This installation guide provides instructions for
installation, startup and adjustment. To receive a copy
of the instruction manual, contact your local Sales
Office or view a copy at www.fisher.com. For further
information refer to: 61 Series Instruction Manual,
D103233X012. For information on mounting on
pilot-operated regulators, refer to: Type 1098-EGR
Instruction Manual, D100339X012, or Type 99
Instruction Manual, D100260X012.
PED Categories
1. Type 61LD construction has narrower proportional band than the standard Type 61L Pilot.
2. Type 61LE construction has wider proportional band than the standard Type 61L Pilot.
Table 1. Reduced Pressure Ranges
TYPE
(1)
61LD
61L,
(1)
61LD
,
(2)
61LE
61H0.69 to 4.510 to 65
61HP
0 to 10 mbar
7 to 30 mbar
17 mbar to 0.14
69 mbar to 0.35
0.14 to 0.69
0.35 to 1.0
0.69 to 1.4
1.0 to 3.1
2.4 to 6.9
6.9 to 20.7
This product may be used as a safety accessory with
pressure equipment in the following Pressure Equipment
Directive categories. It may also be used outside of the
Pressure Equipment Directive using sound engineering
practice (SEP) per table below. For information on the
current PED revision see Bulletin: D103053X012.
PRODUCT SIZECATEGORIESFLUID TYPE
1/4 NPTSEP1
Installation
!
Only qualied personnel should install
or service a regulator. Regulators
should be installed, operated and
maintained in accordance with
international and applicable codes
Specifications
Available Configurations
Type 61L: Low pressure pilot for 0.02 to 1.38 bar /
0.25 to 20 psig set points
Type 61LD: Low pressure, narrow proportional
band pilot for 0 to 1.38 bar / 0 to 20 psig
Type 61LE: Low pressure, wide proportional band
pilot for 0.02 to 1.38 bar / 0.25 to 20 psig
Type 61H: high pressure pilot for set pressures
from 0.69 to 4.48 bar / 10 to 65 psig
Type 61HP: high pressure pilot for set pressures
from 1.03 to 20.7 bar / 15 to 300 psig
Maximum Inlet Pressure
Types 61L, 61LE, 61H
Type 61LD: 11 bar / 160 psig
Type 61HP: 41.4 bar / 600 psig
Reduce Pressure Ranges
See Table 1
Proof Test Pressure
All Pressure Retaining Components have been
proof tested per Directive.
Temperature Capabilities
Standard Elastomers: -29 to 66°C / -20 to 150°F
High-Temperature Elastomers: -18 to 149°C /
0 to 300°F, except -18 to 82°C / 0 to 180°F for
water service
(1)(2)
(3)
: 20.7 bar / 300 psig
(1)
and regulations and Emerson Process
Management Regulator Technologies,
Inc. instructions.
If the regulator vents uid or a leak
develops in the system, it indicates that
service is required. Failure to take the
regulator out of service immediately may
create a hazardous condition.
Personal injury, equipment damage or
leakage due to escaping uid or bursting
of pressure-containing parts may result
if this regulator is overpressured or
is installed where service conditions
could exceed the limits given in the
Specications section, or where
conditions exceed any ratings of the
adjacent piping or piping connections.
To avoid such injury or damage, provide
pressure-relieving or pressure-limiting
devices (as required by the appropriate
code, regulation or standard) to prevent
service conditions from exceeding limits.
Additionally, physical damage to the
regulator could result in personal injury
and property damage due to escaping
uid. To avoid such injury and damage,
install the regulator in a safe location.
1. The pressure/temperature limits in this installation guide or any applicable standard limitation should not be exceeded.
2. For stability or overpressure protection, a pressure reducing regulator may be installed upstream of the pilot according to the Installation section.
3. Type 61H pilot used with a 99 Series regulator can handle a maximum inlet pressure of 27.6 bar / 400 psig.
PILOT CONTROL SPRING
Reduced Pressure Ranges
barpsig
0 to 4 in. w.c.
3 to 12 in. w.c.
0.25 to 2
1 to 5
2 to 10
5 to 15
10 to 20
15 to 45
35 to 100
100 to 300
WARNING
61 Series
Clean out all pipelines before installation of the
regulator and check to be sure the regulator has not
been damaged or has collected foreign material during
shipping. For NPT bodies, apply pipe compound to the
external pipe threads. For anged bodies, use suitable
line gaskets and approved piping and bolting practices.
Install the regulator in any position desired, unless
otherwise specied, but be sure ow through the body
is in the direction indicated by the arrow on the body.
Note
It is important that the regulator be
installed so that the vent hole in the
spring case is unobstructed at all times.
For outdoor installations, the regulator
should be located away from vehicular
trac and positioned so that water, ice,
and other foreign materials cannot enter
the spring case through the vent. Avoid
placing the regulator beneath eaves or
downspouts, and be sure it is above the
probable snow level.
Overpressure Protection
The recommended pressure limitations are stamped
on the regulator nameplate. Some type of overpressure
protection is needed if the actual inlet pressure
exceeds the maximum operating outlet pressure rating.
Overpressure protection should also be provided if the
regulator inlet pressure is greater than the safe working
pressure of the downstream equipment.
Regulator operation below the maximum pressure
limitations does not preclude the possibility of damage
from external sources or debris in the line. The
regulator should be inspected for damage after any
overpressure condition.
Startup
The regulator is factory set at approximately
the midpoint of the spring range or the pressure
requested, so an initial adjustment may be required
to give the desired results. With proper installation
completed and relief valves properly adjusted, slowly
open the upstream and downstream shuto valves.
Adjustment
To change the outlet pressure, remove the closing
cap or loosen the locknut and turn the adjusting
screw clockwise to increase outlet pressure or
counterclockwise to decrease pressure. Monitor
the outlet pressure with a test gauge during the
adjustment. Replace the closing cap or tighten the
locknut to maintain the desired setting.
Taking Out of Service (Shutdown)
WARNING
!
To avoid personal injury resulting from
sudden release of pressure, isolate
the regulator from all pressure before
attempting disassembly.
Parts List
Key Description
1 Relay Spring Case
2 Relay Valve Body
3 Bottom Cover
4 Relay Yoke
5 Closing Cap Assembly, 61 Series except Type 61HP
6 Adjusting Screw
7 Control Spring
8 Relay Orice, 61 Series except Type 61HP
Fast close and open, open only or close only (Types 61L and
61LD only)
Special orice, fast open only application (Types 61L and 61LD only)
9* Disc Holder Assembly, 61 Series except Type 61HP
10* Bleed Orice, 61 Series except Type 61HP
Capped bleed (Types 61L and 61LD only)
11 Diaphram Nut, 61 Series except Type 61HP
12* O-ring Seal, 61 Series except Type 61HP
13 Relay Spring
14* Upper Relay Diaphragm
15* Lower Relay Diaphragm
16 Upper Relay Head, 61 Series except Type 61HP
Diaphragm Plate, Type 61HP only
17 Lower Relay Head, 61 Series except Type 61HP
18 Spring Seat, 61 Series except Type 61HP
19 Hex Nut
20 Cap Screw, 61 Series except Type 61HP
23 Pipe Plug, Types 61L, 61LD and 61LE only, or
Vent Assembly, Type 61H only
24 Pipe Nipple
25 Filter Assembly
26 Bleed Valve
27 Nameplate
28* Gasket, 61 Series except Type 61HP
30 Pipe Plug, 61 Series except Type 61HP
32 Bleed Orice Cap, Types 61L and 61LD with capped bleed only
33 Handwheel, Types 61L, 61LD and 61LE only
34 Hex Nut
35 Spring Seat
40* O-ring, Types 61L, 61LD and 61LE only
41 Adaptor, Type 61H only
42 Yoke Cap, Type 61HP only
43 Lockwasher, Types 61L, 61LD and 61LE only
44 Machine Screw, Types 61L, 61LD and 61LE only
45 Valve Spring Seat, Type 61HP only
46 Cap Screw, Type 61HP only
47 Machine Screw, Type 61HP only
48 Cap Screw, Type 61HP only
50 Drive Screw
51* Diaphragm Insert, Type 61HP only
52 Lower Yoke Cap, Type 61HP only
53 Bleed Plug, Type 61HP only
*Recommended spare part.
2
1
35
40
34
33
43
28
5
6
44
5
28
34
6
35
41
61 Series
20A6326
10
20
13
3
26
11
16
14
12
9
4
24
8
27
25
17
19
28
15
23
30A6327
1
DETAIL OF HANDWHEEL OPTION
2
18
7
50
6
5
TYPES 61L, 61LD AND 61LE PILOT
35
1
20A6328
DETAIL OF CAPPED
ADJUSTING SCREW OPTION
28
30A6330
DETAIL OF CAPPED
ADJUSTING SCREW OPTION
Figure 1. Types 61L, 61LD and 61LE Pilot Assemblies
30
26
13
14
25
4
24
2
15
18
7
1
35
23
32A2068
6
TYPE 61H PILOT
50
27
3
10
11
16
20
12
9
8
17
19
34
Figure 2. Type 61H Pilot Assembly
3
61 Series
34A0396
6
7
50
27
16
14
4
26
47
15
51
3
34
35
1
48
42
10
45
13
2
52
53
19
46
Webadmin.Regulators@emerson.com
Fisher.com
Emerson Automation Solutions
Americas
McKinney, Texas 75070 USA
T +1 800 558 5853
+1 972 548 3574
Europe
Bologna 40013, Italy
T +39 051 419 0611
For further information on the current
PED revision see Bulletin: D103053X012
or scan the QR code.
The contents of this publication are presented for information purposes
only, and while eort has been made to ensure their accuracy, they are
not to be construed as warranties or guarantees, express or implied,
regarding the products or services described herein or their use or
applicability. All sales are governed by our terms and conditions, which
are available on request. We reserve the right to modify or improve the
designs or specications of our products at any time without notice.
Emerson Process Management Regulator Technologies, Inc does not
assume responsibility for the selection, use or maintenance of any
product. Responsibility for proper selection, use and maintenance of any
Emerson Process Management Regulator Technologies, Inc. product
remains solely with the purchaser.