Fisher IM Supplement: FIELDVUE DVC6200 SIS-Partial Stroke Test using ValveLink Mobile Software | Fisher Manuals & Guides

Instruction Manual Supplement
D104168X012
DVC6200 SIS
September 2017
Partial Stroke Test using ValveLink™ Mobile Software
A partial stroke test allows DVC6200 SIS digital valve controllers to perform a diagnostic test while the instrument is in service and operational. In a safety application, it is important to be able to exercise and test the valve to verify that it will open or close when commanded. If a safety demand arises, the partial stroke test will abort and the valve will move to its commanded position.
The test procedure contained in this Instruction Manual Supplement is to be considered as a guideline only and should be modified to address site‐specific requirements. Use this procedure in conjunction with the Safety Manual (D103601X012 Emerson sales office or Local Business Partner, or at Fisher.com abide by specific plant safety guidelines for safe operation.
WARNING
This document is not intended to be used as a stand‐alone document. It must be used in conjunction with the following documents: Safety Manual for FIELDVUE
Fisher
Failure to use this instruction manual supplement in conjunction with the above referenced manuals could result in personal injury or property damage. If you have any questions regarding these instructions or need assistance in obtaining any of these documents, contact your Emerson sales office
FIELDVUE DVC6200 SIS Instruction Manual (D103557X012)
), Instruction Manual (D103557X012) and 475 Field Communicator User’s Manual, available from your
. In addition, exercise good engineering practices and
DVC6200 SIS Digital Valve Controller and Position Monitor (D103601X012)
or Local Business Partner.
Note
This procedure requires the use of ValveLink Mobile Software and a 475 Field Communicator. This procedure should be performed with the digital valve controller's Instrument Mode set to “In Service”.
www.Fisher.com
DVC6200 SIS
September 2017
Instruction Manual Supplement
D104168X012
Partial Stroke Test Procedure
1. Physically inspect the valve and the DVC6200 SIS for any loose screws, loose mounting bracket, loose feedback linkage, loose or broken tubing/conduit or the other mechanically loose conditions. Check the air filter regulator to ensure that it is clean and operating properly. Inspect gauges and verify that they are reading correctly.
2. Connect the 475 Communicator to the DVC6200 SIS digital valve controller. Be sure to carefully read, understand, and follow the contents of the 475 User’s Manual
3. Initiate ValveLink Mobile software within the 475 Field Communicator (figure 1).
Figure 1. Field Communicator Main Menu
, including all safety cautions and warnings.
4. In the 475 Handheld Communicator select “HART” communication from the ValveLink Mobile Main Menu (figure 2).
Figure 2. ValveLink Mobile Main Menu