Instruction Manual Supplement
D104368X012
DVC6200p
September 2019
Changing PROFIBUS Device Address Using
Siemens SIMATIC PDM
Prior to going Online with the Device
1. Launch the SIMATIC PDM software to access the PROFIBUS DP Network. Right click on SIMATIC PDM and select
Start LifeList.
2. Select Start Scan or click the Green Arrow to start the scan.
www.Fisher.com

DVC6200p
September 2019
Instruction Manual Supplement
3. After the scan is complete select Assign Address and TAG in the resulting window.
D104368X012
4. Enter the desired address and select Transfer.
2