Fisher IM Supplement: Configuring the DVC6200 SIS for Throttling Control Using ValveLink Software Manuals & Guides

Instruction Manual Supplement
D103988X012
DVC6200 SIS
October 2017
Configuring the FIELDVUE™ DVC6200 SIS for
Throttling Control Using ValveLink
WARNING
This instruction manual supplement is not intended to be used as a stand-alone document. It must be used in conjunction with the following documents:
• Safety manual for DVC6200 SIS Digital Valve Controller (D103601X012
• Fisher FIELDVUE DVC6200 SIS Instruction Manual (D103557X012
Failure to use this instruction manual supplement in conjunction with the above referenced manuals could result in personal injury or property damage. If you have any questions regarding these instructions or need assistance in obtaining either of these documents, contact your Emerson sales office
This instruction manual supplement is intended to assist in the use of the DVC6200 SIS as a SIL capable position monitor AND as a non-SIL capable throttling digital valve controller.
or Local Business Partner.
), sections pertaining to the Position Monitor
)
Software
WARNING
The DVC6200 SIS failure rates for the digital valve controller safety function, as listed in the FMEDA and SIL certificate, are not valid in this configuration (with 420 mA operation).
www.Fisher.com
DVC6200 SIS
October 2017
Instruction Manual Supplement
D103988X012
Configuration
WARNING
When using natural gas as the supply medium:
D Remove electrical power before removing the housing cap. Personal injury or property damage from fire or explosion
may result if power is not disconnected before removing the cap.
D Ensure that the cover is correctly installed before putting this unit back into service. Failure to do so could result in
personal injury or property damage from fire or explosion.
1. Remove the Printed Wiring Board from the DVC6200 SIS.
WARNING
The DVC6200 SIS failure rates for the digital valve controller safety function, as listed in the FMEDA and SIL certificate, are not valid in this configuration (with 420 mA operation).
2. Ensure that the Hardware Shutdown DIP Switch is configured to disabled, as shown in figure 1.
3. Confirm that the Output DIP Switch is in the desired position for use as either a Position Transmitter or Switch.
Figure 1. Printed Wiring Board
CONFIRM OUTPUT DIP SWITCH SETTING
HARDWARE SHUTDOWN DIP SWITCH DISABLED
4. Reassemble the DVC6200 SIS.
5. Connect the DVC6200 SIS to ValveLink software.
6. Run a PST Calibration, if not done earlier.
7. Under Detailed Setup, select Travel/Pressure Control, see figure 3 for tab location.
a. Set the Low Limit/Cutoff Point to 0.5-1% more than the Travel Low Low Alert Point in the Travel Alerts tab (refer
to figure 2 for Travel Alerts tab).
2
Loading...
+ 2 hidden pages