Fisher IM Supplement: HART Communicating FIELDVUE DVC6200 Digital Valve Controllers-Zero Point Calibration | Fisher Manuals & Guides

Instruction Manual Supplement
D104328X012
Zero Point Calibration
DVC6200 Digital Valve Controller
June 2018
HART
®
Communicating Fisher™ FIELDVUE
DVC6200 Digital Valve Controllers
WARNING
Personal injury or property damage, caused by unexpected valve movement and an uncontrolled process, could result if this procedure is attempted when the valve is not locked at its present position. If you cannot safely lock the valve in position until this procedure is complete, do not proceed with this procedure.
Notes
This procedure should only used for the partial or complete replacement of a digital valve controller when the valve does not have a bypass or the process cannot be shut down. Do not proceed with this procedure if the valve has a bypass or the process can be shut down.
This procedure assumes the array was set up properly on the existing DVC6200 and has not been moved or adjusted since setup.
The valve will need to be locked at its present position. This can be accomplished by using a handwheel or other mechanism. If you
cannot safely lock the valve in position until this procedure is complete, do not proceed with this procedure.
This procedure requires the use of a 475 Field Communicator, AMS Trex
This procedure can be used to swap a DVC6200 with another DVC6200. You cannot swap a DVC6000 with a DVC6200 using this procedure. The DVC6200 used to replace the existing digital valve controller must be a new, factory calibrated instrument. This procedure will not work if a previously installed and calibrated digital valve controller is used.
Device Communicator, or ValveLink™ software.
Zero Point Configuration Process
HART DD
CAUTION
The touch screen of the 475 Field Communicator or AMS Trex Device Communicator should only be contacted by blunt items. The use of a sharp instrument can cause damage to the touch screen interface.
www.Fisher.com
DVC6200 Digital Valve Controller
June 2018
Instruction Manual Supplement
475 Field Communicator and AMS Trex Device Communicator
1. If using the 475 Field Communicator, Select the HART Icon from the Main Menu, shown in figure 1. If using the Trex Communicator, select Field Communicator from the main menu.
Figure 1. 475 Field Communicator Menu Screen
D104328X012
2. From the Online menu select Configure > Guided Setup > Device Setup.
3. Provide the requested information, including: Pressure Units, Relay Type, Control mode (Travel Control, Pressure Control, Fallback-Sensor Failure, Fallback-Sensor/Tvl Deviation), max supply pressure, Actuator manufacturer, Actuator model, Actuator size, Volume Booster/Quick Release.
4. Send the configuration to the instrument.
5. Use factory defaults for setup
6. Select Cancel (475) or Abort (Trex) when prompted to run Auto Tvl Calib.
7. Place the instrument “In Service”.
ValveLink Mobile
AMS Trex Device Communicator or 475 Field Communicator
1. Select ValveLink Mobile from the Field Communicator Main Menu (see figure 1).
2. Select HART device.
3. Select Connect from the ValveLink Mobile main menu (see figure 2) to connect to the instrument.
4. Select Setup > Setup Wizard.
5. Provide the requested information then select Apply.
6. When prompted to run an Auto Travel Calibration select No.
7. Place the instrument “In Service”.
2