Fisher IM Supplement: Digital Setpoint Control for Fisher DVC6200 and DVC6000 Digital Valve Controllers Manuals & Guides

Instruction Manual Supplement
D104140X012
FIELDVUE Digital Valve Controllers
March 2019
Digital Setpoint Control for Fisher™ FIELDVUE
DVC6200 and DVC6000 Digital Valve Controllers
1. Digital Valve Controller Setup
A. Electrical Power
Set the digital valve controller to PT-PT or MULTI-DROP.
Voltage ‐- ensure the switch is set in the “MULTI-DROP” position. The current will be fixed around 8.3 mA with a 24 V power source.
Milliamp current ‐- ensure the switch is set in the “PT-PT” position. Milliamp signal power to the instrument should be set to a value between 6 and 20 mA.
Notes
Factory default is switch set to PT-PT.
D
D
For Multi-Drop and 24 V power a LC340 Line Conditioner may be required to ensure quality HART
For Point-to-Point and a milliamp powered system a HF340 HART filter may be required to ensure quality HART
D
communications.
®
communications.
Figure 1. PT-PT or MULTI-DROP Selection
PT-PT/ MULTI-DROP SELECTION
www.Fisher.com
FIELDVUE Digital Valve Controllers
Instruction Manual Supplement
March 2019
Using a Field Communicator or AMS Device Manager verify or set the following:
B. Control Mode set to “Digital” C. Restart Control Mode set to “Digital” D. Instrument mode set to “In Service”
If additional product information is needed refer to Related Documents on page 5.
2. 775 THUM™ Setup
A. Electrical Wiring diagrams are shown in figure 2.
Notes
This configuration is only appropriate for one digital valve controller and one THUM adapter.
D
The THUM adapter requires up to 2.5 VDC additional compliance voltage above and beyond the digital valve controller
D
requirements.
Figure 2. Wiring Diagrams
OPTIONAL LC340
24 V
LOOP +
FLD  - /)
LOOP -
SYS  - /)
LC340
SPLICE CONNECTOR
GROUND
LOOP -
LOOP +
GREEN
RED BLACK WHITE
YELLOW
THUM ADAPTER
D104140X012
4 -20 mA
LOOP +
FLD  - /)
SYS  - /)
HF340
LOOP -
SPLICE CONNECTOR
DIGITAL VALVE CONTROLLER
PWB SET TO Multi
24 V POWER SOURCE
OPTIONAL HF340
GROUND
LOOP ­LOOP +
DIGITAL VALVE CONTROLLER
PWB SET TO PT-PT
MILLIAMP SIGNAL POWER
GREEN RED BLACK WHITE
YELLOW
THUM ADAPTER
PWB— PT-PT/MULTI SWITCH LOCATION
2
Loading...
+ 4 hidden pages