Fisher IM Supplement: CSA Hazardous Area Approvals - FIELDVUE DVC6200 Series Digital Valve Controllers Manuals & Guides

Instruction Manual Supplement
D104203X012
DVC6200 Digital Valve Controllers
July 2017
CSA Hazardous Area Approvals
Fisher
FIELDVUE™ DVC6200 Series
Digital Valve Controllers
Hazardous Area Approvals and Special Instructions for “Safe Use” and Installations in Hazardous Locations
Certain nameplates may carry more than one approval, and each approval may have unique installation/wiring requirements and/or conditions of “safe use”. These special instructions for “safe use” are in addition to, and may override, the standard installation procedures. Special instructions are listed by approval type.
Note
This information supplements the nameplate markings affixed to the product and the DVC6200 Series quick start guide (D103556X012
Always refer to the nameplate itself to identify the appropriate certification.
), available from your Emerson sales office or Local Business Partner, or at Fisher.com.
SIS
WARNING
Failure to follow these conditions of “safe use” could result in personal injury or property damage from fire or explosion and area re‐classification.
Ordinary Locations Approval
Complies with general electrical safety CAN/CSAC22.2 No. 6101012004
SELV, conduit connected, Enclosure Type 4X, IP66, Installation Category I, Pollution Degree 4
DVC6200 Series (HART HW1, F Rated Input 9-30 VDC, 4-20 mA
-52_C to + 80_C Ambient DVC6205 (HART HW1, F Rated Input 9-30 VDC, 4-20 mA Rated Input 10 VDC max, 3.5 mA max
Outputs 0-9.6 VDC, 0-3.5 mA -52 to 125_C Ambient-52_C to + 80_C Ambient
OUNDATION Fieldbus, PROFIBUS)
OUNDATION fieldbus, PROFIBUS) DVC6215 Remote Mount
www.Fisher.com
DVC6200 Digital Valve Controllers
July 2017
Instruction Manual Supplement
Explosion-proof and Dust Ignition-proof
DVC6200 and DVC6205 Series (HART HW1 & HW2, SIS, FOUNDATION Fieldbus, PROFIBUS)
Class I, Division 1, Groups B,C,D ; Class I, Division 2, Groups A,B,C,D Class II, Division 1, Groups E,F,G ; Class II, Division 2, Groups F,G Class III, Division 1 Ex d IIC Ex nC IIC Type 4X, IP66 Single Seal Device (HART HW2 and SIS pending)
Rated input 30 Vmax, 20 mA
- 52_C < Ambient < + 80_C Max inlet pressure 10 bar (145 psig) (air or natural gas) Temperature Code: T6 (Tamb 75_C), T5 (Tamb 80_C)
DVC6215 Remote Mount
Class I, Division 1, Groups A,B,C,D ; Class I, Division 2, Groups A,B,C,D Class II, Division 1, Groups E,F,G ; Class II, Division 2, Groups F,G Class III, Division 1 Ex d IIC Ex nA IIC Type 4X, IP66
Rated input 30 Vmax, 20 mA
- 52_C < Ambient < + 125_C Temperature Code: T6 (Tamb 75_ C), T5 (Tamb 90_C), T4 (Tamb 125_C)
D104203X012
Intrinsically Safe
Class I, Division 1, Groups A,B,C,D Class II, Division 1, Groups E,F,G Class III, Division 1 Ex ia IIC Type 4X, IP66 Single Seal Device (HART HW2 and SIS pending)
Rated input 30 V DC max, 20 mA
- 52 _C < Ambient < + 80_C (-52_C to 125_C for DVC6215) Max inlet pressure 10 bar (145 psig) (air or natural gas)
Intrinsically safe when connected per installation drawing GE42818, as shown in the following figures
DVC6200 HW2 and DVC6200 SIS figure 1 and 6...........................
DVC6205, DVC6205 SIS, and DVC6215 Remote Mount figure 2 and 6........
DVC6200f and DVC6200p figure 3 and 6.................................
DVC6205f, DVC6205p, and DVC6215 Remote Mount figure 4 and 6.........
DVC6200 HW1 figure 5 and 6...........................................
2
Instruction Manual Supplement
D104203X012
Figure 1. CSA Loop Schematics—FIELDVUE DVC6200 HW2 and DVC6200 SIS
DVC6200 Digital Valve Controllers
July 2017
CLASS I, ZONE 0, GROUP IIC CLASS I, DIV 1, GROUPS ABCD CLASS II, DIV 1, GROUPS EFG CLASS III
HW2 - WITH OR WITHOUT I/O PACKAGE DVC6200, DVC6200S
LOOP TERMINALS
Vmax = 30 VDC Imax = 130 mA Ci = 15 nF Li = 0.55 mH Pi = 1.0 W
OUTPUT TERMINALS
Vmax = 28 VDC Imax = 100 mA Ci = 15 nF Li = 0.5 mH Pi = 1.0 W
HAZARDOUS LOCATION
1 NOTE 7
NON‐HAZARDOUS LOCATION
CSA APPROVED BARRIER
NOTE 1, 3, 4, 5, 6 1
CSA APPROVED BARRIER
NOTE 1, 3, 4, 5, 6 1
POWER MAY BE APPLIED TO EITHER THE LOOP TERMINALS OR OUTPUT TERMINALS OR TO BOTH SETS OF TERMINALS AT THE SAME TIME
UNITS WITHOUT THE I/O PACKAGE WILL NOT HAVE “OUTPUT TERMINALS” AVAILABLE FOR CONNECTION
T CODE T (amb) T (amb)
T5 80_C 80_C
T6 61_C 74_C
GE42818 Sheet 11, Rev. C
1 SEE NOTES IN FIGURE 6
WITH
I/O PACKAGE
WITHOUT
I/O PACKAGE
3