Fisher IM Supplement: Control Schematics for FIELDVUE DVC6200 SIS Digital Valve Controller Manuals & Guides

Instruction Manual Supplement
D103858X012
DVC6200 SIS
February 2022
Control Schematics for FIELDVUE™ DVC6200 SIS Digital Valve Controller
The below drawings are guidelines ONLY, and should be modified/changed for site specific conditions. The guidelines are not specific to individual user needs, applications, process conditions, environmental conditions, or safe state functions and should be finalized in consultation with your local impact partner before implementation. References to the make and model number of specified third party vendor products is not to be construed as an endorsement from Emerson —Fisher Controls International LLC.
For clarification or consultation, please contact your Emerson sales office
The attached schematics provide examples of a DVC6200 SIS in different modes (point-to-point mode or multidrop mode). The DVC6200 SIS can operate through a command signal from either a DCS (basic process control system, BPCS) or logic solver (safety instrumented system, SIS). These are basic schematics that have been developed to provide details of the connections between the control system and user interface. Drawings indicated as “PST Only” depict the use of a DVC6200 SIS with a reverse acting relay (relay B).
These drawings are for reference ONLY and it may be possible to have many different combinations or permutations of such schematics.
who will consult Fisher Global Industry Sales.
www.Fisher.com
DVC6200 SIS
February 2022
Instruction Manual Supplement
D103858X012
DISPLAY ALARMS
ESDV STATUS
IN PROGRESS
SERIAL
IN OUT
PST Abnormal
PST Pass
Options Available:
LCP200 Local Control Panel or external pushbutton SIL 2 Capable 420 mA position transmitter or discrete switch Discrete switch can be configured for position or alert annunciation
AI or DI*
OUT IN
Benefits:
SIL 3 Capable digital valve controller Valve Shutdown and PST capability PST with DVC6200 SIS provides diagnostic coverage
Optional Position Feedback (420 mA Analog or 1 A Discrete Switch)
DO
LC340
HART
ValveLink
Software
IN OUT
MULTIPLEXER**
BPCS SIS FIELD
Scenario 1: SIS with DO to DETT FIELDVUE DVC6200 SIS
Example Drawing Only, may require modifications to meet site specific requirements
*Position Monitor AI or DI may reside in SIS or BPCS **PC with ValveLink software or Emerson Field Communicator can be used in lieu of multiplexer
024V DC + HART
Notes:
Loss of electrical power or pneumatic supply to DVC6200 SIS exhausts air to valve Trigger diagnostics or capture of demand/reset strokes unavailable since power to DVC6200 SIS is interrupted during a demand
Instrument
Instrument Air Output
Air Supply
Optional LCP200 or
External Pushbutton PST
2
Instruction Manual Supplement
D103858X012
DVC6200 SIS
February 2022
DISPLAY ALARMS
ESDV STATUS
IN PROGRESS
SERIAL
IN OUT
PST Abnormal
PST Pass
Options Available:
LCP200 Local Control Panel or external pushbutton SIL 2 Capable 420 mA position transmitter or discrete switch Discrete switch can be configured for position or alert annunciation
AI or DI*
OUT IN
Benefits:
SIL 3 Capable digital valve controller Valve Shutdown and PST capability PST with DVC6200 SIS provides diagnostic coverage
Optional Position Feedback (420 mA Analog or 1 A Discrete Switch)
Non-HART AO
HF341/
IN OUT
ValveLink
Software
HF340***
HART
4-20 mA + HART
MULTIPLEXER**
BPCS SIS FIELD
Scenario 2: SIS with AO to DETT DVC6200 SIS
Example Drawing Only, may require modifications to meet site specific requirements
*Position Monitor AI or DI may reside in SIS or BPCS **PC with ValveLink software or Emerson Field Communicator can be used in lieu of multiplexer ***HF341/HF340 may be required with legacy hosts to provide proper impedance to support HARTr communication
Notes:
Loss of electrical power or pneumatic supply to DVC6200 SIS exhausts air to valve
-8 mA minimum is required when the LPC200 is loop powered
Instrument Instrument Air Output
Air Supply
Optional LCP200 or
External Pushbutton PST
3
DVC6200 SIS
February 2022
Instruction Manual Supplement
D103858X012
DISPLAY ALARMS
ESDV STATUS
IN PROGRESS
PST Abnormal
PST Pass
Options Available:
LCP200 Local Control Panel or external pushbutton SIL 2 Capable 420 mA position transmitter or discrete switch Discrete switch can be configured for position or alert annunciation
Benefits:
SIL 3 Capable digital valve controller Valve Shutdown and PST capability PST with DVC6200 SIS provides diagnostic coverage Trigger diagnostics capture shutdown event and reset
AI or DI*
OUT IN
HART AO
IN OUT
HART Pass Through
4-20 mA + HART
ValveLink
Software
BPCS SIS FIELD
Asset Management System
Scenario 3: SIS with HART I/O to DETT DVC6200 SIS
Example Drawing Only, may require modifications to meet site specific requirements
*Position Monitor AI or DI may reside in SIS or BPCS
Notes:
Loss of electrical power or pneumatic supply to DVC6200 SIS exhausts air to valve
-8 mA minimum is required when the LPC200 is loop powered
Optional Position Feedback (420 mA Analog or 1 A Discrete Switch)
Instrument Air Output
Instrument Air Supply
Optional LCP200 or
External Pushbutton PST
4
Instruction Manual Supplement
D103858X012
DVC6200 SIS
February 2022
DISPLAY ALARMS
ESDV STATUS
IN PROGRESS
SERIAL
IN OUT
Non-HART AO
IN OUT
PST Abnormal
PST Pass
4-20 mA
HF341/ HF340***
HART
Options Available:
LCP200 Local Control Panel or external pushbutton SIL 2 Capable 420 mA position transmitter or discrete switch Discrete switch can be configured for position or alert annunciation
IN OUT
AI or DI*
OUT IN
4-20 mA + HART
Benefits:
Prevents spurious trips on loss of electrical power to DVC6200 SIS PST with DVC6200 SIS provides diagnostic coverage Trigger diagnostics captures safety demand and reset ‐Solenoid health monitoring
DO
Optional Position Feedback (420 mA Analog or 1 A Discrete Switch)
0-24 V DC
Notes:
‐DVC6200 SIS with Relay B in ETT configuration for PST diagnostic only Loss of pneumatic supply to DVC6200 SIS exhausts air to valve
-8 mA minimum is required when the LPC200 is loop powered
Instrument Air Supply
Actuator Pressure Sensing
MULTIPLEXER**
ValveLink Software
BPCS SIS FIELD
Scenario 4: SIS with DO to DETT Solenoid BPCS with AO to DVC6200 SIS (PST Only)
Y
Optional LCP200 or External Pushbutton PST
Instrument Air Output
Y
S
Example Drawing Only, may require modifications to meet site specific requirements
*Position Monitor AI or DI may reside in SIS or BPCS **PC with ValveLink software or Emerson Field Communicator can be used in lieu of multiplexer ***HF341/HF340 may be required with legacy hosts to provide proper impedance to support HART communication
5
DVC6200 SIS
February 2022
Instruction Manual Supplement
D103858X012
DISPLAY ALARMS
ESDV STATUS
IN PROGRESS
SERIAL
IN OUT
PST Abnormal
PST Pass
Options Available:
LCP200 Local Control Panel or external pushbutton SIL 2 Capable 420 mA position transmitter or discrete switch Discrete switch can be configured for position or alert annunciation
IN OUT
Benefits:
PST with DVC6200 SIS provides diagnostic coverage Trigger diagnostics captures safety demand and reset ‐Solenoid valve test diagnostics and evaluation
DO
0-24 V DC
Non-HART AO
4-20 mA
IN OUT
HART
HF341/ HF340***
Actuator Pressure Sensing
MULTIPLEXER**
4-20 mA + HART
ValveLink
Software
BPCS SIS FIELD
Scenario 4.1: SIS with DO to DETT Solenoid for Solenoid Valve Testing BPCS with AO to DVC6200 SIS (PST Only)
Example Drawing Only, may require modifications to meet site specific requirements
**PC with ValveLink software or Emerson Field Communicator can be used in lieu of multiplexer ***HF341/HF340 may be required with legacy hosts to provide proper impedance to support HART communication
Notes:
‐DVC6200 SIS with Relay B in ETT configuration for PST diagnostic only Loss of pneumatic supply to DVC6200 SIS exhausts air to valve
-8 mA minimum is required when the LPC200 is loop powered
Instrument
Y
Optional LCP200 or External Pushbutton PST
Air Output
0-24 V DC
S
Y
Instrument Air Supply
6
Instruction Manual Supplement
D103858X012
DVC6200 SIS
February 2022
DISPLAY ALARMS
ESDV STATUS
IN PROGRESS
PST Abnormal
PST Pass
Options Available:
LCP200 Local Control Panel or external pushbutton Integral 4-20 mA position transmitter or discrete switch
Benefits:
Prevents spurious trip on loss of electrical power to DVC6200 SIS Trigger diagnostics captures safety demand and reset PST with DVC6200 SIS provides diagnostic coverage ‐Solenoid health monitoring
DO
IN OUT
AI or DI*
OUT IN
0-24 V DC
Optional Position Feedback (420 mA Analog or 1 A Discrete Switch)
HART AO
IN OUT
4-20 mA + HART
ValveLink
Software
BPCS SIS FIELD
Asset Management System
Scenario 5: SIS with DO to SOV BPCS with HART I/O to DVC6200 SIS (PST Only)
Example Drawing Only, may require modifications to meet site specific requirements
*Position Monitor AI or DI may reside in SIS or BPCS
Notes:
‐DVC6200 SIS with Relay B in ETT configuration for PST diagnostic only Loss of pneumatic supply to DVC6200 SIS exhausts air to valve
-8 mA minimum is required when the LPC200 is loop powered
Instrument Air Output
Y
Optional LCP200 or External Pushbutton PST
Y
Actuator Pressure Sensing
Instrument Air Supply
S
7
DVC6200 SIS
February 2022
Instruction Manual Supplement
D103858X012
DISPLAY ALARMS
ESDV STATUS
IN PROGRESS
PST Abnormal
PST Pass
Options Available:
LCP200 Local Control Panel or external pushbutton Integral 4-20 mA position transmitter or discrete switch
Benefits:
Trigger diagnostics captures safety demand and reset PST with DVC6200 SIS provides diagnostic coverage ‐Solenoid valve test diagnostics and evaluation
Notes:
‐ DVC6200 SIS with Relay B in ETT configuration for PST diagnostic only Loss of pneumatic supply to DVC6200 SIS exhausts air to valve
-8 mA minimum is required when the LPC200 is loop powered
DO
IN OUT
HART AO
IN OUT
4-20 mA + HART
ValveLink
Software
BPCS SIS FIELD
Asset Management System
0-24 V DC
Actuator Pressure Sensing
Instrument Air Supply
Y
Instrument Air Output
Optional LCP200 or External Pushbutton PST
0-24 V DC
S
Y
Scenario 5.1: SIS with DO and HART I/O to DVC6200 SIS for PST and Solenoid Valve Testing
Example Drawing Only, may require modifications to meet site specific requirements
8
Instruction Manual Supplement
D103858X012
DVC6200 SIS
February 2022
DISPLAY ALARMS
ESDV STATUS
IN PROGRESS
PST Abnormal
PST Pass
Options Available:
LCP200 Local Control Panel or external pushbutton Integral 4-20 mA position transmitter or discrete switch
Benefits:
Prevents spurious trip on loss of electrical power to DVC6200 SIS Trigger diagnostics captures safety demand and reset PST with DVC6200 SIS provides diagnostic coverage ‐Solenoid Health Monitoring
Notes:
‐DVC6200 SIS with Relay B in ETT configuration for PST diagnostic only Loss of pneumatic supply to DVC6200 SIS exhausts air to valve
-DeltaV SIS Solution
-8 mA minimum is required when the LPC200 is loop powered
DO
IN OUT
Non-SIL Rated HART AO* **
IN OUT
8-20 mA + HART
ValveLink
Software
BPCS SIS FIELD
Asset Management System
0-24 V DC
Actuator Pressure Sensing
Instrument Air Supply
Y
Instrument Air Output
Optional LCP200 or External Pushbutton PST
Scenario 5.2: SIS with DO to SOV Non-SIL Rated HART AO to DVC6200 SIS (PST Only)
Example Drawing Only, may require modifications to meet site specific requirements
*PST Initiation from VaveLink software ** With Relay B scheme, on demand trip of the SIS DO from 24 V to 0 V, the non-SIL rated AO is configured
** to switch current from 8 mA to 20 mA and revert back to 8 mA to DVC6200 SIS upon DO reset to 24 V.
S
Y
9
DVC6200 SIS
February 2022
Instruction Manual Supplement
D103858X012
DISPLAY ALARMS
ESDV STATUS
IN PROGRESS
PST Abnormal
PST Pass
Options Available:
LCP200 Local Control Panel or external pushbutton SIL 2 Capable 420 mA position transmitter or discrete switch Discrete switch can be configured for position or alert annunciation
Benefits:
SIL3 Capable digital valve controller ‐Redundant DVC6200 SIS and SOV Trigger diagnostics captures safety demand and reset PST with DVC6200 SIS provides diagnostic coverage ‐Solenoid health monitoring
DO
IN OUT
AI or DI*
OUT IN
Optional Position Feedback (420 mA Analog or 1 A Discrete Switch)
HART AO
ValveLink
Software
BPCS SIS FIELD
Asset Management System
HART Pass Through
IN OUT
4-20 mA + HART
Scenario 6: SIS with HART I/O to DETT DVC6200 SIS SIS DO to DETT Solenoid
Example Drawing Only, may require modifications to meet site specific requirements
*Position Monitor AI or DI may reside in SIS or BPCS
0-24 V DC
Notes:
Loss of electrical power or pneumatic supply to DVC6200 SIS exhausts air to valve
-8 mA minimum is required when the LPC200 is loop powered
Instrument Air Output
S
Instrument
Y
Air Supply
Actuator Pressure Sensing
Optional LCP200 or External Pushbutton PST
10
Instruction Manual Supplement
D103858X012
DVC6200 SIS
February 2022
DISPLAY ALARMS
ESDV STATUS
IN PROGRESS
PST Abnormal
PST Pass
Options Available:
LCP200 Local Control Panel or external pushbutton SIL 2 Capable 420 mA position transmitter or discrete switch Discrete switch can be configured for position or alert annunciation
Benefits:
SIL3 Capable digital valve controller ‐Redundant DVC6200 SIS and SOV Trigger diagnostics captures safety demand and reset PST with DVC6200 SIS provides diagnostic coverage ‐Solenoid valve test diagnostics and evaluation
Notes:
Loss of electrical power or pneumatic supply to DVC6200 SIS exhausts air to valve
-8 mA minimum is required when the LPC200 is loop powered
DO
IN OUT
0-24 V DC
0-24 V DC
S
Instrument Air Output
Y
HART AO
ValveLink
Software
BPCS SIS FIELD
Asset Management System
HART Pass Through
IN OUT
4-20 mA + HART
Scenario 6.1: SIS with HART I/O to DETT DVC6200 SIS for Solenoid Valve Testing SIS DO to DETT Solenoid
Instrument Air Supply
Actuator Pressure Sensing
Optional LCP200 or External Pushbutton PST
11
DVC6200 SIS
February 2022
Instruction Manual Supplement
D103858X012
DISPLAY ALARMS
ESDV STATUS
IN PROGRESS
SERIAL
IN OUT
PST Abnormal
PST Pass
Options Available:
LCP200 Local Control Panel or external pushbutton SIL 2 Capable 420 mA position transmitter or discrete switch Discrete switch can be configured for position or alert annunciation
AI or DI*
OUT IN
Benefits:
SIL3 Capable digital valve controller ‐Redundant DVC6200 SIS and SOV Wiring to both SOV and DVC6200 SIS saves I/O PST with DVC6200 SIS provides diagnostic coverage
Optional Position Feedback (420 mA Analog or 1 A Discrete Switch)
DO
IN OUT
ValveLink
Software
LC340
HART
MULTIPLEXER**
BPCS SIS FIELD
Scenario 7: SIS with single DO to DETT DVC6200 SIS and DETT SOV
Example Drawing Only, may require modifications to meet site specific requirements
*Position Monitor AI or DI may reside in SIS or BPCS **PC with ValveLink software or Emerson Field Communicator can be used in lieu of multiplexer
0-24 V DC
Notes:
Loss of electrical power or pneumatic supply to DVC6200 SIS exhausts air to valve ‐Single DO is a common cause failure point Trigger diagnostics or capture of demand/reset strokes unavailable since power to DVC6200 SIS is interrupted during a demand
Instrument Air Output
S
Y
Optional LCP200 or External Pushbutton PST
Instrument Air Supply
12
Instruction Manual Supplement
D103858X012
DVC6200 SIS
February 2022
DISPLAY ALARMS
ESDV STATUS
IN PROGRESS
PST Abnormal
PST Pass
Options Available:
LCP200 Local Control Panel or external pushbutton SIL 2 Capable 420 mA position transmitter or discrete switch Discrete switch can be configured for position or alert annunciation
Benefits:
SIL3 Capable digital valve controller ‐Redundant DVC6200 SIS and SOV PST with DVC6200 SIS provides diagnostic coverage ‐Solenoid health monitoring
DO
SERIAL
IN OUT
IN OUT
AI or DI*
OUT IN
Optional Position Feedback (420 mA Analog or 1 A Discrete Switch)
0-24 V DC
DO
ValveLink
Software
IN OUT
LC340
HART
MULTIPLEXER**
BPCS SIS FIELD
Scenario 8: SIS with separate DO to DETT DVC6200 SIS and DETT SOV
Example Drawing Only, may require modifications to meet site specific requirements
*Position Monitor AI or DI may reside in SIS or BPCS **PC with ValveLink Software or Emerson Field Communicator can be used in lieu of multiplexer
0-24 V DC + HART
Notes:
Loss of electrical power or pneumatic supply to DVC6200 SIS exhausts air to valve Trigger diagnostics or capture of demand/reset strokes unavailable since power to DVC6200 SIS is interrupted during a demand
Instrument Air Output
S
Instrument
Y
Air Supply
Actuator Pressure Sensing
Optional LCP200 or
External Pushbutton PST
13
DVC6200 SIS
February 2022
Instruction Manual Supplement
D103858X012
DISPLAY ALARMS
ESDV STATUS
IN PROGRESS
PST Abnormal
PST Pass
Options Available:
LCP200 Local Control Panel or external pushbutton SIL 2 Capable 420 mA position transmitter or discrete switch Discrete switch can be configured for position or alert annunciation
Benefits:
SIL3 Capable digital valve controller ‐Redundant DVC6200 SIS and SOV PST with DVC6200 SIS provides diagnostic coverage ‐Solenoid valve test diagnostics and evaluation
SERIAL
IN OUT
DO
OUT IN
0-24 V DC
DO
ValveLink
Software
IN OUT
LC340
HART
0-24 V DC + HART
MULTIPLEXER**
BPCS SIS FIELD
Scenario 8.1: SIS with separate DO to DETT DVC6200 SIS and DETT SOV for Solenoid Valve Testing
Example Drawing Only, may require modifications to meet site specific requirements
**PC with ValveLink Software or Emerson Field Communicator can be used in lieu of multiplexer
Notes:
Loss of electrical power or pneumatic supply to DVC6200 SIS exhausts air to valve Trigger diagnostics or capture of demand/reset strokes unavailable since power to DVC6200 SIS is interrupted during a demand
0-24 V DC
S
Instrument Air Output
Instrument
Y
Air Supply
Actuator Pressure Sensing
Optional LCP200 or
External Pushbutton PST
Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Fisher, FIELDVUE, and ValveLink are marks owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. Emerson Automation Solutions, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. HART is a registered trademark of FieldComm Group. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.
Emerson Automation Solutions
Marshalltown, Iowa 50158 USA Sorocaba, 18087 Brazil Cernay, 68700 France Dubai, United Arab Emirates Singapore 128461 Singapore
www.Fisher.com