Fisher IM Supplement: FIELDVUE DVC6200 - Implementation of Lock-in-Last Strategy Manuals & Guides

Instruction Manual Supplement
D103261X012
DVC6200 Digital Valve Controllers
February 2020
Implementation of Lock‐in‐Last Strategy
Supplement to Fisher™ FIELDVUE™ DVC6200 Digital Valve Controller Instruction Manuals
Many applications require a valve assembly to remain in the position it was prior to a specific control system failure (lock‐in‐last position). Functionality and safety can be designed into valve assemblies with FIELDVUE digital valve controllers by utilizing an array of accessories. The following paragraphs describe standard solutions for a number of generic lock‐in‐last applications with HART
Note
This instruction manual supplement also pertains to FELDVUE DVC6000 digital valve controllers; refer to the appropriate DVC6200 or DVC6000 document below, available from your Emerson sales office or at Fisher.com.
DVC6200 Series Digital Valve Controller Quick Start Guide (D103556X012)
D D DVC6200 HW2 Digital Valve Controller Instruction Manual (D103605X012)
D
DVC6200 HW1 Digital Valve Controller Instruction Manual (D103409X012)
D DVC6000 Digital Valve Controllers Instruction Manual (D102794X012)
Other related documents include:
D
Fisher 377 Trip Valve Instruction Manaul (D200319X012)
D 167D, 167DA, 167DS and 167DAS Switching Valves Installation Guide (D103234X014) D 167D, 167DA, 167DS and 167DAS Switching Valves Instruction Manual (D103234X012)
®
Communicating DVC6200 digital valve controllers.
Lock‐in‐Last on Loss of Supply Pressure
Once the supply pressure falls below a minimum value, the digital valve controller can no longer position a valve assembly; the valve will start to go to the actuator “at rest” position. The locking device senses this change and activates, preventing the remaining air from venting. The valve is “locked‐in” this new position.
Note
The locked‐in valve position depends on the exhausting speed of the actuator.
Assemblies with Single‐Acting Actuators
A Fisher 167DA three‐way switching valve should be used for locking a single‐acting actuator in place on loss of supply pressure. Figure 1 is a schematic representing proper assembly layout. In normal operation, the digital valve controller output passes through the switching valve from port A to port B and on to the actuator.
www.Fisher.com
DVC6200 Digital Valve Controllers
Instruction Manual Supplement
February 2020
Figure 1. Lock‐in‐Last on Loss of Supply Pressure for an Assembly with a Single‐Acting Actuator
FISHER 167DA THREE‐WAY SWITCHING VALVE
D
D103261X012
DIGITAL
VALVE
CONTROLLER
B
OUTPUT SUPPLY
A
C
AIR SUPPLY
FISHER 67CFR FILTER/REGULATOR
In a fail condition, the pressure at port D is below the switching valve's set point, causing the switching valve to trip. This closes port B, which locks the pressure in the actuator. Port C is plugged so the digital valve controller output will not exhaust to the atmosphere.
Assemblies with Double‐Acting Actuators
Similar to the locking strategy used with single‐acting actuators, the locking strategy with double‐acting actuators also uses a valve for locking supply pressure in the actuator. For assemblies with double‐acting actuators, a Fisher 377L trip valve is used as the locking device. The 377L trip valve has two output ports for locking pressure on both sides of a double‐acting actuator. Figure 2 is a schematic representing proper assembly layout.
Figure 2. Lock‐in‐Last on Loss of Supply Pressure for an Assembly with a Double‐Acting Actuator
FISHER 377L TRIP VALVE
INPUT
D
A
E
B
F
C
FISHER 67D REGULATOR
DIGITAL
VALVE
CONTROLLER
2
OUTPUT SUPPLY OUTPUT
AIR SUPPLY
Instruction Manual Supplement
D103261X012
DVC6200 Digital Valve Controllers
February 2020
Connection of the digital valve controller output to a double‐acting actuator determines the action of the actuator. Figure 2 shows the digital valve controller providing lower cylinder pressure through ports D and E, and upper cylinder pressure through ports A and B. When the supply pressure falls below the set point of the trip valve, the trip valve closes ports D and A and connects port B to C and port E to F. Because C and F are plugged, the control valve is locked in place by locking pressure on both sides of the actuator piston. The assembly returns to normal operation once supply pressure is restored at the trip valve INPUT port.
Note
Double‐acting actuators with a 377L trip valve require a Fisher 67D or MR95H regulator. Regulators with smaller flow capacities may cause the trip valve to cycle (lock and unlock repeatedly) due to air flow demand as the assembly attempts to reset. Use a Fisher 252 or 262C pilot filter to filter supply air.
Both the 167DA switching valve and the 377L trip valve have a deadband that must be overcome. The switching valve must be calibrated to reset upon restoration of adequate supply pressure to the regulator. The 377L trip valve has only one spring selection. However, for minimal deadband, the lightest appropriate spring should be selected for the 167DA switching valve.
Lock‐in‐Last Using Solenoid Valves
Solenoid valves are used with valve assemblies in many ways. Their electrical control can be utilized in combination with switches and controller logic to perform a number of functions.
Note
Solenoid valves placed between the output of a DVC6200 digital valve controller and the input to an actuator require a minimum C
of 0.49. Greater restrictions can affect the response of the assembly. An example of an appropriate three‐way solenoid valve for
v
use with the digital valve controller is the ASCO
Assemblies with Single‐Acting Actuators
A three‐way universal solenoid valve can be placed between the digital valve controller output and the actuator input. Switching the valve assembly from an unlocked state to a locked state is controlled by switching power on and off to the solenoid valve. Figure 3 depicts proper assembly layout.
Under normal operating conditions the solenoid is energized and supply air flows from the digital valve controller output to the actuator input. In the fail state, power is removed from the solenoid causing the solenoid valve to close, locking air pressure in the actuator. Port 1 of the solenoid valve is plugged, preventing actuator air pressure from exhausting to the atmosphere.
8327 Series solenoid valve from ASCO Valve, Inc.
3
Loading...
+ 5 hidden pages