Instruction Manual Supplement
D103987X012
L2e Controller
September 2017
Changing easy-Drive™ Electric Actuator On/Off Input Configuration from Single Dry Contact Control to Dual Dry Contact Control
Supplement to Fisher™ L2e Electric Level Controller Instruction Manual (D103531X012)
This supplement contains information for converting the easyDrive Electric Actuator from Single Dry Contact Control Mode to Dual Dry Contact Control Mode.
Refer to the L2e instruction manual (D103531X012 Partner, or at Fisher.com
The Dual Dry Contact Control Mode of operation has proven to be a superior and reliable method of operation with the easyDrive actuator. This method provides a more stable switch actuation by reducing, or eliminating, the switch bounce that may be associated with the Single Dry Contact Control Mode.
Refer to the appropriate easyDrive Electric Actuator instruction manual for cautions, warnings, and instructions on removing the easyDrive actuator cover.
D Fisher D3 Control Valve with easyDrive Electric Actuator (D103460X012 D Fisher D4 Control Valve with easyDrive Electric Actuator (D103597X012
Note
This procedure is for easyDrive Electric Actuators configured for ON/OFF INPUT only.
, for all other information regarding the L2e electric level controller.
), available from your Emerson sales office or Local Business
) )
L2e Switch Wiring Conversion
1. Ensure easyDrive actuator power is turned off and remove cover.
2. Observe easyDrive actuator electrical connector to determine Dry Contact Control Mode.
3. If easyDrive actuator is wired as shown in figure 1, the actuator is already configured as Dual Dry Contact Control Mode and no further action is required. Replace easyDrive actuator cover and apply power to put system in service.
4. If easyDrive actuator is wired as shown in figure 2, the actuator is configured as Single Dry Contact Control Mode. Proceed with the following instructions to reconfigure to Dual Dry Contact Control Mode.
5. Loosen binding screw #2 on easyDrive actuator
6. Install red wire from L2e in easyDrive actuator electrical connector location #2 (marked as “OPEN” or “N.O.”) and tighten binding screw (see figure 1).
7. Loosen binding screw #3 in easyDrive actuator electrical connector, install blue wire from L2e, and tighten binding screw (see figure 1).
electrical connector (see figure 2) and remove wire.
www.Fisher.com
L2e Controller
September 2017
Instruction Manual Supplement
D103987X012
8. The L2e wires should now be connected as shown in figure 1:
a. Brown to position #1 (COMM)
b. Red to position #2 (OPEN or N.O.)
c. Blue to position #3 (CLOSE or N.C.)
9. The wiring is now configured as Dual Dry Contact Mode. Proceed to next section for easyDrive electric actuator software configuration.
Figure 1. Dual Dry Contact Control Figure 2. Single Dry Contact Control