Instruction Manual Supplement
D103560X012
DVC6200p Digital Valve Controller
August 2020
Fisher™ FIELDVUE™ DVC6200p Digital Valve
Controller Device Setup and Accessing
Communication and Calibration using Siemens
SIMATIC Manager/PDM
Contents
Related Documents 2...........................
Connecting the Digital Valve Controller using
Enhanced Device Description (EDD) for Siemens
SIMATIC PDM 3................................
Setting PG/PC Interface 4.......................
Loading the DVC6200p EDD to the SIMATIC
Manager/PDM Catalog 8.....................
Device Setup using Siemens PDM Software 11.....
Going Online with the DVC6200p 17..............
Performing One-Step Local Quick Setup
to Calibrate and Tune the DVC6200p 19........
This document takes you through setting up and accessing the DVC6200p using Siemens SIMATIC PDM software, as
well as performing initial actuator and valve configuration, calibration, and tuning using the Guided Setup procedure.
The procedures covered in this supplement were completed using Siemens SIMATIC Manager/PDM 9.1. While the
steps taken should remain basically the same, screens may vary slightly if you are using a different version of the
software.
Ensure that all necessary files, including the latest DVC6200p EDD, are available.
Note
Setting PG/PC Interface and loading the DVC6200p EDD are generally required only once per computer.
Refer to the DVC6200 Series Quick Start Guide (D103556X012) for DVC6200p
installation, connection and initial configuration information. If a copy of this
quick start guide is needed scan or click the QR code at the right, contact your
Emerson sales office
sales office or visit our website at www.Fisher.com.
Scan or click
to access
field support
www.Fisher.com

DVC6200p Digital Valve Controller
August 2020
Related Documents
D DVC6200 Series Digital Valve Controller quick start guide (D103556X012)
D DVC6200p Digital Valve Controller instruction manual (D103563X012)
Instruction Manual Supplement
D103560X012
All documents are available from your Emerson sales office
. Also visit our website at www.Fisher.com.
2

Instruction Manual Supplement
D103560X012
DVC6200p Digital Valve Controller
August 2020
Connecting the DVC6200p using Enhanced Device Description
(EDD) for Siemens SIMATIC PDM
Refer to figure 1.
Figure 1. Connecting the FIELDVUE DVC6200p using EDD for Siemens SIMATIC PDM
PROFIBUS PA
POWER
SUPPLY
230V/120V AC
DP/PA COUPLER
24 VDC SUPPLY VOLTAGE
FOR DP/PA COUPLER
DP 9-PIN
CABLE CONNECTORS
BACK-RAIL
DP CABLE (PURPLE)
PROFIBUS USB
INTERFACE ADAPTER
PROFIBUS DP
MASTER SYSTEM
(CLASS-2
MASTER)
3

DVC6200p Digital Valve Controller
August 2020
Instruction Manual Supplement
D103560X012
Setting PG/PC Interface
Note
Setting the PG/PC interface or PC card (CP 5711 or similar PROFIBUS card) is done only once, after the first hardware installation of
the PC card inside the computer.
1. Set PG/PC Interface is available under the PC ‘Control Panel’ once Siemens STEP 7 or SIMATIC Manager/PDM
software is installed.
a. Go to Set PG/PC Interface as shown in figure 2.
b. Under the Interface, click on Select... to add the PCI/PCMCIA/USB type PROFIBUS card installed on the PC.
c. Once the interface or card appears as shown in figure 2, select the interface adapter installed and click on
Properties. In this example, the PC Adapter USB A2.PROFIBUS.1 <Active> is selected.
For further support on Setting PG/PC Interface visit the following Siemens website for detailed setup procedures:
http://support.automation.siemens.com/WW/view/en/25471997
Figure 2. Set PG/PC Interface
SELECT THE
PROFIBUS
INTERFACE
ADAPTER
4

Instruction Manual Supplement
D103560X012
DVC6200p Digital Valve Controller
August 2020
2. If the PROFIBUS card is the only master on the bus select 'PG/PC is the only master on the bus', as shown in figure 3.
If there are other Class 1 or Class 2 masters on the bus, then DO NOT select PG/PC is the only master on the bus.
Under Network Parameters select the appropriate Transmission Rate of the bus. Click OK when all parameters are
set.
Figure 3. PROFIBUS Card Parameter Setting
PARAMETER SETTINGS
Note
The parameter setting above applies only if the PG/PC card is the only master on the bus.
5

DVC6200p Digital Valve Controller
August 2020
3. Click on Diagnostics... as shown in figure 4.
Figure 4. Diagnostics...
Instruction Manual Supplement
D103560X012
4. In the Diagnostics window, shown in figure 5, click on Test to check the status of the PROFIBUS card and network.
Figure 5. Status/Network Diagnostics—Test
6