1.4.1 MRMS_IC IP Startup ............................................................ 1-6
1.4.2 MRMS_IC Serial Startup ...................................................... 1-7
1.4.3 Logging Onto the ControlWave Micro .................................. 1-7
1.5 Accessing Pages of the MRMS_IC Application ............................... 1-8
1.6 Entering Data in Fields of the MRMS_IC Application ...................... 1-9
1.1 What is MRMS-IC?
1.2 Before You Begin
Multi-Run Multi-Station (MRMS) software with Industry Canada (IC) /
Measurement Canada approvals is a software application that allows the
ControlWave Micro controller to manage up to six (6) natural gas
measurement stations.
The MRMS-IC application consists of:
A ControlWave project file (*.PRO) pre-programmed for multi-run
multi-station natural gas measurement.
A customized flash configuration profile (*.FCP) file that configures
the ports, audit, and archive parameters of the ControlWave Micro
for the MRMS_IC.
A TechView session. This includes the TechView session file
(*.TVS), associated *.INI files, and a set of HTM menus customized
for the MRMS-IC application. You use these menus to configure the
application.
You must install the ControlWave Micro controller on site and
connect field devices to its I/O modules. For information on
ControlWave Micro hardware, see document CI-ControlWave Micro.
You must install OpenBSI 5.7 software including TechView on your
PC workstation. You must also install the latest service pack and
patches (Service Pack 2, Patch D). See the OpenBSI Utilities
Manual (D5081), the BSI_Config User’s Manual (D5128), and the
TechView User Manual (D5131) for details on installation
requirements.
Issued: May-2012 Getting Started 1-1
ControlWave MRMS-IC Configuration Manual (D5140)
You must connect the PC workstation to the ControlWave Micro
controller. You can communicate using a serial cable or an Ethernet
cable. Cable diagrams are included in CI-ControlWave Micro.
The ControlWave Micro must be running a flash configuration
profile file (*.FCP) compatible with MRMS-IC software. For
information on updating FCP files, see Chapter 5 of the OpenBSI Utilities Manual (D5081).
The ControlWave Micro must be running the ControlWave project
(*.PRO) file configured for the MRMS-IC. See Chapter 7 of the OpenBSI Utilities Manual (D5081) for information on downloading
a ControlWave project (*.PRO) file.
Note: If you ordered your ControlWave Micro with MRMS-IC
software pre-installed, the FCP and PRO files are already loaded
when the unit ships from the factory.
1.3 Installing MRMS-IC Software
Note: MRMS_IC runs on the following Windows operating systems:
Windows XP
1. Double-click on the MRMS-IC application icon.
2. Click Next on the welcome screen of the installer.
Click “Next”
Figure 1-1. MRMS_IC Installer – Welcome Screen
1-2 Getting Started Issued: May-2012
ControlWave MRMS-IC Configuration Manual (D5140)
3. The next screen includes a “Read Me” file which describes the
changes since the last release of MRMS IC. Click Next after you
review the changes.
Click I Agree
Figure 1-2. Read Me Page
4. Review the license agreement and click the I Agree button to
proceed with the installation or Cancel to abort the installation
process.
Figure 1-3. License Agreement page
Issued: May-2012 Getting Started 1-3
ControlWave MRMS-IC Configuration Manual (D5140)
Figure 1-4. Installation in Progress
5. The installation begins. If you see the following message box,
click OK to confirm that you have the proper OpenBSI version
installed.
Click OK
Figure 1-5. Confirm OpenBSI Version
6. At the completion of the installation, click Next.
1-4 Getting Started Issued: May-2012
Click Next
ControlWave MRMS-IC Configuration Manual (D5140)
Figure 1-6. Installation Completion
7. Now click Finish to exit the installer.
Click Finish
Figure 1-7. Exit the Installer
Issued: May-2012 Getting Started 1-5
ControlWave MRMS-IC Configuration Manual (D5140)
1.4 Starting MRMS-IC Software
You start the MRMS_IC software by invoking the proper TechView
file. There are two ways to do this:
Starting MRMS_IC from
the Start Programs
Menu
Starting MRMS_IC from
an icon
1.4.1 MRMS_IC IP Startup
For an IP connection, click: Start > Programs > MRMS_IC >
MRMS_IC_IP_tvs
For a serial connection, click: Start > Programs > MRMS_IC >
MRMS_IC_Serial_tvs
From a desktop icon, similar to those below, or from the
\MRMS_IC\SUPPORT folder, double-click the IP or serial TVS file,
depending upon your type of connection.
Figure 1-8. MRMS_IC TVS file icons
For IP communication, see Section 1.4.1MRMS_IC IP Startup.
For serial communication see Section1.4.2 MRMS_IC Serial Startup.
Note: Although you can view data through an IP connection, the
MRMS-IC application only allows configuration changes when
you establish a physical serial connection to serial
communication port 1 on the ControlWave Micro.
Once you start the TVS file for IP operation, TechView opens the
Runtime Configuration Parameters dialog box:
Figure 1-9. IP Runtime Parameters
1. Ignore the number of runs; this parameter does not apply for
1-6 Getting Started Issued: May-2012
MRMS-IC.
2. Enter the IP address of the ControlWave Micro IP port to
which you are connected.
3. Click OK.
4. Log onto the ControlWave Micro as described in Section 1.4.3.
1.4.2 MRMS_IC Serial Startup
Once you start the TVS file for serial operation, TechView opens the
Runtime Configuration Parameters dialog box:
ControlWave MRMS-IC Configuration Manual (D5140)
Figure 1-10. Serial Runtime Parameters
1. Ignore the number of runs; this parameter does not apply to
MRMS-IC.
2. Enter the BSAP local address of the ControlWave Micro to
which you are connected.
3. Select the serial communication port on the PC which you are
using to communicate with the ControlWave Micro.
4. Select the baud rate on the serial communication line.
5. Click OK.
6. Log onto the ControlWave Micro as described in Section 1.4.3.
1.4.3 Logging Onto the ControlWave Micro
In the SignOn to RTU dialog box, enter a Username / Password
combination that allows full access to the ControlWave Micro, then
click the SignOn button.
Issued: May-2012 Getting Started 1-7
ControlWave MRMS-IC Configuration Manual (D5140)
y
Figure 1-11. Logging onto the ControlWave Micro
1.5 Accessing Pages of the MRMS_IC Application
To access various pages of the MRMS_IC application, click on the tab
for the function you want to configure, then click on the buttons which
appear on that tab. By default, the I/O tab appears first.
Click on the tab you want to access, then
click on an
of the buttons for that tab
Tabs
Buttons
Figure 1-12. Tabs and Buttons in MRMS_IC
The next several chapters describe the functions available on each tab of
the application.
1-8 Getting Started Issued: May-2012
ControlWave MRMS-IC Configuration Manual (D5140)
You need not configure all the features of the application; only those
that you need for your particular purpose and measurement needs.
1.6 Entering Data in Fields of the MRMS_IC Application
Whenever you select a field and enter data, or select from a drop-down
menu, you must press the [Enter] key to confirm and save your choice.
To exit a field without entering data, press the [Esc] key.
Issued: May-2012 Getting Started 1-9
This page is intentionally left blank
ControlWave MRMS-IC Configuration Manual (D5140)
Chapter 2 – Configuring Inputs and Outputs (I/O Tab)
This chapter discusses configuring the MRMS-IC application to accept
field inputs and outputs (I/O). This is accomplished from the MRMSIC’s I/O tab.
Note: Although you can view data through an IP connection, the
MRMS-IC application only allows configuration changes when
you establish a physical serial connection to serial
communication port 1 on the ControlWave Micro.
2.8 Time Set/Daylight Saving Time ..................................................... 2-29
2.1 I/O Tab
Click the I/O tab to display the various I/O options you can configure.
We’ll discuss each of these in the sections that follow.
To configure an
I/O function or
feature, click on
its button.
Figure 2-1. I/O Tab in MRMS-IC
Issued: May-2012 Configuring Inputs and Outputs (I/O Tab) 2-1
ControlWave MRMS-IC Configuration Manual (D5140)
2.2 I/O Usage
When you click the button on
the I/O tab, the I/O Usage page displays a graphical representation of
the ControlWave Micro, showing each of the I/O modules detected by
the MRMS-IC. If MRMS-IC cannot detect a particular module or an I/O
slot is empty, its graphic shows “Not Present.” MRMS-IC only uses
Mixed I/O modules.
Click on the graphical
representation of a module
to configure its I/O.
When you move the cursor over the CPU module, an Expansion
Communication (ECOM) module, or any I/O module, you’ll see a
yellow box on the screen. To configure I/O, follow these steps:
1. From the I/O tab, click the I/O Usage button.
2. Position the cursor over the I/O module you want to configure; a
yellow box indicates the cursor position on any configurable
module.
3. Click on the module you want to configure. This opens a screen
showing the possible choices for I/O. The Mixed I/O Module
shows multiple types of I/O (see Figure 2-3).
2-2 Configuring Inputs and Outputs (I/O Tab) Issued: May-2012
ControlWave MRMS-IC Configuration Manual (D5140)
Figure 2-3. Mixed I/O Module
4. The I/O assignments in the MRMS-IC application are fixed
based on the I/O slot. Because you can have an expanded
communication module (ECOM) in either I/O slot 1 or 2, I/O
designations begin with the right-most slot and go in reverse order. In other words, the mixed I/O module in I/O slot 6 holds
user DI1, whereas the mixed I/O module in I/O slot 1 holds user
DI6.
5. Configuration is limited based on the I/O type. Refer to the sub-
sections that follow.
Note: You may have noticed that when the cursor is left hovered over
an IO point, the graphics to the left display the applicable
connection points for direct and remote IO.
Issued: May-2012 Configuring Inputs and Outputs (I/O Tab) 2-3
ControlWave MRMS-IC Configuration Manual (D5140)
Graphic displays
location of
physical I/O
connections for
an I/O point,
when you hover
the cursor over
the PNT.
Figure 2-4. Connection Points for Physical I/O
Notes:
The MRMS-IC application only uses Mixed I/O modules.
Depending upon your particular configuration, you might not use all
the inputs or outputs in a particular meter run or station.
If you have I/O that comes from an ultrasonic flow meter or a multi-
variable transmitter that communicates with the MRMS-IC through
a communication port, instead of an I/O module, you configure it
from the UFM or Transducer pages, discussed later in this chapter.
To return to the I/O Usage page from any page underneath it, click
the Go Back link.
2-4 Configuring Inputs and Outputs (I/O Tab) Issued: May-2012
2.2.1 Discrete Inputs (DI)
Discrete inputs (DIs) include the following fields:
Field Description
PNT
INV If you click this box for a given I/O point so that “Y” is
Live
ControlWave MRMS-IC Configuration Manual (D5140)
This read-only field displays the I/O point number.
displayed, MRMS-IC inverts the real-live field value and
uses the inverted value as the process value. For
example, if the Live value of discrete I/O point 5 is OFF,
and INV is selected for that point, PV is set ON and that’s
what MRMS-IC uses for control and processing.
This read-only field shows the actual ON/OFF status of
this discrete input point.
PV
Assignment
2.2.2 Discrete Outputs (DO)
Discrete outputs (DOs) include the following fields:
Field Description
PNT
Points that are ON show in red.
Points that are OFF show in green.
This read-only field shows the value of the process
variable (PV) used in MRMS-IC. This matches the Live
value unless you invert the input using INV.
Points that are ON show in red.
Points that are OFF show in green.
This read-only field shows details of the fixed I/O
assigned to this point.
This read-only field displays the I/O point number.
PV
Assignment
This read-only field shows the value of the process
variable (PV) MRMS-IC will output to the field device.
This read-only field shows details of the fixed I/O
assigned to this point.
Issued: May-2012 Configuring Inputs and Outputs (I/O Tab) 2-5
ControlWave MRMS-IC Configuration Manual (D5140)
A
2.2.3 Analog Inputs (AI)
Analog inputs (AIs) include the following fields:
Field Description
PNT
This read-only field displays the I/O point number.
PV
Zero
Span Enter the value that, when added to the Zero value,
Units
Assignment
Use Stacked DP
Transmitter / Use
Single DP Transmitter
Only button
This read-only field shows the calculated value of the
analog input process variable (PV) based on the
configured Zero and Span.
If the value shows in red, the value is
questionable
connection, a communication problem with the field
device, data timeout or some other problem that could
cause the value to be invalid.
Enter the value that the process variable should read
when the AI field input is 4mA. Press [Enter] to save
your selection.
represents what the process variable should display
when the AI field input is 20m
your selection.
For example, if Zero is 5 and Span is 20, then:
If the AI field input is:
4mA 5
20mA 25
12mA 15
The engineering units for this process variable. Click in
the field and select the proper units from the drop-down
menu. Press [Enter] to save your selection.
This read-only field shows details of the fixed I/O
assigned to this point.
This button toggles I/O assignments based on whether
you use a single DP transmitter, or stacked DP
transmitters.
To use stacked, click the Use Stacked DP Transmitter
and assignments change to stacked; the label on the
button then changes to Use Single DP Transmitter Only.
To use a single DP transmitter, click the Use Single DP Transmitter and assignments change to single; the label
on the button then changes to Use Stacked DP Transmitter.
. This could indicate no
. Press [Enter] to save
PV will be:
2-6 Configuring Inputs and Outputs (I/O Tab) Issued: May-2012
2.2.4 Analog Outputs (AO)
Analog outputs (AOs) include the following fields:
Field Description
PNT
ControlWave MRMS-IC Configuration Manual (D5140)
This read-only field displays the I/O point number.
PV
Zero
Span Enter the value that, when added to the Zero value,
Units
Assignment
This read-only field shows the calculated value of the
analog output process variable (PV) based on the
configured Zero and Span. This value will be sent to the
field device.
Enter the value that the process variable should read
when the AO field output is 4mA. Press [Enter] to save
your selection.
represents what the process variable should display
when the AO field output is 20mA. Press [Enter] to save
your selection.
For example, if Zero is 5 and Span is 20, then:
If PV is:
5 4mA
25 20mA
10 8mA
The engineering units for this process variable. Click in
the field and select the proper units from the drop-down
menu. Press [Enter] to save your selection.
This read-only field shows details of the fixed I/O
assigned to this point.
The AO field output is:
Issued: May-2012 Configuring Inputs and Outputs (I/O Tab) 2-7
ControlWave MRMS-IC Configuration Manual (D5140)
2.2.5 High Speed Counters (HSC)
High speed counters (HSC) include the following fields:
Field Description
PNT
This read-only field displays the I/O point number. The
number varies depending upon the type of I/O module.
Counts
Time Stamp
Assignment
Use AutoAdjust / Use
Single HSC Input button
This read-only field displays the number of counts since
the last power cycle.
This read-only field displays the timestamp of the last
sample from the HSC module. The timestamp is the
number of milliseconds since boot.
This read-only field shows details of the fixed I/O
assigned to this point.
This button toggles I/O assignments based on whether
you use a single HSC input, or you use Auto Adjust
which requires two HSC inputs.
To use auto adjust, click the Use AutoAdjust and
assignments change to show two HSC inputs; the label
on the button then changes to Use Single HSC Input.
To use a single HSC input, click the Use Single HSC Input and assignments change to a single HSC; the
label on the button then changes to Use AutoAdjust.
2-8 Configuring Inputs and Outputs (I/O Tab) Issued: May-2012
ControlWave MRMS-IC Configuration Manual (D5140)
2.2.6 Ultrasonic Flow Meters (UFM)
If you have one or more ultrasonic flow meters, click the UFMs link on
the top of the I/O Usage page to call up the UFM page.
Figure 2-5. Ultrasonic Flow Meter (UFM) Configuration
Configure the following fields for your ultrasonic flow meter.
Field Description
Enabled/Disabled
Port
Address Enter the address of the UFM here. Press [Enter] to
Type
Issued: May-2012 Configuring Inputs and Outputs (I/O Tab) 2-9
Click this button to enable communication from this UFM
to the MRMS-IC.
Use the dropdown menu to specify the ControlWave
Micro serial communication port which connects to this
UFM. Press [Enter] to save the selection.
save the selection.
Use the drop-down menu to select the type of UFM.
Press [Enter] to save your selection.
ControlWave MRMS-IC Configuration Manual (D5140)
2.2.7 Multi-variable Transmitters (Transducers)
If you have one or more multi-variable transmitters, click the
Transducers link on the top of the I/O Usage page to call up the
Transducers page.
The Transducers page shows the first three multi-variable transmitters
(MVTs). If you want to view a different group of three MVTs, click the
button corresponding to the range of MVTs (1-3 or 4-6) on the top of
the screen.
2-10 Configuring Inputs and Outputs (I/O Tab) Issued: May-2012
Click this button to enable communication from this
MVT to the MRMS-IC.
Click the BSAP/MODBUS button to toggle the method
used to communicate with this MVT between BSAP
protocol and MODBUS protocol.
Use the dropdown menu to specify the ControlWave
Micro serial communication port which connects to this
MVT. Press [Enter] to save the selection.
ControlWave MRMS-IC Configuration Manual (D5140)
Address Enter the address of the MVT here. Press [Enter] to
save the selection.
Xmtr Type
Register Set
Comm Stats
% Good
Good Polls
Bad Polls
Reset
Current Status
Tag Name
Serial Number
Time Stamp
DP
SP
Use the drop-down menu to select the type of data
coming from this MVT. Choose either:
: Data from this type:
Type
GP/T gage pressure and temperature
DP/P/T differential pressure, static pressure, and
temperature
T temperature
Press [Enter] to save your selection.
This field applies only to MODBUS communication.
Click either 7xxx or 4xxxx to select the MODBUS
register set used by this MVT.
This read-only field shows the percentage of
successful communication transactions with this MVT.
This read-only field shows the number of good poll
messages in communications with this MVT.
This read-only field shows the number of bad poll
messages in communications with this MVT.
This button resets the communication statistics in the
%Good, Good Polls, and Bad Polls fields.
These read-only fields display the most recent status
messages from this MVT.
This read-only field shows the tag name from this
MVT. (BSAP only)
This read-only field shows the serial number from this
MVT. (MODBUS only)
This read-only field shows the time stamp of the most
recent value received from this MVT.
This read-only field shows the most recent differential
pressure reading from this MVT.
This read-only field shows the most recent static
Issued: May-2012 Configuring Inputs and Outputs (I/O Tab) 2-11
ControlWave MRMS-IC Configuration Manual (D5140)
A
FT
Units
Zero
Span
2.3 Local DLM
Notes:
The local Data Line Monitor (DLM) provides details about low-
level communication messages sent through a selected serial port
used by the MRMS-IC.
pressure reading from this MVT.
This read-only field shows the most recent
temperature reading from this MVT.
This read-only field shows the engineering units for this
variable.
This read-only field shows the value for this variable
when the MVT receives a 4mA field input.
This read-only field shows the value that, when added
to the Zero value, represents what the process
variable should display when the field input to the MVT
is 20mA.
Typically, you would only use the local DLM if you are a very
advanced user and need to perform communication troubleshooting
for a particular port.
The local DLM only displays the first 80 characters of a message.
The local DLM only captures messages approximately every half
second, therefore, it can miss some messages.
Click the button on the I/O tab to
activate the Data Line Monitor function. The DLM includes the
following fields:
Field Description
Monitor Port
TX Data
Use the dropdown menu to select the ControlWave
Micro serial communication port you want the DLM to
monitor. Press [Enter] to save the selection.
Note:
the monitor port, you can copy data from the window to
the clipboard. You can then paste this data into
another file for off-line review.
This read-only field shows the most recent message
transmitted through this port.
fter you collect the data, if you select “None” for
RX Data
window The window shows successive messages detected by
2-12 Configuring Inputs and Outputs (I/O Tab) Issued: May-2012
This read-only field shows the most recent message
received through this port.
the DLM. Most recent messages appear at the top;
you can use the scroll bar to adjust the window to
show earlier messages.
ControlWave MRMS-IC Configuration Manual (D5140)
Figure 2-7. Local DLM
Issued: May-2012 Configuring Inputs and Outputs (I/O Tab) 2-13
ControlWave MRMS-IC Configuration Manual (D5140)
2.4 Customer Modbus Slave
MRMS-IC supports a single Modbus slave session you can configure to
provide a Modbus slave interface to the controller.
Click the button on the I/O tab to bring up
the Customer Modbus Slave page.
You can
view either
coils or
registers in
the Signal
List grid.
Figure 2-8. Customer Slave Page
This page includes the following fields:
Field Description
Settings
Communications Port
Serial Click the Serial selection to use serial Modbus
2-14 Configuring Inputs and Outputs (I/O Tab) Issued: May-2012
Modbus communications can use either serial or IP
communications.
communication, and specify the port you want to
use. (See Port).
ControlWave MRMS-IC Configuration Manual (D5140)
Field Description
Port
IP Click the IP selection to use IP Modbus (Open
Modbus Slave Address
Modbus Type
Specify the serial communication port on the
ControlWave Micro you want to use for Modbus slave
communication. Use the following code:
Enter this
1 COM1
2 COM2
3 COM3
4 COM4
5 COM5
6 COM6
7 COM7
8 COM8
9 COM9
10 COM10
11 COM11
Press [Enter] to save the selection.
Modbus) communication.
Enter the Modbus slave address. If the local slave
address you enter has already been assigned to
either the SCADA Enron Modbus slave interface, or
any of the other Customer Modbus Slave sessions,
you will see a Loc Addr Conflict message. Modify
the Modbus Slave Address as required to resolve
the conflict.
: To select this serial CW Micro port:
Enron If you want to communicate using Enron Modbus,
click this selection.
Gould If you want to communicate using Gould Modbus,
click this selection.
Data Parameters
Word Order Choose the data word order to match the data word
order used by the Modbus Master that
communicates with this Modbus Slave.
High Word First
Low Word First
Byte OrderChoose the data byte order to match the data byte
Issued: May-2012 Configuring Inputs and Outputs (I/O Tab) 2-15
Click this to specify that the high word is first.
Click this to specify that the low word is first.
ControlWave MRMS-IC Configuration Manual (D5140)
Field Description
High Byte First
order used by the Modbus Master that
communicates with this Modbus Slave.
Click this to specify that the high byte is first.
Low Byte First
Bit OrderChoose the data bit order to match the data bit order
High Bit First
Low Bit First
Data Size
Click this to specify that the low byte is first.
used by the Modbus Master that communicates with
this Modbus Slave.
Click this to specify that the high bit is first.
Click this to specify that the low bit is first.
Select the appropriate data format for Modbus Register data from the drop down menu. The available selections are:
Single Bit – Each Register will include a single bit Byte Data – Each Register will include a single byte16 Bit Integer – Each Register will include a single
16-bit integer 32 Bit Int., 1 Reg., Cnt*1, Adr*1 – Each Register
will include a 32-bit double integer. 32 Bit Float, 1 Reg., Cnt*1, Adr*1 – Each Register
will include a 32-bit floating point number 32 Bit Int., 2 Reg., Cnt*2, Adr*2 – Two registers will
be used for each 32-bit double integer. The MODBUS Master must poll two registers for each 32 bit integer.
32 Bit Float, 2 Reg., Cnt*2, Adr*2 – Two registers will be used for each 32-bit floating point number. The MODBUS Master must poll two registers for each 32 bit number.
32 Bit Int., 2 Reg., Cnt*2, Adr*1 - Two registers will be used for each 32-bit double integer. The MODBUS Master must poll a single register for each 32 bit integer.
32 Bit Float, 2 Reg., Cnt*2, Adr*1 - Two registers will be used for each 32-bit floating point number. The MODBUS Master must poll a single register for each 32 bit number.
Press [Enter] to save the selection.If you don’t make a selection, the field shows Not Set.
2-16 Configuring Inputs and Outputs (I/O Tab) Issued: May-2012
Loading...
+ 110 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.