Fisher 4195K User Manual

Product Bulletin
4195K Pressure Controllers
D200050X012
November 2019
Fisher™ 4195K Gauge Pressure Indicating Controllers
34.5:4195K
Fisher 4195K gauge pressure indicating controllers show process pressure and set point on an easy‐to‐read process scale. The controllers compare process pressure with an operator‐adjusted set point and delivers a pneumatic signal to a control element so that process pressure changes toward the set point. Controller types are available for proportional‐only,
proportional‐plus‐reset, proportional‐plus‐reset‐ plus‐rate, and differential gap for on‐off control. 4195K controllers are used in industries where accurate pressure control and process monitoring are required.
Unless otherwise noted, all NACE references are to NACE MR0175-2002.
1
W5660‐1
W5663‐1
YOKE‐MOUNTED CONTROLLER
Notes:  1 An internal cover protects the proportional band adjustment mechanism. In this photograph, the cover has been removed.  2 Controller components are indicated in figure 1.
www.Fisher.com
INTERIOR OF A FISHER 4195KBME CONTROLLER
2
Product Bulletin
34.5:4195K November 2019
Specifications
4195K Pressure Controllers
D200050X012
Available Configurations
See table 1
Process Sensor Range (Input Signal)
Lower and Upper Range Limits: As shown in tables 2 and 5
Maximum Allowable Pressure:
As shown in tables 2 and 5
Process Scale
Standard scale is matched to the range of the sensing element, with exception of receiver controllers. Optional scales available
(1)
.
Process Connections
Standard: 1/4 NPT internal stainless steel (all input ranges) Optional: 1/2 NPT adaptors (see table 3)
Output Signal
Proportional, Proportional‐Plus‐Reset, or Proportional‐Plus‐Reset‐Plus‐Rate Range:
1.0 bar (3 to 15 psig) or Differential Gap Range:
0 to 2.4 bar (0 to 35 psig)
Action: Field‐reversible between
0.4 to 2.0 bar (6 to 30 psig)0 to 1.4 bar (0 to 20 psig) or
direct (increasing
0.2 to
sensed pressure increases output pressure), and
reverse (increasing sensed pressure decreases
output pressure) action
Supply and Output Connections
1/4 NPT internal
Supply Pressure Medium
Air or non-corrosive Natural Gas
Remote Set Point Pressures
0.2 to 1.0 bar (3 to 15 psig) or 0.4 to 2.0 bar
(6 to 30 psig)
Construction Materials
See table 6
Controller Adjustments
Proportional Band: 5 to 500% of process scale span Reset: Adjustable from 0.01 to more than 74 minutes
per repeat (from 100 to less than 0.0135 repeats per minute)
Rate: Adjustable from 0 to 20 minutes Differential Gap Controllers: Adjustable from 5 to
100% of process scale span Set Point: Adjustable from 0 to 100% of the scale span
Controller Performance
Repeatability: 0.4% of output span Dead Band: Less than 0.4% of process scale span Typical Frequency Response: 1.5 hertz and 90 degree
phase shift with 3.05 m (10 feet) of 6.4 mm (1/4‐inch) tubing and 1639 cm
Steady‐State Air Consumption
0.2 to 1.0 Bar (3 to 15 Psig) Output:
0.08 m
0.4 to 2.0 Bar (6 to 30 Psig) Output:
0.07 m
3
/hr (2.8 scfh)
3
/hr (2.5 scfh)
3
(100 cubic inch) volume
(3)(4)
Supply Pressure Requirements
(2)
See table 4
Table of Contents
Features 4.....................................
Construction Features 4.........................
Principle of Operation 8.........................
Proportional-Only Controllers 8..................
Proportional-Plus-Reset and
Proportional-Plus-Reset-Plus Rate Controllers 8..
Differential Gap Controllers 10..................
Remote Set Point Option 10....................
2
(continued)
Operative Ambient Temperature Limits
(2)(5)
-40 to 71C (40 to 160F)
Auto/Manual Station Option 10..................
Anti-Reset Windup Option 11...................
External Feedback Option 11....................
Installation 12.................................
Ordering Information 12.........................
Application 12................................
Construction 12...............................
4195K Pressure Controllers
D200050X012
Specifications (continued)
Product Bulletin
34.5:4195K
November 2019
Hazardous Area Classification
Complies with the requirements of ATEX Group II Category 2 Gas and Dust
Housing
Designed to NEMA 3 (Weatherproof) and IEC 529 IP54 Specifications
Ex h IIC Tx Gb Ex h IIIC Tx Db
Maximum surface temperature (Tx) depends on
Mounting
operating conditions
Gas: T6 Dust: T71
Controller can be mounted on
wall, or pipestand
Meets Customs Union technical regulation TP TC 012/2011 for Groups II/III Category 2 equipment
II Gb c T*X III Db c T*X
NOTE: Specialized instrument terms are defined in ANSI/ISA Standard 51.1 - Process Instrument Terminology.
1. Consult your Emerson sales office
2. The pressure/temperature limits in this document and any applicable code or standard should not be exceeded.
3. Normal m
4. Without auto/manual station. With auto/manual station add 0.01 m
5. Also use these temperatures for transportation and storage limits.
3
/hr‐‐normal cubic meters per hour (m3/hr, 0C and 1.01325 bar, absolute). Scfh‐‐standard cubic feet per hour (ft3/hr, at 60F and 14.7 psig).
for additional information.
3
/hr (0.5 scfh).
Approximate Weight
4.5 kg (10 pounds)
Table 1. Available Configurations
MODES OPTIONS
TYPE
NUMBER
4195KA
4195KAE
4195KAM
4195KAME
4195KB 4195KBE 4195KBF
4195KBFE
4195KBM 4195KBME 4195KBFM
4195KBFME
4195KC 4195KCE 4195KCF
4195KCFE
4195KCM 4195KCME 4195KCFM
4195KCFME
4195KS
4195KSE
4195KSM 4195KSME
1. Reverse‐acting constructions are designated by the suffix letter R in the type number.
(1)
Proportional‐
Only
X X X X
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
Proportional‐
Plus‐Reset
- - -
- - -
- - -
- - ­X
X X X X X X X
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
Proportional‐
Plus‐Reset‐
Plus‐Rate
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
X X X X X X X X
- - -
- - -
- - -
- - -
Differential
Gap
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
X X X X
Anti‐Reset
Windup
(suffix letter F)
- - -
- - -
- - -
- - -
- - -
- - ­X X
- - -
- - ­X X
- - -
- - ­X X
- - -
- - ­X X
- - -
- - -
- - -
- - -
actuator, panel,
Remote
Set Point
(suffix letter M)
- - -
- - ­X X
- - -
- - -
- - -
- - ­X X X X
- - -
- - -
- - -
- - ­X X X X
- - -
- - ­X X
Internal Auto/
Manual Station
(suffix letter E)
- - ­X
- - ­X
- - ­X
- - ­X
- - ­X
- - ­X
- - ­X
- - ­X
- - ­X
- - ­X
- - ­X
- - ­X
3
Product Bulletin
34.5:4195K November 2019
4195K Pressure Controllers
D200050X012
Features
n Easy Maintenance—Simple design allows fast, easy
maintenance and minimal spare parts inventory.
nEasy Adjustment—Adjusting the set point, the zero
and span of the process pointer, and switching between direct and reverse action are accomplished quickly and without special tools. Additionally, the set point and proportional band can be adjusted with no interaction between the two adjustments.
n Application Versatility—Either a Bourdon tube or
capsular input element is available to control a wide range of positive pressures, vacuum pressures, or compound pressures.
n Mounting Versatility—A 4195K controller can be
mounted directly on the actuator or it can mount on a pipestand, wall, or in a panel.
n Vibration Resistance—The simple design and low
mass of internal parts allow a 4195K controller to withstand the vibration levels encountered in most plant environments.
Construction Features
Simplified Relay Maintenance
A clean‐out wire provides a fast, easy means of cleaning the relay primary orifice during service.
Pressure Protection for the Case
A rubber plug in the plastic case pops out to relieve excessive pressure buildup inside the case.
Easy Direct/Reverse Switching
Controller action can be switched from direct to reverse or vice versa by simply loosening the screws on the proportional band cover and moving the cover out to rotate the proportional band knob to the desired action (see figure 1).
Easy Mode Conversion
Conversion from proportional to proportional‐plus‐reset control requires the addition of a reset valve and two pieces of tubing. Conversion from proportional to proportional‐plus‐reset‐plus‐rate control requires the addition of a reset/rate valve and three pieces of tubing. Conversion from proportional to differential gap for on/off control requires the addition of one piece of tubing.
n High‐Visibility Display—Two red pointers on a
114 mm (4 1/2‐inch) long, white‐on‐black scale show process pressure and deviation from set point at a glance. Two other gauges monitor supply pressure and output pressure.
n Low Air/Gas Consumption—The relay and nozzle
design reduces the steady-state consumption rate to as low as 0.07 m 6 scfh requirement set for the oil and gas industry by the US Environmental Protection Agency (New Source Performance Standards Subpart OOOO, EPA‐HQ‐QAR‐2010-0505).
n Corrosion Resistance—Tough, plastic housing resists
such corrosive environments as chemical plants and the salt spray atmosphere on an offshore oil platform. Internal constructions are available to resist a corrosive supply pressure media.
4
3
/hr (2.5 scfh); less than the
Anti‐Reset Windup
Anti‐reset windup is available with proportional‐plus‐reset controllers. A relief valve may be installed to limit reset windup in either direction.
Remote Set Point
The capability to adjust the set point from a remote location is available as an option on 4195K controllers.
Auto/Manual Capability
An optional internal auto/manual station permits smooth, bumpless transfer between automatic control and manual operation without disturbing the controller output. A positive‐acting, two‐position switch, showing either automatic or manual control mode, is clearly visible with the controller cover closed.
Product Bulletin
(1)
4195K Pressure Controllers
D200050X012
Table 2. Process Sensor (Capsular Element) Pressure Ratings
CAPSULE
MATERIAL
Metric
units
N09902
Nickel Alloy
U.S. units
1. Minimum or maximum span or any span in between may be positioned anywhere within the operating range. For example, if a 0 to 350 mbar (0 to 5 psig) sensing element is used and the minimum span of 175 mbar (2.5 psig) is set, the process indication can be calibrated to a range of 340 mbar to 203 mbar (10 inch Hg to 6 inch Hg), 0 to 172 mbar (0 to 2.5 psig), 172 to 345 mbar (2.5 to 5 psig), 305 to 480 mbar (4.5 to 7 psig), or any value between minimum and maximum values of operating range.
2. Capsules with the travel stops set may be pressured to this value without permanent zero shift.
CAPSULAR
STANDARD RANGES
0 to 150 mbar 0 to 400 mbar 0 to 0.6 bar
Positive
pressure
Vacuum
Compound
Positive
pressure
Vacuum
Compound
0.2 to 1 bar 0 to 1 bar
0 to 1.4 bar 0 to 1.6 bar
0.4 to 2 bar 0 to 2 bar
-150 to 0 mbar
-340 to 0 mbar
-400 to 0 mbar
-0.6 to 0 bar
-1 to 0 bar
-50 to 100 mbar
-175 to 175 mbar
-150 to 250 mbar
-0.2 to 0.4 bar
-0.4 to 0.6 bar
-0.6 to 0.8 bar
-1 to 0.6 bar
-1 to 1 bar 0 to 60 inch wc
0 to 5 psig 0 to 10 psig 3 to 15 psig 0 to 15 psig
0 to 20 psig 6 to 30 psig 0 to 30 psig
-5 to 0 inch Hg
-10 to 0 inch Hg
-20 to 0 inch Hg
-30 to 0 inch Hg
-30 to 30 inch wc
-5 inch Hg to 2.5 psig
-10 inch Hg to 5 psig
-15 inch Hg to 7.5 psig
-20 inch Hg to 10 psig
-30 inch Hg to 15 psig
100 mbar 350 mbar
0.35 bar
0.4 bar
0.5 bar
0.7 bar 1 bar
0.8 bar 1 bar
85 mbar 170 mbar 350 mbar
0.35 bar
0.5 bar 100 mbar
175 mbar 350 mbar
0.35 bar
0.5 bar
0.7 bar 1 bar 1 bar
40 inch wc
2.5 psig 5 psig 6 psig
7.5 psig 10 psig
12 psig 15 psig
2.5 inch Hg 5 inch Hg 10 inch Hg 15 inch Hg
40 inch wc
2.5 psig 5 psig
7.5 psig 10 psig 15 psig
SPAN
Min Max Min Max
160 mbar 700 mbar
0.7 bar
0.8 bar 1 bar
1.4 bar 2 bar
1.6 bar 2 bar
170 mbar 340 mbar 700 mbar
0.7 bar 1 bar
160 mbar 350 mbar 700 mbar
0.7 bar 1 bar
1.4 bar 2 bar 2 bar
60 inch wc 5 psig 10 psig 12 psig 15 psig
20 psig 24 psig 30 psig
5 inch Hg 10 inch Hg 20 inch Hg 30 inch Hg
60 inch wc 5 psig 10 psig
15 psig 20 psig 30 psig
OPERATING RANGE
-350 mbar
-1 bar
-1 bar
-1 bar
-1 bar
-1 bar
-1 bar
-1 bar
-1 bar
-350 mbar
-480 mbar
-1 bar
-1 bar
-1 bar
-350 mbar
-480 mbar
-1 bar
-1 bar
-1 bar
-1 bar
-1 bar
-1 bar
-10 inch Hg
-14 inch Hg
-30 inch Hg
-30 inch Hg
-30 inch Hg
-30 inch Hg
-30 inch Hg
-30 inch Hg
-10 inch Hg
-14 inch Hg
-30 inch Hg
-30 inch Hg
-10 inch Hg
-14 inch Hg
-30 inch Hg
-30 inch Hg
-30 inch Hg
-30 inch Hg
350 mbar 1 bar 1 bar
1.4 bar
1.4 bar
1.7 bar
2.4 bar 2 bar
2.4 bar 350 mbar
480 mbar 1 bar 1 bar
1.4 bar 350 mbar
480 mbar 1 bar 1 bar
1.4 bar
1.7 bar
2.4 bar
2.4 bar 5 psig
7 psig 15 psig 20 psig 20 psig
25 psig 30 psig 35 psig
5 psig 7 psig 15 psig 20 psig
5 psig 7 psig 15 psig
20 psig 25 psig 35 psig
34.5:4195K
November 2019
OPERATING
LIMIT
510 mbar
1.5 bar
1.5 bar 2 bar 2 bar
2.5 bar
3.5 bar 3 bar
3.5 bar 510 mbar
724 mbar
1.5 bar
1.5 bar 2 bar
510 mbar 724 mbar
1.5 bar
1.5 bar 2 bar
2.5 bar
3.5 bar
3.5 bar
7.5 psig
10.5 psig
22.5 psig 30 psig 30 psig
37.5 psig 45 psig
52.5 psig
7.5 psig
10.5 psig
22.5 psig 30 psig
7.5 psig
10.5 psig
22.5 psig
30 psig
37.5 psig
52.5 psig
(2)
Table 3. Optional Process Connection Adaptors
BAR INPUT
RANGE
Up to 0 to 400
0 to 400 to 0 to 600
0 to 400 to 0 to 600
PSIG INPUT
RANGE
Up to 0 to 5000
0 to 5000 to 0 to 10,000
0 to 5000 to 0 to 10,000
CONNECTION
Size Material
1/2 NPT external or1/2 NPT internal
1/2 NPT internal stainless
1/2 NPT external stainless
steel orstainless
steel
steel
steel
Table 4. Supply Pressure Data
Normal
Output Signal Range
0.2 to 1.0 or 0 and 1.4 (diff gap)
Bar
0.4 to 2.1 or 0 and 2.4 (diff gap)
3 to 15 or 0 and 20 (diff gap) 20 40
Psig
6 to 30 or 0 and 35 (diff gap) 35 40
1. If this pressure is exceeded, control stability may be impaired.
2. If this pressure is exceeded, damage to controller components may result.
Operating
Supply
(1)
Pressure
1.4 2.8
2.4 2.8
Maximum
Pressure
(2)
Limit
5