FM Hazardous Area Approvals
Fisher
Hazardous Area Classifications and Special Instructions for “Safe Use” and Installations in Hazardous Locations
Certain nameplates may carry more than one approval, and each approval may have unique installation/wiring requirements and/or conditions of “safe use”. These special instructions for “safe use” are in addition to, and may override, the standard installation procedures. Special instructions are listed by approval.
Note
This information supplements the nameplate markings affixed to the product and the 4200 Instruction Manual (D200354X012 available from your Emerson sales office
Always refer to the nameplate itself to identify the appropriate certification.
4200 Electronic Position Transmitters
or Local Business Partner, or at www.Fisher.com.
),
WARNING
Failure to follow these conditions of “safe use” could result in personal injury or property damage from fire or explosion, or area re‐classification.
Intrinsically Safe, Explosion-proof, Dust Ignition-proof, Non‐Incendive
No special conditions for safe use.
Refer to table 1 for approval information.
Table 1. Hazardous Area Classifications—FM (United States)
Certification Body Type Certification Obtained Entity Rating Temperature Code
Vmax = 30 VDC Imax = 150 mA Pi = 1.0 W Ci = 18 nF Li = 0 mH
- - - T5 (Tamb 71°C)
- - - T4 (Tamb 71°C)
T4 (Tamb 71°C)
FM
4211, 4221
4210, 4211, 4212, 4215, 4220, 4221, 4222
4211, 4221
4210, 4211, 4212, 4215, 4220, 4221, 4222
Intrinsically Safe Class I,II,III Division 1 GP A,B,C,D,E,F,G per drawing GE16019 (see figure 1)
Explosion-proof Class I Zone 1 AEx d IIC T5 Class I, Division 1 GP A,B,C,D T5
Class I Division 2 GP A,B,C,D T4 Class II Division 2 GP F,G T4
Class II Division 1 GP E,F,G T5 - - - T5 (Tamb 71°C)
www.Fisher.com
4200 Transmitters
October 2017
Figure 1. Fisher 4211 and 4221 FM Schematic (Drawing GE16019)
HAZARDOUS LOCATION NON-HAZARDOUS LOCATION
I.S. CLASS I,II,III DIV 1, GROUPS A,B,C,D,E,F,G
N.I. CLASS I, DIV 2, GROUPS A,B,C,D
4211, 4221
Vmax = 30 VDC
Imax = 150 mA
Pi = 1.0 W
Ci = 18 nF Li = 0 mH
WARNING
THE APPARATUS ENCLOSURE CONTAINS ALUMINUM AND IS CONSIDERED TO CONSTITUTE A POTENTIAL RISK OF IGNTION BY IMPACT AND FRICTION. AVOID IMPACT AND FRICTION DURING INSTALLATION AND USE TO PREVENT RISK OF IGNTION.
Instruction Manual Supplement
D104309X012
FM APPROVED BARRIER SEE NOTE 6
NOTES:
1. THE INSTALLATION MUST BE IN ACCORDANCE WITH THE NATIONAL ELECTRIC  CODE (NEC), NFPA 70, ARTICLE 504 AND ANSI/ISA RP12.6.
2. THE CLASS 1, DIV 2 APPLICATIONS MUST BE INSTALLED AS SPECIFIED IN NEC  ARTICLE 501‐4(B). EQUIPMENT AND FIELD WIRING IS NON‐INCENDIVE WHEN  CONNECTED TO APPROVED BARRIERS WITH ENTITY PARAMETERS.
3. LOOPS MUST BE CONNECTED ACCORDING TO THE BARRIER MANUFACTURER'S  INSTRUCTIONS.
4. MAXIMUM SAFE AREA VOLTAGE SHOULD NOT EXCEED 250 Vrms.
5. RESISTANCE BETWEEN BARRIER GROUND AND EARTH GROUND MUST BE LESS  THAN ONE OHM.
6. FOR ENTITY INSTALLATION (I.S. AND N.I.):     Vmax > Voc, or Vt Ci + Ccable < Ca     Imax > Isc, or It Li + Lcable < La     Pi > Po, or Pt
GE16019-B
Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Fisher is a mark owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. Emerson Automation Solutions, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.
Emerson Automation Solutions
Marshalltown, Iowa 50158 USA Sorocaba, 18087 Brazil Cernay, 68700 France Dubai, United Arab Emirates Singapore 128461 Singapore
www.Fisher.com
2
E 2017 Fisher Controls International LLC. All rights reserved.
Loading...