Fisher Fisher D4 Control Valve with Gen 2 easy-Drive Electric Actuator Manuals & Guides

Instruction Manual
D104188X012
D4 Valve with Gen 2 easy-Drive Actuator
April 2022
Fisher™ D4 Control Valve with Gen 2 easy-Drive Electric Actuator

Contents

Introduction 1.................................
Scope of Manual 1.............................
Specifications 3...............................
Educational Services 3.........................
Installation 4..................................
Special Instructions for “Safe Use” and Installations
in Hazardous Locations 5.....................
Startup Overview 6............................
Default Input Signals 11........................
Configuration 11..............................
Input Configuration 11.....................
Changing the Inputs from Default Settings 11..
Modbus Setup 11.............................
Connecting using the Fisher easy-Drive
configuration software 12................
Initial Setup 12............................
Calibration Instructions 13..................
Licensing 16..............................
Startup 18................................
Troubleshooting 19.............................
Maintenance 20................................
Valve Plug and Seat Ring 20.....................
Valve Packing 22..............................
Parts Ordering 27...............................
Parts Kits 27...................................
Figure 1. Fisher D4 Control Valve with Gen 2 easy-Drive Electric Actuator
W9933-5
Repair Kits 27..................................
Parts List 28...................................
Appendix A - Modbus 31.........................
Appendix B - Certificate of Conformance 36.........

Introduction

Scope of Manual

This instruction manual provides installation, maintenance, and parts information for the Fisher D4 control valve with Gen 2 easy-Drive electric actuator. For Gen 1 electric actuators, use Fisher D4 with easy-Drive Instruction Manual,
(
D103597X012). If the actuator has a RPU-100 installed refer to easy-Drive RPU-100 Instruction Manual,
(D104551X012
www.Fisher.com
).
Do not install, operate, or maintain a D4 control valve with Gen 2 easy-Drive electric actuator without being fully trained and qualified in valve, actuator, and accessory installation, operation, and maintenance. To avoid personal injury or property damage, it is important to carefully read, understand, and follow all the contents of this manual, including all safety cautions and warnings. If you have any questions about these instructions, contact your Emerson sales office
before proceeding.
D4 Valve with Gen 2 easy-Drive Actuator
April 2022
Table 1. Specifications
Instruction Manual
D104188X012
Valve Body Sizes and End Connection Styles
(1)
See table 2
Maximum Inlet Pressures and Temperatures
(1)
If the valve nameplate shows an ASME pressure‐temperature class, maximum inlet pressure and temperature is consistent with the applicable class per ASME B16.34. If the nameplate does not show an ASME class, it will show a maximum cold working pressure at 38_C (100_F) (for example, 293 bar [4250 psi])
Maximum Pressure Drops
(1)
See table 4
Shutoff Classification per ANSI/FCI 70‐2 and IEC 60534‐4
Class IV
Material Temperature Capabilities
(1)
Valve Body Assembly:
Standard Bonnet O‐Ring: -40 to 135°C (-40 to 275°F) Optional Fluorocarbon Bonnet O‐Ring: -23 to 204°C
(-10 to 400°F)
Flow Characteristic
Equal percentage
Flow Direction
Flow up only
Port Diameters
See table 2
Power Requirements
11-30 VDC, minimum 4 amp power supply required (fuse to 5 amps)
Maximum Current Draw
4 amps
Idle Current Draw
15 mA at 24 VDC, 25 mA at 12 VDC
Conduit Connections
Two 3/4 NPT connections
Stroke Length
19 mm (0.75 inch)
Nominal Stroke Speed
(2)
3.9 mm/s (0.15 inch/s) at 24 VDC
2.2 mm/s (0.09 inch/s) at 12 VDC
Hazardous Area Approvals
CSA (C/US): ExplosionProof Class I, Division 1, Groups C and D, T6, Ex db IIA T6, Class I, Zone 1, AEx db IIA T6
ATEX Flameproof - Gas:
II 2 G, Ex db IIA T6 Gb
IECEx Flameproof - Gas: Ex db IIA T6 Gb
Enclosure Rating
Type 4X and IP66
Valve Plug Travel
19 mm (0.75 inch)
Valve Plug Style
Micro‐Form valve plug
Available Actuator Configurations
On/off (snap acting) Positioning (flow or pressure control)
1. The pressure or temperature limits in the referenced tables and any applicable ASME code limitations should not be exceeded.
2. 10% variation can be expected, based on temperature and pressure of application.
2
Duty Cycle
50% maximum
Enclosure Material
Cast aluminum alloy with powder coat paint
Approximate Weight:
22 - 51 kg (49 - 113 lbs), depending upon construction
Instruction Manual
D104188X012
D4 Valve with Gen 2 easy-Drive Actuator
April 2022

Description

The D4 control valve with easy-Drive electric actuator is a compact, rugged valve designed primarily for high‐pressure throttling applications. This valve is ideal for use on pressure and flow control applications within the oil and gas production industry. The D4 valve also makes an excellent dump valve for high‐pressure separators and scrubbers.
The D4 control valve meets the metallurgical requirements of NACE MR0175/ISO 15156 without environmental limits for temperatures below 135_C (275_F). If the temperature is above 135_C (275_F), the N07718 Belleville washers will impose some limits, as shown in table 3.

Specifications

Table 1 lists specifications for the D4 control valve with easy-Drive electric actuator. Some of the specifications for a given control valve as it originally comes from the factory are stamped on a nameplate located on the lower actuator enclosure.

Educational Services

For information on available courses for the Fisher D4 control valve with easy-Drive electric actuator, as well as a variety of other products, contact:
Emerson Automation Solutions Educational Services - Registration Phone: 1-641-754-3771 or 1-800-338-8158 E-mail: education@emerson.com emerson.com/fishervalvetraining
Table 2. Valve Sizes and Connection Styles
VALVE
SIZE,
NPS
1
2
X = Available construction.
PORT
DIAMETER,
(INCHES)
0.25, 0.375,
0.5, 0.75
0.25, 0.375, 0.5
0.75, 1, 1.25
SCREWED RAISED FACE (RF) FLANGED
4250 psi CL150 CL300 CL600
X X X X X X X
X X X X X X X
Table 3. D4 Environmental Limits for NACE MR0175/ISO 15156 with Sour Trim
MAXIMUM TEMPERATURE MAXIMUM H2S PARTIAL PRESSURE
_C _F MPa psia
232 450 0.2 30 No
204 400 1.4 200 No
199 390 2.3 330 No
191 375 2.5 360 No
149 300 2.8 400 No
135 275 No Limit Yes
CL900 and
CL1500
RING TYPE JOINT
(RTJ) FLANGED
CL600
COMPATIBLE WITH
ELEMENTAL SULFUR
CL900 and
CL1500
3
D4 Valve with Gen 2 easy-Drive Actuator
April 2022
Instruction Manual
D104188X012
Table 4. Fisher D4 easy-Drive Maximum Pressure Drop
PORT DIAMETER MAXIMUM PRESSURE DROP
mm Inch Bar psi
6.4
9.5
12.7
19.1
25.4
31.8
1. Downstream pressure, P2, is limited to 2250 psig.
0.25
0.375
0.5
0.75 1
1.25
293 293 247 105
56 34
(1)
4250 4250 3576
1518
814 495
(1)
(1)
(1)

Installation

WARNING
Always wear protective gloves, clothing, and eyewear when performing any installation operations to avoid personal injury.
To avoid personal injury or property damage caused by bursting of pressure‐retaining parts or by uncontrolled process fluid, be certain the service conditions do not exceed the limits shown on the valve nameplate and in table 1. Use pressure‐relieving devices required by government or accepted industry codes and good engineering practices.
Check with your process or safety engineer for any additional measures that must be taken to protect against process media.
If installing into an existing application, also refer to the WARNING at the beginning of the Maintenance section in this instruction manual.
WARNING
For explosionproof applications, ensure the actuator cover is properly bolted before applying power to the actuator. Personal injury or property damage may result from fire or explosion if power is applied to the actuator with the cover removed in a hazardous area.
For explosion‐proof applications, install rigid metal conduit and a conduit seal no more than 457 mm (18 inches) from the actuator. Personal injury or property damage may result from explosion if the seal is not installed.
Select wiring and/or cable glands that are rated for the environment of use (such as hazardous area, ingress protection, and temperature). Failure to use properly rated wiring and/or cable glands can result in personal injury or property damage from fire or explosion.
Wiring connections must be in accordance with local, regional, and national codes for any given hazardous area approval. Failure to follow the local, regional, and national codes could result in personal injury or property damage from fire or explosion.
CAUTION
When ordered, the valve configuration and construction materials were selected to meet particular pressure, temperature, pressure drop, and controlled fluid conditions. Responsibility for the safety of process media and compatibility of valve materials with process media rests solely with the purchaser and end‐user. Since some body/trim material combinations are limited in their pressure drop and temperature ranges, do not apply any other conditions to the valve without first contacting your Emerson sales office
To avoid product damage, inspect the valve before installation for any damage or any foreign material that may have collected in the valve body. Also remove any pipe scale, welding slag, or other foreign material from the pipeline.
.
4
Instruction Manual
D104188X012
D4 Valve with Gen 2 easy-Drive Actuator
April 2022
WARNING
Avoid personal injury or property damage caused by possible actuator failure. The use of a rigidly‐mounted support on the actuator casing may cause additional stress on the actuator leading to premature wear and/or failure of the actuator components.
CAUTION
To avoid product damage, inspect the valve before installation for any damage or any foreign material that may have collected in the valve body. Also remove any pipe scale, welding slag, or other foreign material from the pipeline.
1. Before installing the control valve assembly, inspect it for any damage and for any foreign material that may have collected in the valve body.
2. Remove any pipe scale, welding slag, and other foreign material from the pipeline.
3. The control valve can be installed in any position, but normally the actuator is vertical above the valve. Install the valve so the flow direction arrow on the side of the valve indicates the direction of the process flow.
4. Install the valve following local and national piping codes when they apply to the application. For screwed connections, treat the external pipe threads with a good grade pipe compound. For flanged valves, use suitable gaskets between valve and pipeline flanges.
5. If continuous operation is required during maintenance and inspection, install a conventional three‐valve bypass around the valve.

Special Instructions for “Safe Use” and Installations in Hazardous Locations

ATEX/IECEx
WARNING
To avoid static discharge from the enclosure, do not rub or clean the enclosure with solvents. To do so could result in an explosion. Clean with a mild detergent and water only.
The enclosure is nonconducting and may generate an ignitioncapable level of electrosatic charges under certain extreme conditions. The user should ensure that the equipment is not installed in a location where it may be subjected to external conditions (such as highpressure steam) which might cause a buildup of electrostatic charges on nonconducting surfaces. Additionally, cleaning of the equipment shall only be done with a damp cloth.
To avoid damage to the enclosure, when screws are fully tightened into blind holes in enclosure walls, with no washer fitted, at least one full thread shall remain free at the base of the hole.
5
D4 Valve with Gen 2 easy-Drive Actuator
April 2022

Startup Overview

Figure 2. Flowchart
Instruction Manual
D104188X012
PREPARE PER INSTRUCTIONS
IN INSTALLATION SECTION
ON/OFF
WIRE PER DIAGRAM FOR L2e
YES
FIRST TIME USING
Modbus?
NO
POSITIONING OR
ON/OFF?
ARE YOU USING
Modbus?
POSITIONING
WIRE PER DIAGRAM FOR 4-20 mA
NO
YES
CONNECT USB-TO-Modbus CONVERTER
TO INTERNET CONNECTED COMPUTER
FOLLOW DRIVER INSTALLATION
INSTRUCTIONS FOR YOUR DEVICE
INSTALL easy-Drive CONFIGURATION OR
Modbus MASTER SOFTWARE
6
CONNECT VIA Modbus TO VALVE AND
MONITOR DESIRED REGISTERS
UNIT IS READY FOR OPERATION
Instruction Manual
D104188X012
Figure 3. Fisher D4 Valve with Gen 2 easy-Drive Actuator Wiring Diagram
CONTROLLER
POWER AND CONTROL TERMINAL
MOTOR / GEARBOX ASSY (GE84238)
GE47302-7
D4 Valve with Gen 2 easy-Drive Actuator
April 2022
FIELD WIRING CONNECTIONS
TOP VIEW CONTROLLER

Power Requirements

Ensure a stable DC power source is available, maintaining less than 5% ripple and sufficiently surge protected for the application. A 4 amp (minimum) power supply is required.

Wiring Instructions

1. Observe local wiring requirements for hazardous location usage.
2. Conduit seals within 450 mm (18 inches) of the enclosure port are required for explosionproof installation.
3. 18 AWG (0.52 mm
2
) to 12 AWG (3.31 mm2) wire size required.
4. Fuse system to 5A.
5. Connect enclosure and analog signal shields.
6. Ensure power is turned off before connecting the wires.
Power
1. Connect 12 or 24 VDC reference to: –
2. Connect 12 or 24 VDC positive to: +
3. Be sure to tighten terminals sufficiently to ensure solid mechanical connection.
7
D4 Valve with Gen 2 easy-Drive Actuator
April 2022
Figure 4. Wiring - Analog Input
Instruction Manual
D104188X012
Figure 5. Wiring - L2e
8
Instruction Manual
D104188X012
Figure 6. Wiring - Single Dry Contact
D4 Valve with Gen 2 easy-Drive Actuator
April 2022
Figure 7. Wiring - Modbus Input
9
D4 Valve with Gen 2 easy-Drive Actuator
April 2022
Figure 8. Wiring - Auxiliary Digital I/O set to input (40080=0)
Instruction Manual
D104188X012
Figure 9. Wiring - Auxiliary Digital I/O set to output (40080=1)
10 V, 25 mA max
10
Instruction Manual
D104188X012
D4 Valve with Gen 2 easy-Drive Actuator
April 2022

Default Input Signals

The D4 with easyDrive comes from the factory calibrated and ready for use with the following default input signals shown in table 5.
Table 5. D4 easy-Drive Default Input Signals
CONFIGURATION ON/OFF POSITIONING
Input Signal L2e (dual dry contact) 4-20 mA
If the input signal of the application matches table 5, proceed to the Wiring Instructions section. If the input signal of the application does not match table 5, proceed to the Configuration section.

Configuration

Input Configuration

There are two functional configurations available for the easyDrive electric actuator: On/Off and Positioning. It is possible to change an actuator from On/Off to Positioning after it has been delivered from the factory using a positioning license key. See licensing section.
All available input signals are shown in table 6.
Table 6. All Available Input Signals
CONFIGURATION ON/OFF POSITIONING
Control Source Modbus Local Modbus Local
Input Signal Modbus
L2e Dual Dry Contact
(default)
Single Dry Contact Modbus 4-20 mA (default)
If you are using the default inputs signals, and the valve has not been disassembled or adjusted in any way, there is no need to recalibrate the assembly. You can proceed directly to Startup (page 18).

Changing the Inputs from Default Settings

All configuration within the valve is done by setting values in Modbus registers. This can be done using any Modbus master (flow computer, PLC, PC). Configuration software, providing a visual interface to the registers, is available through your Emerson sales office or the Fisher website, at www.fisher.com/easyDrive.

Modbus setup

Use of a serial or USB to RS-485 device is required to connect to the actuator. Refer to manufacturer's requirements for installation. The D4 with easyDrive electric actuator Modbus factory defaults are Address 1, 9600 baud, even parity, 1 stop bit, MSB.
When a connection has been achieved, the actuator may be configured to accept the input signal over the Modbus link (ignoring the physical inputs) and the Modbus settings may be changed to accommodate the network to which it is attached. Other changes to functionality are possible, such as:
D Low level cutoff: 40054 (default is 5%)
D Position upon loss of signal: 40053 (default is 0%)
See Appendix A for a full map of Modbus registers and their functions.
11
D4 Valve with Gen 2 easy-Drive Actuator
April 2022
Figure 10. Fisher easy-Drive Configuration Software
Instruction Manual
D104188X012
Connecting using the Fisher easyDrive configuration software
The Fisher easyDrive configuration software allows configuration and diagnosing of the Fisher easyDrive electric actuator with a graphical interface. Connect a PC to the actuator using a USB or serial device to Modbus RTU converter using the wiring instructions above. The USB or serial device will be visible in the drop menu under Serial Port Settings. Baud rate and parity should be set to the Modbus settings of the actuator. Default actuator settings are address 1, 9600 baud, even parity, 1 stop bit, MSB. Press the AUTO button in the upper left corner to connect to the valve.
Use the Fisher easyDrive configuration software (figure 10) to make the desired changes, or register values may be changed to allow different functionality.
Note
If an actuator is on/off, a Modbus command of 0499 in register 40001 will cause the valve to close fully, while a value of 5001000 will cause the valve to open fully. The command register has one implied decimal point.

Initial Setup

The control method selection determines what control signal to which the valve will respond. Only the control signal selected will result in movement of the valve; all others will be ignored. The control methods available are dependent upon the licensing tier purchased with the valve. The functions for each tier are shown below.
D On/Off Tier
12
Instruction Manual
D104188X012
D4 Valve with Gen 2 easy-Drive Actuator
D Dual Contact On/Off
D Single Contact On/Off
D Modbus On/Off
D Positioning Tier - License required (see Licensing section)
D Dual Contact On/Off
D Single Contact On/Off
D Modbus On/Off
D Modbus Positioning
D 4-20mA Positioning
D 4-20mA Level
When using the easy-Drive Configuration Tool, clicking on the “Control Method” box will create a drop menu as shown. Select the desired control source; the selection will turn yellow. A box with Pending Changes will appear showing all changers. Press “APPLY” and the valve will immediately respond to that signal only.
April 2022
Figure 11.

Calibration Instructions

WARNING
To avoid personal injury or property damage, be aware that the valve will open fully and then close fully during the calibration cycle.
13
D4 Valve with Gen 2 easy-Drive Actuator
April 2022
Instruction Manual
D104188X012
If an easy-Drive valve has been shipped from the Fisher factory, it is not necessary to perform a span calibration. If, however, the valve has a new controller board or maintenance has been performed on the valve, such as trim replacement, it will be necessary to perform a span calibration. A span calibration is accomplished by the following method:
1. Ensure the process and valve are in a safe state – the valve may move during this operation
2. Press the CALIBRATE SPAN button to initiate the span calibration. The software will show a progress bar during the
calibration and display Valve Span Calibrated when complete.
Analog Input Calibration
For valves using 4-20 mA as a control source, several options are available to customize control of the actuator. Use a 4-20 mA signal generator to provide the desired signal. It is possible to calibrate the 4-20 mA signal in reverse acting or split-ranging with the method below with at least 4 mA of signal difference between the close and open values. The example shows a valve being changed from normal to reverse acting during the calibration process.
1. With the Control Method set to 4-20mA Positioning or 4-20mA Level, enter the Calibration screen and the
4-20mA Signal Calibration window will be visible.
2. Click the CALIBRATE CLOSE & OPEN VALUES button. A separate window will open to guide through the process.
3. Set the 4-20 mA signal to the desired value for when the valve is to be closed.
4. Enter this value into the Calibrated mA Signal text box and press Next
Figure 12.
5. Set the 4-20 mA signal to the desired value for when the valve is to be open.
6. Enter this value into the Calibrated mA Signal text box and press Next.
14
Instruction Manual
D104188X012
Figure 13.
D4 Valve with Gen 2 easy-Drive Actuator
April 2022
7. If the Close and Open values are as expected, press Confirm to accept these values. If not, press Cancel to restart
the process.
Note
The value of the 4-20 mA signal must have at least 4 mA difference between the close and open signals. A differential less than that amount will cause the actuator to reject the calibration and use the previous values.
Should the entered values vary more than 10% from the expected 4-20 mA values; the actuator will accept the calibration and a Notification displaying “Questionable Analog Calibration” will result.
Figure 14.
Calibration with the use of Modbus
1. After the unit has been properly wired and fused per instructions in the Wiring section of this instruction manual,
turn power to the unit on.
2. Calibrate using Modbus:
a. Send position command of 0% to actuator to prevent unexpected motion. Valve will move to commanded
position following the calibration procedure.
15
D4 Valve with Gen 2 easy-Drive Actuator
April 2022
b. Send a value of 1 to register 40043. Valve plug will move to fully open position and then to fully closed. The valve
plug will then return to the commanded position.
If a Modbus connection is not available, and recalibration is desired, use the appropriate calibration method as determined by the control method of your valve.
Instruction Manual
D104188X012
Calibration without the use of Modbus
1. Turn power to the actuator off.
2. Wait for 10 seconds to ensure all circuits have discharged.
3. Return power to the actuator and use the appropriate calibration method for your control signal. Calibration
sequence must be done within 15 seconds of power being switched on.
4. For positioning operation using 4-20 mA:
c. Apply a 4 mA signal between pins 4-20 mA - and 4-20 mA +. If Span is currently uncalibrated, valve plug will not
move at this time.
d. Apply a 20 mA signal between pins 4-20 mA - and 4-20 mA +. If Span is currently uncalibrated, valve plug will not
move at this time.
e. Apply a 4 mA signal between pins 4-20 mA - and 4-20 mA +; valve plug will move to the upper stop, immediately
followed by moving to the lower, closed position.
f. If calibration of the analog input is desired to improve positional accuracy, an optional operation is listed on
page 14 titled Analog Input Calibration.
5. For On/Off operation using dual-input dry contact:
a. Close the contact to create a short between pins COMMON and CLOSE. If Span is currently uncalibrated, valve
plug will not move at this time.
b. Close the contact to create a short between pins COMMON and OPEN. If Span is currently uncalibrated, valve
plug will not move at this time.
c. Close the contact to create a short between pins COMMON and CLOSE; valve plug will move to the upper, open
position and then to the lower, closed position.
6. For On/Off operation using single dry contact:
a. Open the contact to create an open circuit between pins COMMON and OPEN. If Span is currently uncalibrated,
valve plug will not move at this time.
b. Close the contact to create a short between pins COMMON and OPEN. If Span is currently uncalibrated, valve
plug will not move at this time.
c. Open the contact to create an open circuit between pins COMMON and OPEN; valve plug will move to the upper,
open position and then to the lower, closed position.
7. The unit is now calibrated.

Licensing

The Gen 2 easy-Drive actuator has two differing modes of operation: On/Off and Positioning. The On/Off mode is intended for snap-acting applications where the valve is either fully open or fully closed. In this mode, the valve plug cannot remain at any intermediate position; it will move to a fully closed or fully open position only. For applications that require the actuator to control over the full range of motion, it is necessary to have a Positioning license installed. A positioning license will allow access to 4-20mA positioning, 4-20mA level control and Modbus positioning.
16
Instruction Manual
D104188X012
D4 Valve with Gen 2 easy-Drive Actuator
April 2022
Positioning licenses can be purchased with the actuator and installed at the factory or can be installed at a later date by use of a license key on a USB license dongle. Installation of the license can be completed using the configuration software.
1. Insert the USB license dongle into the computer connected to the Gen 2 easy-Drive actuator.
Figure 15.
2. Click the button labelled MANAGE LICENSES on the left side of the configuration software screen.
Figure 16.
3. The license control screen will open, showing all licenses installed on the USB and the actuator.
Figure 17.
17
D4 Valve with Gen 2 easy-Drive Actuator
April 2022
Instruction Manual
D104188X012
4. After verifying the presence of the desired license on the USB license dongle, click the button labelled ‘easy-Drive’
under Move To, and the license will be transferred to the valve as shown below
Figure 18.
5. It is also possible to transfer licenses from one USB license dongle to another. Place two dongles into the computer
with the configuration software. Type in the number of licenses to move and click USB 2 to move the licenses.

Start Up

WARNING
To avoid personal injury or property damage, be aware that the valve will move and respond to an input signal during start up.
1. Before turning on power to the unit, be sure that a closed signal is being commanded to the unit.
D DryContact: contact is open.
D L2e (Dual Dry Contact): Contact closed across pins COMMON and CLOSE.
D Analog Input: signal = 4 mA.
D Modbus: position demand = 0.
2. Turn on power to the unit.
3. Apply a change in position demand to ensure unit responds properly.
D DryContact:
D Closed contact between pins COMMON and OPEN will open the valve.
D Dual contact / L2e only: Closed contact between pins COMMON and OPEN will open the valve. Closed contact
between pins COMMON and CLOSE will close the valve.
D Analog Input: valve will respond to proportional demand.
18
Instruction Manual
D104188X012
D Modbus: valve will respond to positional demand in register 40001. 0 = fully closed and 1000 = fully open.
4. If the valve does not respond as expected, proceed to Troubleshooting guide on page 19.
5. Check conduit ports.
D Conduit seal must be in place within 450mm (18 inches) of the enclosure.
D Unused conduit ports must be sealed with an explosionproof port plug.
6. Replace the cover and tighten all 8 bolts to 20 Nm (15 ftlbs).
D4 Valve with Gen 2 easy-Drive Actuator

Troubleshooting

1. Unit does not move.
a. Verify that 12VDC to 24VDC is present on the power terminals as shown on the cover. Green heartbeat LED will
pulse near Modbus terminals when power is present.
b. Verify that all wires are firmly attached on both ends.
April 2022
c. Verify that wires are connected to the correct terminals - see Wiring in the manual.
d. Verify mode of operation (on/off or positioning) matches control signal.
e. Verify mode of control (local or Modbus) matches control signal.
2. Unit does not respond to 420 mA signal
a. Verify that 12VDC to 24VDC is present on the power terminals as shown on the cover.
b. Verify that the 420 mA signal is wired correctly and that the terminals are firmly on the wires.
c. Verify mode of operation matches control signal (local control: 40067=0, positioning: 40065=1).
d. Check the value of the analog input in register 40026 to determine if it is 0 or greater.
i. If register 40026 shows 0, the 4-20 mA may be wired backwards. Swap wire and attempt again.
3. Diagnostics show a Motor Stall - Travel Deviation Fault.
a. The easyDrive electric actuator is designed to operate in a manner consistent with a pneumatic actuator. This
means that if the valve plug can not move to its commanded position, the actuator will stop, without damage, and issue a Motor Stall - Travel Deviation Fault warning. When the command signal changes outside of the deadband (Modbus register 40036), it will attempt to move again. Recalibrate the actuator span per instructions in the Startup section of this manual.
19
D4 Valve with Gen 2 easy-Drive Actuator
April 2022
Instruction Manual
D104188X012

Maintenance

Refer to figure 22.
Valve parts are subject to normal wear and must be inspected and replaced as necessary. The frequency of inspection and maintenance depends on the severity of the service conditions.
WARNING
Avoid personal injury from sudden release of process pressure or bursting of parts. Before performing any maintenance operations:
D Do not remove the actuator from the valve while the valve is still pressurized.
D Always wear protective gloves, clothing, and eyewear when performing any maintenance operations to avoid personal
injury.
D Disconnect any operating lines providing air pressure, electric power, or a control signal to the actuator. Be sure the
actuator cannot suddenly open or close the valve.
D Use bypass valves or completely shut off the process to isolate the valve from process pressure. Relieve process pressure
on both sides of the valve. Drain the process media from both sides of the valve.
D Vent the power actuator loading pressure and relieve any actuator spring precompression.
D Use lock‐out procedures to be sure that the above measures stay in effect while you work on the equipment.
D The valve packing box may contain process fluids that are pressurized, even when the valve has been removed from the
pipeline. Process fluids may spray out under pressure when removing the packing hardware or packing rings.
D Check with your process or safety engineer for any additional measures that must be taken to protect against process
media.
WARNING
For explosionproof applications, ensure the actuator cover is properly bolted before applying power to the actuator. Personal injury or property damage may result from fire or explosion if power is applied to the actuator with the cover removed in a hazardous area.
Do not remove the actuator cover for 10 minutes after power is disconnected if the UPS option is installed.
For explosion‐proof applications, install rigid metal conduit and a conduit seal no more than 457 mm (18 inches) from the actuator. Personal injury or property damage may result from explosion if the seal is not installed.
Select wiring and/or cable glands that are rated for the environment of use (such as hazardous area, ingress protection, and temperature). Failure to use properly rated wiring and/or cable glands can result in personal injury or property damage from fire or explosion.
Wiring connections must be in accordance with local, regional, and national codes for any given hazardous area approval. Failure to follow the local, regional, and national codes could result in personal injury or property damage from fire or explosion.

Valve Plug and Seat Ring

Disassembly

Key Numbers are referenced in figures 21 and 22.
1. Isolate the control valve from the line pressure, release pressure from both sides of the valve body (key 1), and drain
the process media from both sides of the valve.
20
Instruction Manual
D104188X012
D4 Valve with Gen 2 easy-Drive Actuator
April 2022
CAUTION
The following steps are intended to prevent damage to the valve plug (key 3) and seat ring (key 2) during the removal of the bonnet and actuator.
2. For Positioning Actuators
Command the valve to anywhere between 10% and 20% travel.
•Isolate power and signal.
•Proceed to step 3.
For ON/OFF Actuators
Command the valve to open or close, and cut the power when the valve is at midstroke.
•Isolate power and signal.
•Proceed to step 3.
3. Break the hammer nut (key 6) loose with a hammer. Continue turning the hammer nut by using a hammer or a
large adjustable wrench, tightened around one ear of the hammer nut. If the bonnet is stuck on the valve, continue to unscrew the hammer nut. The hammer nut will contact the spring pins (key 7) and will force the bonnet out of the valve. Carefully lift the actuator, bonnet, and valve plug assembly from the valve body.
WARNING
The spring pins must always be in place during valve operation. They provide a safeguard against injury when the unit is being disassembled.
4. Use a socket wrench to loosen the seat ring (key 3).
5. Remove the seat ring (key 3) and seat ring gasket (key 9) from the valve body.
6. To replace the plug, the stem nut (key 42) must be removed to expose the groove pin (key 4). Open the
explosionproof enclosure (key 60), using a 13 mm wrench.
7. Remove the stem nut (key 42) using a 11/16 inch wrench; insert a punch in the hole in the stem to restrict rotation
of the stem while removing the stem nut. The travel indicator (key 32) may need to be moved to expose the hole.
8. Push the stem downward just far enough to expose the groove pin (key 4) on the plug.
9. Remove the plug by driving out the groove pin and unscrewing the valve plug from the stem.
WARNING
Be careful to avoid damaging the seating surface on the valve plug or seat ring as damage in these areas will allow excessive leakage at shutoff. Avoid damaging the highly polished valve stem surface. A damaged valve stem could cut the packing and allow process fluid to leak to the atmosphere.
Table 7. Torque for Seat Ring (Key 3)
VALVE SIZE, NPS
1 407 300
2 698 515
NSm LbfSft
RECOMMENDED TORQUE
21
D4 Valve with Gen 2 easy-Drive Actuator
April 2022
Instruction Manual
D104188X012

Assembly

1. Make sure the bonnet O‐ring (key 8) is on the bonnet and lubricated with lithium grease (key 49).
2. Install the plug (key 2) on the stem (key 47) and insert a new groove pin (key 4).
3. Push the plug and stem upward to ensure the threads on the top of the stem are exposed. Thread the stem nut (key
42) onto the top of the stem and tighten the stem nut (key 42) to 39 N•m (29lbf•ft). Insert a punch in the hole in the stem to restrict rotation while tightening the stem nut.
4. Replace the top of the explosion proof enclosure (key 60) and tighten cap screws (key 64) to 20 N•m (15 lbf•ft).
5. Thoroughly clean the seat ring and bonnet threads in the valve body (key 1). Also clean the valve body seat ring
gasket surfaces.
6. Apply anti-seize lubricant (key 54) to the threads of the seat ring (key 3), and its mating threads in the valve body.
7. Apply anti-seize lubricant (key 54) to the seat ring gasket (key 9) and install into the valve body.
8. Screw the seat ring into the valve body. Use a socket wrench to tighten the seat ring to the torque valves shown in
table 7. Remove all excess lubricant after tightening.
9. Lubricate (key 54) the threads on the valve body and hammer nut and the contact surfaces of the bonnet and
hammer nut flange. Install the bonnet and actuator assembly with pinned valve plug onto the valve body. Tighten the hammer nut using an adjustable wrench until the nut stops turning. A few hammer blows will be required to ensure the assembly is tight.

Valve Packing

WARNING
Observe the warning at the start of the Maintenance section.
The valve stem packing can only be accessed from within the valve body. If packing maintenance is required, first disassemble per steps 1, 2, and 6 or 7 in the Valve Plug and Seat Ring Disassembly section of this document.
Note
Packing installation and adjustment is critical to the long-term packing performance. Absolutely no deviations from this procedure are allowed.
To minimize friction and maximize sealing performance, a small amount of fluorinated grease (key 56) is placed between the packing rings.
Single Packing Arrangement
The packing components are to be installed as shown in the assembly drawing per the following procedure:
1. Install packing spacer (key 48) in the packing box.
2. Using a non-marring installation tool, such as a 12 inch length of 1/2 inch PVC pipe, push the first anti-extrusion
washer (key 12) fully into the packing box by hand. Then, use the packing spacer (key 14) to fully seat the anti-extrusion washer by firmly tapping the packing spacer against the anti-extrusion washer with a hammer and the PVC pipe.
22
Instruction Manual
D104188X012
D4 Valve with Gen 2 easy-Drive Actuator
April 2022
3. Using a needle point syringe filled with fluorinated grease, apply a continuous bead of approximately 3/16 inch
diameter inside the V-groove of the female adaptor ring. See figure 2. Take care to keep the lubricant confined to only the V-groove. Do not lubricate the other surfaces of the packing ring, the stem, or the packing box.
CAUTION
All D4 packing kits include a single use packet of high performance fluorinated grease. This is the only acceptable D4 packing lubricant.
4. Install the female adaptor ring using the packing spacer and PVC pipe to push the ring against the anti-extrusion
washer. Apply only enough force to cause the female adaptor to make contact.
5. Using a needle point syringe filled with fluorinated grease, apply a continuous bead of approximately 3/16 inch
diameter inside the V-groove of the white V-ring. See figure 2. Take care to keep the lubricant confined to only the V-groove. Do not lubricate the other surfaces of the packing ring, the stem, or the packing box.
6. Install the V-ring using the packing spacer and PVC pipe to push the V-ring against the female adaptor. Apply only
enough force to cause the female adaptor to make contact.
7. Install the male adaptor.
8. Using the PVC pipe, push the second anti-extrusion washer (key 12) fully into the packing box by hand. Then, use
the packing spacer (key 14) to fully seat the anti- extrusion washer by firmly tapping the packing spacer against the anti-extrusion washer with a hammer and the PVC pipe.
9. Install the packing spacer (key 14) and five Belleville springs (key 11). The Belleville springs (key 11) should be single
stacked with the ID of the inner spring contacting the packing spacer (key 14) and the OD of the outer spring contacting the packing retainer (key 10). The final Belleville spring should be within the 1.26 inch-diameter bore of the bonnet.
10. Adjust the packing retainer by hand until it contacts the Belleville springs. Do not tighten by hand, simply install the packing retainer until it contacts the Belleville springs. Torque the packing retainer to 68 NSm (50 lbfSft).
23
D4 Valve with Gen 2 easy-Drive Actuator
April 2022
Figure 19. Fisher D4 Packing Installation
UNTIGHTENED, NOTE THE GAP
UPPER PACKING SPACER (KEY 48)
Instruction Manual
D104188X012
FULLY TIGHTENED,
FULLY TIGHTENED, NO GAP
NO GAP
BELLEVILLE SPRINGS FULLY ENCLOSED BY
THE PACKING RETAINER
FULLY TIGHTENED, NO GAP
PACKING RETAINER (KEY 8)
VALVE PLUG, BELLEVILLE SPRINGS, AND PACKING
RETAINER CORRECTLY
INSTALLED AND TIGHTENED
24
VALVE PLUG, BELLEVILLE SPRINGS, AND PACKING
RETAINER CORRECTLY
INSTALLED AND TIGHTENED
(DOUBLE PTFE)
Instruction Manual
D104188X012
Figure 20. Lubrication Locations on Packing
FEMALE PACKING ADAPTER
D4 Valve with Gen 2 easy-Drive Actuator
April 2022
PACKING RING
MALE PACKING ADAPTER
LUBRICATE WITH 3mm (1/8 INCH BEAD) OF SUPPLIED HIGH PERFORMANCE FLUORINATED GREASE
LUBRICATE WITH 3mm (1/8 INCH BEAD) OF SUPPLIED HIGH PERFORMANCE FLUORINATED GREASE
Double Packing Arrangement
The packing components are to be installed as shown in the assembly drawing per the following procedure:
1. Using a non-marring installation tool, such as a 12 inch length of 1/2 inch PVC pipe, push the first anti-extrusion washer (key 12) fully into the packing box by hand. Then, use the packing spacer (key 14) to fully seat the anti-extrusion washer by firmly tapping the packing spacer against the anti-extrusion washer with a hammer and the PVC pipe.
2. Using a needle point syringe filled with fluorinated grease, apply a continuous bead of approximately 3/16 inch diameter inside the V-groove of the female adaptor ring. See figure 2. Take care to keep the lubricant confined to only the V-groove. Do not lubricate the other surfaces of the packing ring, the stem, or the packing box.
CAUTION
All D4 packing kits include a single use packet of high performance fluorinated grease. This is the only acceptable D4 packing lubricant.
3. Install the female adaptor ring using the packing spacer and PVC pipe to push the ring against the anti-extrusion washer. Apply only enough force to cause the female adaptor to make contact.
4. Using a needle point syringe filled with fluorinated grease, apply a continuous bead of approximately 3/16 inch diameter inside the V-groove of the white V-ring. See figure 2. Take care to keep the lubricant confined to only the V-groove. Do not lubricate the other surfaces of the packing ring, the stem, or the packing box.
5. Install the V-ring using the packing spacer and PVC pipe to push the V-ring against the female adaptor. Apply only enough force to cause the female adaptor to make contact.
6. Install the male adaptor.
7. Install the packing spacer (key 14).
8. Using a needle point syringe filled with fluorinated grease, apply a continuous bead of approximately 3/16 inch diameter inside the V-groove of the female adaptor ring. See figure 2. Take care to keep the lubricant confined to only the V-groove. Do not lubricate the other surfaces of the packing ring, the stem, or the packing box
9. Install the female adaptor ring using the packing spacer and PVC pipe to push the ring against the anti-extrusion washer. Apply only enough force to cause the female adaptor to make contact.
25
D4 Valve with Gen 2 easy-Drive Actuator
April 2022
Instruction Manual
D104188X012
10. Using a needle point syringe filled with fluorinated grease, apply a continuous bead of approximately 3/16 inch diameter inside the V-groove of the white V-ring. See figure 2. Take care to keep the lubricant confined to only the V-groove. Do not lubricate the other surfaces of the packing ring, the stem, or the packing box.
11. Install the V-ring using the packing spacer and PVC pipe to push the V-ring against the female adaptor. Apply only enough force to cause the female adaptor to make contact.
12. Install the male adaptor.
13. Using the PVC pipe, push the second anti-extrusion washer (key 12) fully into the packing box by hand. Then, use the packing spacer (key 14) to fully seat the anti- extrusion washer by firmly tapping the packing spacer against the anti-extrusion washer with a hammer and the PVC pipe.
14. Install the packing spacer (key 14) and six Belleville springs (key 11). The Belleville springs (key 11) should be double stacked with the ID of the inner spring contacting the packing spacer (key 14) and the OD of the outer spring contacting the packing retainer (key 10). The final Belleville spring should be within the 1.26 inch-diameter bore of the bonnet.
15. Adjust the packing retainer by hand until it contacts the Belleville springs. Torque the packing retainer to 54 NSm (40 lbfSft).
26
Instruction Manual
D104188X012
D4 Valve with Gen 2 easy-Drive Actuator
April 2022

Parts Ordering

Each D4 control valve is assigned a serial number, which can be found on the nameplate. Refer to the number when contacting your Emerson sales office
for assistance or when ordering replacement parts.
WARNING
Use only genuine Fisher replacement parts. Components that are not supplied by Emerson should not, under any circumstances, be used in any Fisher valve, because they may void your warranty, might adversely affect the performance of the valve, and could cause personal injury and property damage.

Parts Kits

Board Replacement Kit (On/Off is default) GE83055X012
Board Replacement Kit + Positioning License Dongle GE83126X012
Motor/Gearbox Assembly GE84237X012
Motor/Gearbox/Board Assembly (On/Off is default) GE84238X012
Motor/Gearbox/Board Assembly + Positioning License Dongle GE89047X012
Replacement Kit, Belleville Springs GE78843X012
Positioning License Dongle (1 License) GE83574X012
Positioning License Dongle (5 License) GE83574X022
Repair Kits
Note
All repair kits are supplied with hydrogenated nitrile bonnet O‐ring. FKM (fluorocarbon) bonnet O‐ring must be ordered separately when required.
Description Part Number
* Packing Repair Kit
 Includes key numbers 4, 8, 12 (qty. 2),   13, and high performance fluorinated grease RD4X0000012
27
D4 Valve with Gen 2 easy-Drive Actuator
April 2022
Instruction Manual
D104188X012

Parts List

Note
Contact your Emerson sales office
Key Description
1 Valve Body 2* Valve Plug 3* Seat Ring 4* Groove Pin 5 Bonnet 6 Hammer Nut 7 Spring Pin 8* Bonnet O‐ring 9* Seat Ring Gasket 10 Packing Retainer 11 Belleville Springs (5 req'd) 12* Anti‐Extrusion Washer (2 req'd) 13* Packing Set
for Part Ordering Information.
Key Description
14 Packing Spacer 16 Valve Nameplate 17 Drive Screw 18* O‐ring 19 Stem O‐ring 32 Travel Indicator 42 Stem Nut 47* Valve Stem 48 Upper packing spacer 49 Lubricant (lithium grease) 54 Lubricant (anti‐seize) 56* High Performance Fluorinated Grease
Packing Lubricant 58 Enclosure O-ring 59 Motor/gearbox/controller assembly 60 Upper Enclosure 61 Lower Enclosure 62 Motor Cap Screws (4 req'd) 63 Motor Cap Screw Washers (4 req'd) 64 Enclosure Cap Screws (8 req'd) 65 Enclosure Cap Screw Retaining Washers (8 req'd) 66 Ground Screw 68 Certification Nameplate 69 easy-Drive Label
28
*Recommended spare parts
Instruction Manual
D104188X012
Figure 21. D4 Valve Assembly
D4 Valve with Gen 2 easy-Drive Actuator
April 2022
64
13 mm
60
65
62
13 mm
58
20
63
27
59
11/16 INCH
1-1/2 INCH
61
29
D4 Valve with Gen 2 easy-Drive Actuator
April 2022
Figure 22. Fisher D4 Valve Assembly
Instruction Manual
D104188X012
30
APPLY LUBRICANT
GE49375-B
Instruction Manual
D104188X012

Appendix A - Modbus

A.1 Register Summary

Table 8. Gen 2 easy-Drive Actuator Modbus Map
(1)
Type
uint16
uint16 Digital output 40002 0 R/W 0,1
uint16 Reset error codes 40003 0 R/W 0,1
uint16 RESERVED 40004
uint16 RESERVED 40005
uint16 RESERVED 40006
uint16 RESERVED 40007
uint16 RESERVED 40008
Modbus position command
Name MB Register Default R/W Values Notes
(100=10.0%)
40001 0 R/W 0-1000
D4 Valve with Gen 2 easy-Drive Actuator
April 2022
Modbus command value with one implied decimal place (1000=100.0%). R/W at all times but only used in Modbus control mode. In on/off mode 0-499 will result in a move to 0% and 500-1000 will result in a move to 100%.
0=no voltage supplied to terminals, 1=voltage supplied to terminals (Only used when output setup is set for Remote controlled)
Value of 1 will clear faults. Will automatically set back to 0.
uint16 RESERVED 40009
Present position of the actuator relative to span with
uint16 Actual position (100=10.0%) 40010 0 R 0-1000
uint16
uint16 Diagnostic Flags 40012 0 R 0-65535 Bit flags - see chart
uint16 Digital status 40013 0 R 0 - 1
uint32 Total Running Time (min) 40014, 40015 0 R 4294967296
uint32 Total Open Time (min) 40016, 40017 0 R 4294967296
uint32 Total Closed Time (min) 40018, 40019 0 R 4294967296
uint32 Number of Closed (Cycle count) 40020, 40021 0 R 4294967296
uint32 Number of Power Cycles 40022, 40023 0 R 4294967296
uint32 Number of Movements 40024, 40025 0 R 4294967296
uint16 Analog input control value 40026 0 R 0-2400
uint16 Incoming voltage 40027 0 R 0-350
uint16 Latch Open State 40028 0 R 0 - 1 Normally open latch state
Commanded position
(100=10.0%)
40011 0 R 0-1000
-Continued-
1 implied decimal place (1000=100.0%). Valid for all control modes.
Present position command of the actuator relative to span (1000=100.0%). Valid for all control modes.
0=no connection between terminals, 1=connection between terminals (Status of digital input or output)
Total number of minutes the actuator has been powered on since time has been reset
Total number of minutes the actuator has been at 100% of travel since time has been reset
Total number of minutes the actuator has been at 0% of travel since time has been reset
Total number of close cycles the actuator has performed since reset. One open/close cycle counts as 1.
Total number of times the actuator has been powered on.
Total number of movements the actuator has performed. Move must be at least 5% of rated travel for cycle to increment.
Value of the analog signal in mA with 2 implied decimals. In analog control mode, this is the command value and is subject to the analog settings in registers 40046 to 40059. Always active but a slower refresh rate when unit is not in analog control mode.
Diagnostic register - value of incoming voltage with 1 implied decimal.
31
D4 Valve with Gen 2 easy-Drive Actuator
Instruction Manual
April 2022
Table 8. Gen 2 easy-Drive Actuator Modbus Map (cont.)
Type Name MB Register Default R/W Values Notes
uint16 Latch Close State 40029 0 R 0 - 1 Normally closed latch state
uint16 RESERVED 40030
uint16 RESERVED 40031
uint16 RESERVED 40032
uint16 RESERVED 40033
uint16 RESERVED 40034
uint16 RESERVED 40035
uint16 RESERVED 40036
uint16 RESERVED 40037
uint16 RESERVED 40038
uint16 RESERVED 40039
uint16 Test Register - 16 bit 40040 45964 R 45964
uint32 Test Register - 32 bit 40041, 40042 3,012,341,331 R 3,012,341,331
uint16 Span calibration 40043 0 R/W 0,1
uint16 RESERVED 40044
Fixed register to test correct reading of 16 bit registers - Hex=B38C, Binary=1011001110001100
Fixed register to test correct reading of 32 bit registers - Hex=B38C AE53, Binary=1011001110001100 1010111001010011
Value of 1 will initiate span calibration. Will automatically set back to 0.
D104188X012
uint16 RESERVED 40045
uint16 RESERVED 40046
uint16 RESERVED 40047
uint16 RESERVED 40048
uint16 RESERVED 40049
uint16
uint16 Modbus timeout (s) 40051 60 R/W 0-65535
uint16 Dual contact timeout (s) 40052 60 R/W 0-3600
Loss of signal position
(100=10.0%)
40050 0 R/W 0-1001
-Continued-
Position to which valve plug will be driven upon loss of signal. Loss of signal is based upon the active control mode. 0-1000=0-100.0% with 1 implied decimal point. In on/off mode 0-499 will result in movement to 0% while 500-1000 will result in movement to 100%. A value of 1001 in any control mode is the setting for "lock-in-last".
Time without a valid Modbus message is seen (to any address) before "loss of signal" motion is engaged when in Modbus control mode. Only active in Modbus control mode. 0=disabled
Time without a digital signal being low (contact made) from either digital input as viewed by voltage level on the digital input terminals. If neither contact has been made (pulled input low) within the timeout period, the valve plug will be moved to the loss-of-signal position. Only active in the local, on-off, dual contact mode. 0=disabled.
32
Instruction Manual
D4 Valve with Gen 2 easy-Drive Actuator
D104188X012
Table 8. Gen 2 easy-Drive Actuator Modbus Map (cont.)
Type Name MB Register Default R/W Values Notes
Minimum percentage signal change to elicit a movement response based upon end position of last movement. For example, if the previous command
uint16 Deadband (10=1.0%) 40053 5 R/W 0-250
uint16
uint16
uint16
uint16 Analog Close Value 40057 40 R 31 - 220
uint16 Analog Open Value 40058 200 R 31 - 220
uint16 Number of retries 40059 2 R/W 0-4
uint16 RESERVED 40060
Low travel cutoff position
(100=10.0%)
Analog on/off close position
(100=10.0%)
Analog on/off open position
(100-10.0%)
40054 50 R/W 0-999
40055 400 R/W 0-999
40056 500 R/W 1-1000
resulted in the actuator moving to 31.2% of travel and deadband is set to 100 (10.0%), setpoint must command valve to 21.2% or 41.2% before valve will move to new position. Default is set set to minimize signal dithering.
Analog input command, in percent with one implied decimal (50=5.0%), below this value will result in the valve plug moving to the closed position. Active in both local and Modbus control modes.
When the valve is in 4-20 mA on/off mode, this value is the point at which the valve will close. It must be set to a smaller value than the analog on/off open position. Percentage position value with one implied decimal (400=40.0%).
When the valve is in 4-20 mA on/off mode, this value is the point at which the valve will open. It must be set to a larger value than the analog on/off close position. Percentage position value with one implied decimal (500=50.0%).
The analog value, in mA with one implied decimal (40=4.0 mA), that defines the closed position
The analog value , in mA with one implied decimal (200=20.0 mA), that defines the open position
When the valve plug encounters an obstruction, how many attempts will it make to move past that point, assuming no change in the command signal within the deadband range
April 2022
uint16 RESERVED 40061
uint16 RESERVED 40062
uint16 RESERVED 40063
uint16 RESERVED 40064
uint16 RESERVED 40065 uint16 RESERVED 40066
0=Dual Contact On/Off 1=Single Contact On/Off,
uint16 Control Source 40067 0 R/W 0-5
uint16 Valve Type 40068 1 R/W 1-10 1=D3, 2=D4
uint16 RESERVED 40069
uint16 RESERVED 40070
uint16 RESERVED 40071
uint16 RESERVED 40072
uint16 RESERVED 40073
uint16 Modbus address 40074 1 R/W 1-247 Slave Address of the actuator
uint16 Baud Rate 40075 5 R/W 4,5,6,7
uint16 Parity 40076 0 R/W 0,1,2 0=Even, 1=Odd, 2=None
uint16 Modbus stop bits 40077 1 R/W 0,1,2
uint16 MSB/LSB 40078 0 R/W 0,1 0=MSB (Big Endian), 1=LSB (Little Endian)
-Continued-
2=Modbus On/Off, 3=Modbus Positioning, 4=4-20 Positioning, 5=4-20 Level
4=4800 baud, 5=9600 baud (default), 6=19200 baud, 7=38400 baud
1 stop bit is the standard with even and odd parity while 2 stop bits is the standard for none.
33
D4 Valve with Gen 2 easy-Drive Actuator
Instruction Manual
April 2022
Table 8. Gen 2 easy-Drive Actuator Modbus Map (cont.)
Type Name MB Register Default R/W Values Notes
uint16 RESERVED 40079
uint16 Digital I/O selection 40080 1 R/W 0,1
uint16 Digital I/O output setup 40081 0 R/W 0,1,2,3
uint16 Digital I/O input setup 40082 0 R/W 0,1
uint16 RESERVED 40083
uint16 RESERVED 40084
uint16 RESERVED 40085
uint16 RESERVED 40086
uint16 RESERVED 40087
uint16 RESERVED 40088
uint16 RESERVED 40089
uint16 RESERVED 40090
uint16 RESERVED 40091
uint16 RESERVED 40092
uint16 RESERVED 40093
uint32 Device Tag 40094-40113 "easyDrive2" R/W
uint32 Valve serial number 40114, 40115 0 R/W* 0-4,294,967,296
uint32 Motor serial number 40116, 40117 0 R/W* 0-4,294,967,296 Motor/gearbox serial number uint32 Motor revision 40118, 40119 0 R/W* 0-4,294,967,296 Motor/gearbox revision uint32 PCB serial number 40120, 40121 0 R/W* 0-4,294,967,296 PCB serial number uint16 PCB revision 40122, 40123 0 R/W* 0-4,294,967,296 PCB revision uint16 Flash Firmware major revision 40124 0 R 0-65535 From flash firmware when compiled uint16 Flash Firmware minor revision 40125 0 R 0-65535 From flash firmware when compiled uint16 Flash Firmware mod revision 40126 0 R 0-65535 From flash firmware when compiled uint16 Flash Firmware build revision 40127 0 R 0-65535 From flash firmware when compiled uint16 Boot Firmware major revision 40128 0 R 0-65535 From boot firmware when compiled uint16 Boot Firmware minor revision 40129 0 R 0-65535 From boot firmware when compiled uint16 Boot Firmware mod revision 40130 0 R 0-65535 From boot firmware when compiled uint16 Boot Firmware build revision 40131 0 R 0-65535 From boot firmware when compiled
uint32 PCB test date 40132, 40133
uint32 Motor test date 40134, 40135 0 R/W* 0-4,294,967,296
uint32 System completion date 40136, 40137 0 R/W* 0-4,294,967,296
1. uint is defined as unsigned integer uint16 – unsigned 16 bit variable, can take value 0-65535. uint32 – unsigned 32 bit variable, can take value 0-4294967295.
(Reserved) – registers used for development use only.
0 R/W* 0-4,294,967,296
0 - 255 per
character
† - 32bit register contains data that spans two registers – reads and write of data needs to be performed within the same Modbus command function to ensure coherency of data.
0=9 V sinking digital input, 1=25 mA at 10 V digital output
Valid only when Digital I/O selection is set to Output (1) - 0=In position, 1=Fully closed, 2=Fully open, 3 = Remote controlled (driven by Digital Output register)
Valid only when Digital I/O selection is set to Input (0)
- 0=Reference only (status appears in 40013 and does nothing else), 1=Override (status appears in 40013 and valve plug is moved to safe position noted in register 40050)
Device Tag (20 character UTF8 string)
Valve assembly serial number assigned at Fisher assembly plant
Seconds since January 1, 2000, Board Supplier Functional Test Date
Seconds since January 1, 2000, Motor Supplier Test Date
Seconds since January 1, 2000, Final Assembly Test Date
D104188X012
34
Instruction Manual
D104188X012
D4 Valve with Gen 2 easy-Drive Actuator
April 2022
Table 9. Diagnostic Fault Flags
Hex Value Bit Mask Description Value Bit Definition
0x8000 1000 0000 0000 0000
0x8000 1000 0000 0000 0000
0x4000 0100 0000 0000 0000 Motor Assembly Stall - Travel Deviation 16384 14
0x2000 0010 0000 0000 0000 Discrete Input override mode active 8192 13
0x1000 0001 0000 0000 0000 System or Watchdog fault 4096 12
0x0800 0000 1000 0000 0000
0x0400 0000 0100 0000 0000
0x0200 0000 0010 0000 0000 Analog Input span calibration not in legal range 512 9
0x0100 0000 0001 0000 0000 256 8
0x0080 0000 0000 1000 0000 Valve was shutdown while moving 128 7
0x0040 0000 0000 0100 0000 Valve span calibrated (informational) 64 6 Span has been calibrated and actuator is ready. 0x0020 0000 0000 0010 0000 Valve position controller active (informational) 32 5 Actuator is active and ready.
0x0010 0000 0000 0001 0000 Loss of signal active 16 4
0x0008 0000 0000 0000 1000 8 3
0x0004 0000 0000 0000 0100
0x0002 0000 0000 0000 0010
0x0001 0000 0000 0000 0001
Fault in N.V. Memory – system has restored default settings
Fault in N.V. Memory – system has restored default settings
Analog Input calibration value not in expected range
Valve travel distance calibration not in legal range
Modbus command has been sent (starts a calibrated system)
Analog input initialized (system has seen input >3 mA/1 V)
Start delay active (within 15 second calibration window)
32768 15
32768 15
2048 11
1024 10
4 2 The actuator is successfully moving the valve.
2 1 4-20 mA analog input has a valid signal present
1 0
A memory fault has occurred and the actuator has been restored to factory defaults. Contact your Emerson sales office
A memory fault has occurred and the actuator has been restored to factory defaults. Contact your Emerson sales office.
The actuator is unable to move to the commanded position and has stopped. Follow troubleshooting guide in Help section to remedy.
The digital input has detected a closed contact and the actuator has moved to its safe position. Check switch input device status.
The actuator has experienced a fatal error and shut down. Contact your Emerson sales office.
The analog values entered do not match the analog signal level. Check analog signal value and value entered.
The valve travel distance is outside the acceptable range. Confirm valve type and that no obstructions are present.
The analog values for open and close are less than 4 mA and previous values have been maintained. Calibrate analog input with differential >4 mA.
Actuator was powered down during a move and actual position may vary from commanded. Recalibrate the valve span.
Control signal not present. Signal is <3 mA, timeout period exceeded (40051 or 40052).
Span calibration using physical inputs allowed during startup
.
35
D4 Valve with Gen 2 easy-Drive Actuator
April 2022

Appendix B - Certificate of Conformance

Instruction Manual
D104188X012
36
Instruction Manual
D104188X012
D4 Valve with Gen 2 easy-Drive Actuator
April 2022
37
D4 Valve with Gen 2 easy-Drive Actuator
April 2022
Instruction Manual
D104188X012
38
Instruction Manual
D104188X012
D4 Valve with Gen 2 easy-Drive Actuator
April 2022
39
D4 Valve with Gen 2 easy-Drive Actuator
April 2022
Instruction Manual
D104188X012
Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Fisher and easy-Drive are marks owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. Emerson Automation Solutions, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.
Emerson Automation Solutions
Marshalltown, Iowa 50158 USA Sorocaba, 18087 Brazil Cernay, 68700 France Dubai, United Arab Emirates Singapore 128461 Singapore
www.Fisher.com
40
E 2016, 2022 Fisher Controls International LLC. All rights reserved.
Loading...