVC6000 Digital Valve Controller
Internal Jumpers And Switches
The input to the DVC6000 is determined by the PtPt/MultiDrop switch on the printed wiring board.
UP = MULTIDROP
DOWN = PT-PT
LOOP+
LOOP-
December 2020
DIP SWITCH
39B3399‐B Sheet 2
Refer to the DVC6000 instruction manual for additional details on the settings of the selection switches.
Write Protection
There are two Write Protection states for the DVC6000: Not Protected or Protected. Protected prevents configuration and calibration changes to the instrument. The default setting is Not Protected. Protection is controlled under software control. Write Protection can be enabled remotely. However, to disable Write Protection to Not Protected, you must have physical access to the instrument. The procedure will require you to short the AUX terminals inside the terminal box when directed by the software as a security measure.
Firmware Upgrade
The firmware of any DVC6000 printed wiring board assembly can be upgraded to the latest firmware version using the “Firmware Download” tool in ValveLink™ software. The new firmware incorporates all of the new functionality and corrections and improvements made to the technology of the DVC6000 product.
The firmware download process requires:
D Around 30 minutes to complete
D The DVC6000's instrument mode must be “Out of Service”
D The DVC6000 is powered with 12 mA or greater
D That you isolate the valve from the process and equalize pressure on both sides of the valve or bleed off the
process fluid because the routine will cause the DVC6000 to restart.
5
DVC6000 Digital Valve Controller
December 2020
Instruction Manual Supplement
D103649X012
Dynamic Variables
Four Dynamic Variables are implemented.
Default Meaning Units
PV Analog Input mA, % SV Travel Setpoint % TV Pressure PSI, BAR, KPA FV Travel %
TV pressure variables are user selectable via Command 51 to any of the following variables. Variable selections are listed below:
Variable Units
Pressure Port A PSI, BAR, KPA
Pressure Port B PSI, BAR, KPA
Pressure A – B PSI, BAR, KPA
Supply Pressure PSI, BAR, KPA
Device Variables
These variables represent measurements taken by the device, are read only values, and are all in float format. These can be read with Commands 33 and 54.
Variable ID Meaning Units
0 Analog Input mA, % 1 Auxiliary Contact Status (0% = Open, 100% = Shorted) % 2 Pressure Port A PSI, BAR, KPA 3 Travel % 4 Drive Signal % 5 Pressure Port B PSI, BAR, KPA 6 Travel Setpoint % 7 Differential Pressure (Port A – Port B) PSI, BAR, KPA 8 Supply Pressure* PSI, BAR, KPA 9 Implied Valve Position (Travel Target) %
10 Primary Feedback (user selected, either Travel or Pressure) %
211 Temperature _C or _F
* Not available with HC diagnostic level
Unit Codes
Variable Units Code Units
0 No Units 6 Pounds per square inch, psi 7 Bar
10 ($0A)
12 ($0C) Kilopascals, kPa 32 ($20) Celsius, _C 33 ($21) Fahrenheit, _F 39 ($27) Milliamps, mA 57 ($39) Percent, %
Kilograms per square
centimeter, kg/cm
2
6
Instruction Manual Supplement
D103649X012
DVC6000 Digital Valve Controller
December 2020
Status Information
Device Status
The Field Device Status Byte is the only status byte defined in the HART protocol. The order and meaning of each of the eight bits within the byte are fixed by the protocol. This byte is one of the status bytes included with each HART response. It is not part of the Command 48 data.
Bit Name of Status Bit Meaning
7 Field Device Malfunction
6 Configuration Changed
5 Cold Start
4 More Status Active when any bit in command 48 is active.
3 Analog Input Fixed
2 Not Used
1 Internal Sensor Out of Limits
0 Loop Current Out of Range Set when any variable 0 (Analog Input) is saturated.
Set / cleared by the firmware based on self test results. This bit is set if the pressure, position or temperature sensors provide invalid readings.
Two such bits exist internally, one for each HART master. Both copies are set when any variable, HART message, tag, descriptor or date are changed from HART. Cleared by command 38, separately for each master. This bit survives loss of power.
Set by the firmware whenever a RESET sequence is executed or at initial device power up. Cleared by the first HART command.
Active if the Instrument Mode of the DVC6000 is in the “Out Of Service” condition or if the Control Mode of the DVC6000 is in one of the digital set point modes.
(This bit is named “NonPrimary Variable Out Of Limits” in the HART documentation for transmitters. It has been renamed to reflect the fact that these variables are INTERNAL INPUTS to FIELDVUE products). The firmware sets this bit when any sensor (pressure, position, temperature) exceeds its operating limits.
7
DVC6000 Digital Valve Controller
December 2020
Instruction Manual Supplement
Universal Commands
The DVC6000 field device implements all HART Revision 5 Universal Commands.
Command 0: Read Unique Identifier Command 1: Read Primary Variable Command 2: Read P.V. Current and Percent of Range Command 3: Read Dynamic Variables and P.V. Current Command 6: Write Polling Address Command 11: Read Unique Identifier Associated with Tag Command 12: Read Message Command 13: Read Tag, Descriptor, Date Command 14: Read Primary Variable Transducer Information Command 15: Read Primary Variable Output Information Command 16: Read Final Assembly Number Command 17: Write Message Command 18: Write Tag, Descriptor, Date Command 19: Write Final Assembly Number
D103649X012
8
Instruction Manual Supplement
D103649X012
Command 0: Read Unique Identifiers
Byte Description Format Value
Request
Data Bytes
Response
Data Bytes
Command
Specific
Response
Codes
none
0 Data type expansion code Byte, hex $FE 1 Manufacturer identification code Byte, hex $13 2 Manufacturer’s Device Type code Byte, hex $03 3 Number of preambles Byte, hex $05 4 Universal command revision Byte, hex $05 5 Device revision Byte, hex See table 1 below 6 Software revision Byte, unsigned integer See table 1 below 7 Hardware revision Byte, unsigned integer $08 8 Device function flags Not Used $00 9 Device Identification number 3 Bytes, hex
Code Description
none
DVC6000 Digital Valve Controller
December 2020
Table 1. Device and Software Revision
Device Revision Software Revision Description
$02 Firmware Revision 2 $03 Firmware Revision 3
$01
$02
$04 Firmware Revision 4 $05 Firmware Revision 5 $06 Firmware Revision 6 $07 Firmware Revision 7 $09 Firmware Revision 9 $0A Firmware Revision 10 $0B Firmware Revision 11
9
DVC6000 Digital Valve Controller
y
y
December 2020
Instruction Manual Supplement
D103649X012
Command 1: Read Primary Variable
This command reads the value of the DVC6000’s Primary Variable, which is Analog Input (loop current). The units are either
“mA” or “%” as configured in the device by Command 44.
Byte Format Description
Request
Data Bytes
Response
Data B
Command
tes
Specific
Response
Codes
none
0 Byte, hex Primary Variable Unit Code, either 39 (mA) or 57(%)
14 Float Primary Variable value
Code Class Description
none
Command 2: Read Primary Variable and Percent of Range
This command reads the value of the DVC6000’s loop current in implied units of “mA” (regardless of the configured setting by Command #44) and the measured Valve Travel in implied units of “%”.
Byte Format Description
Request
Data Bytes
Response
Data B
Command
tes
Specific
Response
Codes
none
03 Float Loop Current 47 Float Valve Travel
Code Class Description
none
10
Instruction Manual Supplement
D103649X012
DVC6000 Digital Valve Controller
December 2020
Command 3: Read Dynamic Variables and Loop Current
This command is used to read the value of Loop Current and the four Dynamic Variables. The four dynamic variables returned depend upon the variable assignment as defined by Command 51 and read back via Command 50.
The default Dynamic Variable assignment and the Variable Units Codes are shown on page 6.
Byte Format Description
Request
Data Bytes
Response
Data Bytes
Command
Specific
Response
Codes
none
03 Float Loop Current (implied units of “mA”)
4 Byte, hex Primary Variable (PV) units code
58 Float Primary Variable (PV) value
9 Byte, hex Secondary Variable (SV) units code
1013 Float Secondary Variable (SV) value
14 Byte, hex Tertiary Variable (TV) units code
1518 Float Tertiary Variable (TV) value
19 Byte, hex Fourth Variable (FV or QV) units code
2023 Float Fourth Variable (FV or QV) value
Code Class Description
8 Warning – Value read invalid (one of the variables is out of range)
Command 14: Read Primary Variable Transducer Information
The transducer limits reported in this command indicate that these values are set to “Not Used”
Note
The Transducer Serial Number is not applicable to the DVC6000 and is set to “0”. The other parameters will be set to “0x7F”, “0xA0”, “0x00”, or “250” Not Used , when they are not applicable.
Byte Format Description Returned Value
Request
Data bytes
Response
Data
Bytes
Response
Codes
None
02 UINT24 Transducer Serial Number 000000
3 Enum Transducer Limits and Minimum Span Units Code 250 (Not Used)
47 Float Upper Transducer Limit 7FA00000 (Not A Number NAN)
811 Float Lower Transducer Limit 7FA00000 (Not A Number NAN)
1215 Float Minimum Span 7FA00000 (Not A Number NAN)
Code Class Description
None
11
DVC6000 Digital Valve Controller
December 2020
Instruction Manual Supplement
D103649X012
Command 15: Read Primary Variable Output Information
This command returns the upper/lower range values for the primary variable which is defined to be the loop current signal. These are the loop current values for the ends of physical travel, and are used to derive set point from the loop current. It reports the range supplied in Command 35.
For example, the lower range, for an increase to open valve, will be the current which will produce a 0% set point. However, for an increase to close valve, the lower range will be the loop current for a 100% set point.
The range values can be changed via Command 35.
The DVC6000 assumes 0% = 4mA and 100% = 20mA.
Byte Format Description Returned Value
Request
Data bytes
Response
Data
Bytes
Response
Codes
None
PV Alarm Selection Code (see Common Table 6, Alarm
0 Enum
1 Enum
2 Enum
3-6 Float AI Upper Range Value From CMD 35
7-10 Float AI Lower Range Value From CMD 35
1114 Float PV Damping Value (units of seconds) 0.0
15 Enum Write Protect Code (192=Disabled, 32=Enabled) 192 or 32
16 Enum Reserved. Must be set to “250”, Not Used. 250
Code Class Description
None
Selection Codes). The Alarm Selection Code indicates the action taken by the device under error conditions. For Actuators, the action taken by the positioner is indicated.
PV Transfer Function Code (see Common Table 3, Transfer Function Codes). The Transfer Function Code must return “0”, Linear, if transfer functions are not supported by the device.
AI Upper and Lower Range Values Units Code, as supplied in command 35.
250 (Not Used)
250 (Not Used)
From CMD 35
12
Instruction Manual Supplement
D103649X012
CommonPractice Commands
The DVC6000 field device supports the following common practice commands:
Supported Commands
Command 33: Read Device Variables Command 35: Write Primary Variable Range Values Command 38: Reset Configuration Change Flag Command 42: Master Reset Command 44: Change Primary Variable Units Code Command 48: Read Additional Status Command 50: Read Dynamic Variable Assignments Command 51: Write Dynamic Variable Assignments Command 54: Read Device Variable Information Command 108: Write Burst Mode Command Number Command 109: Burst Control Mode
DVC6000 Digital Valve Controller
December 2020
Command 33: Read Device Variables
This command is used to read the value of up to four selected Device Variables.
The Device Variables and the Variable Units Code are listed on page 6.
Note: If any one of the requested variable IDs is invalid, the INVALID_SELECTION error will be returned along with no data bytes.
Byte Format Description Allowable choices
0 Variable ID Variable assigned to slot #0 See Device Variables on page 6
Request
Data Bytes
Response
Data Bytes
Command
Specific
Response
Codes
1 Variable ID Variable assigned to slot #1 See Device Variables on page 6 2 Variable ID Variable assigned to slot #2 See Device Variables on page 6 3 Variable ID Variable assigned to slot #3 See Device Variables on page 6 0 Variable ID Variable assigned to slot #0 1 Byte, hex Slot #0 Variable units code
25 Float Slot #0 Variable value
6 Variable ID Variable assigned to slot #1 7 Byte, hex Slot #1 Variable units code
811 Float Slot #1 Variable value
12 Variable ID Variable assigned to slot #2 13 Byte, hex Slot #2 Variable units code
1417 Float Slot #2 Variable value
18 Variable ID Variable assigned to slot #3 19 Byte, hex Slot #3 Variable units code
2023 Float Slot #3 Variable value
Code Class Description
2 Invalid selection – Invalid Variable ID (see note above)
13
DVC6000 Digital Valve Controller
December 2020
Instruction Manual Supplement
D103649X012
Command 35: Write Primary Variable Range Values
In the DVC6000, the Primary Variable is defined to be the Analog Input (loop current).
This command is used to write the ranging values reported in Command 15. It controls how the DVC6000 interprets the loop current when creating the Travel Target. The upper range must be greater than the lower range.
This command does not do units conversion, but requires that the units code supplied match the PV units configured in the device as set by Command 44.
If the range values are in percent, then they are assumed to be percent of 420 mA. For example, to range an increase to open unit from 8 mA to 16 mA, but using percent range numbers, specify lower_range = 25% and upper_range = 75%.
This ranging is done in conjunction with the zero power condition. For an Increase to Open valve, the lower range is the 0% setpoint level (valve plug in the valve seat), while the upper range is the 100% setpoint level. An Increase to Close valve is exactly opposite.
This command will be accepted when the DVC6000’s Instrument Mode is In Service but will be rejected if Write Protection is in effect.
Byte Format Description Allowable choices
Request
Data Bytes
Response
Data Bytes
Command
Specific
Response
Codes
0 UINT8 Upper and Lower Range Values Unit Code Unit Code 39 (mA) or 57(%) 1  4 Float Primary Variable Upper Range Value 5  8 Float Primary Variable Lower Range Value
0 UINT8 Upper and Lower Range Values Unit Code Unit Code 39 (mA) or 57(%) 1  4 Float Primary Variable Upper Range Value 5  8 Float Primary Variable Lower Range Value
Code Class Description
2 Invalid selection  Units code did not match configured units
7 In Write Protect Mode
16 Access Restricted  other master has access locked. 32 Busy
Command 38: Reset Configuration Change Flag
Resets the configuration changed flag in the DVC6000.
The DVC6000 contains two configuration changed bits, one for each master. Both bits are set when any write operation occurs. This command clears the bit corresponding to the master sending this command, leaving the other bit unmodified. Any write to the DVC6000 other than digital setpoint values and write protect status will cause the configuration change flag to be set.
Byte Format Description
Request
Data Bytes
Response
Data Bytes
Command
Specific
Response
Codes
none
none
Code Class Description
none
14
Instruction Manual Supplement
D103649X012
DVC6000 Digital Valve Controller
December 2020
Command 42: Perform Master Reset
This reset command has two options. If no data bytes are supplied, respond immediately and then perform a “warm” reset. This is not equivalent to power up in that restart modes and default IVP are not adopted and the realtime clock is not reset. All other data is read from nonvolatile memory and put into effect. The second option is hard reset. This requires two data bytes set as described below. If this form is received, the unit will save modes and counters, then execute a hard reset by exercising the watchdog timer. The next response will have the “cold_start” bit set.
A “soft reset” command will be honored while the DVC6000 Instrument Mode is in the “In Service” condition.
A “hard reset” command requires the DVC6000 Instrument Mode be in the “OutofService” condition.
Byte Format Description
Request
Data
bytes
Response
Data
Bytes
Command
specific
Response
Codes
0  1 Uint16
None
Code Class Description
16 Error Access Restricted
[Optional] If hex 0x6969 is supplied as request data bytes, a hard reset is performed. Otherwise a soft reset is performed.
Command 44: Change Primary Variable Units Code
This command is issued to change the units of the Primary Variable, which is defined in the DVC6000 as the Analog Input (loop current). The choices for units are Percent (code 57) or Milliamps (code 39). This command should be sent prior to a Command 35 which sets the upper and lower Primary Variable range values.
In addition to changing the units code, execution of this command will also change the DVC6000’s Analog Input Upper and Lower Range values to reflect the new units (For example: When the DVC6000’s Analog Input is configured as “420 mA” and Command 44 with request Data Byte 57 is executed, the DVC6000’s Analog Input units and range values will change to “0100%”. Likewise When the DVC6000’s Analog Input is configured as “0100%” and Command 44 with request Data Byte 39 is executed, the DVC6000’s Analog Input units and range values will change to “420 mA”.).
This command will be accepted when the DVC6000’s Instrument Mode is In Service, but will be rejected if Write Protection is in effect.
Byte Format Description Allowable choices
Request
Data Bytes
Response
Data Bytes
Command
Specific
Response
Codes
0 UINT8 Primary Variable Units Code Unit Code 39 (mA) or 57(%)
0 UINT8 Primary Variable Units Code Unit Code 39 (mA) or 57(%)
Code Class Description
2 Invalid selection  Units code did not match configured units
7 In Write Protect Mode
15
DVC6000 Digital Valve Controller
December 2020
Command 48: Read Additional Status
Byte Format Description
Request
Data
bytes
Response
Data
Bytes
0 None
0 Uint8 Command 48 Response Byte 0
1 Uint8 Command 48 Response Byte 1
2 Uint8 Command 48 Response Byte 2
3 Uint8 Command 48 Response Byte 3
4 Uint8 Command 48 Response Byte 4
5 Uint8 Command 48 Response Byte 5
6 Uint8 Operating Mode
7 Uint8 Reserved
Instruction Manual Supplement
D103649X012
16
Instruction Manual Supplement
D103649X012
DVC6000 Digital Valve Controller
Additional Device Status— DVC6000 Device Revision 1, Firmware 2, 3, 4, 5, 6
Command 48 returns 8 bytes of data, with the following status information:
Byte Bit Name of Status Bit Meaning
Active if there is a failure associated with flash ROM (read only
7 Flash Integrity Failure
6 No Free Time
5 Reference Voltage Failure
4 Drive Current Failure
0
3 Critical NVM Failure
2 Temperature Sensor Failure
1 Pressure Sensor Failure*
0 Travel Sensor Failure
7 Alert Record Not Empty Alert 6 Dynamic Bypass Enabled Active if Dynamic Bypass is enabled. 5 Calibration In Progress Alert 4 Diagnostics in Progress Alert
1
3 Pressure Fallback Active Alert
2 Custom Characterization
1 Input Characterization
0 Auto Cal in Progress Alert 7 PWB Set to “Multi−Drop” Active is PWB switch is set to “Multi”
6 NonCritical NVM Alert
5 Cycle Counter High Alert
Travel Accumulator High
4
Alert
2
Instrument Time is Invalid
3
Alert
2 Alert Record Full Alert
1 Offline / Failed Alert
0 Auxiliary Input Alert
1,2
memory). Active if the microprocessor detects a fault in the servo execution
1,2
period. Active if there is a failure associated with the internal voltage
1,2
reference. Active when the drive current to the I/P converter is not flowing as
1,2
expected. Active if there is a failure of nonvolatile memory used for
1,2
configuration data critical for instrument operation. Active when the instrument temperature sensor fails or the sensor
1,2
reading is outside of the range of 60° to 100°C (76° to 212°F). Active if any of the 3 pressure sensor readings are outside the range
1,2
of 24.0% to 125.0% of the calibrated pressure for more than 60 seconds. Active if the sensed travel is outside the range of 25.0% to 125.0%
1,2,3
*DVC6000 fw 6 (any) Pressure Sensor does not set “Field Device Malfunction”.
of calibrated travel.
2
Active when there are 1 or more alerts stored in the alert record.
2
Active when calibration is in progress.
2
Active when a diagnostic test is in progress. Active when the instrument has detected a problem with the travel feedback and is now controlling the output like an I/P transducer. Custom Characterization in Effect active if the user-defined Custom Characterization is enabled. Input Characterization in Effect active if any of the user-defined Characterizations other than “Linear” is enabled.
2
Active when auto calibration is in progress.
Active if there is a failure of nonvolatile memory used for data not
2
critical for instrument operation.
2
Active if the Cycle Counter exceeds the Cycle Count Alert Point. Active if the Travel Accumulator exceeds the Travel Accumulator
2
Alert Point. Active if the instrument has been powered down since the last time the instrument clock was set. Active when the alert record contains the maximum number of 11
2
alerts.
2
Active if a shutdown alert has put the DVC6000 in a failed state. Active when the AUX input is configured as an alarm switch and the
2
alarm is active
December 2020
"Reserved" bits are always set to 0.
1. Sets “Field Device Malfunction”.
2. Sets “More Status Available”.
3. Except when in Forced_Pressure mode.
4. Suppressed by default. Alerts can be enabled or suppressed, as desired by the user.
5. Enabled by default. Alerts can be enabled or suppressed, as desired by the user.
6. DVC6000 SIS only, otherwise “Reserved”. (continued)
17
DVC6000 Digital Valve Controller
December 2020
Instruction Manual Supplement
D103649X012
Additional Device Status— DVC6000 Device Revision 1, Firmware 2, 3, 4, 5, 6 (continued)
Byte Bit Name of Status Bit Meaning
7 Reserved 6 Valve Stuck
5 Supply Pressure Alert
4 Pressure Deviation Alert
3
3 Reserved 2 Power Starvation
Integrator Saturated High
1
Alert Integrator Saturated Low
0
Alert 7 Travel Alert Lo Active when the Travel is below the Travel Alert Lo Point. 6 Travel Alert Lo Lo Active when the Travel is below the Travel Alert Lo Lo Point. 5 Travel Alert Hi Active when the Travel exceeds the Travel Alert Hi Point. 4 Travel Alert Hi Hi Active when the Travel exceeds the Travel Alert Hi Hi Point.
4
3 Travel Deviation Alert
2 Travel Limit/Cutoff Hi Alert Active when the Travel exceeds the Hi Limit/Cutoff Point. 1 Travel Limit/Cutoff Lo Alert Active when the Travel falls below the Lo Limit/Cutoff Point.
0 Drive Signal Alert
7 Reserved 6 Reserved 5 Reserved
5
4 Reserved 3 Reserved 2 Reserved 1 Reserved 0 Reserved
Byte Left Digit Name of Status Bit
“0” Out of Service “1” In Service
Right Digit Name of Status Bit
6
“3”
“Analog (RSP)” Control
Mode “2” “Digital” Control Mode “1” Not used “0” “Test” Control Mode
2,6
Active if SIS Partial Stroke Test Failed Active if the supply pressure falls below the supply pressure alert
2
point. Active if the instrument is in pressure control and the pressure is
2
not tracking the set point within the configured deviation allowance.
Active if the instrument integrator is saturated at the high
2
extreme.
2
Active if the instrument integrator is saturated at the low extreme.
Active if the difference between the Travel Target and the Travel
2
exceeds the Travel Deviation Alert Point for more than the Travel Deviation Time.
Active when the Drive Signal exceeds target limits (<10% or
2
>90%) for more than 20 seconds when not in Cutoff condition.
"Reserved" bits are always set to 0.
1. Sets “Field Device Malfunction”.
2. Sets “More Status Available”.
3. Except when in Forced_Pressure mode.
4. Suppressed by default. Alerts can be enabled or suppressed, as desired by the user.
5. Enabled by default. Alerts can be enabled or suppressed, as desired by the user.
6. DVC6000 SIS only, otherwise “Reserved”.
18
Instruction Manual Supplement
D103649X012
DVC6000 Digital Valve Controller
Additional Device Status - DVC6000 Device Revision 2, Firmware 7, 9, 10*, 11*
Command 48 returns 8 bytes of data, with the following status information:
Byte Bit Name of Status Bit Meaning
Active if there is a failure associated with flash ROM (read only
7 Flash Integrity Failure
6 Reserved
5 Reference Voltage Failure
4 Drive Current Failure
0
3 Critical NVM Failure
2 Temperature Sensor Failure
1 Pressure Sensor Failure
0 Travel Sensor Failure
7 Alert Record Not Empty Alert
6 SIS_LCP_TRIPPED
5 Calibration In Progress Alert
1
4 Diagnostics in Progress Alert
3 Pressure Fallback Active Alert
2 Reserved 1 Reserved 0 Auto Cal in Progress Alert 7 PWB Set to “Multi−Drop”
6 NonCritical NVM Alert
5 Cycle Counter High Alert
Travel Accumulator High
4
Alert
2
Instrument Time is Invalid
3
Alert
2 Alert Record Full Alert
1 Offline / Failed Alert
0 Auxiliary Input Alert
1,2
memory).
Active if there is a failure associated with the internal voltage
1,2
reference. Active when the drive current to the I/P converter is not flowing as
1,2
expected. Active if there is a failure of nonvolatile memory used for
1,2
configuration data critical for instrument operation. Active when the instrument temperature sensor fails or the sensor
1,2
reading is outside of the range of 60° to 100°C (76° to 212°F). Active if any of the 3 pressure sensor readings are outside the range
2
of 24.0% to 125.0% of the calibrated pressure for more than 60 seconds. Active if the sensed travel is outside the range of 25.0% to 125.0%
1,2,3
of calibrated travel.
4
Active when there are 1 or more alerts stored in the alert record. Active when the DVC6000 SIS is in the tripped position as a result
6
of someone pressing the Trip button on the Local Control Panel (LCP).
4
Active when calibration is in progress.
4
Active when a diagnostic test is in progress. Active when the instrument has detected a problem with the travel
4
feedback and is now controlling the output like an I/P transducer.
4
Active when auto calibration is in progress.
4
Active is PWB switch is set to “Multi” Active if there is a failure of nonvolatile memory used for data not
4
critical for instrument operation.
4
Active if the Cycle Counter exceeds the Cycle Count Alert Point. Active if the Travel Accumulator exceeds the Travel Accumulator
4
Alert Point. Active if the instrument has been powered down since the last time
4
the instrument clock was set. Active when the alert record contains the maximum number of 11
4
alerts.
2,5
Active if a shutdown alert has put the DVC6000 in a failed state. Active when the AUX input is configured as an alarm switch and the
4
alarm is active
December 2020
"Reserved" bits are always set to 0.
1. Sets “Field Device Malfunction”.
2. Sets “More Status Available”.
3. Except when in Forced_Pressure mode.
4. Suppressed by default. Alerts can be enabled or suppressed, as desired by the user.
5. Enabled by default. Alerts can be enabled or suppressed, as desired by the user.
6. DVC6000 SIS only, otherwise “Reserved”. (continued)
* Also applicable to DVC6200 HW1, Device Revision 2, Firmware 10 & 11
19
DVC6000 Digital Valve Controller
December 2020
Instruction Manual Supplement
D103649X012
Additional Device Status - DVC6000 Device Revision 2, Firmware 7, 9, 10*, 11* (continued)
Byte Bit Name of Status Bit Meaning
Active when diagnostic data has been collected and is being stored
7 Diagnostic Data Available Alert
6 Valve Stuck
5 Supply Pressure Alert
3
4 Pressure Deviation Alert
3 Locked in Safety Alert 2 Power Starvation
Integrator Saturated High
1
Alert 0 Integrator Saturated Low Alert 7 Travel Alert Lo 6 Travel Alert Lo Lo 5 Travel Alert Hi 4 Travel Alert Hi Hi
4
3 Travel Deviation Alert
2 Travel Limit/Cutoff Hi Alert 1 Travel Limit/Cutoff Lo Alert
0 Drive Signal Alert
7 Reserved 6 Reserved 5 Reserved 4 Reserved
5
3 SIS Panel Comm Error
2 Reserved 1 Reserved 0 Reserved 7 Reserved 6 Reserved 5 Reserved
6
4 Reserved 3 Reserved 2 Reserved 1 Reserved 0 Reserved
2,5
in the instrument.
2,5,6
Active if SIS Partial Stroke Test Failed Active if the supply pressure falls below the supply pressure alert
2,5
point. Active if the instrument is in pressure control and the pressure is
2,5
not tracking the set point within the configured deviation allowance.
2,5,6
Active when the DVC6000 SIS is in the tripped position.
4
Active if the instrument integrator is saturated at the high
2,5
extreme.
2,5
Active if the instrument integrator is saturated at the low extreme.
4
Active when the Travel is below the Travel Alert Lo Point.
4
Active when the Travel is below the Travel Alert Lo Lo Point.
4
Active when the Travel exceeds the Travel Alert Hi Point.
4
Active when the Travel exceeds the Travel Alert Hi Hi Point. Active if the difference between the Travel Target and the Travel
2,5
exceeds the Travel Deviation Alert Point for more than the Travel Deviation Time.
4
Active when the Travel exceeds the Hi Limit/Cutoff Point.
4
Active when the Travel falls below the Lo Limit/Cutoff Point. Active when the Drive Signal exceeds target limits (<10% or >90%)
2,5
for more than 20 seconds when not in Cutoff condition.
Active if the AUX terminals are configured for use with the local
5,6
control panel (LCP) but communication between the DVC6000 SIS and the LCP is not occurring.
"Reserved" bits are always set to 0.
1. Sets “Field Device Malfunction”.
2. Sets “More Status Available”.
3. Except when in Forced_Pressure mode.
4. Suppressed by default. Alerts can be enabled or suppressed, as desired by the user.
5. Enabled by default. Alerts can be enabled or suppressed, as desired by the user.
6. DVC6000 SIS only, otherwise “Reserved”.
* Also applicable to DVC6200 HW1, Device Revision 2, Firmware 10 & 11
20
Instruction Manual Supplement
D103649X012
DVC6000 Digital Valve Controller
December 2020
Command 50: Read Dynamic Variable Assignments
This command returns a list of four device variable codes, taken from the Device Variables table on page 6, which are returned in Command 3. These Dynamic Variables are specified via Command 51 and control the Command 3 response, whether burst or by request.
Byte Format Description
Request
Data Bytes
Response
Data Bytes
Command
Specific
Response
Codes
None
0 UINT8 ID of variable returned as the first variable (PV) in Command #3 1 UINT8 ID of variable returned as the second variable (SV) in Command #3 2 UINT8 ID of variable returned as the third variable (TV) in Command #3 3 UINT8 ID of variable returned as the fourth variable (FV) in Command #3
Code Class Description
None
Command 51: Write Dynamic Variable Assignments
This command allows the values that fill slots 1 through 3 in Command 3 to be specified. These also control the burst form of Command 3. Note that slot 0 is constrained to be only variable 0 (Analog Input). The variables in slots 13 can be any Device Variable 0…10 inclusive or 211 which includes Analog Input, Temperature, all pressure readings, Travel, or Travel Setpoint.
This command is accepted when in service, and is afforded write protection.
Byte Format Description
0 UINT8 Slot #0 variable ID (must be variable 0 only)
Request Data
Bytes
Response
Data Bytes
Command
Specific
Response
Codes
1 UINT8 Slot #1 variable ID (010, 211) 2 UINT8 Slot #2 variable ID (010, 211) 3 UINT8 Slot #3 variable ID (010, 211) 0 UINT8 Slot #0 variable ID 1 UINT8 Slot #1 variable ID 2 UINT8 Slot #2 variable ID 3 UINT8 Slot #3 variable ID
Code Class Description
2 Invalid selection (Slot #0 is not 0) or other slots not 0…10 or 211. 7 In Write Protect Mode
16 Access Restricted  other master has access locked.
21
DVC6000 Digital Valve Controller
December 2020
Instruction Manual Supplement
D103649X012
Command 54: Read Device Variable Information
Used to identify each of the Device Variables in the range of IDs 0…10 inclusive and 211. Responds with the Sensor Serial Number, Sensor range Units, Sensor ranges, Damping Value, and Minimum Span of the selected Variable. The Variable range values will be in the same units as the Variable Units.
Byte Format Description
Request Data
Bytes
Response
Data Bytes
Command
Specific
Response
Codes
0 Enum
0 UINT8 Device Variable ID
13
4 UINT8 Device variable units code
58 Float Device Variable Upper Range
912 Float Device Variable Lower Range
1316 Float
1720 Float Device Variable Minimum Span (NOT USED  always zero)
Code Class Description
2 Invalid Selection
Device Variable ID, this command is applicable to variables 010 or 211. All others will return invalid selection
Device Variable Sensor Serial Number, 24bit number (NOT USED  always zero)
Device Variable Damping Value, (NOT USED  always zero)
Device-Specific Commands
The DVC6000 field device supports devicespecific commands. However, these devicespecific commands require use of the ValveLink software application or DD methods and cannot be utilized outside of those controlled environments.
Burst Mode
This field device supports Burst Mode.
Catch Device Variable
This field device does not support Catch Device Variable.
Performance
Refer to the appropriate instruction manual or bulletin; see Reference Documentation on page 3.
22
Instruction Manual Supplement
D103649X012
DVC6000 Digital Valve Controller
Annex A Compatibility Checklist
Manufacturer, Model, and Revision Fisher Controls DVC6000 Device Revision 1 and 2
Device Type Pneumatic Control Valve Positioner HART Protocol Revision 5 User switchable between HART 5 mode and
HART 7 mode? Device Description Available? Number and type of process connections None Number of host connections Input: Control signal to Loop ± terminals Number of Dynamic Variables 4 Mappable Dynamic Variables? Yes. TV is mappable. PV is not. Number of Device Variables 12 Number of Supported Common Practice
Commands Burst Mode? Capture Device Variables? No Write Protection? Yes
No
Yes
11
Yes
December 2020
23
DVC6000 Digital Valve Controller
December 2020
Instruction Manual Supplement
D103649X012
Annex B DVC6000 Parameters as part of a Rosemount 1410 / 1420 WirelessHART Gateway
A FIELDVUE DVC6000 can join a wireless network through the addition of a Rosemount 775 THUM WirelessHART adapter. The wireless adapter acts both as a HART modem for communications coming to the DVC6000 from application software and as an independent master issuing commands periodically to the wired device pertaining to it’s status. This independently gathered status information is relayed back to the Rosemount 1410 or 1420 Wireless Gateway and is made available to the user either through viewing the HTML interface or via mapping as “Published Data” parameters via the Gateway’s MODBUS or OPC outputs.
For HART 5 devices the PV, SV, TV, and QV variables can be mapped.
Configure the THUM as follows:
Navigate to Configure > Manual Setup Under the Wired Device tab select Configure HART Polling
Select Yes if changes are required
Wired Device tab
FOR PRIMARY DEVICE INFORMATION:
Select PV, SV, TV, and QV
FOR SECONDARY DEVICE INFORMATION:
Select Device Status
24
Instruction Manual Supplement
D103649X012
DVC6000 Digital Valve Controller
The FIELDVUE instrument is defined on the Gateway by “Tag” (read from the device’s “Message” field).
December 2020
For each Tag, the Gateway provides updated values for:
D Variables
D Additional Status
D Published Data
25
DVC6000 Digital Valve Controller
December 2020
Published Data, used for the Gateway’s OPC and Modbus outputs, falls into the following categories:
Instruction Manual Supplement
Field Device Identification Values:
Values that define the identity of the DVC6000. These include:
D MANUFACTURER (for “Fisher Controls” the value is “19”)
D DEVICE_TYPE (for a DVC6000 HW1 the value is “3”)
D DEVICE_REVISION
D HARDWARE_REVISION
D SOFTWARE_REVISION
D DEVICE_ID
D UNIVERSAL_REVISION (HART version)
D REQUEST_PREAMBLES
D RESPONSE_PREAMBLES
D103649X012
Variable information:
The Gateway receives updates concerning the DVC6000’s four “Dynamic Variables”. The information for any given device variable is displayed by:
1. Dynamic Variable indicator (“PV”, “SV”, etc.)
2. The Device Variable ID number assigned to that Dynamic Variable
3. By the Device Variable Name (only if the Gateway has version 4.3 firmware or later)
Dynamic Variable Device Variable ID Device Variable Name(s)
Analog Input PV 0 LOOP_CURRENT
Travel Setpoint SV 9 TRAVEL_SETPOINT
2 PRESSURE_A
Pressure TV
Travel QV 10 TRAVEL
Milliamp Current 245 CURRENT
Any of these choices [Dynamic Variable, Device Variable ID, or Device Variable Name(s)] can be substituted for the “#” sign in the Variable Identifier fields below.
Variable Identifier Comments / Explanation
# See any of the variable identifiers in the table immediately above. #_CLASS Always “0”. #_CODE The “Device Variable ID” number in the table immediately above. #_HEALTHY A “true” or “false” indication of the health of the sensor providing this value. #_STATUS #_UNITS Decimal “Variable Units code” number from the “Units Codes” table on page 6.
5 PRESSURE_B 7 DIFFERENTIAL_PRESSURE 8 SUPPLY_PRESSURE
26
Instruction Manual Supplement
D103649X012
DVC6000 Digital Valve Controller
December 2020
Device Status:
The eight standard status conditions (present in ANY HART field device) are all represented by a Boolean “true” or “false” state. These eight conditions, discussed on page 7, are:
D DEVICE_MALFUNCTION
D CONFIGURATION_CHANGED
D COLD_START
D MORE_STATUS_AVAILABLE
D LOOP_CURRENT_FIXED
D LOOP_CURRENT_SATURATED
D NONPRIMARY_VALUE_OUT_OF_LIMITS
D PRIMARY_VALUE_OUT_OF_LIMITS
Detailed Device Alerts:
The Alert Groupings are:
D ADDITIONAL_STATUS_0
D ADDITIONAL_STATUS_1
D ADDITIONAL_STATUS_2
D ADDITIONAL_STATUS_3
D ADDITIONAL_STATUS_4
D ADDITIONAL_STATUS_5
D ADDITIONAL_STATUS_6
D ADDITIONAL_STATUS_7
Each of these status bytes represent eight individual bits with values that range from “00” to “255”. To determine which of the eight bits are active requires converting a decimal value to its binary equivalent value. Refer to Command 48, starting on page 17, for details on the individual alert bits inside of each Additional Status Byte.
Note
Gateways with firmware version 4.3 define the alerts of DVC6000 hardware 1 devices. There are slight differences between the names of the alerts as defined in the Gateway in the Command 48 tables, as detailed in the following tables for DVC6000 Device Revision 2, Firmware 7, 9, 10, 11.
27
DVC6000 Digital Valve Controller
December 2020
Instruction Manual Supplement
ADDITIONAL_STATUS_0 According to Command 48: As defined in the Gateway:
Bit 7 Flash Integrity Failure FLASH_ROM_FAIL Bit 6 Reserved Bit 5 Reference Voltage Failure REFERENCE_VOLTAGE_FAIL Bit 4 Drive Current Failure DRIVE_CURRENT_FAIL Bit 3 Critical NVM Failure NVM_FAIL Bit 2 Temperature Sensor Failure TEMPERATURE_SENSOR_FAIL Bit 1 Pressure Sensor Failure PRESSURE_SENSOR_FAIL Bit 0 Travel Sensor Failure TRAVEL_SENSOR_FAIL
ADDITIONAL_STATUS_1 According to Command 48: As defined in the Gateway:
Bit 7 Alert Record Not Empty Alert ALERT_RECORD_HAS_ENTRIES Bit 6 SIS-LCP Tripped Bit 5 Calibration in Progress Alert CALIBRATION_IN_PROGRESS Bit 4 Diagnostics in Progress Alert DIAGNOSTIC_IN_PROGRESS Bit 3 Pressure Fallback Active Alert PRESSURE_CONTROL_IS_ACTIVE Bit 2 Reserved Bit 1 Reserved Bit 0 Auto Cal in Progress Alert AUTO_TRAVEL_CALIBRATION_IN_PROGRESS
D103649X012
ADDITIONAL_STATUS_2 According to Command 48: As defined in the Gateway:
Bit 7 PWB Set to “Multi-Drop” MULTI-DROP Bit 6 NonCritical NVM Alert NON_CRITICAL_NVM_ALERT Bit 5 Cycle Counter High Alert CYCLE_COUNT_ALERT Bit 4 Travel Accumulator High Alert TRAVEL_ACCUMULATOR_ALERT Bit 3 Instrument Time is Invalid Alert INSTRUMENT_TIME_IS_INVALID Bit 2 Alert Record Full Alert ALERT_RECORD_IS_FULL Bit 1 Offline / Failed Alert OFFLINE_FAILED_ALERT Bit 0 Auxiliary Input Alert AUXILIARY_TERMINAL_ALERT
ADDITIONAL_STATUS_3 According to Command 48: As defined in the Gateway:
Bit 7 Diagnostic Data Available Alert DIAGNOSTIC_DATA_AVAIL Bit 6 Valve Stuck VALVE_STUCK_OR_PRESSURE_TRAVEL_OBSTRUCTED Bit 5 Supply Pressure Alert SUPPLY_PRESSURE_LO_ALERT Bit 4 Pressure Deviation Alert PRESSURE_DEVIATION_ALERT Bit 3 Locked in Safety Alert LOCKED_IN_SAFETY_ALERT Bit 2 Power Starvation LOW_POWER_WRITE_FAIL Bit 1 Integrator Saturated High Alert INTEGRATOR_SATURATED_HI Bit 0 Integrator Saturated Low Alert INTEGRATOR_SATURATED_LOW
28
Instruction Manual Supplement
D103649X012
DVC6000 Digital Valve Controller
ADDITIONAL_STATUS_4 According to Command 48: As defined in the Gateway:
Bit 7 Travel Alert Lo TRAVEL_ALERT_LO Bit 6 Travel Alert Lo Lo TRAVEL_ALERT_LO_LO Bit 5 Travel Alert Hi TRAVEL_ALERT_HI Bit 4 Travel Alert Hi Hi TRAVEL_ALERT_HI_HI Bit 3 Travel Deviation Alert TRAVEL_DEVIATION_ALERT Bit 2 Travel Limit/Cutoff Hi Alert TRAVEL_LIMIT_HI_OR_TRAVEL_CUTOFF_HI_IN_EFFECT Bit 1 Travel Limit/Cutoff Lo Alert TRAVEL_LIMIT_LOW_OR_TRAVEL_CUTOFF_LOW_IN_EFFECT Bit 0 Drive Signal Alert DRIVE_SIGNAL_ALERT
ADDITIONAL_STATUS_5 According to Command 48: As defined in the Gateway:
Bit 7 Reserved Bit 6 Reserved Bit 5 Reserved Bit 4 Reserved Bit 3 SIS Panel Comm Error SIS_PANEL_COMM_ERROR Bit 2 Reserved Bit 1 Reserved Bit 0 Reserved
December 2020
ADDITIONAL_STATUS_6 According to Command 48: As defined in the Gateway:
Bit 7 Reserved Bit 6 Reserved Bit 5 Reserved Bit 4 Reserved Bit 3 Reserved Bit 2 Reserved Bit 1 Reserved Bit 0 Reserved
ADDITIONAL_STATUS_7 According to Command 48: As defined in the Gateway:
Bit 7 Reserved Bit 6 Reserved Bit 5 Reserved Bit 4 Reserved Bit 3 Reserved Bit 2 Reserved Bit 1 Reserved Bit 0 Reserved
29
DVC6000 Digital Valve Controller
December 2020
Instruction Manual Supplement
D103649X012
Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Fisher, FIELDVUE, Rosemount, and ValveLink are marks owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. Emerson Automation Solutions, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. HART and WirelessHART are marks owned by the HART Communication Foundation. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.
Emerson Automation Solutions
Marshalltown, Iowa 50158 USA Sorocaba, 18087 Brazil Chatham, Kent ME4 4QZ UK Dubai, United Arab Emirates Singapore 128461 Singapore
www.Fisher.com
30
E 2013, 2020 Fisher Controls International LLC. All rights reserved.
Loading...