Fisher IM Supplement: CSA Hazardous Area Approvals-FIELDVUE DVC6005 Series Remote Mount Digital Valve Controllers Manuals & Guides

Page 1
Instruction Manual Supplement
D104209X012
DVC6005 Digital Valve Controllers
August 2017
CSA Hazardous Area Approvals
Fisher
FIELDVUE™ DVC6005 Series
Remote Mount Digital Valve Controllers
Hazardous Area Approvals and Special Instructions for “Safe Use” and Installations in Hazardous Locations
Certain nameplates may carry more than one approval, and each approval may have unique installation/wiring requirements and/or conditions of “safe use”. These special instructions for “safe use” are in addition to, and may override, the standard installation procedures. Special instructions are listed by approval type.
Note
This information supplements the nameplate markings affixed to the product and the DVC6005 Series Remote Mount quick start guide (D103784X012
Approval information is for both aluminum and stainless steel constructions.
Always refer to the nameplate itself to identify the appropriate certification.
), available from your Emerson sales office, Local Business Partner or at Fisher.com.
WARNING
Failure to follow these conditions of “safe use” could result in personal injury or property damage from fire or explosion and area re‐classification.
Ordinary Locations Approval
Complies with general electrical safety CAN/CSAC22.2 No. 6101012004
SELV, conduit connected, Enclosure Type 4X, IP66, Installation Category I, Pollution Degree 4
DVC6005 Series (HART HW1, F Rated Input 9-30 VDC, 4-20 mA
Outputs 0-9.6 VDC, 0-3.5 mA-52_C Ambient +80_C
DVC6015, DVC6025, DVC6035 Rated Input 10 VDC max, 3.5 mA max
-60_C Ambient 125_C
OUNDATION fieldbus)
www.Fisher.com
Page 2
DVC6005 Digital Valve Controllers
August 2017
Explosion-proof and Dust Ignition-proof
Class I, Division 1, Groups B,C,D ; Class I, Division 2, Groups A,B,C,D Class II, Division 1, Groups E,F,G ; Class II, Division 2, Groups F,G Class III, Division 1 Ex d IIC Ex nC IIC (DVC6005 Series) Ex nA IIC (DVC6015, DVC6025, DVC6035) Type 4X, IP66 Single Seal Device (HART HW2 with I/O Package pending)
Instruction Manual Supplement
D104209X012
DVC6005 Series (HART HW1 & HW2, F
OUNDATION FIELDBUS)
Rated input 30 Vmax, 20 mA
- 52_C Ambient + 80_C Max inlet pressure 10 bar (145 psig) (air or natural gas) Temperature Code: T6 (Tamb 75_C), T5 (Tamb 80_C)
DVC6015, DVC6025, DVC6035
Rated input 10 Vmax, 5 mA
- 60_C Ambient + 125_C Temperature Code: T6 (Tamb 80_C), T5 (Tamb 95_C), T4 (Tamb 125_C)
Intrinsically Safe
Class I, Division 1, Groups A,B,C,D Class II, Division 1, Groups E,F,G Class III, Division 1 Ex ia IIC Type 4X, IP66 Single Seal Device (HART HW2 with I/O Package pending)
DVC6005 Series (HART HW1 & HW2, F
Rated input 30 V DC max, 20 mA
- 52_C Ambient + 80_C Max inlet pressure 10 bar (145 psig) (air or natural gas)
DVC6015, DVC6025, DVC6035
Rated input 10 Vmax, 5 mA
- 60_C Ambient + 125_C
Intrinsically safe when connected per installation drawing GE42818, as shown in the following figures
DVC6005 HW1 and DVC6015, DVC6025, DVC6035 figure 1 and 4...........
DVC6005 HW2 and DVC6015, DVC6025, DVC6035 figure 2 and 4...........
DVC6005f and DVC6015, DVC6025, DVC6035 figure 3 and 4................
OUNDATION FIELDBUS)
2
Page 3
Instruction Manual Supplement
DVC6005 Digital Valve Controllers
D104209X012
Figure 1. CSA Loop Schematics FIELDVUE DVC6005 HW1 and DVC6015, DVC6025, DVC6035
August 2017
CLASS I, ZONE 0, GROUP IIC CLASS I, DIV 1, GROUPS ABCD CLASS II, DIV 1, GROUPS EFG CLASS III
DVC6015, DVC6025, DVC6035
Vmax = 30 VDC Imax = 100 mA Ci = 0 uF Li = 0 mH Pi = 160 mW
NOTE 1
T CODE T (amb)
T4 125_C
T5 95_C
T6 80_C
1 SEE NOTES IN FIGURE 4
GE42818 Sheet 5, Rev. F
1
CLASS I, ZONE 0, GROUP IIC CLASS I, DIV 1, GROUPS ABCD CLASS II, DIV 1, GROUPS EFG CLASS III
DVC6005
Voc = 30 VDC Isc = 12 mA Ca = 66 nF La = 246 mH Po = 86 mW
Vmax = 30 VDC Imax = 226 mA Ci = 5 nF Li = 0.55 mH Pi = 1.4 W
T CODE T (amb)
T5 80_C
T6 75_C
HAZARDOUS LOCATION
NOTE 7
1
NON‐HAZARDOUS LOCATION
CSA APPROVED BARRIER
NOTE 1, 3, 4, 5, 6
1
3
Page 4
DVC6005 Digital Valve Controllers
Instruction Manual Supplement
August 2017
Figure 2. CSA Loop Schematics FIELDVUE DVC6005 HW2 and DVC6015, DVC6025, DVC6035
D104209X012
CLASS I, ZONE 0, GROUP IIC CLASS I, DIV 1, GROUPS ABCD CLASS II, DIV 1, GROUPS EFG CLASS III
DVC6015, DVC6025, DVC6035
Vmax = 30 VDC Imax = 100 mA Ci = 0 uF Li = 0 mH Pi = 160 mW
NOTE 1, 3
T CODE T (amb)
T4 125_C
T5 95_C
T6 80_C
1 SEE NOTES IN FIGURE 4
GE42818 Sheet 13, Rev. C
1
CLASS I, ZONE 0, GROUP IIC CLASS I, DIV 1, GROUPS ABCD CLASS II, DIV 1, GROUPS EFG CLASS III
HW2 - WITH OR WITHOUT I/O PACKAGE
DVC6005
REMOTE FIELD WIRING TERMINAL BOX
Voc = 30 VDC Isc = 21.2 mA Ca = 55 nF La = 78 mH Po = 160 mW
WITH
I/O PACKAGE
T CODE T (amb) T (amb)
T5 80_C 80_C
T6 61_C 74_C
HAZARDOUS LOCATION
FIELD WIRING TERMINAL BOX
LOOP TERMINALS
Vmax = 30 VDC Imax = 130 mA Ci = 15 nF Li = 0.55 mH Pi = 1.0 W
OUTPUT TERMINALS
Vmax = 28 VDC Imax = 100 mA Ci = 15 nF Li = 0.5 mH Pi = 1.0 W
WITHOUT
I/O PACKAGE
NOTE 7
1
NON‐HAZARDOUS LOCATION
CSA APPROVED BARRIER
NOTE 1, 3, 4, 5, 6
CSA APPROVED BARRIER
NOTE 1, 3, 4, 5, 6
POWER MAY BE APPLIED TO EITHER THE LOOP TERMINALS OR OUTPUT TERMINALS OR TO BOTH SETS OF TERMINALS AT THE SAME TIME
UNITS WITHOUT THE I/O PACKAGE WILL NOT HAVE “OUTPUT TERMINALS” AVAILABLE FOR CONNECTION
1
1
4
Page 5
Instruction Manual Supplement
DVC6005 Digital Valve Controllers
D104209X012
Figure 3. CSA Loop Schematics FIELDVUE DVC6005f and DVC6015, DVC6025, DVC6035
HAZARDOUS LOCATION
CLASS I, ZONE 0, GROUP IIC CLASS I, DIV 1, GROUPS ABCD CLASS II, DIV 1, GROUPS EFG CLASS III
DVC6005f
Voc = 24 VDC Isc = 17.5 mA Ca = 121 nF La = 100 mH Po = 105 mW
Vmax = 24 VDC Imax = 380 mA Ci = 5 nF Li = 0 mH Pi = 1.4 W
T CODE T (amb)
T4 80_C
T5 77_C T6 62_C
NOTE 7 1
CSA APPROVED ENTITY DEVICE
NOTE 1, 3
CLASS I, ZONE 0, GROUP IIC CLASS I, DIV 1, GROUPS ABCD CLASS II, DIV 1, GROUPS EFG CLASS III
DVC6015, DVC6025,
DVC6035 Vmax = 30 VDC Imax = 100 mA Ci = 0 uF Li = 0 mH Pi = 160 mW
NOTE 1 1
1
T CODE T (amb)
T4 125_C
T5 95_C
T6 80_C
August 2017
NON‐HAZARDOUS LOCATION
CSA APPROVED BARRIER
1 NOTE 1, 3, 4, 5, 6
GE42818 Sheet 6, Rev. F
CSA APPROVED FISCO TERMINATOR
GE42818 Sheet 7, Rev. F
CSA APPROVED FISCO DEVICE
NOTE 2, 3
CLASS I, ZONE 0, GROUP IIC CLASS I, DIV 1, GROUPS ABCD CLASS II, DIV 1, GROUPS EFG CLASS III
DVC6015, DVC6025,
DVC6035 Vmax = 30 VDC Imax = 100 mA Ci = 0 uF Li = 0 mH Pi = 160 mW
1
T CODE T (amb)
NOTE 2
1
T4 125_C T5 95_C T6 80_C
ENTITY FIELDBUS LOOP
CLASS I, ZONE 0, GROUP IIC CLASS I, DIV 1, GROUPS ABCD CLASS II, DIV 1, GROUPS EFG CLASS III
DVC6005f
Voc = 17.5 VDC Isc = 17.5 mA Ca = 121 nF La = 100 mH Po = 105 mW
T CODE T (amb)
T4 80_C T5 77_C
T6 62_C
HAZARDOUS LOCATION
Vmax = 17.5 VDC Imax = 380 mA Ci = 5 nF Li = 0 mH Pi = 5.32 W
NON‐HAZARDOUS LOCATION
CSA APPROVED FISCO BARRIER
1
NOTE 2, 3, 4, 5, 6
1 SEE NOTES IN FIGURE 4
FISCO LOOP
5
Page 6
DVC6005 Digital Valve Controllers
August 2017
Instruction Manual Supplement
D104209X012
Figure 4. Notes for CSA Loop Schematics
THE ENTITY CONCEPT ALLOWS INTERCONNECTION OF INTRINSICALLY SAFE APPARATUS TO ASSOCIATED APPARATUS NOT
SPECIFICALLY EXAMINED IN SUCH COMBINATION. THE CRITERIA FOR INTERCONNECTION IS THAT THE VOLTAGE (Vmax or Ui), THE CURRENT (Imax or Ii), AND THE POWER (Pmax or Pi) OF THE INTRINSICALLY SAFE APPARATUS MUST BE EQUAL TO OR GREATER THAN THE VOLTAGE (Voc or Uo), AND THE CURRENT (Isc or Io), AND THE POWER(Po) DEFINED BY THE ASSOCIATED APPARATUS. IN ADDITION, THE SUM OF THE MAX UNPROTECTED CAPACITANCE (Ci) AND MAX UNPROTECTED INDUCTANCE (Li), INCLUDING THE INTERCONNECTING CABLING CAPACITANCE (Ccable) AND CABLING INDUCTANCE (Lcable) MUST BE LESS THAN THE ALLOWABLE CAPACITANCE (Ca) AND INDUCTANCE (La) DEFINED BY THE ASSOCIATED APPARATUS. IF THE ABOVE CRITERIA IS MET, THEN THE COMBINATION MAY BE CONNECTED.
Vmax or Ui . Voc or Uo Imax or Ii . Isc or Io Pmax or Pi . Po Ci + Ccable Ca Li + Lcable La
THE FISCO CONCEPT ALLOWS INTERCONNECTION OF INTRINSICALLY SAFE APPARATUS TO ASSOCIATED APPARATUS NOT
SPECIFICALLY EXAMINED IN SUCH COMBINATION. THE CRITERIA FOR THE INTERCONNECTION IS THAT THE VOLTAGE (Vmax or Ui), CURRENT (Imax or Ii), AND POWER (Pmax or Pi), WHICH AN INTRINSICALLY SAFE APPARATUS CAN RECEIVE AND REMAIN INTRINSICALLY SAFE, CONSIDERING FAULTS, MUST BE EQUAL TO OR GREATER THAN THE VOLTAGE (Voc or Uo), CURRENT (Isc or Io), AND POWER (Po) LEVELS WHICH CAN BE DELIVERED BY THE ASSOCIATED APPARATUS, CONSIDERING FAULTS AND APPLICABLE FACTORS. IN ADDITION THE MAXIMUM UNPROTECTED CAPACITANCE (Ci) AND INDUCTANCE (Li) OF EACH APPARATUS (OTHER THAN THE TERMINATION) CONNECTED TO THE FIELDBUS MUST BE LESS THAN OR EQUAL TO 5 nF AND 10 uH RESPECTIVELY.
IN EACH SEGMENT ONLY ONE ACTIVE DEVICE, NORMALLY THE ASSOCIATED APPARATUS, IS ALLOWED TO PROVIDE THE NECESSARY ENERGY FOR THE FIELDBUS SYSTEM. THE VOLTAGE (Uo or Voc or Vt) OF THE ASSOCIATED APPARATUS HAS TO BE LIMITED TO THE RANGE OF 9 V TO 17.5 VDC. ALL OTHER EQUIPMENT CONNECTED TO THE BUS CABLE HAS TO BE PASSIVE, MEANING THAT THEY ARE NOT ALLOWED TO PROVIDE ENERGY TO THE SYSTEM, EXCEPT FOR A LEAKAGE CURRENT OF 50 uA FOR EACH CONNECTED DEVICE. SEPARATELY POWERED EQUIPMENT NEEDS A GALVANIC ISOLATION TO ASSURE THAT THE INTRINSICALLY SAFE FIELDBUS CIRCUIT REMAINS PASSIVE.
THE CABLE USED TO CONNECT THE DEVICES NEEDS TO HAVE THE PARAMETERS IN THE FOLLOWING RANGE:
LOOP RESISTANCE R': 15 TO 150 ohms/km INDUCTANCE PER UNIT LENGTH L: 0.4 TO 1 mH/km CAPACITANCE PER UNIT LENGTH C': 80 TO 200 nF/km C' = C' LINE/LINE + 0.5' LINE/SCREEN, IF BOTH LINES ARE FLOATING OR C' = C' LINE/LINE + C' LINE/SCREEN, IF THE SCREEN IS CONNECTED TO ONE LINE. LENGTH OF SPLICE: < 1 m (T‐BOX MUST ONLY CONTAIN TERMINAL CONNECTIONS WITH NO ENERGY STORAGE CAPABILITY) LENGTH OF SPUR CABLE: < 30 M LENGTH OF TRUNK CABLE: < 1 km
AT EACH END OF THE TRUNK CABLE AN APPROVED INFALLIBLE TERMINATION WITH THE FOLLOWING PARAMETERS IS SUITABLE: R = 90 TO 100 ohms AND C = 0 TO 2.2 uF NOTE, A BUILT‐IN TERMINATOR IS INCLUDED IN THE FIELD SIDE AND A SELECTABLE TERMINATOR IS AVAILABLE ON THE HOST SIDE.
THE NUMBER OF PASSIVE DEVICES CONNECTED TO THE BUS SEGMENT IS NOT LIMITED IN THE FISCO CONCEPT FOR INTRINSICALLY SAFE REASONS. IF THE ABOVE RULES ARE RESPECTED, UP TO A TOTAL LENGTH OF 1000 m (SUM OF THE LENGTH OF THE TRUNK CABLE AND ALL SPUR CABLES), THE INDUCTANCE AND CAPACITANCE OF THE CABLE WILL NOT IMPAIR THE INTRINSIC SAFETY OF THE INSTALLATION.
INSTALLATION MUST BE IN ACCORDANCE WITH THE CANADIAN ELECTRICAL CODE (CEC) AND ANSI/ISA RP12.6.
MAXIMUM SAFE AREA VOLTAGE SHOULD NOT EXCEED 250 Vrms.
RESISTANCE BETWEEN INTRINSICALLY SAFE GROUND AND EARTH GROUND MUST BE LESS THAN ONE OHM
LOOPS MUST BE CONNECTED ACCORDING TO THE BARRIER MANUFACTURER'S INSTRUCTIONS.
IF HAND‐HELD COMMUNICATOR OR MULTIPLEXER IS USED, IT MUST BE CSA APPROVED WITH ENTITY PARAMETERS AND INSTALLED
PER THE MANUFACTURER'S CONTROL DRAWINGS.
GE42818 Sheet 8, Rev. E
6
Page 7
Instruction Manual Supplement
D104209X012
DVC6005 Digital Valve Controllers
August 2017
7
Page 8
DVC6005 Digital Valve Controllers
August 2017
Instruction Manual Supplement
D104209X012
Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Fisher and FIELDVUE are marks owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. Emerson Automation Solutions, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.
Emerson Automation Solutions
Marshalltown, Iowa 50158 USA Sorocaba, 18087 Brazil Cernay, 68700 France Dubai, United Arab Emirates Singapore 128461 Singapore
www.Fisher.com
8
E 2016, 2017 Fisher Controls International LLC. All rights reserved.