Instruction Manual Supplement
D104203X012
DVC6200 Digital Valve Controllers
July 2017
CSA Hazardous Area Approvals
™
Fisher
FIELDVUE™ DVC6200 Series
Digital Valve Controllers
Hazardous Area Approvals and Special Instructions
for “Safe Use” and Installations in Hazardous Locations
Certain nameplates may carry more than one approval, and each approval may have unique installation/wiring
requirements and/or conditions of “safe use”. These special instructions for “safe use” are in addition to, and may
override, the standard installation procedures. Special instructions are listed by approval type.
Note
This information supplements the nameplate markings affixed to the product and the DVC6200 Series quick start guide
(D103556X012
Always refer to the nameplate itself to identify the appropriate certification.
), available from your Emerson sales office or Local Business Partner, or at Fisher.com.
SIS
WARNING
Failure to follow these conditions of “safe use” could result in personal injury or property damage from fire or explosion
and area re‐classification.
Ordinary Locations Approval
Complies with general electrical safety CAN/CSAC22.2 No. 6101012004
SELV, conduit connected, Enclosure Type 4X, IP66, Installation Category I, Pollution Degree 4
DVC6200 Series (HART HW1, F
Rated Input 9-30 VDC, 4-20 mA
-52_C to + 80_C Ambient
DVC6205 (HART HW1, F
Rated Input 9-30 VDC, 4-20 mA Rated Input 10 VDC max, 3.5 mA max
Outputs 0-9.6 VDC, 0-3.5 mA -52 to 125_C Ambient
-52_C to + 80_C Ambient
OUNDATION Fieldbus, PROFIBUS)
OUNDATION fieldbus, PROFIBUS) DVC6215 Remote Mount
www.Fisher.com

DVC6200 Digital Valve Controllers
July 2017
Instruction Manual Supplement
Explosion-proof and Dust Ignition-proof
DVC6200 and DVC6205 Series (HART HW1 & HW2, SIS, FOUNDATION Fieldbus, PROFIBUS)
Class I, Division 1, Groups B,C,D ; Class I, Division 2, Groups A,B,C,D
Class II, Division 1, Groups E,F,G ; Class II, Division 2, Groups F,G
Class III, Division 1
Ex d IIC
Ex nC IIC
Type 4X, IP66
Single Seal Device (HART HW2 and SIS pending)
Rated input 30 Vmax, 20 mA
- 52_C < Ambient < + 80_C
Max inlet pressure 10 bar (145 psig) (air or natural gas)
Temperature Code: T6 (Tamb ≤ 75_C), T5 (Tamb ≤ 80_C)
DVC6215 Remote Mount
Class I, Division 1, Groups A,B,C,D ; Class I, Division 2, Groups A,B,C,D
Class II, Division 1, Groups E,F,G ; Class II, Division 2, Groups F,G
Class III, Division 1
Ex d IIC
Ex nA IIC
Type 4X, IP66
Rated input 30 Vmax, 20 mA
- 52_C < Ambient < + 125_C
Temperature Code: T6 (Tamb ≤ 75_ C), T5 (Tamb ≤ 90_C), T4 (Tamb ≤ 125_C)
D104203X012
Intrinsically Safe
Class I, Division 1, Groups A,B,C,D
Class II, Division 1, Groups E,F,G
Class III, Division 1
Ex ia IIC
Type 4X, IP66
Single Seal Device (HART HW2 and SIS pending)
Rated input 30 V DC max, 20 mA
- 52 _C < Ambient < + 80_C (-52_C to 125_C for DVC6215)
Max inlet pressure 10 bar (145 psig) (air or natural gas)
Intrinsically safe when connected per installation drawing GE42818, as shown in the following figures
DVC6200 HW2 and DVC6200 SIS figure 1 and 6...........................
DVC6205, DVC6205 SIS, and DVC6215 Remote Mount figure 2 and 6........
DVC6200f and DVC6200p figure 3 and 6.................................
DVC6205f, DVC6205p, and DVC6215 Remote Mount figure 4 and 6.........
DVC6200 HW1 figure 5 and 6...........................................
2

Instruction Manual Supplement
D104203X012
Figure 1. CSA Loop Schematics—FIELDVUE DVC6200 HW2 and DVC6200 SIS
DVC6200 Digital Valve Controllers
July 2017
CLASS I, ZONE 0, GROUP IIC
CLASS I, DIV 1, GROUPS ABCD
CLASS II, DIV 1, GROUPS EFG
CLASS III
HW2 - WITH OR WITHOUT I/O PACKAGE
DVC6200, DVC6200S
LOOP TERMINALS
Vmax = 30 VDC
Imax = 130 mA
Ci = 15 nF
Li = 0.55 mH
Pi = 1.0 W
OUTPUT TERMINALS
Vmax = 28 VDC
Imax = 100 mA
Ci = 15 nF
Li = 0.5 mH
Pi = 1.0 W
HAZARDOUS LOCATION
1 NOTE 7
NON‐HAZARDOUS LOCATION
CSA APPROVED BARRIER
NOTE 1, 3, 4, 5, 6 1
CSA APPROVED BARRIER
NOTE 1, 3, 4, 5, 6 1
POWER MAY BE APPLIED TO
EITHER THE LOOP TERMINALS OR
OUTPUT TERMINALS OR TO BOTH
SETS OF TERMINALS AT THE SAME
TIME
UNITS WITHOUT THE I/O PACKAGE
WILL NOT HAVE “OUTPUT
TERMINALS” AVAILABLE FOR
CONNECTION
T CODE T (amb) T (amb)
T5 ≤ 80_C ≤ 80_C
T6 ≤ 61_C ≤ 74_C
GE42818 Sheet 11, Rev. C
1 SEE NOTES IN FIGURE 6
WITH
I/O PACKAGE
WITHOUT
I/O PACKAGE
3