Fisher IM Supplement: FM Hazardous Area Approvals - FIELDVUE DVC6200 Series Digital Valve Controllers Manuals & Guides

Instruction Manual Supplement
D104204X012
DVC6200 Digital Valve Controllers
October 2021
FM Hazardous Area Approvals
Fisher
FIELDVUE™ DVC6200 Series
Digital Valve Controllers
Hazardous Area Approvals and Special Instructions for “Safe Use” and Installations in Hazardous Locations
Certain nameplates may carry more than one approval, and each approval may have unique installation/wiring requirements and/or conditions of “safe use”. These special instructions for “safe use” are in addition to, and may override, the standard installation procedures. Special instructions are listed by approval type.
Note
This information supplements the nameplate markings affixed to the product and the DVC6200 Series quick start guide (D103556X012
Always refer to the nameplate itself to identify the appropriate certification.
), available from your Emerson sales office or at Fisher.com.
SIS
WARNING
Failure to follow these conditions of “safe use” could result in personal injury or property damage from fire or explosion and area re‐classification.
Explosion-proof, Dust-Ignition proof, Non-Incendive, Suitable for Use
DVC6200 and DVC6205 Series (HART HW1 & HW2, SIS, FOUNDATION Fieldbus, PROFIBUS)
XP: Class I, Division 1, Groups B,C,D DIP: Class II, III, Division 1, Groups E,F,G NI: Class I, Division 2, Groups A,B,C,D S: Class II, III, Division 2, Groups F,G Class I Zone 1 AEx d IIC Class I Zone 2 Ex nC IIC
T5 Ta = 80°C, T6 Ta = 75°C Type 4X, IP66
www.Fisher.com
DVC6200 Digital Valve Controllers
October 2021
DVC6215 Remote Mount*
XP: Class I, Division 1, Groups A,B,C,D DIP: Class II, III, Division 1, Groups E,F,G NI: Class I, Division 2, Groups A,B,C,D S: Class II, III, Division 2, Groups F,G Class I Zone 1 AEx d IIC Class I Zone 2 Ex nA IIC
T4 Ta = 125°C, T5 Ta = 90°C, T6 Ta = 75°C Type 4X, IP66
*Poured seal required within 2 inches of the enclosure for explosion-proof installations of the DVC6215NA.
Instruction Manual Supplement
Intrinsically Safe and Nonincendive Field Wiring
Intrinsic Safety
IS Class I, II, III Division 1 Groups A,B,C,D,E,F,G Class I Zone 0 AEx ia IIC Class I Zone 2 AEx ic IIC
Nonincendive Field Wiring
NI Class I Division 2 Groups A,B,C,D
Type 4X, IP66 Intrinsically safe or Nonincendive Field Wiring when connected per control drawing GE42819, as shown in the following figures
DVC6200 HW2 and DVC6200 SIS
Intrinsically Safe figure 1 and 15.................................................
Intrinsically Safe or Nonincendive Field Wiring figure 2 and 15........................
DVC6205, DVC6205 SIS, and DVC6215 Remote Mount
Intrinsically Safe figure 3 and 15.................................................
Intrinsically Safe or Nonincendive Field Wiring figure 4 and 15........................
DVC6200f and DVC6200p
Entity Fieldbus Loop: Intrinsically Safe figure 5 and 15...............................
Entity Fieldbus Loop: Intrinsically Safe or Nonincendive Field Wiring figure 6 and 15......
FISCO Installations: Intrinsically Safe figure 7 and 15................................
FISCO Installations: Intrinsically Safe or Nonincendive Field Wiring figure 8 and 15.......
DVC6205f, DVC6205p, and DVC6215 Remote Mount
Entity Fieldbus Loop: Intrinsically Safe figure 9 and 15...............................
Entity Fieldbus Loop: Intrinsically Safe or Nonincendive Field Wiring figure 10 and 15......
FISCO Installations: Intrinsically Safe figure 11 and 15................................
FISCO Installations: Intrinsically Safe or Nonincendive Field Wiring figure 12 and 15.......
DVC6200 HW1
Intrinsically Safe figure 13 and 15.................................................
Intrinsically Safe or Nonincendive Field Wiring figure 14 and 15........................
D104204X012
Special Conditions of Safe Use
D When product is used with natural gas as the pneumatic medium, the maximum working pressure of the natural
gas supply shall be limited to 10 bar (145 psi).
D When product is used with natural gas as the pneumatic medium the product shall not be permitted in a Class I,
Division 2, Group A, B, C, D location without the proper venting installation per the manufacturer's instruction manual.
D The apparatus enclosure contains aluminum and is considered to constitute a potential risk of ignition by impact
or friction. Care must be taken into account during installation and use to prevent impact or friction.
2
Instruction Manual Supplement
D104204X012
DVC6200 Digital Valve Controllers
October 2021
D Part of the enclosure is constructed from plastic. To prevent the risk of electrostatic sparking the plastic surface
should only be cleaned with a damp cloth.
Figure 1. FM Loop Schematics—FIELDVUE DVC6200 HW2 and DVC6200 SIS
INTRINSICALLY SAFE
POWER MAY BE APPLIED TO EITHER THE LOOP TERMINALS OR OUTPUT TERMINALS OR TO BOTH SETS OF TERMINALS AT THE SAME TIME
UNITS WITHOUT THE I/O PACKAGE WILL NOT HAVE “OUTPUT TERMINALS” AVAILABLE FOR CONNECTION
** Li = 0.15 mH WHEN THE AUX TERMINALS ARE NOT USED OR NOT PROVIDED
CLASS I ZONE 0 AEx ia IIC I.S. CL I,II,III DIV 1 GP ABCDEFG
DVC6200, DVC6200S (HW2 CONSTRUCTION)
LOOP TERMINALS
**Vmax = 30 VDC **Imax = 130 mA **Pi = 1.0 W **Ci = 15 nF
**Li = 0.55 mH
OUTPUT TERMINALS
**Vmax = 28 VDC **Imax = 100 mA **Pi = 1.0 W **Ci = 15 nF **Li = 0.50 mH
1 NOTE 9
WITH
I/O PACKAGE
T5 (Tamb) 80_C T6 (Tamb) 61_C
I/O PACKAGE
T5 (Tamb) 80_C T6 (Tamb) 74_C
HAZARDOUS LOCATION
1 NOTE 7
WITHOUT
NON‐HAZARDOUS LOCATION
FM APPROVED BARRIER
NOTE 1, 3, 4, 5, 6 1
FM APPROVED BARRIER
NOTE 1, 3, 4, 5, 6 1
1 SEE NOTES IN FIGURE 15
GE42819 Sheet 11, Rev. C
3
DVC6200 Digital Valve Controllers
October 2021
Figure 2. FM Loop Schematics—FIELDVUE DVC6200 HW2 and DVC6200 SIS
INTRINSICALLY SAFE OR
NONINCENDIVE FIELD WIRING
Instruction Manual Supplement
D104204X012
POWER MAY BE APPLIED TO EITHER THE LOOP TERMINALS OR OUTPUT TERMINALS OR TO BOTH SETS OF TERMINALS AT THE SAME TIME
UNITS WITHOUT THE I/O PACKAGE WILL NOT HAVE “OUTPUT TERMINALS” AVAILABLE FOR CONNECTION
** Li = 0.15 mH WHEN THE AUX TERMINALS ARE NOT USED OR NOT PROVIDED
CLASS I ZONE 2 AEx ic IIC N.I. CL I DIV 2 GP ABCD
DVC6200, DVC6200S (HW2 CONSTRUCTION)
LOOP TERMINALS
**Vmax = N/A **Imax = 130 mA **Pi = N/A **Ci = 15 nF
**Li = 0.55 mH
OUTPUT TERMINALS
**Vmax = N/A **Imax = 100 mA **Pi = N/A **Ci = 15 nF **Li = 0.50 mH
1 NOTE 8
WITH OR WITHOUT
I/O PACKAGE
T5 (Tamb) 80_C T6 (Tamb) 75_C
HAZARDOUS LOCATION
1 NOTE 7
NON‐HAZARDOUS LOCATION
FM APPROVED BARRIER
OR
NONINCENDIVE CIRCUIT
NOTE 1, 3, 4, 5, 6 1
FM APPROVED BARRIER
OR
NONINCENDIVE CIRCUIT
NOTE 1, 3, 4, 5, 6 1
1 SEE NOTES IN FIGURE 15
GE42819 Sheet 11, Rev. C
4
Instruction Manual Supplement
D104204X012
Figure 3. FM Loop Schematics—FIELDVUE DVC6205, DVC6205 SIS, and DVC6215
INTRINSICALLY SAFE
DVC6200 Digital Valve Controllers
October 2021
CLASS I ZONE 0 AEx ia IIC I.S. CL I,II,III DIV 1 GP ABCDEFG
DVC6215
Vmax = 30 VDC Imax = 226 mA Pi = 1.4 W Ci = 50 nF Li = 0.55 mH
NOTE 1, 3 1
T4 (Tamb) 125_C T5 (Tamb) 95_C T6 (Tamb) 80_C
CLASS I ZONE 0 AEx ia IIC I.S. CL I,II,III DIV 1 GP ABCDEFG
DVC6205 (HW2 CONSTRUCTION)
WITH OR WITHOUT I/O PACKAGE
REMOTE FIELD WIRING TERMINAL BOX
REMOTE TERMINALS
Voc = 30 VDC Isc = 21.2 mA Po = 160 mW Ca = 55 nF La = 78 mH
NOTE 9 1
FIELD WIRING TERMINAL BOX
LOOP TERMINALS
**Vmax = 30 VDC **Imax = 130 mA **Pi = 1.0 W **Ci = 15 nF
**Li = 0.55 mH
OUTPUT TERMINALS
**Vmax = 28 VDC **Imax = 100 mA **Pi = 1.0 W **Ci = 15 nF **Li = 0.50 mH
HAZARDOUS LOCATION
NOTE 7
NON‐HAZARDOUS LOCATION
FM APPROVED BARRIER
NOTE 1, 3, 4, 5, 6 1
1
FM APPROVED BARRIER
NOTE 1, 3, 4, 5, 6 1
1 SEE NOTES IN FIGURE 15
GE42819 Sheet 12, Rev. C
WITH
I/O PACKAGE
T5 (Tamb) 80_C T6 (Tamb) 61_C
WITHOUT
I/O PACKAGE
T5 (Tamb) 80_C T6 (Tamb) 74_C
POWER MAY BE APPLIED TO EITHER THE LOOP TERMINALS OR OUTPUT TERMINALS OR TO BOTH SETS OF TERMINALS AT THE SAME TIME
UNITS WITHOUT THE I/O PACKAGE WILL NOT HAVE “OUTPUT TERMINALS” AVAILABLE FOR CONNECTION
** Li = 0.15 mH WHEN THE AUX TERMINALS ARE NOT USED OR NOT PROVIDED
5