Control Schematics for FIELDVUE™ DVC6200 SIS
Digital Valve Controller
The below drawings are guidelines ONLY, and should be modified/changed for site specific conditions. The guidelines
are not specific to individual user needs, applications, process conditions, environmental conditions, or safe state
functions and should be finalized in consultation with your local impact partner before implementation. References to
the make and model number of specified third party vendor products is not to be construed as an endorsement from
Emerson —Fisher Controls International LLC.
For clarification or consultation, please contact your Emerson sales office
The attached schematics provide examples of a DVC6200 SIS in different modes (point-to-point mode or multidrop
mode). The DVC6200 SIS can operate through a command signal from either a DCS (basic process control system,
BPCS) or logic solver (safety instrumented system, SIS). These are basic schematics that have been developed to
provide details of the connections between the control system and user interface. Drawings indicated as “PST Only”
depict the use of a DVC6200 SIS with a reverse acting relay (relay B).
These drawings are for reference ONLY and it may be possible to have many different combinations or permutations of
such schematics.
who will consult Fisher Global Industry Sales.
www.Fisher.com
DVC6200 SIS
February 2022
Instruction Manual Supplement
D103858X012
DISPLAY ALARMS
ESDV STATUS
IN PROGRESS
SERIAL
IN OUT
PST Abnormal
PST Pass
Options Available:
LCP200 Local Control Panel or
external pushbutton
SIL 2 Capable 420 mA position
transmitter or discrete switch
Discrete switch can be configured
for position or alert annunciation
AI or DI*
OUT IN
Benefits:
SIL 3 Capable digital valve controller
Valve Shutdown and PST capability
PST with DVC6200 SIS provides
diagnostic coverage
Optional
Position Feedback
(420 mA Analog
or 1 A Discrete Switch)
DO
LC340
HART
ValveLink
Software
IN OUT
™
MULTIPLEXER**
BPCS SIS FIELD
Scenario 1: SIS with DO to DETT FIELDVUE DVC6200 SIS
Example Drawing Only, may require modifications to meet site specific requirements
*Position Monitor AI or DI may reside in SIS or BPCS
**PC with ValveLink software or Emerson Field Communicator can be used in lieu of multiplexer
024V DC + HART
Notes:
Loss of electrical power or pneumatic
supply to DVC6200 SIS exhausts air to valve
Trigger diagnostics or capture of
demand/reset strokes unavailable since
power to DVC6200 SIS is interrupted during
a demand
Instrument
Instrument
Air Output
Air Supply
Optional LCP200 or
External Pushbutton PST
2
Instruction Manual Supplement
D103858X012
DVC6200 SIS
February 2022
DISPLAY ALARMS
ESDV STATUS
IN PROGRESS
SERIAL
IN OUT
PST Abnormal
PST Pass
Options Available:
LCP200 Local Control Panel or
external pushbutton
SIL 2 Capable 420 mA position
transmitter or discrete switch
Discrete switch can be configured
for position or alert annunciation
AI or DI*
OUT IN
Benefits:
SIL 3 Capable digital valve controller
Valve Shutdown and PST capability
PST with DVC6200 SIS provides
diagnostic coverage
Optional
Position Feedback
(420 mA Analog
or 1 A Discrete Switch)
Non-HART AO
HF341/
IN OUT
ValveLink
Software
HF340***
HART
4-20 mA + HART
MULTIPLEXER**
BPCS SIS FIELD
Scenario 2: SIS with AO to DETT DVC6200 SIS
Example Drawing Only, may require modifications to meet site specific requirements
*Position Monitor AI or DI may reside in SIS or BPCS
**PC with ValveLink software or Emerson Field Communicator can be used in lieu of multiplexer
***HF341/HF340 may be required with legacy hosts to provide proper impedance to support HARTr communication
Notes:
Loss of electrical power or pneumatic
supply to DVC6200 SIS exhausts air to valve
-8 mA minimum is required when the
LPC200 is loop powered
Instrument
Instrument
Air Output
Air Supply
Optional LCP200 or
External Pushbutton PST
3
DVC6200 SIS
February 2022
Instruction Manual Supplement
D103858X012
DISPLAY ALARMS
ESDV STATUS
IN PROGRESS
PST Abnormal
PST Pass
Options Available:
LCP200 Local Control Panel or
external pushbutton
SIL 2 Capable 420 mA position
transmitter or discrete switch
Discrete switch can be configured
for position or alert annunciation
Benefits:
SIL 3 Capable digital valve controller
Valve Shutdown and PST capability
PST with DVC6200 SIS provides
diagnostic coverage
Trigger diagnostics capture
shutdown event and reset
AI or DI*
OUT IN
HART AO
IN OUT
HART Pass Through
4-20 mA + HART
ValveLink
Software
BPCS SIS FIELD
Asset Management System
Scenario 3: SIS with HART I/O to DETT DVC6200 SIS
Example Drawing Only, may require modifications to meet site specific requirements
*Position Monitor AI or DI may reside in SIS or BPCS
Notes:
Loss of electrical power or pneumatic
supply to DVC6200 SIS exhausts air to valve
-8 mA minimum is required when the
LPC200 is loop powered
Optional Position Feedback
(420 mA Analog
or 1 A Discrete Switch)
Instrument
Air Output
Instrument
Air Supply
Optional LCP200 or
External Pushbutton PST
4
Instruction Manual Supplement
D103858X012
DVC6200 SIS
February 2022
DISPLAY ALARMS
ESDV STATUS
IN PROGRESS
SERIAL
IN OUT
Non-HART AO
IN OUT
PST Abnormal
PST Pass
4-20 mA
HF341/
HF340***
HART
Options Available:
LCP200 Local Control Panel or
external pushbutton
SIL 2 Capable 420 mA position
transmitter or discrete switch
Discrete switch can be configured
for position or alert annunciation
IN OUT
AI or DI*
OUT IN
4-20 mA + HART
Benefits:
Prevents spurious trips on loss of
electrical power to DVC6200 SIS
PST with DVC6200 SIS provides
diagnostic coverage
Trigger diagnostics captures safety
demand and reset
‐Solenoid health monitoring
DO
Optional Position Feedback
(420 mA Analog
or 1 A Discrete Switch)
0-24 V DC
Notes:
‐DVC6200 SIS with Relay B in ETT
configuration for PST diagnostic only
Loss of pneumatic supply to DVC6200 SIS
exhausts air to valve
-8 mA minimum is required when the
LPC200 is loop powered
Instrument
Air Supply
Actuator
Pressure
Sensing
MULTIPLEXER**
ValveLink
Software
BPCS SIS FIELD
Scenario 4: SIS with DO to DETT Solenoid BPCS with AO to DVC6200 SIS (PST Only)
Y
Optional
LCP200 or
External
Pushbutton
PST
Instrument
Air Output
Y
S
Example Drawing Only, may require modifications to meet site specific requirements
*Position Monitor AI or DI may reside in SIS or BPCS
**PC with ValveLink software or Emerson Field Communicator can be used in lieu of multiplexer
***HF341/HF340 may be required with legacy hosts to provide proper impedance to support HART communication
5
DVC6200 SIS
February 2022
Instruction Manual Supplement
D103858X012
DISPLAY ALARMS
ESDV STATUS
IN PROGRESS
SERIAL
IN OUT
PST Abnormal
PST Pass
Options Available:
LCP200 Local Control Panel or
external pushbutton
SIL 2 Capable 420 mA position
transmitter or discrete switch
Discrete switch can be configured
for position or alert annunciation
IN OUT
Benefits:
PST with DVC6200 SIS provides diagnostic
coverage
Trigger diagnostics captures safety demand
and reset
‐Solenoid valve test diagnostics and
evaluation
DO
0-24 V DC
Non-HART AO
4-20 mA
IN OUT
HART
HF341/
HF340***
Actuator
Pressure
Sensing
MULTIPLEXER**
4-20 mA + HART
ValveLink
Software
BPCS SIS FIELD
Scenario 4.1: SIS with DO to DETT Solenoid for Solenoid Valve Testing
BPCS with AO to DVC6200 SIS (PST Only)
Example Drawing Only, may require modifications to meet site specific requirements
**PC with ValveLink software or Emerson Field Communicator can be used in lieu of multiplexer
***HF341/HF340 may be required with legacy hosts to provide proper impedance to support HART communication
Notes:
‐DVC6200 SIS with Relay B in
ETT configuration for PST diagnostic
only
Loss of pneumatic supply to
DVC6200 SIS exhausts air to valve
-8 mA minimum is required when the
LPC200 is loop powered
Instrument
Y
Optional
LCP200 or
External
Pushbutton
PST
Air Output
0-24 V DC
S
Y
Instrument
Air Supply
6
Instruction Manual Supplement
D103858X012
DVC6200 SIS
February 2022
DISPLAY ALARMS
ESDV STATUS
IN PROGRESS
PST Abnormal
PST Pass
Options Available:
LCP200 Local Control Panel or
external pushbutton
Integral 4-20 mA position
transmitter or discrete switch
Benefits:
Prevents spurious trip on loss of
electrical power to DVC6200 SIS
Trigger diagnostics captures safety
demand and reset
PST with DVC6200 SIS provides
diagnostic coverage
‐Solenoid health monitoring
DO
IN OUT
AI or DI*
OUT IN
0-24 V DC
Optional Position Feedback
(420 mA Analog
or 1 A Discrete Switch)
HART AO
IN OUT
4-20 mA + HART
ValveLink
Software
BPCS SIS FIELD
Asset Management System
Scenario 5: SIS with DO to SOV BPCS with HART I/O to DVC6200 SIS (PST Only)
Example Drawing Only, may require modifications to meet site specific requirements
*Position Monitor AI or DI may reside in SIS or BPCS
Notes:
‐DVC6200 SIS with Relay B in ETT
configuration for PST diagnostic only
Loss of pneumatic supply to DVC6200 SIS
exhausts air to valve
-8 mA minimum is required when the
LPC200 is loop powered
Instrument
Air Output
Y
Optional
LCP200 or
External
Pushbutton
PST
Y
Actuator
Pressure
Sensing
Instrument
Air Supply
S
7
DVC6200 SIS
February 2022
Instruction Manual Supplement
D103858X012
DISPLAY ALARMS
ESDV STATUS
IN PROGRESS
PST Abnormal
PST Pass
Options Available:
LCP200 Local Control Panel or
external pushbutton
Integral 4-20 mA position
transmitter or discrete switch
Benefits:
Trigger diagnostics captures safety
demand and reset
PST with DVC6200 SIS provides
diagnostic coverage
‐Solenoid valve test diagnostics and evaluation
Notes:
‐ DVC6200 SIS with Relay B in ETT
configuration for PST diagnostic
only
Loss of pneumatic supply to
DVC6200 SIS exhausts air to valve
-8 mA minimum is required when
the LPC200 is loop powered
DO
IN OUT
HART AO
IN OUT
4-20 mA + HART
ValveLink
Software
BPCS SIS FIELD
Asset Management System
0-24 V DC
Actuator
Pressure
Sensing
Instrument
Air Supply
Y
Instrument
Air Output
Optional
LCP200 or
External
Pushbutton
PST
0-24 V DC
S
Y
Scenario 5.1: SIS with DO and HART I/O to DVC6200 SIS for PST and Solenoid Valve Testing
Example Drawing Only, may require modifications to meet site specific requirements
8
Instruction Manual Supplement
D103858X012
DVC6200 SIS
February 2022
DISPLAY ALARMS
ESDV STATUS
IN PROGRESS
PST Abnormal
PST Pass
Options Available:
LCP200 Local Control Panel or
external pushbutton
Integral 4-20 mA position
transmitter or discrete switch
Benefits:
Prevents spurious trip on loss of
electrical power to DVC6200 SIS
Trigger diagnostics captures safety
demand and reset
PST with DVC6200 SIS provides
diagnostic coverage
‐Solenoid Health Monitoring
Notes:
‐DVC6200 SIS with Relay B in ETT
configuration for PST diagnostic
only
Loss of pneumatic supply to
DVC6200 SIS exhausts air to valve
-DeltaV SIS Solution
-8 mA minimum is required when
the LPC200 is loop powered
DO
IN OUT
Non-SIL Rated
HART AO* **
IN OUT
8-20 mA + HART
ValveLink
Software
BPCS SIS FIELD
Asset Management System
0-24 V DC
Actuator
Pressure
Sensing
Instrument
Air Supply
Y
Instrument
Air Output
Optional
LCP200 or
External
Pushbutton
PST
Scenario 5.2: SIS with DO to SOV Non-SIL Rated HART AO to DVC6200 SIS (PST Only)
Example Drawing Only, may require modifications to meet site specific requirements
*PST Initiation from VaveLink software
** With Relay B scheme, on demand trip of the SIS DO from 24 V to 0 V, the non-SIL rated AO is configured
** to switch current from 8 mA to 20 mA and revert back to 8 mA to DVC6200 SIS upon DO reset to 24 V.
S
Y
9
DVC6200 SIS
February 2022
Instruction Manual Supplement
D103858X012
DISPLAY ALARMS
ESDV STATUS
IN PROGRESS
PST Abnormal
PST Pass
Options Available:
LCP200 Local Control Panel or
external pushbutton
SIL 2 Capable 420 mA position
transmitter or discrete switch
Discrete switch can be configured
for position or alert annunciation
Benefits:
SIL3 Capable digital valve controller
‐Redundant DVC6200 SIS and SOV
Trigger diagnostics captures safety
demand and reset
PST with DVC6200 SIS provides
diagnostic coverage
‐Solenoid health monitoring
DO
IN OUT
AI or DI*
OUT IN
Optional Position Feedback
(420 mA Analog or
1 A Discrete Switch)
HART AO
ValveLink
Software
BPCS SIS FIELD
Asset Management System
HART Pass Through
IN OUT
4-20 mA + HART
Scenario 6: SIS with HART I/O to DETT DVC6200 SIS SIS DO to DETT Solenoid
Example Drawing Only, may require modifications to meet site specific requirements
*Position Monitor AI or DI may reside in SIS or BPCS
0-24 V DC
Notes:
Loss of electrical power or
pneumatic supply to DVC6200 SIS
exhausts air to valve
-8 mA minimum is required when
the LPC200 is loop powered
Instrument
Air Output
S
Instrument
Y
Air Supply
Actuator Pressure
Sensing
Optional
LCP200 or
External
Pushbutton
PST
10
Instruction Manual Supplement
D103858X012
DVC6200 SIS
February 2022
DISPLAY ALARMS
ESDV STATUS
IN PROGRESS
PST Abnormal
PST Pass
Options Available:
LCP200 Local Control Panel or
external pushbutton
SIL 2 Capable 420 mA position
transmitter or discrete switch
Discrete switch can be configured
for position or alert annunciation
Benefits:
SIL3 Capable digital valve controller
‐Redundant DVC6200 SIS and SOV
Trigger diagnostics captures safety demand
and reset
PST with DVC6200 SIS provides diagnostic
coverage
‐Solenoid valve test diagnostics and evaluation
Notes:
Loss of electrical power or
pneumatic supply to DVC6200 SIS
exhausts air to valve
-8 mA minimum is required when
the LPC200 is loop powered
DO
IN OUT
0-24 V DC
0-24 V DC
S
Instrument
Air Output
Y
HART AO
ValveLink
Software
BPCS SIS FIELD
Asset Management System
HART Pass Through
IN OUT
4-20 mA + HART
Scenario 6.1: SIS with HART I/O to DETT DVC6200 SIS for Solenoid Valve Testing
SIS DO to DETT Solenoid
Instrument
Air Supply
Actuator Pressure
Sensing
Optional
LCP200 or
External
Pushbutton
PST
11
DVC6200 SIS
February 2022
Instruction Manual Supplement
D103858X012
DISPLAY ALARMS
ESDV STATUS
IN PROGRESS
SERIAL
IN OUT
PST Abnormal
PST Pass
Options Available:
LCP200 Local Control Panel or
external pushbutton
SIL 2 Capable 420 mA position
transmitter or discrete switch
Discrete switch can be configured
for position or alert annunciation
AI or DI*
OUT IN
Benefits:
SIL3 Capable digital valve controller
‐Redundant DVC6200 SIS and SOV
Wiring to both SOV and DVC6200 SIS
saves I/O
PST with DVC6200 SIS provides
diagnostic coverage
Optional Position Feedback
(420 mA Analog
or 1 A Discrete Switch)
DO
IN OUT
ValveLink
Software
LC340
HART
MULTIPLEXER**
BPCS SIS FIELD
Scenario 7: SIS with single DO to DETT DVC6200 SIS and DETT SOV
Example Drawing Only, may require modifications to meet site specific requirements
*Position Monitor AI or DI may reside in SIS or BPCS
**PC with ValveLink software or Emerson Field Communicator can be used in lieu of multiplexer
0-24 V DC
Notes:
Loss of electrical power or pneumatic
supply to DVC6200 SIS exhausts air to valve
‐Single DO is a common cause failure point
Trigger diagnostics or capture of
demand/reset strokes unavailable since
power to DVC6200 SIS is interrupted during
a demand
Instrument
Air Output
S
Y
Optional
LCP200 or
External
Pushbutton
PST
Instrument
Air Supply
12
Instruction Manual Supplement
D103858X012
DVC6200 SIS
February 2022
DISPLAY ALARMS
ESDV STATUS
IN PROGRESS
PST Abnormal
PST Pass
Options Available:
LCP200 Local Control Panel or
external pushbutton
SIL 2 Capable 420 mA position
transmitter or discrete switch
Discrete switch can be configured
for position or alert annunciation
Benefits:
SIL3 Capable digital valve controller
‐Redundant DVC6200 SIS and SOV
PST with DVC6200 SIS provides
diagnostic coverage
‐Solenoid health monitoring
DO
SERIAL
IN OUT
IN OUT
AI or DI*
OUT IN
Optional Position Feedback
(420 mA Analog
or 1 A Discrete Switch)
0-24 V DC
DO
ValveLink
Software
IN OUT
LC340
HART
MULTIPLEXER**
BPCS SIS FIELD
Scenario 8: SIS with separate DO to DETT DVC6200 SIS and DETT SOV
Example Drawing Only, may require modifications to meet site specific requirements
*Position Monitor AI or DI may reside in SIS or BPCS
**PC with ValveLink Software or Emerson Field Communicator can be used in lieu of multiplexer
0-24 V DC + HART
Notes:
Loss of electrical power or pneumatic
supply to DVC6200 SIS exhausts air to valve
Trigger diagnostics or capture of
demand/reset strokes unavailable since
power to DVC6200 SIS is interrupted during
a demand
Instrument
Air Output
S
Instrument
Y
Air Supply
Actuator Pressure
Sensing
Optional LCP200 or
External Pushbutton PST
13
DVC6200 SIS
February 2022
Instruction Manual Supplement
D103858X012
DISPLAY ALARMS
ESDV STATUS
IN PROGRESS
PST Abnormal
PST Pass
Options Available:
LCP200 Local Control Panel or
external pushbutton
SIL 2 Capable 420 mA position
transmitter or discrete switch
Discrete switch can be configured
for position or alert annunciation
Benefits:
SIL3 Capable digital valve controller
‐Redundant DVC6200 SIS and SOV
PST with DVC6200 SIS provides
diagnostic coverage
‐Solenoid valve test diagnostics and
evaluation
SERIAL
IN OUT
DO
OUT IN
0-24 V DC
DO
ValveLink
Software
IN OUT
LC340
HART
0-24 V DC + HART
MULTIPLEXER**
BPCS SIS FIELD
Scenario 8.1: SIS with separate DO to DETT DVC6200 SIS and DETT SOV
for Solenoid Valve Testing
Example Drawing Only, may require modifications to meet site specific requirements
**PC with ValveLink Software or Emerson Field Communicator can be used in lieu of multiplexer
Notes:
Loss of electrical power or pneumatic
supply to DVC6200 SIS exhausts air to valve
Trigger diagnostics or capture of
demand/reset strokes unavailable since
power to DVC6200 SIS is interrupted during
a demand
0-24 V DC
S
Instrument Air Output
Instrument
Y
Air Supply
Actuator Pressure
Sensing
Optional LCP200 or
External Pushbutton PST
Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance
of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Fisher, FIELDVUE, and ValveLink are marks owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co.
Emerson Automation Solutions, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. HART is a registered trademark of
FieldComm Group. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not
to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are
governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such
products at any time without notice.
Emerson Automation Solutions
Marshalltown, Iowa 50158 USA
Sorocaba, 18087 Brazil
Cernay, 68700 France
Dubai, United Arab Emirates
Singapore 128461 Singapore
www.Fisher.com
14
E 2014, 2022 Fisher Controls International LLC. All rights reserved.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.