Partial Stroke Test using ValveLink™ Mobile
Software
A partial stroke test allows DVC6200 SIS digital valve controllers to perform a diagnostic test while the instrument is in
service and operational. In a safety application, it is important to be able to exercise and test the valve to verify that it
will open or close when commanded. If a safety demand arises, the partial stroke test will abort and the valve will move
to its commanded position.
The test procedure contained in this Instruction Manual Supplement is to be considered as a guideline only and should
be modified to address site‐specific requirements. Use this procedure in conjunction with the Safety Manual
(D103601X012
Emerson sales office or Local Business Partner, or at Fisher.com
abide by specific plant safety guidelines for safe operation.
WARNING
This document is not intended to be used as a stand‐alone document. It must be used in conjunction with the following
documents:
Safety Manual for FIELDVUE
™
Fisher
Failure to use this instruction manual supplement in conjunction with the above referenced manuals could result in
personal injury or property damage. If you have any questions regarding these instructions or need assistance in obtaining
any of these documents, contact your Emerson sales office
), Instruction Manual (D103557X012) and 475 Field Communicator User’s Manual, available from your
. In addition, exercise good engineering practices and
™
DVC6200 SIS Digital Valve Controller and Position Monitor (D103601X012)
or Local Business Partner.
Note
This procedure requires the use of ValveLink Mobile Software and a 475 Field Communicator. This procedure should be performed
with the digital valve controller's Instrument Mode set to “In Service”.
www.Fisher.com
DVC6200 SIS
September 2017
Instruction Manual Supplement
D104168X012
Partial Stroke Test Procedure
1. Physically inspect the valve and the DVC6200 SIS for any loose screws, loose mounting bracket, loose feedback
linkage, loose or broken tubing/conduit or the other mechanically loose conditions. Check the air filter regulator to
ensure that it is clean and operating properly. Inspect gauges and verify that they are reading correctly.
2. Connect the 475 Communicator to the DVC6200 SIS digital valve controller. Be sure to carefully read, understand,
and follow the contents of the 475 User’s Manual
3. Initiate ValveLink Mobile software within the 475 Field Communicator (figure 1).
Figure 1. Field Communicator Main Menu
, including all safety cautions and warnings.
4. In the 475 Handheld Communicator select “HART” communication from the ValveLink Mobile Main Menu
(figure 2).
Figure 2. ValveLink Mobile Main Menu
2
Instruction Manual Supplement
D104168X012
DVC6200 SIS
September 2017
5. Connect to your device by selecting the “HART Connect” icon (figure 3). Verify the valve is “Connected” and “In
Service” by looking at the bottom right hand corner.
Figure 3. ValveLink Mobile HART Menu
6. Once connected to your valve, you will be able to find “Partial Stroke” in the “Diagnostics” menu (figure 4 and 5).
Figure 4. ValveLink Mobile HART Main Menu after
Figure 5. Diagnostics Menu
valve is connected and placed in service. Diagnostics
icon is selected.
3
DVC6200 SIS
September 2017
Instruction Manual Supplement
D104168X012
7. After selecting Partial Stroke a notification will appear, warning that running a diagnostic will move the valve
(figure 6). Select “Start” (figure 7).
Figure 6. Partial Stroke Test WarningFigure 7. Partial Stoke Test Warning with Start
Selected
8. The Partial Stroke Test has begun. The test will begin by “Reading Spec Sheet” (figure 8) and “Reading data”
(figure 9).
Figure 8. Partial Stroke Test in Progress – Reading
Spec Sheet
Figure 9. Partial Stroke Test in Progress - Reading
data
4
Instruction Manual Supplement
D104168X012
DVC6200 SIS
September 2017
9. You will begin to see the results showing on the screen (figure 10). Completed results example shown in figure 11.
Select Done.
Figure 10. Partial Stroke Test in Progress – Reading
Figure 11. Partial Stroke Test Completed
data
The information will save under the tag name in ValveLink Mobile. These results may be exported to ValveLink
software on a PC at a later time if necessary.
5
DVC6200 SIS
September 2017
Instruction Manual Supplement
D104168X012
Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance
of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Fisher, FIELDVUE and ValveLink Mobile are marks owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric
Co. Emerson Automation Solutions, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the
property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not
to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are
governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such
products at any time without notice.
Emerson Automation Solutions
Marshalltown, Iowa 50158 USA
Sorocaba, 18087 Brazil
Cernay, 68700 France
Dubai, United Arab Emirates
Singapore 128461 Singapore
www.Fisher.com
6
E 2016, 2017 Fisher Controls International LLC. All rights reserved.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.