Fisher™ D4 Control Valve with easy-Drive
Electric Actuator
Contents
Introduction1.................................
Scope of Manual1.............................
Description3.................................
Specifications3...............................
Educational Services3.........................
Installation4..................................
Special Instructions for “Safe Use” and Installations
in Hazardous Locations5.....................
Startup Overview6............................
Important Technical Notice for easy-Drive
Electric Actuator10.........................
Default Input Signals10........................
Configuration10..............................
Input Configuration10.....................
Changing the Inputs from Default Settings11..
Modbus Setup11.............................
Calibration Instructions13..................
Troubleshooting15.............................
Maintenance16................................
Valve Plug and Seat Ring17.....................
Valve Packing18..............................
Parts Ordering21...............................
Repair Kits21..................................
Parts List21...................................
Appendix A25.................................
Figure 1. Fisher D4 Control Valve with easy-Drive
Electric Actuator
W9933-1
™
Introduction
Scope of Manual
This instruction manual provides installation, maintenance, and parts information for the Fisher D4 control valve with
easy-Drive electric actuator.
Do not install, operate, or maintain a D4 control valve with easy-Drive electric actuator without being fully trained and
qualified in valve, actuator, and accessory installation, operation, and maintenance. To avoid personal injury or
property damage, it is important to carefully read, understand, and follow all the contents of this manual, including all
safety cautions and warnings. If you have any questions about these instructions, contact your Emerson sales office
Local Business Partner before proceeding.
www.Fisher.com
or
D4 Valve with easy-Drive Actuator
October 2017
Table 1. Specifications
Instruction Manual
D103597X012
Valve Body Sizes and End Connection Styles
(1)
See table 2
Maximum Inlet Pressures and Temperatures
(1)
If the valve nameplate shows an ASME
pressure‐temperature class, maximum inlet pressure
and temperature is consistent with the applicable
class per ASME B16.34. If the nameplate does not
show an ASME class, it will show a maximum cold
working pressure at 38_C (100_F) (for example, 293
bar [4250 psi])
Maximum Pressure Drops
(1)
See table 4
Shutoff Classification per ANSI/FCI 70‐2
and IEC 60534‐4
Class IV
Material Temperature Capabilities
(1)
Valve Body Assembly:
Standard Bonnet O‐Ring: -40 to 135°C (-40 to 275°F)
Optional Fluorocarbon Bonnet O‐Ring: -23 to 204°C
(-10 to 400°F)
Flow Characteristic
Equal percentage
Flow Direction
Flow up only
Port Diameters
See table 2
Power Requirements
12 or 24VDC, minimum 4 amp power supply required
(fuse to 5 amps)
Maximum Current Draw
4 amps
Idle Current Draw
38 mA
Conduit Connections
Two 3/4 NPT connections
Stroke Length
19mm (0.75 inch)
Nominal Stroke Speed
(2)
3.9 mm/s (0.15 inch/s) at 24 VDC
2.2 mm/s (0.09 inch/s) at 12 VDC
Hazardous Area Approvals
CSA (C/US): ExplosionProof Class I, Division 1,
Groups C and D, T6, Ex d IIA T6, Class I, Zone 1, AEx d
IIA T6
ATEX Flameproof - Gas:
II 2 G ,Ex d IIA T6
IECEx Flameproof - Gas: Ex d IIA T6
Enclosure Rating
Type 4X and IP66
Valve Plug Travel
19 mm (0.75 inch)
Valve Plug Style
Micro‐Form valve plug
Available Actuator Configurations
On/off (snap acting)
Positioning (flow or pressure control)
1. The pressure or temperature limits in the referenced tables and any applicable ASME code limitations should not be exceeded.
2. 10% variation can be expected, based on temperature and pressure of application.
2
Duty Cycle
50% maximum
Enclosure Material
Cast aluminum alloy with powder coat paint
Approximate Weight:
22 - 51 kg (49 - 113 lbs), depending upon
construction
Instruction Manual
D103597X012
D4 Valve with easy-Drive Actuator
October 2017
Description
The D4 control valve with easy-Drive electric actuator is a compact, rugged valve designed primarily for high‐pressure
throttling applications. This valve is ideal for use on pressure and flow control applications within the oil and gas
production industry. The D4 valve also makes an excellent dump valve for high‐pressure separators and scrubbers.
The D4 control valve meets the metallurgical requirements of NACE MR0175/ISO 15156 without environmental limits
for temperatures below 135_C (275_F). If the temperature is above 135_C (275_F), the N07718 Belleville washers will
impose some limits, as shown in table 3.
Specifications
Table 1 lists specifications for the D4 control valve with easy-Drive electric actuator. Some of the specifications for a
given control valve as it originally comes from the factory are stamped on a nameplate located on the lower actuator
enclosure.
Educational Services
For information on available courses for the Fisher D4 control valve with easy-Drive electric actuator, as well as a
variety of other products, contact:
Table 3. D4 Environmental Limits for NACE MR0175/ISO 15156 with Sour Trim
MAXIMUM TEMPERATUREMAXIMUM H2S PARTIAL PRESSURE
_C_FMPapsia
2324500.230No
2044001.4200No
1993902.3330No
1913752.5360No
1493002.8400No
135275No LimitYes
Table 4. Fisher D4 easy-Drive Maximum Pressure Drop
PORT DIAMETERMAXIMUM PRESSURE DROP
mmInchBarpsi
6.4
9.5
12.7
19.1
25.4
31.8
1. Downstream pressure, P2, is limited to 2250 psig.
0.25
0.375
0.5
0.75
1
1.25
293
293
247
105
56
34
COMPATIBLE WITH
ELEMENTAL SULFUR?
(1)
(1)
4250
(1)
4250
(1)
3576
1518
814
495
3
D4 Valve with easy-Drive Actuator
October 2017
Instruction Manual
D103597X012
Installation
WARNING
Always wear protective gloves, clothing, and eyewear when performing any installation operations to avoid personal
injury.
To avoid personal injury or property damage caused by bursting of pressure‐retaining parts or by uncontrolled process
fluid, be certain the service conditions do not exceed the limits shown on the valve nameplate and in table 1. Use
pressure‐relieving devices required by government or accepted industry codes and good engineering practices.
Check with your process or safety engineer for any additional measures that must be taken to protect against process
media.
If installing into an existing application, also refer to the WARNING at the beginning of the Maintenance section in this
instruction manual.
WARNING
For explosionproof applications, ensure the actuator cover is properly bolted before applying power to the actuator.
Personal injury or property damage may result from fire or explosion if power is applied to the actuator with the cover
removed in a hazardous area.
For explosion‐proof applications, install rigid metal conduit and a conduit seal no more than 457 mm (18 inches) from the
actuator. Personal injury or property damage may result from explosion if the seal is not installed.
Select wiring and/or cable glands that are rated for the environment of use (such as hazardous area, ingress protection, and
temperature). Failure to use properly rated wiring and/or cable glands can result in personal injury or property damage
from fire or explosion.
Wiring connections must be in accordance with local, regional, and national codes for any given hazardous area approval.
Failure to follow the local, regional, and national codes could result in personal injury or property damage from fire or
explosion.
CAUTION
When ordered, the valve configuration and construction materials were selected to meet particular pressure, temperature,
pressure drop, and controlled fluid conditions. Responsibility for the safety of process media and compatibility of valve
materials with process media rests solely with the purchaser and end‐user. Since some body/trim material combinations
are limited in their pressure drop and temperature ranges, do not apply any other conditions to the valve without first
contacting your Emerson sales office
To avoid product damage, inspect the valve before installation for any damage or any foreign material that may have
collected in the valve body. Also remove any pipe scale, welding slag, or other foreign material from the pipeline.
or Local Business Partner.
WARNING
Avoid personal injury or property damage caused by possible actuator failure. The use of a rigidly‐mounted support on the
actuator casing may cause additional stress on the actuator leading to premature wear and/or failure of the actuator
components.
4
Instruction Manual
D103597X012
D4 Valve with easy-Drive Actuator
October 2017
CAUTION
To avoid product damage, inspect the valve before installation for any damage or any foreign material that may have
collected in the valve body. Also remove any pipe scale, welding slag, or other foreign material from the pipeline.
1. Before installing the control valve assembly, inspect it for any damage and for any foreign material that may have
collected in the valve body.
2. Remove any pipe scale, welding slag, and other foreign material from the pipeline.
3. The control valve can be installed in any position, but normally the actuator is vertical above the valve. Install the
valve so the flow direction arrow on the side of the valve indicates the direction of the process flow.
4. Install the valve following local and national piping codes when they apply to the application. For screwed
connections, treat the external pipe threads with a good grade pipe compound. For flanged valves, use suitable
gaskets between valve and pipeline flanges.
5. If continuous operation is required during maintenance and inspection, install a conventional three‐valve bypass
around the valve.
Special Instructions for “Safe Use” and Installations in Hazardous
Locations
ATEX/IECEx
WARNING
To avoid static discharge from the enclosure, do not rub or clean the enclosure with solvents. To do so could result in an
explosion. Clean with a mild detergent and water only.
The enclosure is nonconducting and may generate an ignitioncapable level of electrosatic charges under certain extreme
conditions. The user should ensure that the equipment is not installed in a location where it may be subjected to external
conditions (such as highpressure steam) which might cause a buildup of electrostatic charges on nonconducting surfaces.
Additionally, cleaning of the equipment shall only be done with a damp cloth.
To avoid damage to the enclosure, when screws are fully tightened into blind holes in enclosure walls, with no washer
fitted, at least one full thread shall remain free at the base of the hole.
5
D4 Valve with easy-Drive Actuator
October 2017
Startup Overview
Figure 2. Flowchart
Instruction Manual
D103597X012
WIRE PER WIRING
INSTRUCTIONS ON
PAGES 7-9
ARE YOU USING MODBUS
TO MONITOR REGISTERS?
NO
YES
YES
PROCEED TO
MODBUS SETUP
SECTION ON
PAGE 10
IS YOUR CONTROL
METHOD LISTED IN
TABLE 5 ON PAGE 10?
PROCEED TO
STARTUP SECTION
ON PAGE 14
NO
PROCEED TO
MODBUS SETUP
SECTION ON
PAGE 10
CHANGE INPUTS PER
INSTRUCTIONS ON
PAGE 12
6
Instruction Manual
D103597X012
Figure 3. Fisher D4 Valve with easy-Drive Actuator Wiring Diagram
CONTROLLER
POWER AND
CONTROL TERMINAL
MOTOR / GEARBOX ASSY
(GE48474)
GE47302-7
D4 Valve with easy-Drive Actuator
October 2017
FIELD WIRING CONNECTIONS
TOP VIEW CONTROLLER
Power Requirements
Ensure a stable DC power source is available, maintaining less than 5% ripple and sufficiently surge protected for the
application. A 4 amp (minimum) power supply is required. Use of a 36 volt transient voltage suppressor is highly
recommended.
Wiring Instructions
1. Observe local wiring requirements for hazardous location usage.
2. Conduit seals within 457 mm (18 inches) of the enclosure port are required for explosionproof installation.
3. 22AWG (0.33mm
2
) to 12AWG (3.31mm2) wire size required.
4. Fuse system to 5A.
5. Connect enclosure and analog signal shields.
6. Ensure power is turned off before connecting the wires.
Power
1. Connect 12 or 24 VDC reference to: –
2. Connect 12 or 24 VDC positive to: +
3. Be sure to tighten terminals sufficiently to ensure solid mechanical connection.
7
D4 Valve with easy-Drive Actuator
October 2017
Figure 4. Wiring - Analog Input
Instruction Manual
D103597X012
(420mA: 40033=1, 40034=1, 40043=0
Analog Input
1. Connect signal to terminal 3
2. Connect reference to terminal 4
3. Connect 250 ohm resistor between
terminals 3 and 4 as shown.
NOTE:
1. 40043=0 SETS ANALOG INPUT TO 1-5V AND ASSUMES USE OF RECOMMENDED EXTERNAL 250 OHM RESISTOR.
IF NO EXTERNAL RESISTOR IS USED, SET 40043=1.
(1)
)
Figure 5. Wiring - L2e
L2e (dual dry contact:
40033=0, 40034=0, 40043=0)
1. Connect L2e brown wire to terminal 1 (COMM (com))
2. Connect L2e red wire to terminal 2 (N.O. (OPEN))
3. Connect L2e blue wire to terminal 3 (N.C. (CLOSE))
Your actuator may be labelled:
1. COMM
2. N.O.
3. N.C.
or
1. com
2. OPEN
3. CLOSE
8
Instruction Manual
D103597X012
Figure 6. Wiring - Single Dry Contact
Dry Contact (single dry contact:
40033=0, 40034=0, 40043=1)
1. Connect one side of contact switch to terminal 1 (COMM)
2. Connect other side of contact switch to terminal 2 (N.O.)
D4 Valve with easy-Drive Actuator
October 2017
Figure 7. Wiring - Modbus Input
Modbus Input: 40033=1
1. Connect Channel A (T+) to terminal 5
2. Connect Channel B (T-) to terminal 6
Modbus Defaults
Address 1
9600 Baud
Even parity
1 Stop Bit
9
D4 Valve with easy-Drive Actuator
October 2017
Instruction Manual
D103597X012
Important Technical Notice for easyDrive Electric Actuator
When using the easyDrive electric actuator with a 420mA control signal, the unit should always have 12/24VDC
power present on the power input terminals prior to applying the 420mA signal, unless an external 250 ohm resistor
is installed per figure 4. Failure to do so could result in damage to the analog input circuitry.
It is strongly recommended to place an external 250 ohm resistor between terminals 3 and 4 when using a 4-20mA
signal to control the actuator. When the actuator is configured to 1-5V input with an external 250 ohm resistor in
place, a 4-20mA signal may be safely used without danger to input circuitry.
This order of operation must always be maintained when powering the unit on if no external 250 ohm resistor is used:
1. 12/24VDC power on
2. 420mA control signal engaged
This order of operation must always be maintained when powering the unit off:
1. 420mA control signal disengaged
2. 12/24VDC power off
The result of not following this order of operation could result in permanent damage
to the analog input circuitry. This
damage can result in the inability of the controller to see the control signal, resulting in the actuator moving the valve
plug to the loss of signal position.
Default Input Signals
The D4 with easyDrive comes from the factory calibrated and ready for use with the following default input signals
shown in table 5.
Table 5. D4 easy-Drive Default Input Signals
CONFIGURATIONON/OFFPOSITIONING
Input SignalL2e (dual dry contact)4-20 mA
If the input signal of the application matches table 5, proceed to the Wiring Instructions section. If the input signal of
the application does not match table 5, proceed to the Configuration section.
Configuration
Input Configuration
There are 2 functional configurations available for the easyDrive electric actuator: On/Off and Positioning. It is not
possible to change an actuator from On/Off to Positioning after it has been delivered from the factory. Version 4.21
and higher firmware will allow a positioning unit to be changed to on/off.
All available input signals are shown in table 6.
Table 6. All Available Input Signals
CONFIGURATIONON/OFFPOSITIONING
Control SourceModbusLocalModbusLocal
Input SignalModbus
L2e Dual Dry
Contact (default)
Single Dry ContactModbus4-20 mA (default)1-5 V
If you are using the default inputs signals, and the valve has not been disassembled or adjusted in any way, there is no
need to recalibrate the assembly. You can proceed directly to Startup (page 12).
10
Instruction Manual
D103597X012
D4 Valve with easy-Drive Actuator
October 2017
Changing the Inputs from Default Settings
All configuration within the valve is done by setting values in Modbus registers. This can be done using any Modbus
master (flow computer, PLC, PC). Configuration software, providing a visual interface to the registers, is available
through your Emerson local business partner or the Fisher website.
Modbus setup
Use the instructions in the instruction manual for the Modbus master to initiate the connection. The D4 with
easyDrive electric actuator Modbus factory defaults are Address 1, 9600 baud, even parity, 1 stop bit.
When a connection has been achieved, the actuator may be configured to accept the input signal over the Modbus
link (ignoring the physical inputs) and the Modbus settings may be changed to accommodate the network to which it
is attached. Other changes to functionality are possible, such as:
D Low level cutoff: 40037 (default is 5%)
D Position upon loss of signal: 40035 (default is 0%)
See Appendix A for a full map of Modbus registers and their functions.
Connecting using the Fisher easyDrive configuration software
The Fisher easyDrive configuration software allows configuration and diagnosing of the Fisher easyDrive electric
actuator with a graphical interface. Connect a PC to the actuator using a USB or serial to Modbus RTU converter using
the wiring instructions above. The USB or serial device will be visible in the drop menu under Serial Port Settings. Baud
rate and parity should be set to the Modbus settings of the actuator. Default actuator settings are 9600 baud and Even
parity.
Use the Fisher easyDrive configuration software (figure 8) to make the desired changes, or register values may be
changed to allow different functionality. Modbus register 40034 dictates whether the unit will respond to a physical
signal or to the value in Modbus register 40001. A value of 0 in register 40034 will result in the actuator responding to
the value in 40001 and a value of 1 will result in the actuator responding to physical control signals.
Note
If an actuator is on/off, a Modbus command of 049 in register 40001 will cause the valve to close fully, while a value of 50100 will
cause the valve to open fully.
Local to Modbus Control
Modbus
D Set register 40034 (Control Source)
D 1 = Local Control
D 0 = Modbus control
Configuration Software
D Use radio button to select Local Control or Modbus Control.
420mA to 15V Control
Modbus
D Set register 40043 (Analog I/P mode)
D 0 = 15V
D 1 = 420mA
Configuration Software
D Use radio button to select 420mA or 15V local analog control when Control Source is set to Local.
L2e (Dual dry contact) to Single Dry Contact Control
Modbus
D Set register 40043 (Analog I/P mode)
12
Instruction Manual
D103597X012
D 0 = L2e (Dual dry contact)
D 1 = Single dry contact
Configuration Software
D Use radio button to select L2e or Single pole local digital control when Control Source is set to Local.
D4 Valve with easy-Drive Actuator
October 2017
Calibration Instructions
WARNING
To avoid personal injury or property damage, be aware that the valve will open fully and then close fully during the
calibration cycle.
It is not necessary to calibrate your easyDrive electric actuator prior to use from a factory shipment.
If any of the following are true, recalibration will be required (see next section)
D The actuator has been remounted on a different valve since shipment
D Disassembly of the valve for trim or packing changes
D A new version of firmware has been loaded on the controller
The following scenarios do not require recalibrations
D New unit from the box
D Power dips or interruptions
D Changing of control method (i.e. from 420mA to Modbus control)
D Extended periods of storage
Calibration with the use of Modbus
1. After the unit has been properly wired and fused per instructions in the Wiring section of this instruction manual,
turn power to the unit on.
2. Calibrate using Modbus:
a. Send position command of 0% to actuator to prevent unexpected motion. Valve will move to commanded
position following the calibration procedure.
b. Send a value of 1 to register 40003. Valve plug will move to fully closed. The valve plug will then return to the
commanded position.
If a Modbus connection is not available, and recalibration is desired, use the appropriate calibration method as
determined by the control method of your valve.
Calibration without the use of Modbus
1. Turn power to the actuator off
13
D4 Valve with easy-Drive Actuator
October 2017
2. Wait for 10 seconds to ensure all circuits have discharged.
3. Return power to the actuator and use the appropriate calibration method for your control signal. Calibration
sequence must be done within 15 seconds of power being switched on.
4. For On/Off operation using L2e dualinput dry contact:
a. Close the contact to create a short between pins 1 and 2 – valve plug will not move at this time.
b. Close the contact to create a short between pins 1 and 3 – valve plug will move to the lower, closed position.
5. For On/Off operation using single dry contact:
a. Close the contact to create a short between pins 1 and 2 – valve plug will not move at this time.
b. Open the contact to create an open circuit between pins 1 and 2 – valve plug will move to the lower, closed
position.
6. For positioning operation using 420mA:
a. Apply a 20mA signal between pins 3 and 4 – valve plug will not move at this time.
b. Apply a 4mA signal between pins 3 and 4 – valve plug will move to the lower, closed position.
c. If calibration of the analog input is desired to improve positional accuracy, an optional operation is listed in the
next section titled Analog Input Calibration.
Instruction Manual
D103597X012
7. For positioning operation using 15V:
a. Apply a 5V signal between pins 3 and 4 – valve plug will not move at this time.
b. Apply a 1V signal between pins 3 and 4 – valve plug will move to the lower, closed position.
c. If calibration of the analog input is desired to improve positional accuracy, an optional operation is listed in the
next section titled Analog Input Calibration.
8. The unit is now calibrated.
Analog Input Calibration
Improved positional accuracy may be obtained by calibrating the actuator to the analog signal input. The position of
the valve plug is linearly proportional to the analog control signal end points, with 4 mA/1V equating to fully closed
and 20 mA/5V equating to fully open.
1. Apply a 4 mA or 1V signal between pins 3 and 4 - valve plug will move to the fully open position.
2. Send a value of 1 to register 40004 or click Analog Cal at 0% in the configuration software.
3. Apply a 20 mA or 5V signal between pins 3 and 4 - valve plug will move to the fully closed position.
4. Send a value of 1 to register 40005 or click Analog Cal at 100% in the configuration software.
5. The unit is calibrated to your analog signal.
Start Up
WARNING
To avoid personal injury or property damage, be aware that the valve will move and respond to an input signal during start
up.
14
Instruction Manual
D103597X012
1. Before turning on power to the unit, be sure that a closed signal is being commanded to the unit
D DryContact: contact is open
D L2e (Dual Dry Contact): Contact closed across pins 1 & 3
D Analog Input: signal < 4mA or 1V
D Modbus: position demand = 0
2. Turn on power to the unit
3. Apply a change in position demand to ensure unit responds properly
D DryContact:
D Closed contact between pins 1 & 2 will open the valve
D Dual contact / L2e only (40043=0) : Closed contact between pins 1 & 2 will open the valve. Closed contact
between pins 1 & 3 will close the valve
D Analog Input: valve will respond to proportional demand
D4 Valve with easy-Drive Actuator
October 2017
D Modbus: valve will respond to positional demand in register 40001. 0 = fully closed and 100 = fully open.
4. If the valve does not respond as expected, proceed to Troubleshooting guide on page 15.
5. Check conduit ports
D Conduit seal must be in place within 450mm (18 inches) of the enclosure
D Unused conduit ports must be sealed with an explosionproof port plug
6. Replace the cover and tighten all 8 bolts to 20 Nm (15 ftlbs)
Troubleshooting
1. Unit does not move
a. Verify that 12VDC to 24VDC is present on the power terminals as shown on the cover
b. Verify that all wires are firmly attached on both ends
c. Verify that wires are connected to the correct terminals - see Wiring in the manual
d. Verify mode of operation (on/off or positioning) matches control signal
e. Verify mode of control (local or Modbus) matches control signal
2. Unit does not respond to 420mA signal
a. Verify that 12VDC to 24VDC is present on the power terminals as shown on the cover.
b. Verify that the 420mA signal is wired correctly and that the terminals are firmly on the wires.
c. Verify mode of operation matches control signal (local control: 40033=0, positioning: 40034=1).
15
D4 Valve with easy-Drive Actuator
October 2017
Instruction Manual
D103597X012
d. Check the value of the analog input in register 40025 (middle right of configuration software screen) to
determine if it is 0 or greater.
i. If register 40025 shows 0 and the circuit board is green (not blue), it is possible a 420mA signal was applied
without power to the power terminals and damage to the input circuitry has occurred. Contact your Emerson
sales office or Local Business Partner for further information.
3. Unit moves to fully open when 1V signal is applied and closed when 5V signal is applied
a. Unit is likely configured as an on/off unit with local control; on/off units can not be controlled as an analog
device.
i. If on/off control is desired, use a dry contact switch to control in local mode or change to Modbus mode to
control the unit
ii. If positioning control is desired, contact your Emerson sales office or Local Business Partner to upgrade your
actuator to positioning control.
4. Diagnostics show a Motor Stall Fault
a. The easyDrive electric actuator is designed to operate in a manner consistent with a pneumatic actuator. This
means that if the valve plug can not move to its commanded position, the actuator will stop, without damage,
and issue a Motor Stall Fault warning. When the command signal changes outside of the deadband (Modbus
register 40036), it will attempt to move again. Recalibrate the actuator span per instructions in the Startup
section of this manual.
5. Position on D4 is not accurate (proportional positioning units only)
a. If the valve plug opened during calibration, it is set to a D3. Change valve type to D4 and recalibrate.
b. If the local analog input is being used (420mA or 15V), the analog inputs of the actuator may be calibrated to
match the input signal. Follow instructions in Analog Input Calibration, found in the Calibration section of this
instruction manual.
Maintenance
Refer to figure 12.
Valve parts are subject to normal wear and must be inspected and replaced as necessary. The frequency of inspection
and maintenance depends on the severity of the service conditions.
WARNING
Avoid personal injury from sudden release of process pressure or bursting of parts. Before performing any maintenance
operations:
D Do not remove the actuator from the valve while the valve is still pressurized.
D Always wear protective gloves, clothing, and eyewear when performing any maintenance operations to avoid personal
injury.
D Disconnect any operating lines providing air pressure, electric power, or a control signal to the actuator. Be sure the
actuator cannot suddenly open or close the valve.
D Use bypass valves or completely shut off the process to isolate the valve from process pressure. Relieve process pressure
on both sides of the valve. Drain the process media from both sides of the valve.
D Vent the power actuator loading pressure and relieve any actuator spring precompression.
D Use lock‐out procedures to be sure that the above measures stay in effect while you work on the equipment.
D The valve packing box may contain process fluids that are pressurized, even when the valve has been removed from the
pipeline. Process fluids may spray out under pressure when removing the packing hardware or packing rings.
16
Instruction Manual
D103597X012
D Check with your process or safety engineer for any additional measures that must be taken to protect against process
media.
D4 Valve with easy-Drive Actuator
October 2017
WARNING
For explosionproof applications, ensure the actuator cover is properly bolted before applying power to the actuator.
Personal injury or property damage may result from fire or explosion if power is applied to the actuator with the cover
removed in a hazardous area.
Do not remove the actuator cover for 10 minutes after power is disconnected if the UPS option is installed.
For explosion‐proof applications, install rigid metal conduit and a conduit seal no more than 457 mm (18 inches) from the
actuator. Personal injury or property damage may result from explosion if the seal is not installed.
Select wiring and/or cable glands that are rated for the environment of use (such as hazardous area, ingress protection, and
temperature). Failure to use properly rated wiring and/or cable glands can result in personal injury or property damage
from fire or explosion.
Wiring connections must be in accordance with local, regional, and national codes for any given hazardous area approval.
Failure to follow the local, regional, and national codes could result in personal injury or property damage from fire or
explosion.
Valve Plug and Seat Ring
Disassembly
Key Numbers are referenced in figures 11 and 12.
1. Isolate the control valve from the line pressure, release pressure from both sides of the valve body (key 1), and drain
the process media from both sides of the valve.
CAUTION
The following steps are intended to prevent damage to the valve plug (key 3) and seat ring (key 2) during the removal of the
bonnet and actuator.
2. For Positioning Actuators
•Command the valve to anywhere between 10% and 20% travel.
•Isolate power and signal.
•Proceed to step 3.
For ON/OFF Actuators
•Command the valve to open or close, and cut the power when the valve is at midstroke.
•Isolate power and signal.
•Proceed to step 3.
3. Break the hammer nut (key 6) loose with a hammer. Continue turning the hammer nut by using a hammer or a
large adjustable wrench, tightened around one ear of the hammer nut. If the bonnet is stuck on the valve, continue
to unscrew the hammer nut. The hammer nut will contact the spring pins (key 7) and will force the bonnet out of
the valve. Carefully lift the actuator, bonnet, and valve plug assembly from the valve body.
WARNING
The spring pins must always be in place during valve operation. They provide a safeguard against injury when the unit is
being disassembled.
17
D4 Valve with easy-Drive Actuator
October 2017
Instruction Manual
D103597X012
4. Use a socket wrench to loosen the seat ring (key 3).
5. Remove the seat ring (key 3) and seat ring gasket (key 9) from the valve body.
6. To replace the plug, the stem nut (key 42) must be removed to expose the groove pin (key 4). Open the
explosionproof enclosure (key 60), using a 13mm wrench.
7. Remove the stem nut (key 42) using a 11/16 inch wrench; insert a punch in the hole in the stem to restrict rotation
of the stem while removing the stem nut. The travel indicator (key 32) may need to be moved to expose the hole.
8. Push the stem downward just far enough to expose the groove pin (key 4) on the plug.
9. Remove the plug by driving out the groove pin and unscrewing the valve plug from the stem.
WARNING
Be careful to avoid damaging the seating surface on the valve plug or seat ring as damage in these areas will allow
excessive leakage at shutoff. Avoid damaging the highly polished valve stem surface. A damaged valve stem could cut the
packing and allow process fluid to leak to the atmosphere.
Table 7. Torque for Seat Ring (Key 3)
VALVE SIZERECOMMENDED TORQUE
NPSNSmLbfSft
1407300
2698515
Assembly
1. Make sure the bonnet O‐ring (key 8) is on the bonnet and lubricated with lithium grease (key 49).
2. Install the plug (key 2) on the stem (key 47) and insert a new groove pin (key 4).
3. Push the plug and stem upward to ensure the threads on the top of the stem are exposed. Thread the stem nut (key
42) onto the top of the stem and tighten the stem nut (key 42) to 39 N•m (29lbf•ft). Insert a punch in the hole in
the stem to restrict rotation while tightening the stem nut.
4. Replace the top of the explosion proof enclosure (key 60) and tighten cap screws (key 64) to 20 N•m (15 lbf•ft).
5. Thoroughly clean the seat ring and bonnet threads in the valve body (key 1). Also clean the valve body seat ring
gasket surfaces.
6. Apply anti‐seize lubricant (key 54) to the threads of the seat ring (key 3), and its mating threads in the valve body.
7. Apply anti‐seize lubricant (key 54) to the seat ring gasket (key 9) and install into the valve body.
8. Screw the seat ring into the valve body. Use a socket wrench to tighten the seat ring to the torque values shown in
table 7. Remove all excess lubricant after tightening.
9. Lubricate (key 54) the threads on the valve body and hammer nut and the contact surfaces of the bonnet and
hammer nut flange. Install the bonnet and actuator assembly with pinned valve plug onto the valve body. Tighten
the hammer nut using an adjustable wrench until the nut stops turning. A few hammer blows will be required to
ensure that the assembly is tight.
Valve Packing
WARNING
Observe the warning at the start of the Maintenance section.
18
Instruction Manual
D103597X012
D4 Valve with easy-Drive Actuator
October 2017
The valve stem packing can only be accessed from within the valve body.
Disassembly
1. Disassemble the valve per steps 1 through 12 of the Valve Plug and Seat Ring Disassembly section in this instruction
manual.
2. Unscrew the packing retainer (key 10) from the bonnet (key 5).
3. Remove the five Belleville springs (key 11), packing spacer (key 14), packing (key 13), and two anti‐extrusion rings
(key 12) from the bonnet, using a formed wire hook. To aid in packing removal, the stem may be removed.
4. Clean and inspect the packing box wall to ensure that the packing surfaces are not damaged. If the surface
condition is damaged, and cannot be improved by light sanding, replace the bonnet by contacting your Emerson
sales office or Local Business Partner.
5. Inspect the valve stem for scratches or wear, and valve plug for wear or damage. Replace if necessary.
Figure 9. Fisher D4 Packing Installation
UPPER PACKING
SPACER (KEY 48)
PACKING RETAINER
(KEY 8)
BELLEVILLE SPRINGS FULLY ENCLOSED BY
THE PACKING RETAINER
UNTIGHTENED,
NOTE THE GAP
FULLY TIGHTENED,
NO GAP
VALVE PLUG, BELLEVILLE SPRINGS, AND PACKING RETAINER
CORRECTLY INSTALLED AND TIGHTENED
19
D4 Valve with easy-Drive Actuator
October 2017
Figure 10. Lubrication Locations on Packing
FEMALE PACKING ADAPTER
Instruction Manual
D103597X012
PACKING RING
MALE PACKING ADAPTER
LUBRICATE WITH 3mm (1/8 INCH
BEAD) OF SUPPLIED HIGH PERFORMANCE
FLUORINATED GREASE
LUBRICATE WITH 3mm (1/8 INCH
BEAD) OF SUPPLIED HIGH PERFORMANCE
FLUORINATED GREASE
Assembly
Refer to figures 9, 10, 11, and 12.
1. If the stem was removed during packing disassembly, insert the stem back into the valve/actuator assembly.
2. Ensure the upper packing spacer (key 48) is installed, as shown in figure 9.
3. Using a non‐marring installation tool, such as a 12‐inch length of 1/2 inch PVC pipe, push the first anti‐extrusion
washer (key 12) fully into the packing box by hand. Then, use the packing spacer (key 14) to fully seat the
anti‐extrusion washer by firmly tapping the packing spacer against the anti‐extrusion washer with a hammer and
the PVC pipe.
4. Remove the packing spacer from the packing bore.
CAUTION
All D4 packing kits include a single use packet of high performance fluorinated grease. This is the only acceptable D4
packing lubricant.
Note
In the following procedure, carefully install each packing ring individually over the valve stem and push completely into the
packing box with a non‐marring tube. A 12‐inch length of 1/2 inch PVC pipe works well for this. It is recommended that the
lubricated packing rings be installed individually rather than pushed in as a set.
5. Apply a 3mm (1/8 inch) bead of the supplied high performance fluorinated grease (key 44) around the groove of
the female packing adaptor as shown in figure 10 and install over the valve stem (key 16).
6. Apply a 3mm (1/8 inch) bead of the supplied high performance fluorinated grease (key 44) around the groove of
the packing ring as shown in figure 10 and install over the valve stem.
7. Install the male packing adaptor, lower anti‐extrusion washer (key 10), and lower packing spacer over the valve
stem as shown in figure 9.
20
Instruction Manual
D103597X012
D4 Valve with easy-Drive Actuator
October 2017
8. Firmly press all packing parts into the packing bore with a tube.
9. Install the five Belleville springs (key 11) over the valve stem. The Belleville springs should be single‐stacked with the
inside diameter of the inner spring contacting the packing spacer (key 14), and the outside diameter of the outer
spring contacting the packing retainer (key 10).
10. Lubricate the threads of the packing retainer with anti‐seize and install into the bonnet using a 1‐5/8 inch wrench.
Make sure the Belleville springs are completely enclosed by the packing retainer as shown in figure 9.
11. Torque the packing retainer to 136 NSm (100 lbfSft). The packing retainer has been installed correctly when a
metal‐to‐metal contact has been made between the packing retainer end and the bonnet (key 5). The packing
retainer threads should be completely enclosed by the bonnet.
12. Follow steps 1 through 9 of the Valve Plug and Seat Ring Assembly section in this instruction manual.
Parts Ordering
Each D4 control valve is assigned a serial number, which can be found on the nameplate. Refer to the number when
contacting your Emerson sales office
WARNING
or Local Business Partner for assistance or when ordering replacement parts.
Use only genuine Fisher replacement parts. Components that are not supplied by Emerson Automation Solutions should
not, under any circumstances, be used in any Fisher valve, because they may void your warranty, might adversely affect the
performance of the valve, and could cause personal injury and property damage.
Repair Kits
Note
All repair kits are supplied with hydrogenated nitrile bonnet O‐ring. FKM
(fluorocarbon) bonnet O‐ring must be ordered separately when
required.
Description Part Number
*Packing Repair Kit
Includes key numbers 4, 8, 12 (2 req'd),
13, and high performance fluorinated greaseRD4X0000012
Parts List
Note
For part numbers not shown, contact your Emerson sales office
Business Partner.
or Local
KeyDescription Part Number
1Valve Body
2*Valve Plug
S41000 / S41600 HT
NPS 1 valve
0.25 inch port diameter20C3692X012
0.375 inch port diameter20C3693X012
0.5 inch port diameter20C3694X012
0.75 inch port diameterGE01557X012
NPS 2 valve
0.25 inch port diameterGE00992X012
0.375 inch port diameterGE00993X012
0.5 inch port diameterGE00994X012
0.75 inch port diameterGE01558X012
1‐inch port diameterGE01561X012
1.25 inch port diameterGE01555X012
S17400 H1150 Dbl
NPS 1 valve
0.25 inch port diameter20C3692X032
0.375 inch port diameter20C3693X032
0.5 inch port diameter20C3694X032
0.75 inch port diameterGE01557X032
NPS 2 valve
0.25 inch port diameterGE00992X032
0.375 inch port diameterGE00993X032
0.5 inch port diameterGE00994X032
0.75 inch port diameterGE01558X032
1‐inch port diameterGE01561X032
1.25 inch port diameterGE01555X032
Tungsten Carbide
NPS 1 valve
*Recommended spare parts
21
D4 Valve with easy-Drive Actuator
October 2017
Instruction Manual
D103597X012
KeyDescription Part Number
0.25 inch port diameter20C3696X012
0.375 inch port diameter20C3697X012
0.5 inch port diameter20C3698X012
0.75 inch port diameter20C3699X012
NPS 2 valve
0.25 inch port diameter20C3682X012
0.375 inch port diameter20C3683X012
0.5 inch port diameter20C3685X012
0.75 inch port diameter20C3686X012
1‐inch port diameter20C3687X012
1.25 inch port diameter20C3688X012
3*Seat Ring
S17400 H1150 Dbl
NPS 1 valve
0.25 inch port diameterGE00982X032
0.375 inch port diameterGE00983X032
0.5 inch port diameterGE00984X032
0.75 inch port diameterGE00985X032
NPS 2 valve
0.25 inch port diameterGE00986X032
0.375 inch port diameterGE00987X032
0.5 inch port diameterGE00988X032
0.75 inch port diameterGE00989X032
1‐inch port diameterGE00990X032
1.25 inch port diameterGE00991X032
Tungsten Carbide
NPS 1 valve
0.25 inch port diameterGE07347X012
0.375 inch port diameterGE07363X012
0.5 inch port diameterGE07364X012
0.75 inch port diameterGE07365X012
NPS 2 valve
0.25 inch port diameterGE07389X012
0.375 inch port diameterGE07394X012
0.5 inch port diameterGE07397X012
0.75 inch port diameterGE07398X012
1‐inch port diameterGE07399X012
Packing Lubricant
58Enclosure O-ring
59Motor/gearbox/controller assembly
60Upper Enclosure
61Lower Enclosure
62Motor Cap Screws (4 req'd)
63Motor Cap Screw Washers (4 req'd)
64Enclosure Cap Screws (8 req'd)
65Enclosure Cap Screw Retaining Washers (8 req'd)
66Ground Screw
68Certification Nameplate
69easy-Drive Label
22
*Recommended spare parts
Instruction Manual
D103597X012
Figure 11. D4 Valve Assembly
D4 Valve with easy-Drive Actuator
October 2017
64
13 mm
60
65
62
13 mm
58
20
63
27
59
11/16 INCH
1-1/2 INCH
61
23
D4 Valve with easy-Drive Actuator
October 2017
Figure 12. Fisher D4 Valve Assembly
Instruction Manual
D103597X012
24
APPLY LUBRICANT
GE49375-B
Instruction Manual
D103597X012
D4 Valve with easy-Drive Actuator
October 2017
Appendix A - Modbus
A.1 Register Summary
Table 8. Register Summary
DATALEGAL FUNCTION CODESREGISTER (PHYSICAL)TYPER/WDESCRIPTION
03 – Read Holding Reg
Position Demand – Proportional
Reset Diagnostics
Recalibrate Demand
Analog Cal at 0%
Analog Cal at 100%
Reserved03 – Read Holding Reg40006 (0x0005)UINT16RRead will return power up default of 0
Reserved03 – Read Holding Reg40007 (0x0006)UINT16RRead will return power up default of 0
Reserved03 – Read Holding Reg40008 (0x0007)UINT16RRead will return power up default of 0
Test Register03 – Read Holding Reg40009 (0x0008)UINT16R
Actual Position03 – Read Holding Reg40010 (0x0009)UINT16RValue 0-100 = 0-100% Position
Actual Demand03 – Read Holding Reg40011 (0x000A)UINT16R
On/Off
0 = L2e dual dry contact
1 = Single dry contact
Proportional
0 = 1-5V
1 = 4-20 mA
UINT16 – unsigned 16 bit variable, can take value 0-65535.
UINT32 – unsigned 32 bit variable, can take value 0-4294967295.
(Reserved) – registers used for development use only.
† - 32bit register contains data that spans two registers – reads and write of data needs to be performed within the
same Modbus command function to ensure coherency of data.
0x00040000 0000 0000 0100Modbus command has been sent (starts a calibrated system)
0x00020000 0000 0000 0010Analog input initialized (system has seen input >3mA/1V
0x00010000 0000 0000 0001Start delay active (within 10 second calibration window)
Diagnostic Flags – Binary Mask ValueDescription
October 2017
A.2 Diagnostic Flags
The diagnostic register holds a 16 bit value that represents 16 individual flags, when set (value ‘1’), this indicates the
following conditions have occurred or are still present, the highest 7 bits are latching and will be present in the register
even if the initial cause for the flag being set is removed. If these flags are set, a reset needs to be performed to clear
the fault.
A.2.1 Fault in NV Memory
This is a severe fault and is usually seen when the firmware is upgraded with a program that uses a different
EEPROM/Non-volatile memory map. If this is not the case then the probable cause is a fault in the memory hardware.
A.2.2 Motor Assembly Stall
The valve plug was unable to move to the commanded position. The drive has attempted to move the motor by
applying a non-zero PWM signal, and the speed has not been detected as greater than 0 with a 400ms period. This
fault latches and needs to be reset.
A.2.3 Speed Measurement Fault
The controller detected pulses that correspond to the motor going much faster than the speed the speed
measurement system is designed for – the integrity of the measurement cannot be relied upon. This fault latches and
needs to be reset.
A.2.4 System or Watchdog Fault
The software system has been reset and this flag is set at power up if the case of the reset was the onboard watchdog
either timing out OR being forced by program function call. This flag is used as an indication that this type of reset has
occurred.
27
D4 Valve with easy-Drive Actuator
October 2017
Instruction Manual
D103597X012
A.2.5 Overspeed Condition
The drive speed was detected as being over the speed 3300RPM. This fault latches and needs to be reset.
A.2.6 Calibration Span Not in Legal Range
Following a calibration the detected mechanical travel was detected as being too short for the valve type. This fault
latches and needs to be reset.
A.2.7 Fault in NV Memory – recovered settings
This fault is similar to Fault in NV Memory but is different in that the settings were recovered, however it is possible the
fault was due to a setting being changed during a power cycle. The settings need to be validated before valve
operation.
A.2.8 Communications Timeout
This flag is set after a timeout or loss of valid communications, it will be cleared if communications is reestablished
with the valve controller. If this flag is set and the control demand is set to be taken from the Modbus then the valve
will be commanded to the ‘Loss of communications position’ in setting accessed at Modbus register 40034.
A.2.9 Valve was Shutdown while Moving
The valve was actuating while power was removed, the position information may be unreliable. Command valve to 0%
to assure position information is accurate.
A.2.10 Valve Span Calibrated
The valve is calibrated.
A.2.11 Valve Position Controller Active
The valve is being actively controlled to go to a demanded position. The speed and position control loop logic is
setting the pwm and direction demands to the ValuDrive motor.
A.2.12 Analog Input Below 3mA/0.75V
The analog input is below a set threshold of 3mA. If since being powered up this level has been met the flag ‘Analog
input initialized’ will be set. If the control source is the analog input and this flag is set then the valve will be
commanded to actuate to the ‘Loss of control input’ position.
A.2.13 Motor Overspeed Coast Condition
The drive speed was detected as being over the speed 2500RPM. The flag is cleared if the speed falls below the coast
threshold level. This flag is used purely as a diagnostic.
A.2.14 Modbus Command Initialized
The system has received a command to the Position demand register since being powered up. If Modbus is the
selected control mode the valve will be commanded to this position after the startup period.
28
Instruction Manual
D103597X012
D4 Valve with easy-Drive Actuator
October 2017
A.2.15 Analog Input Initialized
The analog input has been detected as having a control signal within the expected range of 3-20mA. If the analog
input is the selected control signal then this will activate the valve after the startup period.
A.2.16 Start Delay Active
This is a flag set during the startup phase of operation, if this is set then the valve may be recalibrated by sending the
calibration signal sequence (100% demand followed by 0%). It is cleared to indicate normal operation (recalibration will
then require a command to Modbus register 40003).
A.3 Register Description
A.3.1 40001 Position Demand – Proportional [Read & Write]
0x06 – Write Single register, or
0x03 – Read Holding registers.
Description: This is a value between 0 and 100% to demand a valve position. This register will only be used by
the system if the control source (set by register 40035) is set for Modbus RTU control. If the
control type (set by register 40034) is On/Off then value will be resolved with a boolean set
operation for a Open/Closed position demand variable output (e.g. Values 0-49 = ’0’ and
50-100 = ‘100’). This variable needs to be set to 100% then 0% after a power-up to calibrate an
un-calibrated system.
0x06 – Write Single register, or
0x03 – Read Holding registers.
Description: This is a modbus request to reset the system from a fault state (indicated if the Diagnostics flags
register has any set faults). Writing a decimal 1 to the register will start a reset process only if
the system has a fault, otherwise the write will be ignored. Once the fault reset request has
been acknowledged the register will be set to decimal 0. Bit assignments are shown in table 9.
0x06 – Write Single register, or
0x03 – Read Holding registers.
Description: This is a register is used to initiate a calibration of the analog to digital circuit in the system. A
write of a ‘1’ will cause the system to store the value at the analog input. This action should
be performed with a calibrated 1V or 4mA present at the analog input. If this is not performed
the system uses defaults. Values outside the range 0-1 will return an exception code.
0x06 – Write Single register, or
0x03 – Read Holding registers.
Description: This is a register is used to initiate a calibration of the analog to digital circuit in the system. A
write of a ‘1’ will cause the system to store the value at the analog input. This action should
be performed with a calibrated 5V or 20mA present at the analog input. If this is not
performed the system uses defaults. Values outside the range 0-1 will return an exception code.
A.3.6 40004-40008 Reserved [Read Only]
Register: 40004-40008 Address 0x0003 (3) - 0x0007 (7).
Function code: 0x03 – Read Holding registers.
Description: Not used – reads will return a value of 0.
A.3.7 40009 Test Register [Read Only]
Register: 40009, Address 0x0008 (8).
Function code: 0x03 – Read Holding registers.
Description: A test register – can be used to confirm communications. Holds a power up default of 45964
(0xB38C Hex).
A.3.8 40010 Actual Position [Read Only]
Register: 40010, Address 0x0009 (9).
Function code: 0x03 – Read Holding registers.
Description: This is a value between 0 and 100% that indicates the physical position of a calibrated valve
system. If the valve is un-calibrated (indicated if the Diagnostics flags register has a cleared
calibration informational flag), then this register will read 0.
A.3.9 40011 Actual Demand [Read Only]
Register: 40011, Address 0x000A (10).
Function code: 0x03 – Read Holding registers.
Description: This is a value between 0 and 100% that indicates the demand to the position control loop from
the active control source.
A.3.10 40012 Diagnostic Flags [Read Only]
Register: 40012, Address 0x000B (11).
Function code: 0x03 – Read Holding registers.
Description: This is a set of 16 bit flags that indicate the state of the system. The lower order byte contains
flags that cause the system to go to a fault state – actuation of the valve will not be possible
30
Instruction Manual
D103597X012
until the cause of the fault condition has been removed and the fault condition reset by writing
a reset request to register 40001. The upper order byte contains flags used to indicate the
operational status of the valve actuator. See table 9 - Fault Register for details.
D4 Valve with easy-Drive Actuator
October 2017
A.3.11 40013-40014 Number of Open/Close Cycles [Read Only]
Register: 40013-40014, Address 0x000C (12) – 0x000D (13).
Function code: 0x03 – Read Holding registers.
Description: This is a pair of registers that hold a 32bit number indicating the number of actuations of the
valve. A cycle of moving the valve from closed to open and back closed will count as 2 cycles.
The register needs to be read using a single read function command to ensure coherency
of the data in the two registers.
Register: 40015-40016, Address 0x000E (14) – 0x000F (15).
Function code: 0x03 – Read Holding registers.
Description: This is a pair of registers that hold a 32bit number indicating the number of hours the valve has
been powered. The register needs to be read using a single read function command to ensure
coherency of the data in the two registers. If version 4.13 firmware is installed, hours are
displayed. If version 4.21 firmware is installed, minutes are displayed.
A.3.13 40017-40018 Hours/Minutes Open [Read Only]
Register: 40017-40018, Address 0x0010 (16) – 0x0011 (17).
Function code: 0x03 – Read Holding registers.
Description: This is a pair of registers that hold a 32bit number indicating the number of hours the valve has
been in the open (100%) position. The register needs to be read using a single read function
command to ensure coherency of the data in the two registers. If version 4.13 firmware is
installed, hours are displayed. If version 4.21 firmware is installed, minutes are displayed.
Register: 40019-40020, Address 0x0012 (18) – 0x0013 (19).
Function code: 0x03 – Read Holding registers.
Description: This is a pair of registers that hold a 32bit number indicating the number of hours the valve has
been in the closed (0%) position. The register needs to be read using a single read function
command to ensure coherency of the data in the two registers. If version 4.13 firmware is
installed, hours are displayed. If version 4.21 firmware is installed, minutes are displayed.
A.3.15 40021-40022 Number of Power up cycles [Read Only]
Register: 40021-40022, Address 0x0014 (20) – 0x0015 (21).
Function code: 0x03 – Read Holding registers.
Description: This is a pair of registers that hold a 32bit number of times the system has been successfully
powered up. The register needs to be read using a single read function command to ensure
coherency of the data in the two registers.
Description: This is a pair of registers that hold a 32 bit number that can be used to hold a unique serial
number. The register needs to be read using a single read Modbus function
transaction command to ensure coherency of the data in the two registers.
Instruction Manual
D103597X012
A.3.17 40025 Analog I/P value [Read Only]
Register: 40025, Address 0x0018 (24).
Function code: 0x03 – Read Holding registers.
Description: This is a register that holds a 16 bit scaled representation of the analog input. It is scaled
according to input i.e. 0-200 for 0-20.0mA and 0-50 for 1-5 V.
A.3.18 40026 Firmware Project Code [Read Only]
Register: 40026, Address 0x0019 (25).
Function code: 0x03 – Read Holding registers.
Description: This is a register that holds the SRD project code (SRD422) – 422. This is the code used in
Register: 40027, Address 0x001A (26).
Function code: 0x03 – Read Holding registers.
Description: This is a register that holds the SRD document code (SRD422-5007) – 5007. This code along
with the project code is used in version control of SRD documents and source code.
A.3.20 40028 Firmware Version [Read Only]
Register: 40028, Address 0x001B (27).
Function code: 0x03 – Read Holding registers.
Description: This is a register that holds the hex encoded equivalent of a four digit decimal version number
of the firmware, the high order 8bits encode the whole number of the version and the low
order 8 bits the fraction, e.g. v1.16 would be encoded 0x0110, v2.66 would be 0x0242.
Together with the data from registers 40026- 40028 it is possible to determine the unique
identity of the code being run in the processor.
A.3.21 40029 Diagnostic Flags [Read Only]
Register: 40029, Address 0x001C (28).
Function code: 0x03 – Read Holding registers.
Description: This is a set of 16 bit flags that show the accumulation of fault flags that have occurred – as
faults are self resetting. The register is stored in non-volatile memory. The mapping is the same
as the diagnostic register at 40012. See table 9 - Fault Register for guide to values.
A.3.22 40030-40031 Reserved [Read Only]
Register: 40030-40031, Address 0x001D-0x001E (29-30).
Function code: 0x03 – Read Holding registers.
Description: Not used – reads will return a value of 0.
0x06 – Write Single register, or
0x03 – Read Holding registers.
Description: This is a register that holds an enumeration of the three types of valve. This is used to set up
several internal variables and constants. Writes outside of the legal range 0-2 will be rejected
with an exception code.
A.3.24 40033 Control Type [Read Only]
Register: 40033, Address 0x0020 (32).
Function code: 0x03 – Read Holding registers.
Description: This is a register that holds an enumeration of the control type – either 0 for On/Off, or 1 for
0x06 – Write Single register, or
0x03 – Read Holding registers.
Description: This is a register that holds an enumeration of the control source – either 0 for Modbus RTU
control, or 1 for signals local to the system – decided by the contents of register 40032. Note
that if the Modbus serial link is not the active mode then the faults associated with serial
communications will be disabled, although serial communications for such activities as test and
debug monitoring of the analog input will all still function. Writes outside of the legal range
0-1 will be rejected with an exception code.
A.3.26 40035 Loss of Control Default Position [Read & Write]
0x06 – Write Single register, or
0x03 – Read Holding registers.
Description: This is a register that holds a position demand 0-100% that will be applied to the position
control loop if the active control source is determined to be corrupt of out of normal
operating specification, this applies to modbus communications messages being absent or
the analog input being un-calibrated or below 3mA/0.75V(open control loop). Writes outside
of the legal range 0-100 will be rejected with an exception code.
0x06 – Write Single register, or
0x03 – Read Holding registers.
Description: This is a register that holds an integer value of percentage hysteresis used to discriminate
against noise entering the control system from the selected control source, this can take a value
of 0-100%, e.g. a value of 100 would make the system only respond to 0 or 100% demands.
Writes outside of the legal range 0-100 will be rejected with an exception code.
0x06 – Write Single register, or
0x03 – Read Holding registers.
Description: This is a register that holds a value 0-65535 that is the number of seconds for a timeout before
the modbus serial communications channel is determined to be uncommunicative
(0 - ~18Hrs). A valid addressed message must be received by the system within this time limit
if the active control source is Modbus RTU communications. If the time without
communications is exceeded the system will fault and the valve commanded to the default
loss of communications position. A value of 0 can be used to disable this feature. If
communications is resumed then the flag will be cleared and the valve will take the refreshed
position as a demand. The use of this register is shown in table 9 - Fault Register.
0x06 – Write Single register, or
0x03 – Read Holding registers.
Description: This is a register that holds an enumeration of the parity type used by the Modbus serial
interface – either 0 for Odd, or 1 for Even in version 4.13 firmware (version 4.21 firmware
defines 0=Odd, 1=Even, 2=None). Writes outside of the legal range will be rejected with
an exception code.
0x06 – Write Single register, or
0x03 – Read Holding registers.
Description: This is a register that holds an enumeration 0-1 that sets the mode of operation for on/off and
proportional control. When in proportional mode (40033 = 1), a value of 0 sets the unit for
using a 1-5V voltage input. 1 sets up the unit for using a 4-20 mA current command input.
The scaling of the different modes is reflected in the scaling of the value reported in register at
40023 –‘Analog I/P value’. When in on/off mode (40033 = 0), a value of 0 sets the unit for using
both digital inputs, optimized for using the L2e level controller. 1 sets up the unit for using a
single digital input. See Operation for further details.
A.4 Example Modbus Protocol Transactions
A.4.1 Write to Position Demand Register (40002/0x0001/1)
Write of a position demand value of 100% to device at address 1 on the Modbus network – 8 characters.
Write of a position demand value of 101% to device at address 1 on the Modbus network, note that this value (101% is
outside the legal range of values permitted to be written to this address, so an exception frame is generated – 8
characters.
Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance
of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Fisher and easy-Drive are marks owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. Emerson
Automation Solutions, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their
respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not
to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are
governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such
products at any time without notice.
Emerson Automation Solutions
Marshalltown, Iowa 50158 USA
Sorocaba, 18087 Brazil
Cernay 68700 France
Dubai, United Arab Emirates
Singapore 128461 Singapore
www.Fisher.com
36
E 2012, 2017 Fisher Controls International LLC. All rights reserved.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.