Fisher IM Supplement: FM (United States and Canada) Hazardous Area Approvals for Emerson AMIT2000, Electronic Asset Tag Manuals & Guides

Instruction Manual Supplement
D104401X012
AMIT2000 Electronic Asset Tag
February 2019
FM (United States and Canada) Hazardous Area Approvals Emerson AMIT2000, Electronic Asset Tag
Hazardous Area Classifications and Special Instructions for “Safe Use” and Installation in Hazardous Locations
Markings on the product may specify more than one approval, and each approval may have unique installation requirements and/or conditions of “safe use”. These special instructions for “safe use” are in addition to, and may override, the standard installation procedures. Special instructions are listed by approval.
Note
This information supplements the markings affixed to the product and in the AMIT2000 Electronic Asset Tag instruction manual (D104400X012), available from your Emerson sales office
Always refer to the product itself to identify the appropriate certification.
or at Fisher.com.
WARNING
Failure to follow these conditions of “safe use” could result in personal injury or property damage from fire or explosion, and area re‐classification.
Special Conditions of Use:
1. To prevent the risk of electrostatic sparking, the enclosure shall only be cleaned with a damp cloth.
2. Reader transmit power must be less than or equal to 1W.
Standards Used for Certification
United States:
FM Class 3600:2018 FM Class 3610:2018 ANSI/ISA 60079-0:2013 ANSI/ISA 60079-11:2014 ANSI/NEMA 250:2003 ANSI/IEC 60529:2004
Refer to table 1 and 2 for additional information.
Canada:
CSA-C22.2 No. 0:2010 CSA-C22.2 No. 94:R2011 CSA-C22.2 No. 60529:R2010 CAN/CSA-C22.2 No. 60079-0:2015 CAN/CSA-C22.2 No. 60079-11:2014
www.Fisher.com
AMIT2000 Electronic Asset Tag
Instruction Manual Supplement
February 2019
Table 1. Approval Information, FM (United States and Canada) - Class/Division
Certification Body Certification Obtained Temperature Code
FM
FM18US0118X
FMCA0057X
Intrinsically Safe Class I, II, III Division I Groups A, B, C, D, E, F, G T4
T4 (-40°C v Tamb v +85°C)
Table 2. Approval Information, FM (United States and Canada) - Zone
Certification Body Certification Obtained Temperature Code
Intrinsically Safe United States: Gas Class I, Zone 0 AEx ia IIC T4 Ga
FM
FM18US0118X
FMCA0057X
Dust Class I, Zone 20 AEx ia IIIC T135°C Da
Canada: Gas Zone 0 Ex ia IIC T4 Ga Dust Zone 20 Ex ia IIIC T135°C Da
Gas: T4 (-40°C v Tamb v +85°C) Dust: T135°C (-40°C v Tamb v +85°C)
D104401X012
Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Fisher is a mark owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. Emerson Automation Solutions, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.
Emerson Automation Solutions
Marshalltown, Iowa 50158 USA Sorocaba, 18087 Brazil Cernay, 68700 France Dubai, United Arab Emirates Singapore 128461 Singapore
www.Fisher.com
2
E 2018, 2019 Fisher Controls International LLC. All rights reserved.
Loading...