Instruction Manual Supplement
D104401X012
AMIT2000 Electronic Asset Tag
February 2019
FM (United States and Canada) Hazardous Area
Approvals
Emerson AMIT2000, Electronic Asset Tag
Hazardous Area Classifications and Special Instructions for “Safe
Use” and Installation in Hazardous Locations
Markings on the product may specify more than one approval, and each approval may have unique installation
requirements and/or conditions of “safe use”. These special instructions for “safe use” are in addition to, and may
override, the standard installation procedures. Special instructions are listed by approval.
Note
This information supplements the markings affixed to the product and in the AMIT2000 Electronic Asset Tag instruction manual
(D104400X012), available from your Emerson sales office
Always refer to the product itself to identify the appropriate certification.
or at Fisher.com.
WARNING
Failure to follow these conditions of “safe use” could result in personal injury or property damage from fire or explosion,
and area re‐classification.
Special Conditions of Use:
1. To prevent the risk of electrostatic sparking, the enclosure shall only be cleaned with a damp cloth.
2. Reader transmit power must be less than or equal to 1W.
Standards Used for Certification
United States:
FM Class 3600:2018
FM Class 3610:2018
ANSI/ISA 60079-0:2013
ANSI/ISA 60079-11:2014
ANSI/NEMA 250:2003
ANSI/IEC 60529:2004
Refer to table 1 and 2 for additional information.
Canada:
CSA-C22.2 No. 0:2010
CSA-C22.2 No. 94:R2011
CSA-C22.2 No. 60529:R2010
CAN/CSA-C22.2 No. 60079-0:2015
CAN/CSA-C22.2 No. 60079-11:2014
www.Fisher.com

AMIT2000 Electronic Asset Tag
Instruction Manual Supplement
February 2019
Table 1. Approval Information, FM (United States and Canada) - Class/Division
Certification Body Certification Obtained Temperature Code
FM
FM18US0118X
FMCA0057X
Intrinsically Safe
Class I, II, III Division I Groups A, B, C, D, E, F, G T4
T4 (-40°C v Tamb v +85°C)
Table 2. Approval Information, FM (United States and Canada) - Zone
Certification Body Certification Obtained Temperature Code
Intrinsically Safe
United States:
Gas
Class I, Zone 0 AEx ia IIC T4 Ga
FM
FM18US0118X
FMCA0057X
Dust
Class I, Zone 20 AEx ia IIIC T135°C Da
Canada:
Gas
Zone 0 Ex ia IIC T4 Ga
Dust
Zone 20 Ex ia IIIC T135°C Da
Gas: T4 (-40°C v Tamb v +85°C)
Dust: T135°C (-40°C v Tamb v +85°C)
D104401X012
Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance
of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Fisher is a mark owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. Emerson Automation Solutions,
Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not
to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are
governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such
products at any time without notice.
Emerson Automation Solutions
Marshalltown, Iowa 50158 USA
Sorocaba, 18087 Brazil
Cernay, 68700 France
Dubai, United Arab Emirates
Singapore 128461 Singapore
www.Fisher.com
2
E 2018, 2019 Fisher Controls International LLC. All rights reserved.