Read this manual before working with the product. For personal and system
safety, and for optimum product performance, make sure you thoroughly
understand the contents before installing, using, or maintaining this product.
Within the United States, Rosemount Inc. has two toll-free assistance numbers.
Customer Central: 1-800-999-9307 (
Technical support, quoting, and order-related questions.
North American1-800-654-7768 (
Response Center: Equipment service needs.
For equipment service or support needs outside the United States, contact your
local Rosemount representative.
7:00 a.m. to 7:00 p.m. CST)
24 hours a day – Includes Canada)
Rosemount Inc.
8200 Market Boulevard
Chanhassen, MN 55317 USA
Tel 1-800-999-9307
Telex 4310012
Fax (612) 949-7001
This manual is designed to assist in installing, operating, and
maintaining Rosemount
Transmitters.
Section 2 Installation
provides mechanical, electrical, and environmental considerations to
guide you through a safe and effective transmitter installation.
Section 3 Calibration
provides different Model 444 calibration procedures.
Section 4 Maintenance and Troubleshooting
provides hardware diagnostics, maintenance tasks, basic hardware
troubleshooting techniques, and considerations for returning materials.
Section 5 Specifications and Reference Data
provides functional, performance, and physical transmitter
specifications; also includes transmitter dimensional drawings,
ordering information, and spare parts.
Section 6 Options
provides a listing of transmitter options and a description of each.
Appendix A Approval Drawings
contains approval drawings for Canadian Standards Association (CSA)
and Factory Mutual (FM) instrinsic safety installation.
Appendix B Temperature Sensor Reference Information
provides reference information regarding the application of various
Rosemount temperature sensors.
®
Model 444 Alphaline® Temperature
1-1
Rosemount Model 444 Alphaline Temperature Transmitters
1-2
Section
2Installation
OVERVIEW
This section includes the following transmitter installation
information:
• General Considerations
• Mechanical Considerations
Mounting Stability
Access Requirements
• Electrical Considerations
Power Supply
Field Wiring
Sensor Connections
Grounding
Multi-Channel Installations
Surges/Transients
• Environmental Considerations
Temperature Environment
Moist or Corrosive Environments
Hazardous Location Installation
Intrinsically Safe Installation
• Installation Procedure
Mechanical
Electrical
GENERAL
CONSIDERATIONS
Failure to follow these installation guidelines may result in
death or serious injury. Make sure only qualifiedpersonnel
perform the installation.
Explosions can cause death or serious injury. Verify that the
operating atmosphere of the transmitter is consistent with
the appropriate hazardous locationscertifications.
Use the Rosemount Model 444 Alphaline Temperature Transmitter
when the temperature measurement point is remote from the control,
readout, or recording point, or where the measurement point is exposed
to environmental conditions that would be harmful to unprotected
signal conditioning equipment.
Electrical temperature sensors such as RTDs and thermocouples
2-1
Rosemount Model 444 Alphaline Temperature Transmitters
produce low-level signals proportional to their sensed temperature. Model 444
temperature transmitters convert the low-level sensor signal to a standard 4–20
mA dc signal that is relatively insensitive to lead length and electrical noise.
This current signal is then transmitted to the control room via two wires.
Figures 2-1, and 2-2 show recommended mounting configurations for
transmitter and sensor assemblies. See Section 6 Options for information
regarding Model 444 transmitter accessories.
MECHANICAL
CONSIDERATIONS
Mounting Stability
Access
Requirements
Housing RotationYou may rotate the transmitter in 90-degree increments to improve field access
Terminal Side of
Electronics Housing
Circuit Side of
Electronics Housing
You can attach the transmitter directly to the sensor assembly as shown in
Figures 2-1 and 2-2. An optional mounting bracket permits the transmitter to be
mounted remotely from the sensor(s), either on a flat surface or attached to a
two-inch pipe (See Figure 2-11 on page 2-13). The choice of mounting method
must take into account a number of factors:
Mounting stability is an important consideration. The transmitter, though
rugged, may require supplementary support under high-vibration conditions,
particularly if extensive thermowell lagging or long extension fittings are used.
In such instances, the pipestand mounting technique shown in Figure 2-11 on
page 2-13 is preferable.
When choosing an installation location and position, take into account the need
for access to the transmitter.
to both compartments.
Make wiring connections through the conduit openings on the terminal side of
the electronics housing. Mount the transmitter so the terminal side is accessible,
and be sure to provide adequate clearance for cover removal.
The transmitter electronics are installed in the circuit side of the transmitter
housing. In case of electronic malfunction, provide adequate clearance for
circuit-side cover removal. Also, be sure to account for additional clearance if a
meter is to be installed. For more information regarding the meter option, refer
to Section 6 Options.
2-2
FIGURE2-1. Recommended
Process Mounting.
Installation
Thermowell
NOTE
Dimensionsare in inches (millimeters).
FIGURE2-2. Recommended
Process Mounting with
Drain Seal.
Thermowell
Hex
Extension
Nipple
Extension
Length
Union or Coupling
Sensor Hex
Transmitter
Conduit for
Field Wiring
(dc Power)
3.2
(81.3)
444-0200C
Extension
Nipple
Union or Coupling
Sensor Hex
Drain Seal
Conduit for
Field Wiring
(dc Power)
Coupling
Close Nipple
Street Ell
Transmitter
Terminal
Side
444-0200F
2-3
Rosemount Model 444 Alphaline Temperature Transmitters
ELECTRICAL
CONSIDERATIONS
Po wer Supply
FIGURE 2-3. Model 444
Load Limits.
This section contains information that you should consider when preparing to
install Model 444 transmitters. Read this section carefully before going on to the
installation procedures. Metal conduit should be used to enclose cabling for best
results in electrically noisy environments.
The dc power supply should provide power with less than 2% ripple. The input
voltage versus load limitation relationship for 4–20 mA transmitters is shown in
Figure 2-3. Figure 2-4 shows field wiring for a standard Model 444 transmitter.
Figure 2-5 shows field wiring for Models 444LL and 444LM low-power voltage
output units, which require 100K ohms minimum load. The total R-load is the
sum of the resistance of the signal leads and the load resistance of the controller,
indicators, and related devices. Note that the resistance of intrinsic safety
barriers, if used, must be included in the total load.
Power Supply Load Limitations
R
LOAD(MAX.)
1650
1500
1000
500
Load (Ohms)
0
Voltage
Too Low
12203040
=503 (V
Power Supply (V dc)
(MIN.)
Operating
Region
– 12)
Field Wiring
Explosions mayresult in death or serious injury.
Do not remove the instrument cover in explosive
atmospheres when the circuit is alive.
High voltage that may be present on leads can cause
electrical shock.Avoid contact with leads and terminals.
Do not apply high voltage (e.g. ac line voltage) to the
transmitter terminals. Abnormally high voltage can damage
the unit.
All power to the transmitter is supplied over the signal wiring. Signal wiring
need not be shielded, but use twisted pairs for best results. Do not run
unshielded signal wiring in conduit or open trays with power wiring, or near
heavy electrical equipment. To power the transmitter, connect the positive power
lead to the terminal marked “+” and the negative power lead to the terminal
marked “–” (see Figures 2-4 and 2-5). Tighten the terminal screws to ensure
adequate contact. No additional power wiring is required.
2-4
FIGURE 2-4. Field Wiring for
the StandardModel 444
Transmitters.
Meter Connections
and S ignal
Test Points
(+)
{
(–)(–)
(+)
{
dc Power
Installation
FIGURE 2-5. Field Wiring for
Low-Power Model
444 Transmitters
(444LL and LM).
RTD Input
(typical)
Zero Adjust
RTD Input
Zero Adjust
Output Voltage (+)
Optional
Ground
Span Adjust
(+) dc Power
(–) Common
Shield
Span Adjust
–+–+
Power
Supply
+
++––
444-0000C02A
Output Load Limitation
Minimum Load = 100K
AtoD
Converter
Optional
Ground
444-0000A02A
Sensor
Connections
RTD Inputs
Explosion mayresult in death or serious injury. Do not
remove the instrument cover in explosive atmos pheres
when the circuit is alive.
Highvoltagethatmaybe present on leads can causeelectrical
shock. Avoid contact with the leads and the terminals.
Various RTD configurations are used in industry; each configuration offers a
specific solution for compensating the effects of lead wire resistance. They
include 3- and 4-wire designs. The correct installation for each of these RTDs is
shown in Figures 2-6a and b on page 2-6.
If the transmitter is mounted remotely from the RTD, operation will be
satisfactory, without recalibration, for lead wire resistances of up to 2 ohms per
lead (equivalent to 200 feet of 20 AWG wire). In this case, the leads between the
RTD and transmitter should be shielded.
2-5
Rosemount Model 444 Alphaline Temperature Transmitters
The correct connections for a compensation loop RTD and a 2-wire RTD are
shown in Figure 2-6c and Figure 2-6d, respectively. In a 2-wire RTD, however,
both leads are in series with the sensor element, so significant errors (0.1 °C)
could occur if the lead lengths are greater than one foot. For longer runs when
using a 2-wire RTD, attach a third lead and connect as shown in Figure 2-6a.
FIGURE 2-6.Sensor Wiring Diagrams.
Signal
–+
Red
Red
White
Model 444 with 3-Wire RTD
Figure 2-6a
Signal
+ OutputCommon –
Red
Model 444LL or 444LM
with 3-Wire RTD
Figure 2-6e
Signal
–+
Red
Red
White
Model 444 with 4-Wire RTD
Figure 2-6b
Red
White
Model 444MV with Millivolt
Input or Model444T Series
with Grounded or
Ungrounded Thermocouple
White
Signal
–+
Figure 2-6f
Model 444 with
Comp. Loop RTD
Figure 2-6c
–+
High T/C
–+
Signal
–+
Red
Jumper
White
Model 444 with 2-Wire RTD
Black
Black
Signal
++ ––
Model 444MV used as
DifferentialMillivolt
Transmitter (T/C Junctions
must be ungrounded)
Figure 2-6g
Figure 2-6d
–+
Low T/C
Signal
White
Red
–+
444-0203A;B;C;D
FIGURE 2-7.Characteristics of Thermocouple and RTD Input Wires.
Single Element RTDCompensation Loop RTDDual E lement RTD
Red
Red
White
White
2-6
Red
White
Black
Black
Red
White
White
Black
Green
Green
444-0207A
Installation
Thermocouple or
Millivolt Inputs
Grounding
In the case of thermocouples, make connections between the sensor and the
transmitter with thermocouple wire. For process mounting applications, connect
the thermocouple directly to the transmitter. For installations where the
transmitter is mounted remotely from the sensor, use appropriate thermocouple
extension wire. As with all low-level signal wiring, shielding is recommended for
long runs. Make input connections for the Model 444MV Millivolt Transmitter
using copper wires. The correct connections for thermocouple and millivolt
inputs are shown in Figures 2-6f and g.
The transmitter will operate with the current signal loop either floating or
grounded. However, many types of readout devices are affected by the extra
noise in floating systems. If operation appears noisy or erratic, grounding the
current signal loop at a single point may solve the problem. The negative
terminal of the power supply is the best place to ground the loop. Alternately,
either side of the readout device could be grounded. Do not ground the current
signal loop at more than one point.
Thermocouple and millivolt transmitters are isolated, so the input circuit also
may be grounded at any single point (when a grounded thermocouple is used,
this point is the grounded junction), and the signal loop may be grounded at any
point.
The 444RL transmitter is not isolated, so there can be no grounds in the RTD
circuit. Since RTDs must be well-insulated from ground in order to give correct
temperature readings, this is not normally an installation limitation. The
positive side of the power supply should not be grounded for use with RTD input
transmitters. The 444RI9 should be used with grounded RTDs.
Multi-Channel
Installations
FIGURE 2-8. Multi-Channel
Installation.
Transmitter
No. 1
Transmitter
No. 2
If using shielded wire, connect the shield of the sensor-to-transmitter cable to
the shield of the transmitters-to-receiver cable. Ground the shielding only at the
signal loop ground.
Figure 2-8 illustrates how several transmitters can be connected to a single
master power supply. In this instance, the system can be grounded only at the
negative power supply terminal. Since several channels are dependent on one
supply, an uninterruptible power supply or backup battery should be considered
if loss of all channels would pose operational problems. The diodes shown in
Figure 2-8 prevent unwanted charging or discharging of the battery.
ToAdditional
Transmitters
Readout or
Controller No. 1
Readout or
Controller No. 2
+
Backup
Battery
–
dc
Power
Supply
+
–
444-0202A
2-7
Rosemount Model 444 Alphaline Temperature Transmitters
Surges/Transients
ENVIRONMENTAL
CONSIDERATIONS
Temperature
Environment
The transmitter will withstand electrical transients of the energy level usually
encountered in static discharges or induced switching transients. However, highenergy transients, such as those induced in wiring from nearby lightning strikes,
can damage both the transmitter and the sensor.
To protect against high-energy transients, install Model 444 transmitters in
conjunction with the Rosemount Model 470 Transient Protector. The Model 470
prevents damage from transients induced by lightning, welding, heavy electrical
equipment, or switch gears. Refer to the Model 470 Transient Protector product
data sheet, pub. no. 00813-0100-4191 for more information.
The transmitter will operate within specifications for ambient temperatures
between –25 and 85 °C. It will function, but not necessarily within specifications,
in ambient temperatures between
–40 and 100 °C.
Aside from ambient temperature variations, heat from the process is transferred
from the thermowell to the transmitter housing. If the process temperature is
near or beyond specification limits, use excess thermowell lagging or an
extension nipple to protect the transmitter from the high temperature condition.
See Figure 2-10.
EXAMPLE:
Suppose the maximum ambient temperature is 40 °C and the temperature to
be measured is 540 °C. The maximum allowable housing temperature rise is
the rated temperature specification limit minus the existing ambient
temperature (85 – 40), or 45 °C. As shown in Figure 2-9, an “E” dimension of
3.6 inches will result in a housing temperature rise of 22 °C. An “E”
dimension of 4 inches would therefore be the minimum recommended length,
and would provide a safety factor of about about 25 °C. A longer “E”
dimension, such as 6 inches, would be desirable in order to reduce errors
caused by transmitter temperature effect, although in that case the
transmitter would probably require extra support. If a thermowell with
lagging is used, the “E” dimension may be reduced by the length of the
lagging.
2-8
Installation
FIGURE 2-9. Model 444
Transmitter Housing
Temperature Rise.
Sensor Installed in
ConnectionHead(Flat
Cover)withUnionand
Nipple Extension and
Thermowell
SensorLength (Ref.)
Length
X
E
V
(1)
+ 1.75 (44)
T
(1)
T
= 0.0 on Standard Assembly Thermowells
L
0.53 (13) Max.
Thread
Engagement
¾–14 NPT
on Thermowell
U
0.25
(6)
Sensors-0000A06A
2-9
Rosemount Model 444 Alphaline Temperature Transmitters
Moist or Corrosive
Environments
HazardousLocation
Installation
The transmitter is designed to resist attack by moisture and other corrosives.
The coated circuit boards are mounted in a compartment completely sealed from
the conduit entrances. O-ring seals protect the interior when the covers are
installed. In humid environments, however, it is still possible for moisture
“breathing” to occur in conduit lines. If the transmitter is mounted at a low point
in the conduit run, the terminal compartment could fill with water, causing
electrical shorting. The transmitter should be mounted so moisture from the
conduit will not drain into the housing. In some instances a drain seal, installed
as shown in Figure 2-2 on page 2-3, is advisable.
Explosions mayresult in death or serious injury.Verify that
the operating atmosphere of the transmitter is consistent
with the appropriate hazardous locations certifications.
Explosions mayresult in death or serious injury.Both
transmitter covers must be fully engaged to meet explosionproof requirements.
Intrinsically Safe
Installation
The Model 444 is designed with an explosion-proof housing and circuitry
suitable for intrinsically safe and non-incendive operation. Individual
transmitters are clearly marked with a tag indicating the approvals they carry.
The various approvals are available as options. Refer to Section 5 Specifications and Reference Data for a complete listing of available
approvals.
To maintain certified ratings for installed transmitters, install in accordance
with applicable installation codes and approval drawings. Refer to Appendix A Approval Drawings for Model 444 installation drawings. For future orders,
refer to the current product price list for the most up-to-date information on
these approvals.
For explosion-proof installations, installation location must
be m ade in accordance with Rosemount drawing 004440261, Rev. E.
For intrinsically safe installations, installation location must
be m ade in accordance with Rosemount drawing 004440034, Rev. C (CSA) or00444-0264, Rev. B (SAA).
You can use Intrinsically safe installations instead of explosion-proof
installations in hazardous areas. In such configurations, the transmitter and
sensor are located in a hazardous area, and the current signal leads are
connected to equipment in a non-hazardous area through intrinsic safety
barriers that limit the voltage and current fed into the hazardous area. Install in
accordance with the barrier manufacturer’s instructions for the specific barrier
used. For approval information, refer to Table 5-1 on page 5-4, and Table 5-2 on
page 5-5. For installation information, refer to the intrinsically safe barrier
systems reference drawings in Appendix A Approval Drawings.
2-10
Installation
INSTALLATION
PROCEDURE
Installation consists of mounting the transmitter and sensor assembly and
making electrical connections. If mounting the transmitter directly to the sensor
assembly, use the process mounting technique shown in Figure 2-1 or Figure 2-2,
on page 2-3. For transmitter locations remote from the sensor, use conduit
between the sensor and transmitter. Transmitter hubs will accept male conduit
fittings with ½–14 NPT; ½–14 NPSM; or ½–14 taper thread per ANSIC 80.4.
Explosion mayresult in death or serious injury. Do not
remove the instrument cover in explosive atmos pheres
when the circuit is alive.
High voltage that may be present on leads may cause
electrical shock.Avoid contact with the leads and the
terminals.
Process leaks may result in death or serious injury.Install
and tighten thermowells or sensors before applying
pressure, or process leakage may result. Removing the
thermowell or sensor while in operation may cause process
fluid leaks.
Mechanical
Electrical
1. Mount the thermowell to the pipe or process container wall.
2. Attach any necessary extension nipples and adapters. Seal the nipple and
adapter threads with silicone or tape.
3. Screw the sensor into the thermowell.
4. Install drain seals if required for severe environments or to satisfy code
requirements (See Figure 2-2 on page 2-3).
5. Attach the transmitter to the thermowell assembly. Seal the adapter
threads with silicone or tape.
6. Install conduit for field wiring to the remaining conduit entry of the
transmitter. Seal conduit threads with silicone or tape.
7. Pull field wiring leads through the conduit into the terminal side of the
transmitter housing.
For explosion-proof installations, wiring connections must
be m ade in accordance with Rosemount drawing 004440261, Rev. E.
For intrinsically safe installations, wiring connections must
be m ade in accordance with ANSI/ISA-RP12.6, and
Rosemount drawing 00444-0034, Rev.C (CSA) or 004440264, Rev. B (SAA).
For all installations, wiring connections must follow the
National Electric Code.
2-11
Rosemount Model 444 Alphaline Temperature Transmitters
Preliminary Checkout
1. For any Model 444 unit, first verify that the transmitter is calibrated to
the required range. Calibration is usually performed by substituting an
input in place of the sensor, and this is most conveniently accomplished
prior to sensor connection. Refer to the calibration procedures in Section 4 Maintenance and Troubleshooting.
Input Connections
2. Model 444RL: Connect the RTD leads as shown in Figure 2-6a, b, c, d, or
e depending upon the lead compensation method used.
Model 444T series: Connect the thermocouple leads as shown in Figure
2-6f. Polarity is important; be sure to identify the leads accurately. The
negative lead is usually red; if there is no color coding, the characteristics
provided in Figure 2-7 may be helpful.
Model 444MV: If using the transmitter as a millivolt-to-milliampere
converter, use ordinary copper leads for input connections as shown in
Figure 2-6f. If using the transmitter with two thermocouples to measure
differential millivolt, connect the thermocouples as shown in Figure 2-6g.
The “high” thermocouple causes the transmitter output to increase when
its temperature increases relative to the “low” thermocouple. Grounded
thermocouples cannot be used for differential measurements.
Models 444LL and LM: In these low-power option packages, the RTD
leads are connected the same as in the conventional RTD arrangements
shown in Figure 2-6a, b, c, and d.
Output Connections
3. For all 4–20 mA models, use ordinary copper wire of sufficient size to
assure that the voltage across the transmitter power terminals does not go
below 12 V dc (See Figure 2-3). For multi-channel or intrinsically safe
installations, see applicable paragraphs in this section.
Model 444RL: Connect current signal leads as shown in Figure 2-6a, b, c,
or d.
Model 444T series: Connect current signal leads as shown in Figure 2-6f.
Model 444MV: Connect current signal leads as shown in Figure 2-6f or g.
Models 444LL and LM: Connect current signal leads as shown in Figure
2-6e.
Final Checkout
4. For all models, recheck the polarity and correctness of connections; then
turn the power on.
2-12
FIGURE 2-11. Model 444
with
Optional Mounting Bracket.
Installation
PIPESTAND MOUNTING
Clearance Hole
for ¼-inch Bolt
(eight places)
NOTE
Dimensions are in inches (millimeters).
FIGURE 2-12. Model 444
Dimensional Drawings
4.5 Max.
(114)
Transmitter can be Rotated 90°
Mounting Bracket
¼–20 3½-inch
5
/16 –18 U-bolt for
2-inch Pipe (2)
Permanent Tag
(Optional)
Bolt (4)
PANEL OR SURFACE MOUNTING
5.00 (127)
7.5 (191) Max. with Optional
Meter
Meter Housing
5
/16 -inch Bolts
(four required,
not furnished)
2.81 (81)
4.5 Max.
(114)
Hole for
5
/16 -inch
Bolts
(four
places)
0.75 (19)
Clearance for
Cover Removal
(Typical)
444-1151G, 1151F04A
4.5 Max.
Nameplate
Explosion Proof or
Intrinsic Safety L abel
(Optional)
0.375 (10) Min. Dp.
NOTE
Dimensions are in inches (millimeters).
(114)
Mounting Holes
¼–20 UNC–2B
(four places)
½–14 NPT per
ANSI C80.4 for
Conduit or Sensor
Connection
(two places)
0.87 (22)
1.7
(44)
(117)
Terminal
Connections
this Side
0.36 (9)
0.72 (18)
4.2
Terminal
Circuitry
this Side
444-51LTE 05A, 51LTG05A, 51LTF 05A
2-13
Rosemount Model 444 Alphaline Temperature Transmitters
2-14
Section
3Calibration
OVERVIEW
SAFETY MESSAGES
Each transmitter is factory calibrated to the temperature range shown
on the nameplate. If calibration to a specific range is not specified on
the purchase order, the transmitter is calibrated to maximum span
with a base temperature of 0 °C, and the “Calibration” entry on the
transmitter nameplate is left blank. For more specific calibration
information and a complete breakdown of transmitter parts, refer to
Section 5 Specifications and Reference Data.
Only a few calibration laboratories have the kind of precision
temperature baths necessary for accurate direct calibration of a
temperature sensor or sensor/transmitter system. As a result, the
transmitter is normally calibrated by substituting a resistance decade
box for an RTD or a compensated thermocouple simulator for a
thermocouple.
This section contains the following transmitter calibration information:
• Calibrating a RTD Transmitter
• Calibrating a Thermocouple Transmitter
• Calibrating a Low-Power Transmitter
• Calibrating a Millivolt Transmitter
This section contains procedures that require removing the transmitter
covers and making electrical connections. The following safety
messages apply to all such procedures.
Explosion mayresult in death or serious injury. Do not
remove the instrument cover in explosive atmos pheres
when the circuit is alive.
High voltage that may be present on leads can cause
electrical shock.Avoid contact with the leads and the
terminals.
3-1
Loading...
+ 52 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.