Fisher IM Supplement: Getting Started with Modbus and OPC Systems-Fisher 4320 Wireless Position Monitor Manuals & Guides

Instruction Manual Supplement
D103640X012
1
4320 Wireless Position Monitor
January 2018
Getting Started with Modbusr and OPC Systems
Fisher™ 4320 Wireless Position Monitor
Modbus Mapping of Set Point and Discrete Switch States Using Coils
When the DISCRETE SET POINT is written as true, the set point is written as Open. When written as false, the set point is written as Closed.
The Discrete Switch State feedbacks are read back as True/False for the State value shown.
Note: The set point must be 'Open' and the switch state must 'Opened'.
When the DISCRETE SET POINT is written as true, the set point is written as Closed. When written as false, the set point is written as Open.
The Discrete Switch State feedbacks are read back as True/False for the State value shown.
Writing Set Point through Modbus Register or OPC
There are 4 valid values for the Set Point variable:
4 - Close 5 - Open 6 - Closed* 46 - Opened*
Writing one of the above values will cause the gateway to send the corresponding set point.
*Recommended values for set point so the switch state will equal the value for the set point when the valve has reached it's final position.
The Discrete Switch State will report the current switch position. It's enumeration values for control are:
6 - Closed 18 - Closing 52 - Partially Open 17 - Opening 46 - Opened 48 - Error
1. Supplement to Fisher 4320 Wireless Position Monitor Instruction Manual (D103621X012), available from your Emerson sales office This supplement also pertains to TopWorx see instruction manual D103622X012
www.Fisher.com
or at www.Fisher.com.
4310 Wireless Position Monitors (Supported Status),
4320 Wireless Position Monitor
January 2018
Instruction Manual Supplement
D103640X012
To complete the Closed Loop process, the 'Closed' and 'Opened' states should match the corresponding set point.
SCREEN SHOT IS REPRESENTATIVE OF MODBUS
Mapped Variable Examples
SCREEN SHOTS ARE REPRESENTATIVE OF MODBUS
Mapped Alert Examples
SCREEN SHOT IS REPRESENTATIVE OF MODBUS
Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Fisher and TopWorx are marks owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. Emerson Automation Solutions, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.
Emerson Automation Solutions
Marshalltown, Iowa 50158 USA Sorocaba, 18087 Brazil Cernay, 68700 France Dubai, United Arab Emirates Singapore 128461 Singapore
www.Fisher.com
2
E 2012, 2018 Fisher Controls International LLC. All rights reserved.
Loading...