Fisher ControlWave MRMS-IC (D5140) Configuration Manual

s
Instruction Manual
Doc Number D5140
Part Number D301719X012
May 2012
ControlWave® MRMS-IC Configuration Manual
Remote Automa ti on Solution
www.EmersonProcess.com/Remote
This page is intentionally left blank
ControlWave MRMS-IC Configuration Manual (D5140)
Contents
Chapter 1 – Getting Started 1-1
1.1What is MRMS-IC? ................................................................................................................... 1-1
1.2Before You Begin ...................................................................................................................... 1-1
1.3Installing MRMS-IC Software .................................................................................................... 1-2
1.4Starting MRMS-IC Software ...................................................................................................... 1-6
1.4.1MRMS_IC IP Startup ..................................................................................................... 1-6
1.4.2MRMS_IC Serial Startup ............................................................................................... 1-7
1.4.3Logging Onto the ControlWave Micro ........................................................................... 1-7
1.5Accessing Pages of the MRMS_IC Application ........................................................................ 1-8
1.6Entering Data in Fields of the MRMS_IC Application ............................................................... 1-9
Chapter 2 – Configuring Inputs and Outputs (I/O Tab) 2-1
2.1I/O Tab ...................................................................................................................................... 2-1
2.2I/O Usage .................................................................................................................................. 2-2
2.2.1Discrete Inputs (DI) ....................................................................................................... 2-5
2.2.2Discrete Outputs (DO) ................................................................................................... 2-5
2.2.3Analog Inputs (AI) ......................................................................................................... 2-6
2.2.4Analog Outputs (AO) ..................................................................................................... 2-7
2.2.5High Speed Counters (HSC) ......................................................................................... 2-8
2.2.6Ultrasonic Flow Meters (UFM) ...................................................................................... 2-9
2.2.7Multi-variable Transmitters (Transducers) .................................................................. 2-10
2.3Local DLM ............................................................................................................................... 2-12
2.4Customer Modbus Slave ......................................................................................................... 2-14
2.4.1Signal List Grid ............................................................................................................ 2-17
2.4.2Floating Point Format .................................................................................................. 2-19
2.5Generic Modbus Master .......................................................................................................... 2-20
2.6Load/Save Configuration ......................................................................................................... 2-25
2.6.1Performing I/O Array Operations. ............................................................................... 2-26
2.6.2Creating a Recipe ....................................................................................................... 2-27
2.6.3Saving the Recipe ....................................................................................................... 2-28
2.6.4Recalling a Saved Recipe, and Sending Its Values to the Controller ......................... 2-29
2.7Time Set/Daylight Saving Time ............................................................................................... 2-29
Chapter 3 – Configuring Stations and Runs (Measurement Tab) 3-1
3.1Measurement Tab ..................................................................................................................... 3-2
3.2Status/Configuration .................................................................................................................. 3-3
3.2.1Site Configuration Data Tab (Site Configuration) ......................................................... 3-4
3.2.2MVT Common Settings Tab (Site Configuration).......................................................... 3-7
3.2.3Station Summaries Tab (Site Configuration) ................................................................ 3-8
3.2.4Station Configuration Tab (Station Configuration) ...................................................... 3-10
3.2.5Station Data Tab (Station Configuration) .................................................................... 3-15
3.2.6Run Configuration Tab ................................................................................................ 3-16
3.2.7Alarm Configuration Tab (Run Configuration) ............................................................. 3-21
3.2.8Linearization Config Tab (Run Configuration) ............................................................. 3-23
3.2.9PV/GQ Averages Tab (Run Configuration) ................................................................. 3-24
3.2.10Orifice Tab (Run Configuration) .................................................................................. 3-25
3.2.11Turbine Tab (Run Configuration) ................................................................................ 3-29
3.2.12Auto-Adjust Tab (Run Configuration) .......................................................................... 3-32
3.2.13Ultrasonic Tab (Run Configuration) ............................................................................ 3-34
3.2.14PD Tab (Run Configuration) ........................................................................................ 3-37
Issued: May-2012 Contents iii
ControlWave MRMS-IC Configuration Manual (D5140)
3.3View Local Archives ................................................................................................................ 3-39
3.3.1Selecting Logs to View ................................................................................................ 3-39
3.4Collect Local Logs ................................................................................................................... 3-40
3.4.1Selecting Archives for Collection ................................................................................ 3-40
3.4.2Collecting a Single Archive ......................................................................................... 3-40
3.4.3Collecting Multiple Archives ........................................................................................ 3-40
3.4.4Log Collection Parameters .......................................................................................... 3-40
3.5View Audit Log ........................................................................................................................ 3-43
3.5.1Data Storage Parameters dialog box .......................................................................... 3-44
3.5.2Search Data Collection Criteria dialog box ................................................................. 3-45
3.6Maintenance Mode .................................................................................................................. 3-46
3.6.1Site Tab ....................................................................................................................... 3-46
3.6.2Station Tab .................................................................................................................. 3-49
3.6.3Run Tab ...................................................................................................................... 3-51
3.6.4PVs Tab ...................................................................................................................... 3-53
3.6.5AI Maintenance Tab .................................................................................................... 3-54
3.7Gas Chromatograph Configuration ......................................................................................... 3-56
3.7.1General ....................................................................................................................... 3-56
3.7.2Current Tab (Gas Chromatograph Configuration) ...................................................... 3-61
3.7.3Component Tab (Gas Chromatograph Configuration) ................................................ 3-65
3.7.4Delta Limit Tab (Gas Chromatograph Configuration) ................................................. 3-67
3.7.5Normalization Tab (Gas Chromatograph Configuration) ............................................ 3-68
3.7.6Custom Tab (Gas Chromatograph Configuration) ...................................................... 3-69
3.8Summary Pages ...................................................................................................................... 3-70
3.8.1Measurement Tab ....................................................................................................... 3-70
3.8.2Alarm Tab .................................................................................................................... 3-71
3.9Limits Page (Gas Composition Allowable Ranges) ................................................................ 3-72
3.10Daily Run Corrected and Uncorrected Volume ....................................................................... 3-73
Chapter 4 – Sampler (Control Tab) 4-1
4.1Sampler ..................................................................................................................................... 4-1
4.1.1List 29 ............................................................................................................................ 4-4
Appendix E - Troubleshooting E-1
Index IND-1
iv Contents Issued: May-2012
ControlWave MRMS-IC Configuration Manual (D5140)
Chapter 1 – Getting Started
This chapter discusses how to install the MRMS-IC application and provides some general information about how to use it.
In This Chapter
1.1What is MRMS-IC? .......................................................................... 1-1
1.2Before You Begin ............................................................................. 1-1
1.3Installing MRMS-IC Software .......................................................... 1-2
1.4Starting MRMS-IC Software ............................................................ 1-6
1.4.1MRMS_IC IP Startup ............................................................ 1-6
1.4.2MRMS_IC Serial Startup ...................................................... 1-7
1.4.3Logging Onto the ControlWave Micro .................................. 1-7
1.5Accessing Pages of the MRMS_IC Application ............................... 1-8
1.6Entering Data in Fields of the MRMS_IC Application ...................... 1-9
1.1 What is MRMS-IC?
1.2 Before You Begin
Multi-Run Multi-Station (MRMS) software with Industry Canada (IC) / Measurement Canada approvals is a software application that allows the ControlWave Micro controller to manage up to six (6) natural gas measurement stations.
The MRMS-IC application consists of: A ControlWave project file (*.PRO) pre-programmed for multi-run
multi-station natural gas measurement.
A customized flash configuration profile (*.FCP) file that configures
the ports, audit, and archive parameters of the ControlWave Micro for the MRMS_IC.
A TechView session. This includes the TechView session file
(*.TVS), associated *.INI files, and a set of HTM menus customized for the MRMS-IC application. You use these menus to configure the application.
You must install the ControlWave Micro controller on site and
connect field devices to its I/O modules. For information on ControlWave Micro hardware, see document CI-ControlWave Micro.
You must install OpenBSI 5.7 software including TechView on your
PC workstation. You must also install the latest service pack and patches (Service Pack 2, Patch D). See the OpenBSI Utilities
Manual (D5081), the BSI_Config User’s Manual (D5128), and the TechView User Manual (D5131) for details on installation
requirements.
Issued: May-2012 Getting Started 1-1
ControlWave MRMS-IC Configuration Manual (D5140)
You must connect the PC workstation to the ControlWave Micro
controller. You can communicate using a serial cable or an Ethernet cable. Cable diagrams are included in CI-ControlWave Micro.
The ControlWave Micro must be running a flash configuration
profile file (*.FCP) compatible with MRMS-IC software. For information on updating FCP files, see Chapter 5 of the OpenBSI Utilities Manual (D5081).
The ControlWave Micro must be running the ControlWave project
(*.PRO) file configured for the MRMS-IC. See Chapter 7 of the OpenBSI Utilities Manual (D5081) for information on downloading a ControlWave project (*.PRO) file.
Note: If you ordered your ControlWave Micro with MRMS-IC
software pre-installed, the FCP and PRO files are already loaded when the unit ships from the factory.
1.3 Installing MRMS-IC Software
Note: MRMS_IC runs on the following Windows operating systems:
Windows XP
1. Double-click on the MRMS-IC application icon.
2. Click Next on the welcome screen of the installer.
Click “Next”
Figure 1-1. MRMS_IC Installer – Welcome Screen
1-2 Getting Started Issued: May-2012
ControlWave MRMS-IC Configuration Manual (D5140)
3. The next screen includes a “Read Me” file which describes the
changes since the last release of MRMS IC. Click Next after you review the changes.
Click I Agree
Figure 1-2. Read Me Page
4. Review the license agreement and click the I Agree button to
proceed with the installation or Cancel to abort the installation process.
Figure 1-3. License Agreement page
Issued: May-2012 Getting Started 1-3
ControlWave MRMS-IC Configuration Manual (D5140)
Figure 1-4. Installation in Progress
5. The installation begins. If you see the following message box,
click OK to confirm that you have the proper OpenBSI version installed.
Click OK
Figure 1-5. Confirm OpenBSI Version
6. At the completion of the installation, click Next.
1-4 Getting Started Issued: May-2012
Click Next
ControlWave MRMS-IC Configuration Manual (D5140)
Figure 1-6. Installation Completion
7. Now click Finish to exit the installer.
Click Finish
Figure 1-7. Exit the Installer
Issued: May-2012 Getting Started 1-5
ControlWave MRMS-IC Configuration Manual (D5140)
1.4 Starting MRMS-IC Software
You start the MRMS_IC software by invoking the proper TechView file. There are two ways to do this:
Starting MRMS_IC from
the Start Programs
Menu
Starting MRMS_IC from
an icon
1.4.1 MRMS_IC IP Startup
For an IP connection, click: Start > Programs > MRMS_IC > MRMS_IC_IP_tvs
For a serial connection, click: Start > Programs > MRMS_IC > MRMS_IC_Serial_tvs
From a desktop icon, similar to those below, or from the \MRMS_IC\SUPPORT folder, double-click the IP or serial TVS file, depending upon your type of connection.
Figure 1-8. MRMS_IC TVS file icons
For IP communication, see Section 1.4.1 MRMS_IC IP Startup. For serial communication see Section1.4.2 MRMS_IC Serial Startup.
Note: Although you can view data through an IP connection, the
MRMS-IC application only allows configuration changes when you establish a physical serial connection to serial communication port 1 on the ControlWave Micro.
Once you start the TVS file for IP operation, TechView opens the Runtime Configuration Parameters dialog box:
Figure 1-9. IP Runtime Parameters
1. Ignore the number of runs; this parameter does not apply for
1-6 Getting Started Issued: May-2012
MRMS-IC.
2. Enter the IP address of the ControlWave Micro IP port to
which you are connected.
3. Click OK.
4. Log onto the ControlWave Micro as described in Section 1.4.3.
1.4.2 MRMS_IC Serial Startup
Once you start the TVS file for serial operation, TechView opens the Runtime Configuration Parameters dialog box:
ControlWave MRMS-IC Configuration Manual (D5140)
Figure 1-10. Serial Runtime Parameters
1. Ignore the number of runs; this parameter does not apply to
MRMS-IC.
2. Enter the BSAP local address of the ControlWave Micro to
which you are connected.
3. Select the serial communication port on the PC which you are
using to communicate with the ControlWave Micro.
4. Select the baud rate on the serial communication line.
5. Click OK.
6. Log onto the ControlWave Micro as described in Section 1.4.3.
1.4.3 Logging Onto the ControlWave Micro
In the SignOn to RTU dialog box, enter a Username / Password combination that allows full access to the ControlWave Micro, then click the SignOn button.
Issued: May-2012 Getting Started 1-7
ControlWave MRMS-IC Configuration Manual (D5140)
y
Figure 1-11. Logging onto the ControlWave Micro
1.5 Accessing Pages of the MRMS_IC Application
To access various pages of the MRMS_IC application, click on the tab for the function you want to configure, then click on the buttons which appear on that tab. By default, the I/O tab appears first.
Click on the tab you want to access, then click on an
of the buttons for that tab
Tabs
Buttons
Figure 1-12. Tabs and Buttons in MRMS_IC
The next several chapters describe the functions available on each tab of the application.
1-8 Getting Started Issued: May-2012
ControlWave MRMS-IC Configuration Manual (D5140)
You need not configure all the features of the application; only those that you need for your particular purpose and measurement needs.
1.6 Entering Data in Fields of the MRMS_IC Application
Whenever you select a field and enter data, or select from a drop-down menu, you must press the [Enter] key to confirm and save your choice.
To exit a field without entering data, press the [Esc] key.
Issued: May-2012 Getting Started 1-9
This page is intentionally left blank
ControlWave MRMS-IC Configuration Manual (D5140)
Chapter 2 – Configuring Inputs and Outputs (I/O Tab)
This chapter discusses configuring the MRMS-IC application to accept field inputs and outputs (I/O). This is accomplished from the MRMS­IC’s I/O tab.
Note: Although you can view data through an IP connection, the
MRMS-IC application only allows configuration changes when you establish a physical serial connection to serial communication port 1 on the ControlWave Micro.
In This Chapter
2.1 I/O Tab ............................................................................................. 2-1
2.2 I/O Usage ......................................................................................... 2-2
2.2.1 Discrete Inputs (DI) .............................................................. 2-5
2.2.2 Discrete Outputs (DO) .......................................................... 2-5
2.2.3 Analog Inputs (AI) ................................................................. 2-6
2.2.4 Analog Outputs (AO) ............................................................ 2-7
2.2.5 High Speed Counters (HSC) ................................................ 2-8
2.2.6 Ultrasonic Flow Meters (UFM) ............................................. 2-9
2.2.7 Multi-variable Transmitters (Transducers) ......................... 2-10
2.3 Local DLM ...................................................................................... 2-12
2.4 Customer Modbus Slave ............................................................... 2-14
2.4.1 Signal List Grid ................................................................... 2-17
2.4.2 Floating Point Format ......................................................... 2-19
2.5 Ultrasonic Data .............................................................................. 2-20
2.6 Load/Save Configuration ............................................................... 2-25
2.6.1 Performing Array Read or Write Operations. ..................... 2-26
2.6.2 Creating a Recipe ............................................................... 2-27
2.6.3 Changing Floating Point Format of Values in the Recipe .. 2-28
2.6.4 Saving the Recipe .............................................................. 2-28
2.6.5 Recalling a Saved Recipe, and Sending Its Values to the
Controller .......................................................................... 2-29
2.7 Generic Modbus Master ................................................................ 2-29
2.8 Time Set/Daylight Saving Time ..................................................... 2-29
2.1 I/O Tab
Click the I/O tab to display the various I/O options you can configure. We’ll discuss each of these in the sections that follow.
To configure an I/O function or feature, click on its button.
Figure 2-1. I/O Tab in MRMS-IC
Issued: May-2012 Configuring Inputs and Outputs (I/O Tab) 2-1
ControlWave MRMS-IC Configuration Manual (D5140)
2.2 I/O Usage
When you click the button on the I/O tab, the I/O Usage page displays a graphical representation of the ControlWave Micro, showing each of the I/O modules detected by the MRMS-IC. If MRMS-IC cannot detect a particular module or an I/O slot is empty, its graphic shows “Not Present.” MRMS-IC only uses Mixed I/O modules.
Click on the graphical representation of a module to configure its I/O.
I/O modules
Figure 2-2. I/O Usage Screen Showing I/O Modules Detected
When you move the cursor over the CPU module, an Expansion Communication (ECOM) module, or any I/O module, you’ll see a yellow box on the screen. To configure I/O, follow these steps:
1. From the I/O tab, click the I/O Usage button.
2. Position the cursor over the I/O module you want to configure; a
yellow box indicates the cursor position on any configurable module.
3. Click on the module you want to configure. This opens a screen
showing the possible choices for I/O. The Mixed I/O Module shows multiple types of I/O (see Figure 2-3).
2-2 Configuring Inputs and Outputs (I/O Tab) Issued: May-2012
ControlWave MRMS-IC Configuration Manual (D5140)
Figure 2-3. Mixed I/O Module
4. The I/O assignments in the MRMS-IC application are fixed
based on the I/O slot. Because you can have an expanded communication module (ECOM) in either I/O slot 1 or 2, I/O designations begin with the right-most slot and go in reverse order. In other words, the mixed I/O module in I/O slot 6 holds user DI1, whereas the mixed I/O module in I/O slot 1 holds user DI6.
5. Configuration is limited based on the I/O type. Refer to the sub-
sections that follow.
Note: You may have noticed that when the cursor is left hovered over
an IO point, the graphics to the left display the applicable connection points for direct and remote IO.
Issued: May-2012 Configuring Inputs and Outputs (I/O Tab) 2-3
ControlWave MRMS-IC Configuration Manual (D5140)
Graphic displays location of physical I/O connections for an I/O point, when you hover the cursor over the PNT.
Figure 2-4. Connection Points for Physical I/O
Notes:
The MRMS-IC application only uses Mixed I/O modules. Depending upon your particular configuration, you might not use all
the inputs or outputs in a particular meter run or station.
If you have I/O that comes from an ultrasonic flow meter or a multi-
variable transmitter that communicates with the MRMS-IC through a communication port, instead of an I/O module, you configure it from the UFM or Transducer pages, discussed later in this chapter.
To return to the I/O Usage page from any page underneath it, click
the Go Back link.
2-4 Configuring Inputs and Outputs (I/O Tab) Issued: May-2012
2.2.1 Discrete Inputs (DI)
Discrete inputs (DIs) include the following fields:
Field Description PNT
INV If you click this box for a given I/O point so that “Y” is
Live
ControlWave MRMS-IC Configuration Manual (D5140)
This read-only field displays the I/O point number.
displayed, MRMS-IC inverts the real-live field value and uses the inverted value as the process value. For example, if the Live value of discrete I/O point 5 is OFF, and INV is selected for that point, PV is set ON and that’s what MRMS-IC uses for control and processing.
This read-only field shows the actual ON/OFF status of this discrete input point.
PV
Assignment
2.2.2 Discrete Outputs (DO)
Discrete outputs (DOs) include the following fields:
Field Description PNT
Points that are ON show in red. Points that are OFF show in green.
This read-only field shows the value of the process variable (PV) used in MRMS-IC. This matches the Live value unless you invert the input using INV.
Points that are ON show in red. Points that are OFF show in green.
This read-only field shows details of the fixed I/O assigned to this point.
This read-only field displays the I/O point number.
PV
Assignment
This read-only field shows the value of the process variable (PV) MRMS-IC will output to the field device.
This read-only field shows details of the fixed I/O assigned to this point.
Issued: May-2012 Configuring Inputs and Outputs (I/O Tab) 2-5
ControlWave MRMS-IC Configuration Manual (D5140)
A
2.2.3 Analog Inputs (AI)
Analog inputs (AIs) include the following fields:
Field Description PNT
This read-only field displays the I/O point number.
PV
Zero
Span Enter the value that, when added to the Zero value,
Units
Assignment
Use Stacked DP Transmitter / Use Single DP Transmitter Only button
This read-only field shows the calculated value of the analog input process variable (PV) based on the configured Zero and Span.
If the value shows in red, the value is questionable
connection, a communication problem with the field device, data timeout or some other problem that could cause the value to be invalid.
Enter the value that the process variable should read when the AI field input is 4mA. Press [Enter] to save your selection.
represents what the process variable should display when the AI field input is 20m your selection.
For example, if Zero is 5 and Span is 20, then:
If the AI field input is: 4mA 5 20mA 25 12mA 15
The engineering units for this process variable. Click in the field and select the proper units from the drop-down menu. Press [Enter] to save your selection.
This read-only field shows details of the fixed I/O assigned to this point.
This button toggles I/O assignments based on whether you use a single DP transmitter, or stacked DP transmitters.
To use stacked, click the Use Stacked DP Transmitter and assignments change to stacked; the label on the button then changes to Use Single DP Transmitter Only.
To use a single DP transmitter, click the Use Single DP Transmitter and assignments change to single; the label on the button then changes to Use Stacked DP Transmitter.
. This could indicate no
. Press [Enter] to save
PV will be:
2-6 Configuring Inputs and Outputs (I/O Tab) Issued: May-2012
2.2.4 Analog Outputs (AO)
Analog outputs (AOs) include the following fields:
Field Description PNT
ControlWave MRMS-IC Configuration Manual (D5140)
This read-only field displays the I/O point number.
PV
Zero
Span Enter the value that, when added to the Zero value,
Units
Assignment
This read-only field shows the calculated value of the analog output process variable (PV) based on the configured Zero and Span. This value will be sent to the field device.
Enter the value that the process variable should read when the AO field output is 4mA. Press [Enter] to save your selection.
represents what the process variable should display when the AO field output is 20mA. Press [Enter] to save your selection.
For example, if Zero is 5 and Span is 20, then:
If PV is: 5 4mA 25 20mA 10 8mA
The engineering units for this process variable. Click in the field and select the proper units from the drop-down menu. Press [Enter] to save your selection.
This read-only field shows details of the fixed I/O assigned to this point.
The AO field output is:
Issued: May-2012 Configuring Inputs and Outputs (I/O Tab) 2-7
ControlWave MRMS-IC Configuration Manual (D5140)
2.2.5 High Speed Counters (HSC)
High speed counters (HSC) include the following fields:
Field Description PNT
This read-only field displays the I/O point number. The number varies depending upon the type of I/O module.
Counts
Time Stamp
Assignment
Use AutoAdjust / Use Single HSC Input button
This read-only field displays the number of counts since the last power cycle.
This read-only field displays the timestamp of the last sample from the HSC module. The timestamp is the number of milliseconds since boot.
This read-only field shows details of the fixed I/O assigned to this point.
This button toggles I/O assignments based on whether you use a single HSC input, or you use Auto Adjust which requires two HSC inputs.
To use auto adjust, click the Use AutoAdjust and assignments change to show two HSC inputs; the label on the button then changes to Use Single HSC Input.
To use a single HSC input, click the Use Single HSC Input and assignments change to a single HSC; the label on the button then changes to Use AutoAdjust.
2-8 Configuring Inputs and Outputs (I/O Tab) Issued: May-2012
ControlWave MRMS-IC Configuration Manual (D5140)
2.2.6 Ultrasonic Flow Meters (UFM)
If you have one or more ultrasonic flow meters, click the UFMs link on the top of the I/O Usage page to call up the UFM page.
Figure 2-5. Ultrasonic Flow Meter (UFM) Configuration
Configure the following fields for your ultrasonic flow meter.
Field Description Enabled/Disabled
Port
Address Enter the address of the UFM here. Press [Enter] to
Type
Issued: May-2012 Configuring Inputs and Outputs (I/O Tab) 2-9
Click this button to enable communication from this UFM to the MRMS-IC.
Use the dropdown menu to specify the ControlWave Micro serial communication port which connects to this UFM. Press [Enter] to save the selection.
save the selection.
Use the drop-down menu to select the type of UFM. Press [Enter] to save your selection.
ControlWave MRMS-IC Configuration Manual (D5140)
2.2.7 Multi-variable Transmitters (Transducers)
If you have one or more multi-variable transmitters, click the Transducers link on the top of the I/O Usage page to call up the Transducers page.
The Transducers page shows the first three multi-variable transmitters (MVTs). If you want to view a different group of three MVTs, click the button corresponding to the range of MVTs (1-3 or 4-6) on the top of the screen.
Figure 2-6. Transducers Page (Multi-Variable Transmitters)
Each MVT includes the following fields:
Field Description Enabled/Disabled
Communication Protocol (BSAP/MODBUS)
Port
2-10 Configuring Inputs and Outputs (I/O Tab) Issued: May-2012
Click this button to enable communication from this MVT to the MRMS-IC.
Click the BSAP/MODBUS button to toggle the method used to communicate with this MVT between BSAP protocol and MODBUS protocol.
Use the dropdown menu to specify the ControlWave Micro serial communication port which connects to this MVT. Press [Enter] to save the selection.
ControlWave MRMS-IC Configuration Manual (D5140)
Address Enter the address of the MVT here. Press [Enter] to
save the selection.
Xmtr Type
Register Set
Comm Stats
% Good
Good Polls
Bad Polls
Reset
Current Status
Tag Name
Serial Number
Time Stamp
DP
SP
Use the drop-down menu to select the type of data coming from this MVT. Choose either:
: Data from this type:
Type GP/T gage pressure and temperature DP/P/T differential pressure, static pressure, and
temperature
T temperature
Press [Enter] to save your selection.
This field applies only to MODBUS communication. Click either 7xxx or 4xxxx to select the MODBUS register set used by this MVT.
This read-only field shows the percentage of successful communication transactions with this MVT.
This read-only field shows the number of good poll messages in communications with this MVT.
This read-only field shows the number of bad poll messages in communications with this MVT.
This button resets the communication statistics in the %Good, Good Polls, and Bad Polls fields.
These read-only fields display the most recent status messages from this MVT.
This read-only field shows the tag name from this MVT. (BSAP only)
This read-only field shows the serial number from this MVT. (MODBUS only)
This read-only field shows the time stamp of the most recent value received from this MVT.
This read-only field shows the most recent differential pressure reading from this MVT.
This read-only field shows the most recent static
Issued: May-2012 Configuring Inputs and Outputs (I/O Tab) 2-11
ControlWave MRMS-IC Configuration Manual (D5140)
A
FT
Units
Zero
Span
2.3 Local DLM
Notes:
The local Data Line Monitor (DLM) provides details about low-
level communication messages sent through a selected serial port used by the MRMS-IC.
pressure reading from this MVT.
This read-only field shows the most recent temperature reading from this MVT.
This read-only field shows the engineering units for this variable.
This read-only field shows the value for this variable when the MVT receives a 4mA field input.
This read-only field shows the value that, when added to the Zero value, represents what the process variable should display when the field input to the MVT is 20mA.
Typically, you would only use the local DLM if you are a very
advanced user and need to perform communication troubleshooting for a particular port.
The local DLM only displays the first 80 characters of a message. The local DLM only captures messages approximately every half
second, therefore, it can miss some messages.
Click the button on the I/O tab to activate the Data Line Monitor function. The DLM includes the following fields:
Field Description Monitor Port
TX Data
Use the dropdown menu to select the ControlWave Micro serial communication port you want the DLM to monitor. Press [Enter] to save the selection.
Note:
the monitor port, you can copy data from the window to the clipboard. You can then paste this data into another file for off-line review.
This read-only field shows the most recent message transmitted through this port.
fter you collect the data, if you select “None” for
RX Data
window The window shows successive messages detected by
2-12 Configuring Inputs and Outputs (I/O Tab) Issued: May-2012
This read-only field shows the most recent message received through this port.
the DLM. Most recent messages appear at the top; you can use the scroll bar to adjust the window to show earlier messages.
ControlWave MRMS-IC Configuration Manual (D5140)
Figure 2-7. Local DLM
Issued: May-2012 Configuring Inputs and Outputs (I/O Tab) 2-13
ControlWave MRMS-IC Configuration Manual (D5140)
2.4 Customer Modbus Slave
MRMS-IC supports a single Modbus slave session you can configure to provide a Modbus slave interface to the controller.
Click the button on the I/O tab to bring up the Customer Modbus Slave page.
You can view either coils or registers in the Signal List grid.
Figure 2-8. Customer Slave Page
This page includes the following fields:
Field Description
Settings Communications Port
Serial Click the Serial selection to use serial Modbus
2-14 Configuring Inputs and Outputs (I/O Tab) Issued: May-2012
Modbus communications can use either serial or IP communications.
communication, and specify the port you want to use. (See Port).
ControlWave MRMS-IC Configuration Manual (D5140)
Field Description
Port
IP Click the IP selection to use IP Modbus (Open
Modbus Slave Address
Modbus Type
Specify the serial communication port on the ControlWave Micro you want to use for Modbus slave communication. Use the following code:
Enter this 1 COM1 2 COM2 3 COM3 4 COM4 5 COM5 6 COM6 7 COM7 8 COM8 9 COM9 10 COM10 11 COM11 Press [Enter] to save the selection.
Modbus) communication.
Enter the Modbus slave address. If the local slave address you enter has already been assigned to either the SCADA Enron Modbus slave interface, or any of the other Customer Modbus Slave sessions, you will see a Loc Addr Conflict message. Modify the Modbus Slave Address as required to resolve the conflict.
: To select this serial CW Micro port:
Enron If you want to communicate using Enron Modbus,
click this selection.
Gould If you want to communicate using Gould Modbus,
click this selection.
Data Parameters Word Order Choose the data word order to match the data word
order used by the Modbus Master that communicates with this Modbus Slave.
High Word First
Low Word First
Byte Order Choose the data byte order to match the data byte
Issued: May-2012 Configuring Inputs and Outputs (I/O Tab) 2-15
Click this to specify that the high word is first.
Click this to specify that the low word is first.
ControlWave MRMS-IC Configuration Manual (D5140)
Field Description
High Byte First
order used by the Modbus Master that communicates with this Modbus Slave.
Click this to specify that the high byte is first.
Low Byte First
Bit Order Choose the data bit order to match the data bit order
High Bit First
Low Bit First
Data Size
Click this to specify that the low byte is first.
used by the Modbus Master that communicates with this Modbus Slave.
Click this to specify that the high bit is first.
Click this to specify that the low bit is first.
Select the appropriate data format for Modbus Register data from the drop down menu. The available selections are:
Single Bit – Each Register will include a single bit Byte Data – Each Register will include a single byte 16 Bit Integer – Each Register will include a single
16-bit integer 32 Bit Int., 1 Reg., Cnt*1, Adr*1 – Each Register
will include a 32-bit double integer. 32 Bit Float, 1 Reg., Cnt*1, Adr*1 – Each Register
will include a 32-bit floating point number 32 Bit Int., 2 Reg., Cnt*2, Adr*2 – Two registers will
be used for each 32-bit double integer. The MODBUS Master must poll two registers for each 32 bit integer.
32 Bit Float, 2 Reg., Cnt*2, Adr*2 – Two registers will be used for each 32-bit floating point number. The MODBUS Master must poll two registers for each 32 bit number.
32 Bit Int., 2 Reg., Cnt*2, Adr*1 - Two registers will be used for each 32-bit double integer. The MODBUS Master must poll a single register for each 32 bit integer.
32 Bit Float, 2 Reg., Cnt*2, Adr*1 - Two registers will be used for each 32-bit floating point number. The MODBUS Master must poll a single register for each 32 bit number.
Press [Enter] to save the selection. If you don’t make a selection, the field shows Not Set.
2-16 Configuring Inputs and Outputs (I/O Tab) Issued: May-2012
ControlWave MRMS-IC Configuration Manual (D5140)
A
Field Description RTS Delay Mode
Select from one of two modes for the Ready-to-Send (RTS) delay mode.
Message Delay Mode ­raises RTS, a delay timer starts. The length of the delay is determined by the value in the Delay Time field. No message is sent until after this delay expires. The value of CTS does not affect the operation of this mode.
CTS Timeout Mode - After the Modbus slave port raises RTS, it uses the Delay Time value as the maximum time to wait for CTS to be received from the master. If the Modbus slave port receives CTS at any time before this time expires, the port starts to transmit the message. If the Modbus slave port does not receive a CTS from the master prior to the expiration of the Delay Time, it does not respond to the master and instead reports an error.
Press [Enter] to save the selection.
Delay msec Specify the Delay (in milliseconds) used by the RTS
Delay Mode and CTS Timeout Mode.
Coils List 12
Each Modbus slave session has two dedicated lists, one for Modbus Registers and the other for Modbus Coils. To display coils in the signal list grid, click this button. See Section 2.4.1 for instructions on using the signal list grid.
fter the Modbus Slave port
Register List 13
Status
2.4.1 Signal List Grid
The Signal List grid displays lists of variables included in the MRMS­IC application.
Each Modbus slave session has two dedicated lists, one for Modbus Registers and the other for Modbus Coils. To display registers in the signal list grid, click this button. See Section 2.4.1 for instructions on using the signal list grid.
This read-only field displays a status code indicating the health of the Modbus slave communications.
If you see any code other than 0 here or see an error message above the code, see Appendix E – Errors and Troubleshooting for more information.
Issued: May-2012 Configuring Inputs and Outputs (I/O Tab) 2-17
ControlWave MRMS-IC Configuration Manual (D5140)
Figure 2-9. Signal List Grid Control
Field Description
Signal List Information
The list window shows the contents of lists within the
application.
Number
Max Signals to Collect
Start Index
Collect List
Floating Point Format
Signal Name
Data Type Alarm
Specifies the number of the list. In some cases, pushing a button elsewhere on the page fills in this number; in other cases, you must enter a list number directly.
Specifies the number of list items to retrieve into the grid control. Depending upon how many list items are collected, you may need to use a scroll bar to view them.
Normally, the signal list grid displays variables beginning with the first variable in the list. If you want to skip further into the list, enter the number of the first list item you want to see in this field, and the grid starts displaying from that item forward.
Click this button to force the Signal List grid to collect the specified list now.
Click this to specify the Floating Point Format dialog box. See Figure 2-10
Shows the variable name for this list item, or its descriptor.
Shows the variable type, such as Real or Boolean. If this variable is an alarm, and this shows “AI” it
indicates the variable is alarm inhibited. If this shows “AE” it indicates that the variable is alarm enabled.
Control
2-18 Configuring Inputs and Outputs (I/O Tab) Issued: May-2012
If this shows “CI” it indicates the variable is control inhibited. If this shows “CE” it indicates that the variable is control enabled.
ControlWave MRMS-IC Configuration Manual (D5140)
Field Description Manual
If this shows “MI” it indicates the variable is manual inhibited. If this shows “ME” it indicates that the variable is manual enabled.
Value Units
Signals Collected
Shows the current value of the variable. Shows the engineering units (if specified) for this
variable. Displays a count of the number of variables collected
into the signal list grid.
2.4.2 Floating Point Format
The floating point format is the way floating point (real) numbers display within a screen in the MRMS-IC application.
To change this format, you click the button on a page, to call up the Float Format dialog box.
Figure 2-10. Floating Point Format dialog box
Field Description Width
Precision
Exponent
OK
Cancel
Choose the total number of characters in the field (including the decimal point) used to display a floating point number.
Choose the number of places to the right of the decimal point which the floating point number should show.
Select one of these formats:
e show number in exponential notation f show number in floating point notation g allow application to choose the “best fit” format
for this number.
Click this to save your entries and exit the dialog box.
Click this to discard your entries and exit the dialog
Issued: May-2012 Configuring Inputs and Outputs (I/O Tab) 2-19
ControlWave MRMS-IC Configuration Manual (D5140)
Field Description
2.5 Generic Modbus Master
Click the button on the I/O tab to activate the Generic Modbus page. There are multiple pages for Modbus Master 1 (MB1) to Modbus Master 5 (MB5). You click on a tab to call up the appropriate Modbus Master.
box.
Figure 2-11. Generic Modbus Master
This page includes the following fields:
Field Description
Settings Communications Port
Modbus communications can use either serial or IP communications.
2-20 Configuring Inputs and Outputs (I/O Tab) Issued: May-2012
ControlWave MRMS-IC Configuration Manual (D5140)
Field Description Serial Click the Serial selection to use serial Modbus
communication, and specify the port you want to use. (See Port).
Port
IP Click the IP selection to use IP Modbus (Open
Specify the serial communication port on the ControlWave Micro you want to use for Modbus master communication. Use the following code:
Enter this 1 COM1 2 COM2 3 COM3 4 COM4 5 COM5 6 COM6 7 COM7 8 COM8 9 COM9 10 COM10 11 COM11 Press [Enter] to save the selection.
Modbus) communication.
: To select this serial CW Micro port:
IP Address
Modbus Slave Address
Data Parameters Word Order Choose the data word order to match the data word
High Word First
Low Word First
Byte Order Choose the data byte order to match the data byte
If you want to use IP Modbus (Open Modbus), enter the IP address of the port used by this master.
Enter the Modbus slave address. If the local slave address you enter has already been assigned to either the SCADA Enron Modbus slave interface, or any of the other Customer Modbus Slave sessions, you will see a Loc Addr Conflict message. Modify the Modbus Slave Address as required to resolve the conflict.
order used by the Modbus Slave that communicates with this Modbus Master.
Click this to specify that the high word is first.
Click this to specify that the low word is first.
order used by the Modbus Slave that communicates with this Modbus Master.
Issued: May-2012 Configuring Inputs and Outputs (I/O Tab) 2-21
ControlWave MRMS-IC Configuration Manual (D5140)
Field Description High Byte First
Click this to specify that the high byte is first.
Low Byte First
Bit Order Choose the data bit order to match the data bit order
High Bit First
Low Bit First
Data Size
Click this to specify that the low byte is first.
used by the Modbus Slave that communicates with this Modbus Master.
Click this to specify that the high bit is first in a byte of data..
Click this to specify that the low bit is first in a byte of data.
Select the appropriate data format for Modbus Register data from the drop down menu. The available selections are:
Single Bit – Each Register will include a single bit Byte Data – Each Register will include a single byte 16 Bit Integer – Each Register will include a single
16-bit integer 32 Bit Int., 1 Reg., Cnt*1, Adr*1 – Each Register
will include a 32-bit double integer.
Function Code
32 Bit Float, 1 Reg., Cnt*1, Adr*1 – Each Register
will include a 32-bit floating point number 32 Bit Int., 2 Reg., Cnt*2, Adr*2 – Two registers will
be used for each 32-bit double integer. The MODBUS Master must poll two registers for each 32 bit integer.
32 Bit Float, 2 Reg., Cnt*2, Adr*2 – Two registers will be used for each 32-bit floating point number. The MODBUS Master must poll two registers for each 32 bit number.
32 Bit Int., 2 Reg., Cnt*2, Adr*1 - Two registers will be used for each 32-bit double integer. The MODBUS Master must poll a single register for each 32 bit integer.
32 Bit Float, 2 Reg., Cnt*2, Adr*1 - Two registers will be used for each 32-bit floating point number. The MODBUS Master must poll a single register for each 32 bit number.
Press [Enter] to save the selection. If you don’t make a selection, the field shows Not Set.
Select the Modbus function from the drop-down menu.
2-22 Configuring Inputs and Outputs (I/O Tab) Issued: May-2012
ControlWave MRMS-IC Configuration Manual (D5140)
Field Description
Press [Enter] to save the selection.
RTS Delay Mode
Delay msec Specify the Delay (in milliseconds) used by the RTS
Time Out msec
Select from one of two modes for the Ready-to-Send (RTS) delay mode.
Message Delay Mode - After the Modbus Master port raises RTS, a delay timer starts. The length of the delay is determined by the value in the Delay field. No message is sent until after this delay expires. The value of CTS does not affect the operation of this mode.
CTS Timeout Mode - After the Modbus Master port raises RTS, it uses the Delay value as the maximum time to wait for CTS to be received from the slave. If the Modbus Master port receives CTS at any time before this time expires, the port starts to transmit the message. If the Modbus master port does not receive a CTS from the slave prior to the expiration of the Delay it does not respond to the slave and instead reports an error.
Press [Enter] to save the selection.
Delay Mode and CTS Timeout Mode. Press [Enter] to save the selection.
Specify the time (in milliseconds) that the Modbus master must wait for a response from the Modbus slave before the master declares that the slave timed out. Press [Enter] to save the selection.
Collection Rate msec
Start Register
Issued: May-2012 Configuring Inputs and Outputs (I/O Tab) 2-23
Specify the interval (in milliseconds) between poll attempts by the Modbus master. Press [Enter] to save the selection.
Specify the starting address for coil or register operations. The address transmitted to the Slave is one less than the value specified here. For example, the address 7031 is sent as 7030 for Function code
ControlWave MRMS-IC Configuration Manual (D5140)
Field Description
3. Press [Enter] to save the selection.
Register Count
Disabled/Enabled If this shows Disabled, click on it to enable the
Status
List Number
Specify the number of coils or registers the Master should read. The value can range from 1 to 2000 for coils or 1 to 125 for 16-bit registers, or 1 to 62 for 32­bit registers. Press [Enter] to save the selection.
Modbus Master.
This read-only field displays a status code indicating the health of the Modbus master communications.
If you see any code other than 0 here or see an error message above the code, see Appendix E – Errors and Troubleshooting for more information.
Shows the number of the list you can open in DataView to see the collected Modbus data.
2-24 Configuring Inputs and Outputs (I/O Tab) Issued: May-2012
2.6 Load/Save Configuration
The Load/Save Configuration feature provides a way to save and restore MRMS-IC configuration data. It uses the Data Array Save/Restore utility and the recipe utility to accomplish the read/write operations.
Click the button on the I/O tab to activate the Load/Save Configuration page.
ControlWave MRMS-IC Configuration Manual (D5140)
Figure 2-12. Load/Save Configuration
Issued: May-2012 Configuring Inputs and Outputs (I/O Tab) 2-25
ControlWave MRMS-IC Configuration Manual (D5140)
2.6.1 Performing I/O Array Operations.
1. Enter a valid username/password combination for the controller
that has full privileges in the RTU User Name and RTU Password fields.
Figure 2-13. Array Read / Write
2. To read values from the I/O array in the controller and store
those values in a PC disk file, click Save I/O Configuration to Disk.
3. The Data Array Save/Restore utility starts. Note: Allow the Data Array/Save Restore utility to run by itself; you
need not enter any values unless it generates an error.
2-26 Configuring Inputs and Outputs (I/O Tab) Issued: May-2012
2.6.2 Creating a Recipe
ControlWave MRMS-IC Configuration Manual (D5140)
Figure 2-14. Recipe
To create a recipe you must first specify the variables you want included in the recipe. One way to do this is to either right-click on the grid in the center of the Recipe page and choose "Insert Signal" from the pop-up menu, or click the Insert Signal button.
Figure 2-15. Insert Signal Property dialog box
In either case, a dialog box opens and you can enter the variable's name. If desired, you can also enter a value for the variable. Click OK when you are finished. Repeat for each additional variable.
If you don't enter values for the variable when you insert it you can load the current values in the MRMS-IC for all variables in the recipe by clicking on Read From RTU.
Issued: May-2012 Configuring Inputs and Outputs (I/O Tab) 2-27
ControlWave MRMS-IC Configuration Manual (D5140)
Another way to specify variables for the recipe is to load the variables from the list. To do this, click the Load Signal List from RTU button, then specify the number of the signal list and click OK.
Figure 2-16. Signal List to Load
If, as you are creating the recipe, you decide you want to change a variable or value for a particular entry, either right click on the entry and choose "Edit Signal" from the pop-up menu, or click the Modify Signal button. Make changes, as desired, and click OK.
If you want to delete a variable in the recipe, either right-click on the line for that variable and choose "Delete Signal" from the pop-up menu, or click the Delete Signal button. You will be prompted to confirm the deletion.
For information on changing the floating point format of values in the recipe, see Section 2.4.2.
2.6.3 Saving the Recipe
Type the path and filename for your recipe file in the "Filename" field or click Change Filename to select a recipe from the default recipe area. Standard recipe files are stored with a file extension of (.RCP). You also have the option of saving the file as a .CFG file (which is intended for use with Coastal Flow Measurement Inc. Flow-Cal™ software.)
Figure 2-17. Edit Signal Property
2-28 Configuring Inputs and Outputs (I/O Tab) Issued: May-2012
ControlWave MRMS-IC Configuration Manual (D5140)
Figure 2-18. Saving the Recipe
Once you have specified the path and filename, click on the Write to File button; answer Yes to the confirmation prompt, and the control
writes the recipe to the specified file.
2.6.4 Recalling a Saved Recipe, and Sending Its Values to the Controller
To recall a recipe which you have saved previously, use the Change Filename button to locate it, or type its path and filename in directly in
the "Filename" field. Finally, click the Read From File button, and the recipe will be brought into the web page.
Once the recipe file has been loaded, you can send the recipe values to the controller by clicking on the Write to RTU button; answer Yes to the confirmation prompt, and the control writes the recipe to the controller
2.7 Time Set/Daylight Saving Time
Click the button on the I/O tab to open the Time Set/Daylight Saving Time page.
Issued: May-2012 Configuring Inputs and Outputs (I/O Tab) 2-29
ControlWave MRMS-IC Configuration Manual (D5140)
Figure 2-19. Time Set/Daylight Saving Time page
Field Description Current RTU Date and
Time Current PC Date and
Time
Clear Registers Click this button to set all six time registers (Year,
Load Registers with the RTUs Date/Time
Load Registers with the PCs Date/Time
Year
Month
Day
This read-only field shows the current date and time setting at the controller.
This read-only field shows the current date and time at the PC workstation.
Month, Day, Hour, Minutes and Seconds) to zero.
Click this button to store the controller time in the six time registers.
Click this button to store the PC workstation time in the six time registers.
This time register holds a year value. You can set it by typing in a value, or you can load it by one of the buttons.
This time register holds a month value. You can set it by typing in a value, or you can load it by one of the buttons.
This time register holds a day value. You can set it by typing in a value, or you can load it by one of the buttons.
2-30 Configuring Inputs and Outputs (I/O Tab) Issued: May-2012
ControlWave MRMS-IC Configuration Manual (D5140)
Field Description Hour
Minutes
Seconds
Set RTU Date/Time with Register Values
This time register holds an hour value. You can set it by typing in a value, or you can load it by one of the buttons.
This time register holds a minute value. You can set it by typing in a value, or you can load it by one of the buttons.
This time register holds a seconds value. You can set it by typing in a value, or you can load it by one of the buttons.
Click this button to update the controller’s date and time with the values currently in the time registers.
Issued: May-2012 Configuring Inputs and Outputs (I/O Tab) 2-31
This page is intentionally left blank
ControlWave MRMS-IC Configuration Manual (D5140)
Chapter 3 – Configuring Stations and Runs (Measurement
Tab)
Note: Although you can view data through an IP connection, the MRMS-
IC application only allows configuration changes when you establish a physical serial connection to serial communication port 1 on the ControlWave Micro.
This chapter discusses configuring the stations and meter runs for the MRMS-IC application as well as all the measurement functions for the various meter runs. This is accomplished from the MRMS-IC Measurement tab.
In This Chapter
3.1Measurement Tab ........................................................................................................ 3-2
3.2Status/Configuration ..................................................................................................... 3-3
3.2.1 Site Configuration Data Tab (Site Configuration) ..................................... 3-4
3.2.2 MVT Common Settings Tab (Site Configuration) ..................................... 3-7
3.2.3 Station Summaries Tab (Site Configuration) ............................................ 3-8
3.2.4 Station Configuration Tab (Station Configuration).................................. 3-10
3.2.5 Station Data Tab (Station Configuration) ............................................... 3-15
3.2.6 Run Config Tab (Run Configuration) ...................................................... 3-16
3.2.7 Alarm Configuration Tab (Run Configuration) ........................................ 3-21
3.2.8 Linearization Config Tab (Run Configuration) ........................................ 3-23
3.2.9 PV/GQ Averages Tab (Run Configuration) ............................................ 3-24
3.2.10 Orifice Tab (Run Configuration).............................................................. 3-25
3.2.11 Turbine Tab (Run Configuration) ............................................................ 3-29
3.2.12 Auto-Adjust Tab (Run Configuration) ..................................................... 3-32
3.2.13 Ultrasonic Tab (Run Configuration) ........................................................ 3-34
3.2.14 PD Tab (Run Configuration) ................................................................... 3-37
3.3View Local Archives ................................................................................................... 3-39
3.3.1 Selecting Logs to View ........................................................................... 3-39
3.4Collect Local Logs ...................................................................................................... 3-40
3.4.1 Selecting Archives for Collection ............................................................ 3-40
3.4.2 Collecting a Single Archive ..................................................................... 3-40
3.4.3 Collecting Multiple Archives .................................................................... 3-40
3.4.4 Log Collection Parameters ..................................................................... 3-40
3.5View Audit Log ........................................................................................................... 3-43
3.5.1 Data Storage Parameters dialog box ..................................................... 3-44
3.5.2 Search Data Collection Criteria dialog box ............................................. 3-45
3.6Maintenance Mode ..................................................................................................... 3-46
3.6.1 Site Tab .................................................................................................. 3-46
3.6.2 Station Tab ............................................................................................. 3-49
3.6.3 Run Tab .................................................................................................. 3-51
3.6.4 PVs Tab .................................................................................................. 3-53
3.6.5 AI Maintenance Tab................................................................................ 3-54
3.7Gas Chromatograph Configuration ............................................................................ 3-56
3.7.1 General ................................................................................................... 3-56
3.7.2 Current Tab (Gas Chromatograph Configuration) .................................. 3-61
3.7.3 Component Tab (Gas Chromatograph Configuration) ........................... 3-65
3.7.4 Delta Limit Tab (Gas Chromatograph Configuration) ............................. 3-67
3.7.5 Normalization Tab (Gas Chromatograph Configuration) ........................ 3-68
Issued: May-2012 Configuring Stations and Runs (Measurement Tab) 3-1
ControlWave MRMS-IC Configuration Manual (D5140)
3.7.6 Custom Tab (Gas Chromatograph Configuration) ................................. 3-69
3.8Summary Pages ......................................................................................................... 3-70
3.8.1 Measurement Tab................................................................................... 3-70
3.8.2 Alarm Tab ............................................................................................... 3-71
3.9Limits Page (Gas Composition Allowable Ranges) ................................................... 3-72
3.10Daily Run Corrected and Uncorrected Volume .......................................................... 3-73
3.1 Measurement Tab
Click the Measurement tab to display the measurement options you can configure. We’ll discuss each of these in the sections that follow.
Figure 3-1. Measurement Tab in MRMS-IC
Click on the button to configure or view a particular function
3-2 Configuring Stations and Runs (Measurement Tab) Issued: May-2012
3.2 Status/Configuration
When you click the button on the Measurement tab, MRMS-IC opens up a tree structure that shows the site and lists the stations and meter runs.
ControlWave MRMS-IC Configuration Manual (D5140)
Calling up pages for configuring the site,
station, or meter run
Double-click on items in the tree to bring up configuration pages for the site, station, or meter run.
Click on the site name to call up pages for site. If no site name exists yet, click on “Unnamed Site.”
Click on the “Station n” name to call up pages for configuring the station.
Click on the “Run n” name to call up pages for configuring the meter run.
configuring the
Figure 3-2. Selecting the Site, Stations, and Runs
Issued: May-2012 Configuring Stations and Runs (Measurement Tab) 3-3
ControlWave MRMS-IC Configuration Manual (D5140)
3.2.1 Site Configuration Data Tab (Site Configuration)
The Site Configuration Data tab shows basic information about the site.
Figure 3-3. Site Configuration data tab
Field Description
Site Name
Software
Program Name
Revision
PLC Firmware These fields refer to the ControlWave internal system
The site refers to the geographical location or an organizational name associated with this MRMS-IC controller. You might name the site after the RTU node name or a place. Enter a name and press the [Enter] key to save your entry.
This read-only field shows the name of the MRMS-IC software installed on the RTU.
This read-only field shows the revision of the MRMS­IC software running on the RTU.
The revision is in the format V.v Rnn Where: V is the major version number
v is the minor version number
Rnn is the revision build number, if this is
a revision release of the software.
firmware that controls operation the ControlWave Micro.
3-4 Configuring Stations and Runs (Measurement Tab) Issued: May-2012
ControlWave MRMS-IC Configuration Manual (D5140)
r
r
Major
Minor
OBSI Version Reserved for future use. Load Versions The load version fields let you compare the revisions of
RAM: Name
RAM: Date
BOOTFILE: Name
BOOTFILE: Date
Status This read-only field shows Match if the name and date
PLC Time This read-only field shows the current date and time
This read-only field shows the major revision numbe of the system firmware running in the ControlWave Micro.
This read-only field shows the minor revision numbe of the system firmware running in the ControlWave Micro.
the ControlWave project stored in flash (ControlWave bootproject) and the revision of the ControlWave project currently executing in SDRAM.
This read-only field shows the name of the ControlWave project executing in the ControlWave Micro’s SDRAM.
This read-only field shows the date and time stamps of the ControlWave project executing in the ControlWave Micro’s SDRAM. Dates use the format mm/dd/yyyy where mm is the two-digit month (01 to 12), dd is the two-digit day (01 to 31), and yyyy is the four-digit year. Timestamps are in the format hh:mm:ss where hh is the 2-digit hour (0 to 23), mm is the 2-digit minute (0 to
59) and ss is the two-digit second (0 to 59). This read-only field shows the name of the
ControlWave bootproject stored in FLASH at the ControlWave Micro.
This read-only field shows the date and time stamps of the ControlWave bootproject stored in FLASH at the ControlWave Micro. Dates use the format mm/dd/yyyy where mm is the two-digit month (01 to 12), dd is the two-digit day (01 to 31), and yyyy is the four-digit year. Timestamps are in the format hh:mm:ss where hh is the 2-digit hour (0 to 23), mm is the 2-digit minute (0 to
59) and ss is the two-digit second (0 to 59).
of the ControlWave project executing in SDRAM is identical to that for the bootproject stored in FLASH.
If this field shows Mismatch this indicates that the ControlWave project executing in SDRAM is not the same as the bootproject.
This is an error condition because if the unit restarts for any reason, the bootproject overwrites the project executing in SDRAM on restart and you will lose the SDRAM project.
stamps of the ControlWave Micro’s real time clock. Dates use the format mm/dd/yyyy where mm is the two-digit month (01 to 12), dd is the two-digit day (01 to
31), and yyyy is the four-digit year. Timestamps are in the format hh:mm:ss where hh is the 2-digit hour (0 to
23), mm is the 2-digit minute (0 to 59) and ss is the two-digit second (0 to 59).
Issued: May-2012 Configuring Stations and Runs (Measurement Tab) 3-5
ControlWave MRMS-IC Configuration Manual (D5140)
PLC Identification This read-only field identifies boot PROM firmware
Power These fields show information about power status at
installed in the ControlWave Micro. To use the MRMS-IC application, your boot PROM firmware must have the prefix CWM.
the ControlWave Micro.
DC
Detected I/O These fields show the types of I/O modules detected
Slot n
Total Points These fields show the total number of different types of
AIs
AOs
DIs
DOs
HSCs
RTDs
TCs
This read-only field shows the DC voltage level at the ControlWave Micro’s power supply sequencer module (PSSM).
by the MRMS-IC as being installed in the ControlWave Micro.
This read-only field shows details of the installed I/O module that the MRMS-IC detects in this ControlWave Micro slot. The slot number from 1 to 14 refers to slots in the base and expansion housings.
I/O points from all the I/O modules detected by the MRMS-IC application.
This read-only field shows the total number of analog inputs residing across all I/O modules detected by the MRMS-IC application.
This read-only field shows the total number of analog outputs residing across all I/O modules detected by the MRMS-IC application.
This read-only field shows the total number of discrete inputs residing across all I/O modules detected by the MRMS-IC application. Note: This count includes all possible DIs, including a DI/DO point configured as a DO.
This read-only field shows the total number of discrete outputs residing across all I/O modules detected by the MRMS-IC application. Note: This count includes all possible DOs, including a DI/DO point configured as a DI.
This read-only field shows the total number of high speed counter inputs residing across all I/O modules detected by the MRMS-IC application.
This read-only field shows the total number of resistance temperature device inputs residing across all I/O modules detected by the MRMS-IC application.
This read-only field shows the total number of thermocouple inputs residing across all I/O modules detected by the MRMS-IC application.
3-6 Configuring Stations and Runs (Measurement Tab) Issued: May-2012
ControlWave MRMS-IC Configuration Manual (D5140)
3.2.2 MVT Common Settings Tab (Site Configuration)
This page configures details for the multivariable transmitter/transducer (MVT).
Figure 3-4. MVT Common Settings tab
Field Description Collect Process
Variable (PV) Data every msecs
Collect Diagnostic Data every msecs
Indicate Communications Failure when No Response after msecs
Maximum Monitor Count
Enter how often (in milliseconds) the ControlWave Micro should collect process variable (PV) data. For natural gas measurement in custody transfer applications, the API requires updates no less frequent than 1.0 seconds (1,000 milliseconds). The ControlWave Micro can communicate with up to eight (8) MVTs per second using a single RS-485 port at 19,200 baud. Press the [Enter] key to save your entry.
Enter how often to collect diagnostic data from the MVT (in milliseconds). You should not set the interval of this collection to be very short, because it may interfere with the higher priority PV data collection. Press the [Enter] key to save your entry.
Enter the period (in milliseconds) that the MRMS-IC application waits before declaring that a loss in communications to the MVT constitutes a communications timeout.
Enter the maximum number of polls that the MRMS-IC application uses to count good/bad polls and determine the %good.
Issued: May-2012 Configuring Stations and Runs (Measurement Tab) 3-7
ControlWave MRMS-IC Configuration Manual (D5140)
3.2.3 Station Summaries Tab (Site Configuration)
Figure 3-5. Station Summaries tab
Note: Fields appear grayed out if the station is not configured.
Field Description Station n Identifies one of the six stations.
Flow Rate Fwd
Flow Rate Rev
Energy Rate Fwd
This read-only field shows the instantaneous flow rate at this station. If this station supports bi­directional flow, this is the instantaneous forward flow rate when flow is in the forward direction (odd) or is the instantaneous reverse flow rate (even).
This read-only field shows the instantaneous reverse flow rate from the corresponding bi-directional even numbered station when flow is in the reverse direction. (Odd stations only.)
This read-only field shows the instantaneous energy rate at this station. If this station supports bi­directional flow, this is the instantaneous forward energy rate when flow is in the forward direction (odd) or is the instantaneous reverse energy rate (even).
Energy Rate Rev
Today’s Volume Fwd
3-8 Configuring Stations and Runs (Measurement Tab) Issued: May-2012
This read-only field shows the instantaneous reverse energy rate from the corresponding bi-directional even numbered station when flow is in the reverse direction. (Odd stations only.)
This read-only field shows today’s accumulated flow total (volume). If this station supports bi-directional flow, this is the accumulated forward flow total when flow is in the forward direction (odd) or is the
ControlWave MRMS-IC Configuration Manual (D5140)
accumulated reverse flow total (even).
Today’s Volume Rev
Today’s Energy Fwd
Today’s Energy Rev
This read-only field shows today’s accumulated flow total from the corresponding bi-directional even numbered station when flow is in the reverse direction. (Odd stations only.)
This read-only field shows today’s accumulated energy total. If this station supports bi-directional flow, this is the accumulated forward energy total when flow is in the forward direction (odd) or is the accumulated reverse energy total (even).
This read-only field shows today’s accumulated energy total from the corresponding bi-directional even numbered station when flow is in the reverse direction. (Odd stations only.)
Issued: May-2012 Configuring Stations and Runs (Measurement Tab) 3-9
ControlWave MRMS-IC Configuration Manual (D5140)
3.2.4 Station Configuration Tab (Station Configuration)
MRMS-IC supports up to six individual stations.
Figure 3-6. Station Configuration tab
Field Description
Station Name
Station Common Settings
Atmospheric Pressure Value, Units
Base Pressure Value, Units
The station refers to a natural gas measurement station with one or more associated meter runs. Enter a name and press the [Enter] key to save your entry.
Enter the standard atmospheric (barometric) pressure for the station in the Value field and press [Enter] to save your entry. Then select the desired Units of measure from the drop-down menu and press [Enter] to save your selection. The default is 14.7 PSI. Note: Units are absolute pressure units.
Enter the base pressure that the MRMS-IC application should use when it performs AGA calculations in the Value field and press [Enter] to save your entry. Then select the desired Units of measure from the drop-down menu and press [Enter] to save your selection. The default is 14.73 PSI
3-10 Configuring Stations and Runs (Measurement Tab) Issued: May-2012
ControlWave MRMS-IC Configuration Manual (D5140)
(absolute).
Base Temperature Value, Units
Contract Hour
Flowing Units You can select units for corrected flow (Flow),
Flow Rate Units
Enter the base temperature that the MRMS-IC application should use when it performs AGA calculations in the Value field and press [Enter] to save your entry. Then select the desired Units of measure from the drop-down menu and press [Enter] to save your selection. The default is 60 Deg F.
The contract hour determines the start of the gas day. This is when the current day totals and averages get rolled over to the previous day totals and averages. The contract hour is based on a 24 hour clock; 1 PM is 13, 2 PM is 14, and so on. Midnight is 00. Enter the desired contract hour and press [Enter] to save your entry. The default is 9 (9AM).
Uncorrected (UC) Flow, and Energy rates for the combined station flow and energy rates independently of the meter run rates.
Select the desired units of measure for the corrected flow rate from the drop-down menu and press [Enter] to save your selection.
Flow rate units include: MSCF/YEAR Thousands of Standard Cubic Feet
per Year
MSCF/DAY MSCF/HOUR Thousands of Standard Cubic Feet MSCF/MIN MSCF/SEC E3M3/YEAR Thousands of Standard Cubic Meters E3M3/DAY E3M3/HOUR Thousands of Standard Cubic Meters E3M3/MIN Thousands of Standard Cubic Meters E3M3/SEC MMSCF/YEAR Millions of Standard Cubic Feet per MMSCF/DAY Millions of Standard Cubic Feet per MMSCF/HOUR Millions of Standard Cubic Feet per
Thousands of Standard Cubic Feet per Day
per Hour Thousands of Standard Cubic Feet per Minute Thousands of Standard Cubic Feet per Second
per Year Thousands of Standard Cubic Meters per Day
per Hour per Minute
Thousands of Standard Cubic Meters per Second
Year Day Hour
Issued: May-2012 Configuring Stations and Runs (Measurement Tab) 3-11
ControlWave MRMS-IC Configuration Manual (D5140)
MMSCF/MIN Millions of Standard Cubic Feet per MMSCF/SEC Millions of Standard Cubic Feet per
E6M3/YEAR Millions of Standard Cubic Meters per E6M3/DAY Millions of Standard Cubic Meters per E6M3/HOUR Millions of Standard Cubic Meters per E6M3/MIN E6M3/SEC
Energy Rate Units
Energy Rate Time Units
Select the desired units of measure for the energy rate from the drop-down menu and press [Enter] to save your selection.
Energy rate units include: MMBTU Millions of British Thermal Units
MJ Megajoules KJ Kilojoules J Joules ERG Ergs KCAL Kilocalories CAL Calories CHU Centigrade Heat Unit KWH Kilowatt Hour QUAD
THERM Therms TONTNT Tons of TNT TONCOAL Tons of coal MMMBTU Billions of British Thermal Units GJ Gigajoules
Select the desired units of time to associate with the energy rate units from the drop-down menu and press [Enter] to save your selection.
Minute Second
Year Day Hour
Millions of Standard Cubic Meters per Minute Millions of Standard Cubic Meters per Second
short scale quadrillion British Thermal Units
UC Flow Rate Units
3-12 Configuring Stations and Runs (Measurement Tab) Issued: May-2012
Select the desired units of measure for the uncorrected flow rate from the drop-down menu and press [Enter] to save your selection.
Uncorrected flow rate units include: MACF/YEAR Thousands of Actual Cubic Feet per
Year
ControlWave MRMS-IC Configuration Manual (D5140)
Gas Chromatograph
MACF/DAY
Thousands of Actual Cubic Feet per Day
MACF/HOUR Thousands of Actual Cubic Feet per
Hour
MACF/MIN MACF/SEC
Thousands of Actual Cubic Feet per Minute Thousands of Actual Cubic Feet per
Second E3M3/YEAR Thousands of Cubic Meters per Year E3M3/DAY Thousands of Cubic Meters per Day E3M3/HOUR Thousands of Cubic Meters per Hour E3M3/MIN Thousands of Cubic Meters per
Minute E3M3/SEC Thousands of Cubic Meters per
Second MMACF/YEAR Millions of Actual Cubic Feet per Year MMACF/DAY Millions of Actual Cubic Feet per Day MMACF/HOUR Millions of Actual Cubic Feet per Hour MMACF/MIN Millions of Actual Cubic Feet per
Minute MMACF/SEC Millions of Actual Cubic Feet per
Second E6M3/YEAR Millions of Cubic Meters per Year E6M3/DAY Millions of Cubic Meters per Day E6M3/HOUR Millions of Cubic Meters per Hour E6M3/MIN Millions of Cubic Meters per Minute E6M3/SEC
Millions of Cubic Meters per Second
BTU Saturation Setting
Chromatograph Data Set
Compressibility Calc
Gross Method
Click the Dry BTU button if you want MRMS-IC to use the dry BTU value from the gas chromatograph, or click the Sat. Wet BTU button if you want MRMS­IC to use the saturated (wet) BTU value from the gas chromatograph.
Enter the chromatograph data set you want to use and press [Enter] to save your entry. Specify 0 if you want to set this on a per run basis.
Use the drop-down menu to select the calculation you want MRMS-IC to use for compressibility, and press the [Enter] key to save your selection.
If you choose AGA8 Gross for your compressibility calculations select the gross method here from the drop-down menu, and press the [Enter] key to save your selection.
Choices include: SG, CO2, N2 The MRMS-IC application performs
calculations using inputs of relative
density (specific gravity or SG), and
the mole fractions of nitrogen (N2)
Issued: May-2012 Configuring Stations and Runs (Measurement Tab) 3-13
ControlWave MRMS-IC Configuration Manual (D5140)
HV, SG, CO2 The MRMS-IC application performs
Note: MRMS-IC ignores the method setting for calculations other than AGA8 Gross.
Calculations Uses
Averaging Averaging Method
Upon Flow Failure Use
This setting determines whether the MRMS-IC application uses “In Use” or “Fixed” gas chromatograph data if the gas chromatograph (GC) fails. A GC failure could include a communication failure, a range problem and so on. Click the Fixed - Scheduled button to use fixed data during a GC failure, or the GC button to use in-use GC data during a GC failure.
Use the drop-down menu to select the averaging method you want MRMS-IC to use, and press the [Enter] key to save your selection.
This setting determines whether the MRMS-IC application uses a flow weighted average, or a straight average during a no flow condition. Click the Flow Weighted button to use a flow weighted average when there is no flow. Click the Straight Average button to use a straight average when there is no flow.
and carbon dioxide (CO2).
calculations using inputs of the
heating value (HV), the relative
density (specific gravity or SG), and
the mole fraction of carbon dioxide
(CO2).
3-14 Configuring Stations and Runs (Measurement Tab) Issued: May-2012
ControlWave MRMS-IC Configuration Manual (D5140)
3.2.5 Station Data Tab (Station Configuration)
The current station Flow and Energy rates are indicated here. The flow rate is in units of MSCF per hour and the energy rate is in units of MMBTU per hour.
Station
Accumulations
Forward / Reverse
The current hour, contract day and contract month, and the previous hour, contract day and contract month accumulations are displayed here, in units of MSCF and MMBTU.
When configuring for bidirectional flow, the stations must be paired (1 and 2; 3 and 4; or 5 and 6).
The odd-numbered stations (1, 3, or 5) are the “forward” flowing stations, and the even-numbered stations (2, 4, or 6) are the “reverse” flowing stations.
When a pair of stations is configured for bidirectional flow, the Station Summary screen for the odd-numbered (forward) stations will indicate flow and energy rates in the “forward” column when flow is in the “forward” direction, and will indicate flow and energy rates in the “reverse” column when flow is in the “reverse” direction.
However, the Station Summary screen for the even-numbered (reverse) stations, will indicate flow and energy rates in the “forward” column when flow for the combined station is in the “reverse” direction, and will always indicate no flow or energy rate in the “reverse” column.
Figure 3-7. Station Data tab
Issued: May-2012 Configuring Stations and Runs (Measurement Tab) 3-15
ControlWave MRMS-IC Configuration Manual (D5140)
r
3.2.6 Run Configuration Tab
Figure 3-8. Run Configuration tab
Field Description
Run ID
Measurement Type
Chromatograph Data Set
Direction
PVs
Enter a name and press the [Enter] key to save you entry. The generic Run ID of Run 1 will be replaced by the user specific Run ID. Select the measurement type from the drop-down menu.
The chromatograph stream used for measurement of this run may be assigned at the Station level, or at the Run level. If a chromatograph stream is assigned at the Station level, the user will be unable to assign the stream at the run level.
If the chromatograph stream is assigned as 0 at the Station level, the user will be able to assign the stream at the run level.
If the run being configured has been assigned to a station configured as a forward flowing station, this will be indicated on this screen as “Forward”, and the PV’s section will be grayed out.
If the run being configured has been assigned to a station configured as a reverse flowing station, this will be indicated on this screen as “Reverse.” It will then be possible to configure the PVs (Process Variables) section. The user may then select
3-16 Configuring Stations and Runs (Measurement Tab) Issued: May-2012
ControlWave MRMS-IC Configuration Manual (D5140)
between Isolated and Non-Isolated PVs. Isolated PV is used when the forward run and reverse run each are using different Input Sources.
Non-Isolated PV is used when the forward run and reverse run are using the same Input Sources.
Station Assignment
Static Pressure and Flowing Temperature
Source
MVT#
To assign the run to a station, click on the Station Assignment box.
Select a station from the drop down menu, and press [Enter]. (Note, if the Station ID has been changed on the Station Configuration screen, the user defined Station Name will appear in the drop down menu, instead of the generic Station Name.) After assigning a run to a station, the run will appear under the station in the Site Tree.
Every type of measurement requires a static pressure measurement and a temperature measurement.
The source for these measurements may come from either Analog Inputs via the I/O cards (Hardware AI) or via serial communications to the Multi-Variable Transmitters (MVT).
The selection of the source is made by clicking on the button. If MVT is chosen, the user may select from any of the 12 MVTs.
Issued: May-2012 Configuring Stations and Runs (Measurement Tab) 3-17
ControlWave MRMS-IC Configuration Manual (D5140)
Override/Live
Value
Units
Flowing Units
The user may override the measurement values in use by selecting Override instead of Live
When Override is selected, the user may enter the desired value for the measurement to be used.
When Live is selected, the Value will be driven by the appropriate input value.
Note: the action of changing from Live to Override or Override to Live is entered in the Audit trail. When in Override, any changes made to the Value are entered in the Audit Trail.
Note: These overrides are done at the Run Measurement level, not at the I/O level. Because of this, care needs to be taken when overriding runs configured for bidirectional measurement, because the logic overriding the measurement values occurs after the logic for routing the measurement inputs to the proper run.
The static pressure and flowing temperature values in use are shown here.
When “Live” is selected via the “Override/Live” button, this value is the value coming from the Static Pressure or Flowing Temperature Source.
When “Override” is selected via the “Override/Live” button, this value may be entered by the user, and the entered value will be used in the measurement calculation. The units for the measurement inputs come from the input source.
Flow Rate and Energy Rate units may be assigned on a per run basis.
Flow Rate Units MSCF/YEAR MSCF/DAY MSCF/HOUR MSCF/MIN MSCF/SEC E3M3/YEAR E3M3/DAY E3M3/HOUR E3M3/MIN E3M3/SEC MMSCF/YEAR MMSCF/DAY MMSCF/HOUR MMSCF/MIN MMSCF/SEC
3-18 Configuring Stations and Runs (Measurement Tab) Issued: May-2012
ControlWave MRMS-IC Configuration Manual (D5140)
E6M3/YEAR E6M3/DAY E6M3/HOUR E6M3/MIN E6M3/SEC
where: MSCF – Thousands of Standard Cubic Feet MMSCF – Millions of Standard Cubic Feet E3M3 – Thousands of Cubic Meters E6M6 – Millions of Cubic Meters MIN – Minutes SEC - Seconds
Uncorrected (UC) Flow Rate Units MACF/YEAR MACF/DAY MACF/HOUR MACF/MIN MACF/SEC E3M3/YEAR E3M3/DAY E3M3/HOUR E3M3/MIN E3M3/SEC MMACF/YEAR MMACF/DAY MMACF/HOUR MMACF/MIN MMACF/SEC E6M3/YEAR E6M3/DAY E6M3/HOUR E6M3/MIN E6M3/SEC
where: ACF – Actual Cubic Feet E3M3 – Thousands of Cubic Meters E6M3 –Millions of Cubic Meters
Energy Rate Units MMBTU MJ KJ J ERG KCAL CAL CHU KWH QUAD THERM TONTNT TONCOAL MMMBTU GJ
Issued: May-2012 Configuring Stations and Runs (Measurement Tab) 3-19
ControlWave MRMS-IC Configuration Manual (D5140)
where: MMBTU – Millions of British Thermal Units MJ – Mega joules KJ – Kilojoules J – Joules ERG – Ergs KCAL – Kilocalories CAL – Calories CHU - Celsius-heat unit KWH – Kilowatt Hours QUAD - short-scale quadrillion THERM – Therms TONTNT – Tons of TNT TONCOAL – Tons of Coal MMMBTU – Billions of BTU GJ – Gigajoules
Energy Rate Time Units: YEAR DAY HOUR MIN
SEC
3-20 Configuring Stations and Runs (Measurement Tab) Issued: May-2012
ControlWave MRMS-IC Configuration Manual (D5140)
3.2.7 Alarm Configuration Tab (Run Configuration)
The MRMS-IC program allows for certain items to be configured as alarms.
When an item is configured as an alarm, then any time the value goes into or out of the alarm state, an entry will be made in the Audit Trail.
In addition, if the MRMS-IC controller is being used in a BSAP network, then these alarms will be reported to the SCADA host, if the SCADA host supports BSAP alarms.
To configure the alarm limits for run specific data, click on the Alarm Configuration Tab
This screen opens.
Figure 3-9. Alarm Configuration tab
The following items may be configured for alarms.
Field Description Flow Rate
Diff Pressure
Static Pressure
Issued: May-2012 Configuring Stations and Runs (Measurement Tab) 3-21
The High and Low Limits for the flow rate are automatically calculated, based on the Maximum and Minimum flow rates through the meter run.
For an orifice meter only, High-High, High, Low, and Low-Low alarm limits may be set for the differential pressure input.
For all meter types, High-High, High, Low, and Low-Low alarm limits may be set for the static pressure input.
ControlWave MRMS-IC Configuration Manual (D5140)
Temperature
Beta Ratio
Speed of Sound
Frequency
Enabled/Disabled
For all meter types, High-High, High, Low, and Low-Low alarm limits may be set for the flowing temperature input.
For an orifice meter only, High and Low alarm limits may be set for the calculated beta ratio.
For an ultrasonic meter only, the High alarm limit for the deviation between the speed of sound as calculated using AGA 10 and the speed of sound reported from the ultrasonic meter may be configured.
For linear meter types (ultrasonic, turbine, AutoAdjust, and positive displacement (PD) meters, High-High, High, Low, and Low-Low alarm limits may be set for the frequency input.
An alarm may be Enabled or Disabled via the Enable/Disable button. By default, the alarms are disabled. When an alarm is disabled, no entries are made into the Audit Trail if the value goes in to or out of alarm.
3-22 Configuring Stations and Runs (Measurement Tab) Issued: May-2012
ControlWave MRMS-IC Configuration Manual (D5140)
3.2.8 Linearization Config Tab (Run Configuration)
The MRMS-IC program allows for the linearization of the frequency outputs of turbine meters.
To configure the linearization table, click on the Linearization Config Tab This screen opens.
Figure 3-10. Linearization Config tab
This linearization table must be configured by the user. Click the Push to Edit Values button to makes your entries. For up to 12 points, the user
must enter an uncorrected flow rate in units of Actual Cubic Feet per hour, and an associated correction factor (C factor). The MRMS-IC program will interpolate between any two points on this table to calculate the C Factor for a specific flow rate. When you finish making your entries, click the Push to Confirm and Lock Values button.
Caution
If the user does not configure all 12 points, then the last non-zero entry for ACF/H will be used as the last correction factor. Any uncorrected flow rate above this point will use the correction factor for this point, there will be no interpolation performed.
Issued: May-2012 Configuring Stations and Runs (Measurement Tab) 3-23
ControlWave MRMS-IC Configuration Manual (D5140)
3.2.9 PV/GQ Averages Tab (Run Configuration)
The MRMS-IC program calculates and displays averages for the process values used for measurement, and the gas quality data used by the measurement for each run.
To view the averages for the process variables and gas quality data, click on the PV/GQ Averages Tab. This screen will appear.
Figure 3-11. PV/GQ Averages tab
The averaging method for the differential pressure is always flow­dependent time-weighted linear averaging.
The averaging method for the static pressure and flowing temperature may be any of the API averaging methods.
The averaging method for the gas quality data is always time-weighted linear averaging.
3-24 Configuring Stations and Runs (Measurement Tab) Issued: May-2012
ControlWave MRMS-IC Configuration Manual (D5140)
3.2.10 Orifice Tab (Run Configuration)
To configure a run as an orifice meter, click on the Measurement Type on the Run Configuration tab and select Orifice from the drop down menu, then press Enter.
Click on the Orifice tab, and the following screen opens.
Figure 3-12. Orifice tab
Field Description
Settings
Orifice Diameter
Pipe Diameter
Issued: May-2012 Configuring Stations and Runs (Measurement Tab) 3-25
The Orifice Diameter in use is displayed in the “Settings” section of this screen. To change the orifice diameter, see the “Plate Change” section.
The pipe diameter change may be made by clicking on the box with the pipe diameter value in it and entering the desired pipe diameter value. When the new value of the pipe diameter is entered, a new beta ratio will be calculated and displayed in the “Plate Change” section.
ControlWave MRMS-IC Configuration Manual (D5140)
Low Flow Cutoff
Pressure Tap Location
Differential Pressure
Source
MVT#
The low flow cutoff is the minimum value for differential pressure where measurement will be performed. If the differential pressure drops below this value, the measured flow goes to zero.
The user may change the low flow cutoff value by clicking on the box with the low flow cutoff value and entering a new value, and clicking OK.
The user may change the units that the low flow cutoff value is measured, by clicking on the units box, and selecting the desired units from the drop down menu.
The user may change the pressure tap location by clicking on Pressure Tap Location button.
The source for the Differential Pressure measurement may come from either Analog Inputs via the I/O cards (Hardware AI) or via serial communications to the Multi-Variable Transmitters (MVT).
The selection of the source is made via the Hardware AI/MVT button on the screen:
If MVT is chosen, the user may select from any of 12 MVTs.
Default AI / Stacked DP
Override / Live
3-26 Configuring Stations and Runs (Measurement Tab) Issued: May-2012
The user may select from either the default AI (as specified in the Run x Differential Pressure field on the I/O configuration page) or a pair of stacked transmitters (Stacked DP x Lo/Hi selections the on I/O configuration page).
The user may override the measurement values in use by selecting Override instead of Live
When Override is selected, the user may enter the desired value for the measurement to be used.
When Live is selected, the Value will be driven by the appropriate input value.
Note: the action of changing from Live to Override or
ControlWave MRMS-IC Configuration Manual (D5140)
Override to Live is entered in the Audit trail. When in Override, any changes made to the Value are entered in the Audit Trail.
Note: This override is done at the Run Measurement level, not at the I/O level. Because of this, care needs to be taken when overriding runs configured for bidirectional measurement, because the logic overriding the measurement values occurs after the logic for routing the measurement inputs to the proper run.
Value
Units
Stacked Transmitters
Set Point
Dead Band
Current Rate
Plate Change To change the orifice diameter, the user must
The differential pressure value in use is shown here. When “Live” is selected via the “Override/Live”
button, this value is the value coming from the Differential Pressure Source.
When “Override” is selected via the “Override/Live” button, this value may be entered by the user, and the entered value will be used in the measurement calculation.
The units for the measurement inputs come from the input source.
Stacked Transmitters operate such that one transmitter measures at a low range of measurement, and a second transmitter measures at a higher range. These selections are not available if you choose “Default AI.”
When using Stacked Transmitters, the user must enter a set point where the measurement will transition from the low range transmitter to the high range transmitter.
A deadband may be entered, that will prevent the measurement from switching back and forth between the high and low transmitters.
The current flow and energy rates are displayed on this screen. The units of flow and energy rates are set from the Run Configuration page.
change the Plate Change mode from Normal (Inactive) to Plate Change (Active)
While the Plate Change mode is Active, the Differential Pressure, Static Pressure and Temperature values are frozen.
Elapsed Time
Issued: May-2012 Configuring Stations and Runs (Measurement Tab) 3-27
While the Plate Change mode is Active, the elapsed time is displayed.
ControlWave MRMS-IC Configuration Manual (D5140)
New Orifice Diameter
The new orifice diameter and orifice diameter units may be entered here.
Beta Ratio
Min/Max Rates for this Run
The orifice diameter in use does not change until the plate change mode changes from “Plate Change (Active)” to “Normal (Inactive)”.
The Orifice Diameter in use appears in the Settings section
The beta ratio is the orifice diameter divided by the pipe diameter.
The beta ratio is displayed on this screen. If the beta ratio is out of range, it will appear in red text. The low limit for the beta ratio is 0.15 and the high limit for the beta ratio is 0.60.
The minimum and maximum flow rates for an orifice run are calculated outputs of the AGA3I. The DP minimum is always 10 inches and the DP maximum is equal to the DP span
3-28 Configuring Stations and Runs (Measurement Tab) Issued: May-2012
ControlWave MRMS-IC Configuration Manual (D5140)
3.2.11 Turbine Tab (Run Configuration)
Click on the Turbine tab, and the following screen opens.
Figure 3-13. Turbine tab
Field Description
Settings
HSC#
Maximum Input
Low Flow Cutoff
The source for the High Speed Counter (HSC) comes from a High Speed Counter Input via the I/O cards. The user may select from the Default HSC (this would be the “Run X AGA7 Hz” selection from the I/O configuration page), or from a Shared Hz input.
The maximum input is used to calculate the minimum and maximum flow rates through the meter run.
The low flow cutoff is the minimum frequency that will still be considered valid for flow measurement. If the frequency of the inputs from the high speed counter fall below this number, volume will not be measured.
Issued: May-2012 Configuring Stations and Runs (Measurement Tab) 3-29
ControlWave MRMS-IC Configuration Manual (D5140)
Correction Factor (K)
Linearization Enabled / Disabled
C Factor
Current
Counts
Pulse Counter Input Override / Input
Frequency (Hz)
Correction Factor / Pulse/ Second
The correction factor represents either the volume (in Cubic Feet) per pulse, or the number of pulses per volume (in Cubic Feet). The K factor value is entered as shown in the box below, while the K factor units are selected by using the pushbutton. This information is available from the turbine meter data plate.
Enables/disables use of the linearization table.
The current linearization factor being used.
The “Counts” value represents the total number of events (pulses) in the most recent execution cycle coming from the High Speed Counter Input.
The user may override the measurement values in use by selecting Override instead of Live
When Override is selected, the user may enter the desired value for the frequency to be used.
When Live is selected, the Value will be driven by the appropriate high speed counter input value.
Note: The action of changing from Live to Override or Override to Live is entered in the Audit trail. When in Override, any changes made to the Value are entered in the Audit Trail.
Note: This override is done at the Run Measurement level, not at the I/O level. Because of this, care needs to be taken when overriding runs configured for bidirectional measurement, because the logic overriding the measurement values occurs after the logic for routing the measurement inputs to the proper run.
The frequency value in use is shown here. When “Live” is selected via the “Override/Live”
button, this value is the value coming from the HSC input.
When “Override” is selected via the “Override/Live” button, this value may be entered by the user. The entered value will be used in the measurement calculation.
This is the correction factor calculated by the AGA 7 equation.
This correction factor multiplied by the frequency will
3-30 Configuring Stations and Runs (Measurement Tab) Issued: May-2012
ControlWave MRMS-IC Configuration Manual (D5140)
provide the corrected flow rate.
(K) Used
Corrected Flow Rate, Energy Rate, Uncorrected Flow Rate
Min / Max Rates for this Run
The AGA 7 calculation requires the K factor to be input in units of Cubic Feet/Pulse. The (K) Used value always represents the K factor in the units of Cubic Feet/Pulse.
The current corrected flow, energy rate, and uncorrected flow rate are displayed on this screen. The units of flow and energy rates are set from the Run Configuration page.
The minimum and maximum flow rates for a turbine meter run are calculated as follows:
Minimum Flow Rate = max frequency * AGA7 Factor * (Min /100)
Maximum Flow Rate = max frequency * AGA7 Factor * (Max/100)
Where: Min defaults to 5 Max defaults to 90
Issued: May-2012 Configuring Stations and Runs (Measurement Tab) 3-31
ControlWave MRMS-IC Configuration Manual (D5140)
3.2.12 Auto-Adjust Tab (Run Configuration)
Click on the Auto-Adjust tab, and the following screen opens.
Figure 3-14. Auto-Adjust tab
Field Description
Settings
Low Flow Cutoff
Main Rotor Factor (Km)
Sense Rotor Factor (Ks)
Linearization Enabled / Disabled
Max Meter Flow
Expected Deviation (Abar)
The low flow cutoff is the minimum flow, in units of Actual Cubic Feet per second that will still be considered valid for flow measurement. If the flow rate falls below this number, volume will not be measured.
The main rotor is the upstream rotor and has a greater blade angle to the flow of gas.
The sense rotor is the downstream rotor and has a shallower blade angle to the flow of gas.
Enable / disable use of the linearization table.
The maximum meter flow is the maximum flow rate through the meter, in units of thousands of actual cubic feet per hour. This number is used to calculate the Minimum and maximum flow rate through the meter.
Average relative adjustment between main and sense rotors.
3-32 Configuring Stations and Runs (Measurement Tab) Issued: May-2012
ControlWave MRMS-IC Configuration Manual (D5140)
Deviation Error Limit
C Factor Current
Main Rotor Count Input
Sense Rotor Count Input
ACF/s (DeltaVa)
Deviation (Delta Abar)
Corrected Flow Rate, Energy Rate, Uncorrected Flow Rate
Min / Max Rates for this Run
This sets a limit on the difference between the expected Abar and the calculated Abar.
Current linearization factor.
Pulse count from main rotor.
Pulse count from sense rotor.
The ACF/s (DeltaVa) reading is displayed here.
The Deviation (Delta ABar) reading is displayed here.
The current corrected flow, energy rate, and uncorrected flow rate are displayed on this screen. The units of flow and energy rates are set from the Run Configuration page.
The minimum and maximum flow rates for an auto-adjust meter run are calculated as follows:
Minimum Flow Rate = max frequency * AGA7 Factor * (Min /100)
Maximum Flow Rate = max frequency * AGA7 Factor * (Max/100)
Where: Min defaults to 5 Max defaults to 90
Issued: May-2012 Configuring Stations and Runs (Measurement Tab) 3-33
ControlWave MRMS-IC Configuration Manual (D5140)
3.2.13 Ultrasonic Tab (Run Configuration)
Click on the Ultrasonic tab, and the following screen opens.
Figure 3-15. Ultrasonic tab
Field Description
Settings
HSC#
Maximum Input
Low Flow Cutoff
Correction Factor (K)
Current
The source for the Counter input comes from a High Speed Counter Input via the I/O cards. The user may select from the Default HSC (this would be the “Run X AGA7 Hz” selection from the I/O configuration page), or from a Shared Hz input.
The maximum input is used to calculate the minimum and maximum flow rates through the meter run.
The low flow cutoff is the minimum frequency that will still be considered valid for flow measurement. If the frequency of the inputs from the high speed counter fall below this number, volume will not be measured.
The correction factor represents either the volume (in Cubic Feet) per pulse, or the number of pulses per volume (in Cubic Feet). The K factor value is entered as shown in the box below, while the K factor units are selected by using the push button. This information is available from the UFM meter data plate.
Counts
3-34 Configuring Stations and Runs (Measurement Tab) Issued: May-2012
The “Counts” value represents the event (pulse) total during the most recent execution cycle coming from the High Speed Counter Input.
ControlWave MRMS-IC Configuration Manual (D5140)
Pulse Counter Input Override / Live
Frequency (Hz)
Correction Factor / Pulse/ Second
(K) Used
Corrected Flow Rate, Energy Rate, Uncorrected Flow Rate
Min / Max Rates for this Run
Ultrasonic Meter Data
US Meter Number
Speed of Sound
The user may override the measurement values in use by selecting Override instead of Live
When Live is selected, the Value will be driven by the appropriate high speed counter input value.
Note: the action of changing from Live to Override or Override to Live is entered in the Audit trail. When in Override, any changes made to the Value are entered in the Audit Trail.
Note: This override is done at the Run Measurement level, not at the I/O level. Because of this, care needs to be taken when overriding runs configured for bidirectional measurement, because the logic overriding the measurement values occurs after the logic for routing the measurement inputs to the proper run.
When Override is selected, the user may enter the desired value for the frequency to be used.
This is the correction factor calculated by the AGA 7 equation. This correction factor multiplied by the frequency will provide the
corrected flow rate. The AGA 7 calculation requires the K factor to be input in units of
Cubic Feet/Pulse. The (K) Used value always represents the K factor in the units of Cubic Feet/Pulse.
The current corrected flow, energy rate, and uncorrected flow rate are displayed on this screen. The units of flow and energy rates are set from the Run Configuration page.
The minimum and maximum flow rates for an ultrasonic meter run are calculated as follows:
Minimum Flow Rate = max frequency * AGA7 Factor * (Min /100) Maximum Flow Rate = max frequency * AGA7 Factor * (Max/100) Where: Min defaults to 5
Max defaults to 90
If a MODBUS interface to the ultrasonic meter has been configured from the I/O Configuration section, the data collected from the ultrasonic meter is displayed here.
To select the ultrasonic meter that data is being collected from, right click on the US Meter Number box, and enter the appropriate meter number.
The Speed of Sound (SOS) readings from each path of the ultrasonic meter are displayed, and the average is calculated. At the same time, the Multi-Run Multi-Station controller calculates the Speed of Sound per the AGA 10 equations. The calculated value is
Issued: May-2012 Configuring Stations and Runs (Measurement Tab) 3-35
ControlWave MRMS-IC Configuration Manual (D5140)
compared to the average value from the ultrasonic meter, and if the deviation is greater than the deviation limit, an alarm will be generated. This alarm will be entered into the Audit Trail, and will be available via both the BSAP Slave communications and MODBUS communications interfaces.
Status
Diagnostics information relating to communications with the ultrasonic meter, the gain on each path, and the overall status of the ultrasonic meter is collected and displayed here.
3-36 Configuring Stations and Runs (Measurement Tab) Issued: May-2012
ControlWave MRMS-IC Configuration Manual (D5140)
A
3.2.14 PD Tab (Run Configuration)
Click on the PD tab, and the following screen opens.
Figure 3-16. PD tab
Field Description
Settings
Maximum Input
Low Flow Cutoff
Correction Factor (K)
The maximum input is used to calculate the minimum and maximum flow rates through the meter run.
A positive displacement meter typically has very low frequency counts. be several seconds between pulses. It is not unusual to see 30 seconds or more between pulses from a PD meter, during normal flowing conditions.
Therefore, the low flow cutoff for a PD meter is the maximum amount of time allowed between two consecutive pulses before the flow rate is zeroed. However, all pulses received by the MRMS-IC controller from a PD meter are included in volume totalization for the meter run.
The correction factor represents either the volume (in Cubic Feet) per pulse, or the number of pulses per volume (in Cubic Feet). The K factor value is entered as shown in the box below, while the K factor units are selected by using the push button. This information is available from the PD meter data plate.
valid frequency may be well below 1 Hz, that is, it can
Issued: May-2012 Configuring Stations and Runs (Measurement Tab) 3-37
ControlWave MRMS-IC Configuration Manual (D5140)
Current
Counts
Frequency (Hz)
Correction Factor / Pulse/ Second
(K) Used
Corrected Flow Rate, Energy Rate, Uncorrected Flow Rate
Min / Max Rates for this Run
This shows the number of pulses received at the high speed counter input.
This is the derived frequency. Because a positive displacement meter can have very low frequency pulses (< 1 Hz), this number can be a fraction less than 1.0.
This is the correction factor calculated by the AGA 7 equation. This correction factor multiplied by the frequency will provide
the corrected flow rate.
The AGA 7 calculation requires the K factor to be input in units of Cubic Feet/Pulse. The (K) Used value always represents the K factor in the units of Cubic Feet/Pulse.
The current corrected flow, energy rate, and uncorrected flow rate are displayed on this screen. The units of flow and energy rates are set from the Run Configuration page.
The minimum and maximum flow rates for a PD meter run are calculated as shown below:
Minimum Flow Rate = max freq * (Min /100) * AGA7 Factor Maximum Flow Rate = max freq* (Max /100) * AGA7 Factor
Where: Min defaults to 5 Max defaults to 90
3-38 Configuring Stations and Runs (Measurement Tab) Issued: May-2012
3.3 View Local Archives
Note: To collect the Archives for storage on the PC hard drive, it is
The MRMS-IC controller maintains Hourly Archives (Logs) for each meter run and each gas chromatograph stream. To view the Archive, select the Measurement tab, and click on the
The following screen opens:
ControlWave MRMS-IC Configuration Manual (D5140)
recommended that the Collect Local Logs function be used.
button.
Figure 3-17. Selecting a Log to View
3.3.1 Selecting Logs to View
To view the desired archive:
1. Click on the description for the desired archive in the Select an
Archive from the List Below box. This updates the File Number in the Archive Collection Parameters field.
2. Now click the [Collect Data] button. (See Figure 3-17.)
Figure 3-18. Archive
Issued: May-2012 Configuring Stations and Runs (Measurement Tab) 3-39
ControlWave MRMS-IC Configuration Manual (D5140)
3.4 Collect Local Logs
One or more Archives can be selected for collection. From the MRMS-IC Measurement tab, click the
button to begin.
3.4.1 Selecting Archives for Collection
To select an Archive or for collection click on the desired description in the log collection control.
Figure 3-19. Selecting Logs for Collection
3.4.2 Collecting a Single Archive
To collect one of the Archives, listed for collection, highlight the desired item in the list, then click on the [Start Collection] button.
3.4.3 Collecting Multiple Archives
To collect more than one Archive hold down the [Ctrl] key to highlight multiple items, and then click on the “Start Collection” button.
3.4.4 Log Collection Parameters
There are several different log collection parameters and read-only fields which govern or report how the log collections operate.
3-40 Configuring Stations and Runs (Measurement Tab) Issued: May-2012
ControlWave MRMS-IC Configuration Manual (D5140)
Field Site Name
Storage Folder
Type
Description
Log #
Description
The Site Name is defined by the user on the Site Configuration screen, via the Status/Configuration menu item. The Site Name is used as the base name for the files created by the collection and conversion processes.
By default, the storage folder for the Archive collections is C:\Mrms_ic\Logs.
This may be changed by clicking on the Browse button, and locating a different folder. However, this change is not permanent, and the next time the “Collect Local Logs” screen is opened, the Storage Folder will revert to C:\Mrms_ic\Logs.
The type of log, either Audit or Archive.
A description of the log.
The log number is populated automatically, when the Archive or Audit is selected from the “Hourly Logs” table
Target File
The Target File name will be automatically created. The file base name will be the Site Name (in this
case “Unamed Site”) and the extension will be one of the following:
Rnn Where R indicates an Archive for a
measurement run, and nn indicates the run number.
Gnn Where G indicates an Archive for a gas
chromatograph stream, and nn indicates the
stream number AUD Represents the Audit Trail collection. If a file of the same name exists in the Storage
Folder, any new Archive data collected since the last Archive data was collected will be appended to the file. The Archive Data will not include duplicate data.
However, whenever the Audit Trail is collected, the entire audit trail is collected. If there is an existing Audit Trail file on the PC hard drive, the data from this collection is appended to the existing file. There may be duplicate data in the .AUD file.
Issued: May-2012 Configuring Stations and Runs (Measurement Tab) 3-41
ControlWave MRMS-IC Configuration Manual (D5140)
A
Start Collection
Stop Collection
View Storage
Convert to CSV
Click here to start the log collection.
While an Archive or the Audit Trail is being collected, the user may stop the collection by clicking on the Stop Collection button.
It is possible to view the stored data locally. Select the item that includes local data, and then
click on “View Storage” button. Note: Only one item may be selected for the View Storage feature to be available. A screen similar to this one will appear:
It is possible to convert the stored data to a comma separated variable (CSV) file.
Collection Status
Messages
Select the item that includes local data, and then click on “Convert to CSV” button. Note: Only one item may be selected for the Convert to CSV feature to be available.
A message will appear in the message window indicating that the conversion is complete.
file with an extension of CSV will now be located in the same folder as the stored data. The file name will be of the format
sitename_originalextension.CSV Where:
sitename is the Site Name. originalextension is the original extension (Rnn, Gnn,
or AUD)
While collections are in progress, status messages will be posted in the message window. When the collection is complete, the message “Log Collection Complete will appear.
3-42 Configuring Stations and Runs (Measurement Tab) Issued: May-2012
3.5 View Audit Log
ControlWave MRMS-IC Configuration Manual (D5140)
Note: To collect the Audit Trail for storage on the PC hard drive, it is
recommended that the Collect Local Logs function be used.
The MRMS-IC controller maintains an Audit Trail. The audit trail includes entries any time a configuration change is made that could affect measurement.
To view the Audit Trail:
1. Select the “Measurement” tab, and click the
button.
2. The following screen will appear. Click on the [Collect Data] button.
3. This will collect the first set of records (typically 24 records). To view
additional records, scroll down using the vertical scroll bars
Figure 3-20. Audit Log
The buttons associated with audit collection are.
Field Description Collect Data
Data Storage
Search Criteria
To view the current entries in the Audit Trail, click on the Collect Data button.
To store the collected data, click on the Data Storage button.
Note: It is recommended that the “Collect Local Logs” function be used to collect and store Audit Trail data to the PC hard drive, rather than this function, since more features are available for collecting, storing, and viewing the data.
Click this button to specify search criteria.
Issued: May-2012 Configuring Stations and Runs (Measurement Tab) 3-43
ControlWave MRMS-IC Configuration Manual (D5140)
3.5.1 Data Storage Parameters dialog box
Figure 3-21. Data Storage Parameters dialog box
Field Description Store Data on
Collection
Storage Parameters
When this box is checked, the data will be stored automatically on collection. This means as additional data is collected by scrolling down using the vertical scroll bar, this data is automatically written to the PC hard drive.
File
Create File
Append File
Data Delimiter
Convert Data to Extended Format
Define the storage location and file name for the collected data.
If Create File is selected, a new file will be created every time data is collected. If the name of the file is one previously created, all previous data will be lost.
If Append File is selected, newly collected data will be added to previously collected data, in the file of the same name.
The following data delimiters may be selected – Space, Comma, or Semicolon. This will be the delimiter used to separate the data fields (Date/Time, Signal, Description, Audit Seq#, Global Seq#).
Not applicable
3-44 Configuring Stations and Runs (Measurement Tab) Issued: May-2012
ControlWave MRMS-IC Configuration Manual (D5140)
3.5.2 Search Data Collection Criteria dialog box
The following search criteria may be applied:
Figure 3-22. Select Data Collection Criteria dialog box
Field
Records
Search Method
Direction
Description
The user may elect to collect to view Alarms and Events, Events Only, or Alarms Only
The user may elect to Collect All Available
Records, or may specify the time period. Start Date Enter the start date here. All records
that occurred on or after that date will be collected.
Period The user may specify a period from which
to collect the data. The available selections are Today, This Week, or This Month.
The data may be collected and viewed from the Oldest entry to the Newest entry or from the Newest entry to the Oldest entry.
Issued: May-2012 Configuring Stations and Runs (Measurement Tab) 3-45
ControlWave MRMS-IC Configuration Manual (D5140)
3.6 Maintenance Mode
It is possible to put the Site, Stations, Runs, or individual analog inputs into maintenance mode.
To enter Maintenance Mode, select the “Measurement” tab, and click on the button. The following screen opens:
3.6.1 Site Tab
Figure 3-23 Maintenance Mode - Site tab
The entire site may be placed in Maintenance Mode. When this occurs, all runs at the site are placed in Maintenance Mode.
The following items are available on the Site Maintenance Mode screen.
Field Description
Site
Maint Off / Maintenance
Auto Rst Off
This section of the screen controls the maintenance mode for the site.
To disable the maintenance mode, toggle the button to Maint Off. To enable the maintenance mode, toggle the button to Maintenance.
If Auto Reset is enabled, maintenance mode for the site will be disabled automatically after the period set under the Maintenance Mode Auto Reset Timer
If Auto Reset is disabled, maintenance mode for the site will never be disabled automatically
Note: if Auto Reset is set at the Station level or Run Level, it
3-46 Configuring Stations and Runs (Measurement Tab) Issued: May-2012
ControlWave MRMS-IC Configuration Manual (D5140)
takes precedence over the setting at the site level. To disable Auto Reset, make certain that it is disabled at the site, station, and run level.
Maintenance Mode Time
Elapsed Time
The Maintenance Mode Auto Reset Timer is in the format DD HH:MM:SS.S
Where:
DD number of days HH number of hours MM number of minutes SS.S number of seconds (resolution of 10ths)
The maximum time allowed for the maintenance mode auto reset timer is
24 20:31:23.9 – (24 Days, 20 hours, 31 minutes, 23.9 seconds)
This is the amount of time the site has been in maintenance mode.
Remaining Time
Summary
When Auto Reset is enabled, this is the time remaining until the maintenance mode is automatically reset.
When Auto Reset is disabled, this field remains at 00 00:00:00.0.
In this section of the display, the maintenance mode status will be indicated.
Any runs not assigned to stations are shown in the “Unassigned” column.
Runs assigned to stations are displayed in the appropriate Station n columns.
In this example, the runs are assigned as follows: Run 1 to Station 1
Run 2 to Station 2 Run 3 to Station 1 Run 4 to Station 2 Run 5 to Station 1 Run 6 to Station 2
Issued: May-2012 Configuring Stations and Runs (Measurement Tab) 3-47
ControlWave MRMS-IC Configuration Manual (D5140)
Runs or Stations in Maintenance mode will be indicated with a magenta outline around the black box.
When not in Maintenance mode, the box will be black, with no border
3-48 Configuring Stations and Runs (Measurement Tab) Issued: May-2012
3.6.2 Station Tab
Individual stations may be put into Maintenance Mode. When this occurs, all runs assigned to the station are placed in Maintenance Mode.
The following items are available on the Station Maintenance Mode screen.
ControlWave MRMS-IC Configuration Manual (D5140)
Figure 3-24. Maintenance Mode - Station tab
Field Description
Station n
Maint Off / Maintenance
Auto Rst Off
This section of the screen controls the maintenance mode for the selected station.
To disable the maintenance mode, toggle the button to Maint Off. To enable the maintenance mode, toggle the button to Maintenance.
I If Auto Reset is enabled, maintenance mode for the station will be disabled automatically after the period set under the Maintenance Mode Auto Reset Timer
If Auto Reset is disabled, maintenance mode for the station will never be disabled automatically.
Note: If Auto Reset is set at the Station level, it takes precedence over the setting at the site and run level. To disable Auto Reset, make certain that it is disabled at the site, station, and run level.
Issued: May-2012 Configuring Stations and Runs (Measurement Tab) 3-49
ControlWave MRMS-IC Configuration Manual (D5140)
Maintenance Mode Time
Elapsed Time
Remaining Time
Summary
The Maintenance Mode Auto Reset Timer is in the format DD HH:MM:SS.S
Where: DD number of days
HH number of hours MM number of minutes SS.S number of seconds (resolution of 10ths)
The maximum time allowed for the maintenance mode auto reset timer is
24 20:31:23.9 – (24 Days, 20 hours, 31 minutes, 23.9 seconds)
This is the amount of time the station has been in maintenance mode.
When Auto Reset is enabled, this is the time remaining until the maintenance mode is automatically reset.
When Auto Reset is disabled, this field remains at 00 00:00:00.0.
For each station, the runs assigned to that station are displayed.
Runs in Maintenance mode will be indicated with a magenta outline around the black box.
When not in Maintenance mode, the box will be black, with no border
3-50 Configuring Stations and Runs (Measurement Tab) Issued: May-2012
3.6.3 Run Tab
ControlWave MRMS-IC Configuration Manual (D5140)
Individual runs may be put into Maintenance Mode. The following items are available on the Run Maintenance Mode screen.
Figure 3-25. Maintenance Mode - Run tab
Field
Run n
This section of the screen controls the maintenance mode for
Maint Off / Maintenance
Auto Rst Off
Description
the selected run.
To disable the maintenance mode, toggle the button to Maint Off. To enable the maintenance mode, toggle the button to Maintenance.
If Auto Reset is enabled, maintenance mode for the run will be disabled automatically after the period set under the Maintenance Mode Auto Reset Timer
If Auto Reset is disabled, maintenance mode for the site will never be disabled automatically.
NOTE – if Auto Reset is set at the Run level, it takes precedence over the setting at the site or station level. To disable Auto Reset, make certain that it is disabled at the site, station, and run level.
Issued: May-2012 Configuring Stations and Runs (Measurement Tab) 3-51
ControlWave MRMS-IC Configuration Manual (D5140)
Maintenance Mode Time
Elapsed Time
Remaining Time
The Maintenance Mode Auto Reset Timer is in the format DD HH:MM:SS.S
Where: DD number of days
HH number of hours MM number of minutes SS.S number of seconds (resolution of 10ths)
The maximum time allowed for the maintenance mode auto reset timer is
24 20:31:23.9 – (24 Days, 20 hours, 31 minutes, 23.9 seconds)
This is the amount of time the run has been in maintenance mode.
When Auto Reset is enabled, this is the time remaining until the maintenance mode is automatically reset.
When Auto Reset is disabled, this field remains at 00 00:00:00.0.
3-52 Configuring Stations and Runs (Measurement Tab) Issued: May-2012
3.6.4 PVs Tab
ControlWave MRMS-IC Configuration Manual (D5140)
From this screen, you can view individual process variables for each run.
Figure 3-26. Maintenance Mode - PVs tab
The Live values always show the live value coming into the MRMS-IC controller (either through an analog input, or a multi-variable transmitter (MVT).
The In Use values are the values currently in use for measurement.
Issued: May-2012 Configuring Stations and Runs (Measurement Tab) 3-53
ControlWave MRMS-IC Configuration Manual (D5140)
3.6.5 AI Maintenance Tab
It is possible to put any analog input into maintenance mode. The following items are available on the AI Maintenance Mode screen.
Figure 3-27. Maintenance Mode – AI Maintenance tab
Field
AI Maintenance
Maint Off / Maintenance
Auto Rst Off
Maintenance Mode Time
Description
This section of the screen controls the maintenance mode for
the selected AI input.
To disable the maintenance mode, toggle the button to Maint Off. To enable the maintenance mode, toggle the button to Maintenance.
If Auto Reset is enabled, maintenance mode for the AI input will be disabled automatically after the period set under the Maintenance Mode Auto Reset Timer If Auto Reset is disabled, maintenance mode for the AI input will never be disabled automatically.
The Maintenance Mode Auto Reset Timer is in the format DD HH:MM:SS.S
3-54 Configuring Stations and Runs (Measurement Tab) Issued: May-2012
Loading...