26
8.4 Outdoor unit point check function
There is a check switch in outdoor PCB.
Press the switch N times it will display the content corresponding to No. N. After getting into the check function, it
will display No. N with 1.5s, meanwhile the low bit decimal of digit display flashing, indicated to get into the check
function display. After 1.5s, it will display the content corresponding to No. N.
the digital display tube will display the follow procedure when push SW1 each time.
Display Remark
0 Normal display
Display running frequency, running state or malfunction code
1 No. of indoor units in good connection Actual data
2 Outdoor unit running mode code Off:0,Fan only 1, Cooling:2, Heating:3, Forced cooling:4
3 A indoor unit capacity
The capacity unit is horse power. If the indoor unit is not connected, the digital
display tube will show: “――”
(7K:0.8HP, 9 K:1HP,12K:1.2HP,18K:1.5HP)
4 B indoor unit capacity
5 C indoor unit capacity
6 D indoor unit capacity
7 E indoor unit capacity
8 A Indoor unit capacity demand code
Norm value*HP
(7K:0.8HP, 9 K:1HP,12K:1.2HP,18K:1.5HP)
9 B Indoor unit capacity demand code
10 C Indoor unit capacity demand code
11 D Indoor unit capacity demand code
12 E Indoor unit capacity demand code
13 Total indoor units amendatory capacity demand code
Forced cooling:7
14 The frequency corresponding to the total indoor units
amendatory capacity demand
15 The frequency after the frequency limit
16 The frequency sending to compressor control chip
17 A indoor unit evaporator outlet temp.(T2BA)
If the temp. is lower than -9 degree, the digital display tube will show “-9”.If the
temp. is higher than 70 degree, the digital display tube will show “70”. If the indoor
unit is not connected, the digital display tube will show: “――”
18 B indoor unit evaporator outlet temp.(T2BB)
19 C indoor unit evaporator outlet temp.(T2BC)
20 D indoor unit evaporator outlet temp.(T2BD)
21 E indoor unit evaporator outlet temp.(T2BE)
22 A indoor unit room temp.(T1A) If the temp. is lower than 0 degree, the digital display tube will show “0”.If the temp.
is higher than 50 degree, the digital display tube will show “50”. If the indoor unit is
not connected, the digital display tube will show: “――”
23 B indoor unit room temp.(T1B)
24 C indoor unit room temp.(T1C)
25 D indoor unit room temp.(T1D)
26 E indoor unit room temp.(T1E)
27 A indoor unit evaporator temp.(T2A)
If the temp. is lower than -9 degree, the digital display tube will show “-9”.If the
temp. is higher than 70 degree, the digital display tube will show “70”. If the indoor
unit is not connected, the digital display tube will show: “――”
28 B indoor unit evaporator temp.(T2B)
29 C indoor unit evaporator temp.(T2C)
30 D indoor unit evaporator temp.(T2D)
31 E indoor unit evaporator temp.(T2E)
32 Condenser pipe temp.(T3)
33 Outdoor ambient temp.(T4)
34 Compressor discharge temp.(Tp) The display value is between 30~129 degree. If the temp. is lower than 30 degree, the
digital display tube will show “30”.If the temp. is higher than 99 degree, the digital
display tube will show single digit and tens digit. For example, the digital display
tube show “0.5”,it means the compressor discharge temp. is 105 degree.)
35 AD value of current
The display value is hex nu mber.
For example ,the digital di splay tube show “Cd”, it means AD value is 205.
36 AD value of voltage