This instruction manual includes installation, operation,
calibration, maintenance, and parts ordering information for the 3582 Series pneumatic valve positioners,
the Type 3582i electro-pneumatic valve positioner,
and the 3583 Series pneumatic valve stem position
transmitters. Refer to separate instruction manuals for
information on the control valve, actuator, and accessories.
Only personnel qualified through training or experience
should install, operate, or maintain the valve positioner
or valve stem position transmitter. If there are any
questions concerning the instructions in this manual,
contact your Fisher sales office or representative before proceeding.
Description
The 3582 Series pneumatic valve positioners and the
Type 3582i electro-pneumatic valve positioner shown
in figure 1 are used with diaphragm-actuated, slidingstem control valve assemblies. The pneumatic valve
positioners receive a pneumatic input signal from a
control device and modulate the supply pressure to
the control valve actuator. The positioner adjusts the
actuator supply pressure to maintain a valve stem
position proportional to the pneumatic input signal.
Type 3582NS positioners meet typical requirements of
the nuclear power industry. The Type 3582NS
construction includes materials that provide superior
performance at elevated temperature and radiation
levels. The O-rings are EPDM (ethylene propylene)
and the diaphragms are EPDM/Nomex. EPDM
onstrates superior temperature capability and shelf life
over nitrile. The Nomex diaphragm fabric demonstrates improved strength retention at elevated temperature and radiation conditions.
(1)
dem-
Removing and Replacing the Relay23. . . . . . . . . . .
Removing the Type 582i Converter24. . . . . . . . . . .
Reassembling the Type 582i Converter25. . . . . . .
Parts Ordering
Parts Kits
Parts List
In addition, the Type 3582NS positioner is qualified
“commercial grade dedicated” under Fisher’s
10CFR50, Appendix B, quality assurance program.
These can be supplied as 10CFR21 items.
The Type 3582i is an electro-pneumatic valve positioner, consisting of a Type 582i electro-pneumatic converter installed on a Type 3582 pneumatic valve positioner. The Type 3582i valve positioner provides an
accurate valve stem position that is proportional to a
dc current input signal.
The Type 582i electro-pneumatic converter is a modular unit that can be installed at the factory or in the
field. However, do not plan to install a Type 582i converter on an existing positioner until you contact your
Fisher sales office or representative for application
assistance.
The Type 582i converter receives the dc current input
signal and, through a nozzle/flapper arrangement, provides a proportional pneumatic output signal. This
pneumatic output signal provides the input signal to
the pneumatic valve positioner, eliminating the need
for a remote-mounted transducer.
The 3583 Series pneumatic valve stem position transmitters are for use with sliding-stem diaphragm actuators. These units provide an output signal that is directly proportional to the valve stem position.
Refer to the type number description for a detailed
explanation of type numbers.
The following descriptions provide specific information
on the different valve positioner or valve stem position
transmitter constructions. If the type number is not
known, refer to the nameplate on the positioner. For
the location of the nameplate, refer to key 25 in figure
21.
2
1. Use a clean, dry, oil-free air supply with instruments containing EPDM components.
EPDM is subject to degradation when exposed to petroleum-based lubricants.
3582 and 3583 Series
Table 1. Specifications for 3582 Series and Type 3582i Valve Positioners
Input Signal
(1)
,
3582 Series:
J 3 to 15 psig (0.2 to 1.0 bar), J 6 to 30 psig (0.4
to 2.0 bar), or J split range, see table 5
Type 3582i:
4 to 20 mA dc constant current with 30 V dc maximum compliance voltage, can be split range, see
table 5
Equivalent Circuit for Type 3582i
The Type 582i converter equivalent circuit is 120
ohms, shunted by three 5.6-volt zener diodes (see
figure 11)
Output Signal
(1)
Type: Pneumatic pressure as required by actuator
up to 95 percent of maximum supply
Action
(1)
: Field-reversible between J direct and
J reverse within the pneumatic valve positioner
Supply Pressure
(1)
Recommended: 5 psi (0.3 bar) above actuator re-
quirement
Maximum: 50 psig (3.4 bar) or pressure rating of
actuator, whichever is lower
Input Bellows Pressure Rating
(2)
See table 4 for minimum and maximum pressure
ratings (allowable input signal) for each available
range spring
Maximum Steady-State Air Consumption
(1)(3)
For 3582 Series
20 Psig (1.4 bar) Supply:
14.0 scfh (0.38 normal
m3/hr)
30 Psig (2.0 bar) Supply:
18.0 scfh (0.48 normal
m3/hr)
35 Psig (2.4 bar) Supply:
20.0 scfh (0.54 normal
m3/hr)
For Type 3582i Only
20 Psig (1.4 bar) Supply:
17.2 scfh (0.46 normal
m3/hr)
30 Psig (2.0 bar) Supply:
21.4 scfh (0.58 normal
m3/hr)
35 Psig (2.4 bar) Supply:
23.8 scfh (0.64 normal
m3/hr)
Maximum Supply Air Demand
(1)
For 3582 Series and Type 3582i
20 Psig (1.4 bar) Supply:
164.5 scfh (4.7 normal
m3/hr)
30 Psig (2.0 bar) Supply:
248.5 scfh (7.0 normal
m3/hr)
35 Psig (2.4 bar) Supply:
m3/hr)
Performance
For 3582 Series
Independent Linearity
span
Hysteresis
(1)
:
0.5 percent of span
For Type 3582i Only
Independent Linearity
span
Hysteresis
(1)
:
0.6 percent of span
(1)
:
±1 percent of output signal
(1)
:
±2 percent of output signal
Electromagnetic Interference (EMI)
per SAMA Standard PMC 33.1-1978, change in
steady-state deviation is less than ±1% in an electromagnetic field classified as 3-abc with a field
strength of 30 V/m. Positioner is tested with housing cap on and with external field wiring in rigid metal conduit.
For 3582 Series and Type 3582i
Open Loop Gain (Output Signal)
J 100 in the range of 3 to 15 psig (0.2 to 1.0 bar)
J 55 in the range of 6 to 30 psig (0.4 to 2.0 bar)
Operating Influences
(1)
Supply Pressure, For 3582 Series Units: Valve
travel changes less than 0.25 percent per 2 psi
(1.67 percent per bar) change in supply pressure
Supply Pressure, For Type 3582i Units: Valve
travel changes less than 1.5 percent per 2 psi (3.62
percent per bar) change in supply pressure
Operative Temperature Limits
Standard Construction, For 3582 Series and
Type 3582i Units: –40 to +160_F (–40 to +71_C)
Type 3582NS Units: –40 to +180_F (–40 to
+82_C) with EPDM elastomers
High-Temperature Construction, For Types
3582A and C only: 0 to +220_F (–18 to +104_C)
without gauges
Electrical Classification for Type 3582i
Please refer to the Hazardous Area Classifications
Bulletins for specific approvals. Also, refer to the
nameplates shown in figure 2 for the location of positioner or transmitter classification information and
approval descriptions.
Housing Classification for Type 3582i
NEMA 3, IEC 529 IP54: Mount instrument with vent
on the side or bottom if weatherproofing is a concern.
- Continued -
285.5 scfh (8.1 normal
(1)
:
When tested
(1)
:
(1)(2)
3
3582 and 3583 Series
Table 1. Specifications for 3582 Series and Type 3582i Valve Positioners (Continued)
Pressure Gauges
1-1/2 inch (40 mm) diameter with plastic case and
brass connection J triple scale (PSI, MPa, and bar)
Maximum Valve Stem Travel
4-1/8 inches (105 mm); adjustable to obtain lesser
travels with standard input signals
or J dual scale (PSI and kg/cm2)
Characterized Cams
Pressure Connections
See characterized cams section
1/4-inch NPT female
Approximate Weight
Electrical Connection for Type 3582i
1/2-14 NPT conduit connection
1. This term is defined in ISA Standard S51.1-1979.
2. Do not exceed any of the pressure or temperature limits in this instruction manual. Also, any applicable standard or code should not be exceeded.
3. Scfh—Standard cubic feet per hour (60_F and 14.7 psia); normal m3/hr—normal cubic meters per hour (0_C and 1.01325 bar, absolute).
3582 Series Units: 5-1/2 pounds (2.5 kg)
Type 3582i: 8 pounds (3.6 kg)
11B5625-E SHT B / DOC
Type 3582—Pneumatic valve positioner with bypass
and instrument, supply, and output pressure gauges.
Type 3582A—Pneumatic valve positioner without bypass and without pressure gauges.
Type 3582C—Pneumatic valve positioner without bypass and with automotive tire valves instead of pressure gauges.
Type 3582D—Pneumatic valve positioner with bypass
and with automotive tire valves instead of pressure
gauges.
Type 3582G—Pneumatic valve positioner without bypass and with instrument, supply, and output pressure
gauges.
Type 3582NS—Pneumatic valve positioner for nuclear
service applications with or without bypass and with
automotive tire valves instead of pressure gauges.
Type 3582i—Electro-pneumatic valve positioner without bypass; with Type 582i converter; and with: supply
and output pressure gauges, automotive tire valves, or
pipe plugs.
Type 582i—Electro-pneumatic converter with: supply
and output pressure gauges, automotive tire valves, or
pipe plugs. Used for conversion of a 4 to 20 milliampere input signal to a 3 to 15 psig (0.2 to 1.0 bar) input
signal for the pneumatic valve positioner.
Type 3583—Pneumatic valve stem position transmitter with supply and output pressure gauges.
Type 3583C—Similar to the Type 3583 valve stem
position transmitter except with automotive tire valves
in place of pressure gauges.
Specifications
Specifications for the valve positioners are shown in
table 1. Specifications for the valve stem position
transmitters are shown in table 2.
Refer to the unit nameplate to determine the type of
positioner or transmitter, supply pressure, etc. A typical nameplate is shown in figure 2.
4
3582 and 3583 Series
Table 2. Specifications for 3583 Series Valve Stem Position Transmitters
Input Signal
(1)
4-1/8 inches (105 mm) of valve stem travel; adjust-
Reference Accuracy
±1 percent of output signal span
(1)
able to obtain full output signal with lesser stem
travels
Output Signal
(1)
Operating Influence
Output signal changes 0.23 percent per 2 psig (1.67
percent per bar) change in supply pressure
(1)
Type: J 3 to 15 psig (0.2 to 1.0 bar) or J 6 to 30
psig (0.4 to 2.0 bar) pneumatic pressure
Action: Field-reversible between direct and reverse
Operative Ambient Temperature Limits
Standard Construction, 3583 Series: –40 to
Output Bellows Pressure Rating
(2)
See table 4 for minimum and maximum pressure
+160 _F (–40 to +71_C)
High-Temperature Construction, Type 3583C
only: 0 to +220 _F (–18 to +104_C)
ratings (allowable input signal) for each available
range spring
Supply Pressure
(1)
Recommended: 5 psi (0.3 bar) above upper limit of
output signal range
Maximum: 35 psig (2.4 bar) or pressure rating of
connected equipment, whichever is lower
Pressure Connections
Supply and output pressure connections are
1/4-inch NPT female
Maximum Valve Stem Travel
4-1/8 inches (105 mm); adjustable to obtain full output signal with lesser stem travels
Maximum Steady-State Air Consumption
20 Psig (1.4 bar) Supply:
14.0 scfh (0.38 normal
m3/hr)
30 Psig (2.0 bar) Supply:
18.0 scfh (0.48 normal
m3/hr)
35 Psig (2.4 bar) Supply:
20.0 scfh (0.54 normal
m3/hr)
1. This term is defined in ISA Standard S51.1-1979.
2. Do not exceed any of the pressure or temperature limits in this instruction manual. Also, any applicable standard or code should not be exceeded.
3. Scfh—Standard cubic feet per hour (60_F and 14.7 psia); normal m3/hr—normal cubic meters per hour (0_C and 1.01325 bar, absolute).
(1)(3)
Cam
Linear
Approximate Weight
5-1/2 pounds (2.5 kg)
(1)(2)
Installation
Note
All valve positioners and valve stem
position transmitters are shipped with
foam rubber packing material inside the
case. Remove the cover (key 33, figure
21) and the packing material before attempting to operate the unit. Make sure
all vent openings are clear before installation of the unit and that they remain
clear during use.
Typically, the positioner or transmitter is ordered with
the actuator. If so, the factory mounts the valve positioner or valve stem position transmitter and connects
the valve positioner output to the actuator. If a Type
67AFR filter-regulator is specified, it may be integrally
mounted to the valve positioner or valve stem position
transmitter, except for the Type 3582NS positioner.
For the Type 3582NS, the Type 67AFR is separately
mounted, not integrally mounted to the positioner.
Note
In some cases, alignment and calibra-
tion of the valve positioner or valve
stem position transmitter at the factory
may not be possible, and field align-
ment and calibration is required. Before
putting the valve positioner or valve
stem position transmitter into service,
check the operation of the unit to be
sure it is calibrated. If the valve posi-
tioner or valve stem position transmitter
requires alignment or calibration, refer
to the appropriate calibration instruc-
tions in this manual.
If the valve positioner or valve stem position transmitter is ordered separately, disconnected, or removed
from the actuator, refer to the appropriate sections of
this manual for installation information.
5
3582 and 3583 Series
41B8569-C SHT 1 AND 2 / DOC
Mounting
Key numbers used in this procedure are shown in figure 3 except where indicated.
1. Figure 3 shows the various mounting parts required
for mounting on Fisher actuators. Mounting parts for
Fisher actuators that require spacers have the spacers
(key 50) included. Type 657 and 667 actuators, sizes
70 through 100, with or without a side-mounted handwheel, use spacers (keys 97 and 102) between the
stem connector and the connector arm (key 48). On all
other actuators that use spacers, place the spacers
(key 50) between the mounting plate (key 63) and the
actuator mounting boss.
6
Figure 3. Mounting Assembly
When mounting the valve positioner or valve stem
position transmitter on an actuator by another
manufacturer, provide spacers, if necessary, by cutting sections from 1/2- or 3/8-inch pipe so that the ‘‘X’’
dimension matches the value given in figure 6.
2. As shown in figures 3 and 4, attach the connector
arm (key 48) to the stem connector so that the connector arm extends through the yoke legs on the side
of the lower mounting boss.
3. Attach the valve positioner or valve stem position
transmitter to the mounting plate (key 63) using the
holes shown in figure 5.
4. Mount the Type 67AFR regulator:
3582 and 3583 Series
TYPE
SIZE
POSITION
()
TYPE
SIZE
POSITION
()
SideMounted
SideMounted
Table 3. 3582 and 3583 Series Mounting Information
ACTUATOR
TYPE
513 & 513R20
65630
657-4 Without
Side-Mounted
Handwheel
657-4 With
Side-Mounted
Handwheel
657-8
667-4 Without
Side-Mounted
Handwheel
1. The indicated set number should be considered a reference point only, due to the variables related to making up the stem connection.
2. Normal position is shown in figure 4.
3. Travel pin position for Type 657 is normal.
4. Travel pin position for Type 667 is normal.
ACTUATOR
SIZE
32
40
60
7041023Inverted702
70
87
30
34
40
40
46
46
47
47
60
70
70
87
MAXIMUM
TRAVEL
Inchmm
3/4
3/41919
2
3-1/2
4
44102
2-1/8
2-1/8
3-1/8
3-1/2
3-1/8
4-1/8
3-1/8
4-1/8
4-1/8
4-1/8
44102
51
89
102
102
54
54
79
89
79
105
79
105
105
105
102
MOUNTING
HOLES
SET NO.
(1)
2
2
4
4
4
2
1
3
3
3
3
2
2
2
1
4
2
1
1
TRAVEL PIN
POSITION
(2)
Normal
Normal
Inverted
Inverted
Inverted
Inverted
Inverted
Normal
Normal
Normal
Normal
Normal
Normal
Inverted
Inverted
Inverted
Inverted
Normal
Normal
ACTUATOR
TYPE
657 & 667
Without
Side-Mounted
Handwheel
657 & 667
With
Side-Mounted
Handwheel
ACTUATOR
SIZE
30
34
40
45
45
50
60
2-1/16–3
3-1/16–4
80376
872
2-1/16–3
3-1/16–4
1004102
34
40
45
50
60
70
80
873
3-1/16–47678–10222
MAXIMUM
TRAVEL
Inchmm
3/4
1-1/8
1-1/2
3/4
2
2
2
3/4
1-1/2
2
2
2
4
3
19
19
38
19
51
51
51
51
52–76
78–102
51
52–76
78–102
19
38
51
51
51
102
76
MOUNTING
HOLES
SET NO.
657667
3
3
2
1
1
1
1
2
3
3
22Normal
2
2
3
44Inverted
2
1
1
4
3
2
2
TRAVEL PIN
(1)
POSITION
4
2
3
4
1
2
2
1
2
1
2
2
1
2
2
4
1
1
2
2
2
1
Normal
Normal
Normal
Inverted
Normal
Normal
Normal
Normal
Normal
Inverted
Normal
Normal
Inverted
Normal
Normal
Normal
Inverted
Inverted
Inverted
Normal
Normal
Inverted
(2)
(3)
(4)
(4)
(4)
(4)
CV1768-C
A1397–2/IL
Figure 4. Isometric View Showing Motion Feedback
Arrangement and Typical Stem Connection
3582 Series valve positioners (except Type
3582NS) and 3583 Series valve stem position
transmitters, mount the regulator on the integral boss
on the bypass block.
Type 3582NS valve positioners, use the
mounting plate with provision for separately mounting
the Type 67AFR regulator. Separately mount the positioner and the regulator on the mounting plate.
Type 3582i valve positioners, mount the regu-
lator on the integral boss that is part of the Type 582i
converter housing.
5. As shown in figure 5, the mounting bracket has four
sets of holes for mounting the assembly to the actuator. Refer to table 3 to determine which set of mounting holes to use, then attach the assembly to the lower
mounting pad on the actuator.
CAUTION
To avoid equipment damage, be certain
the connector arm clears the valve positioner or valve stem position transmitter
case as the actuator moves through its
complete stroke.
7
3582 and 3583 Series
SET NO. 1
SET NO. 2
SET NO. 3
HOLES FOR
MOUNTING REGULATOR
HOLES FOR MOUNTING
PLATE TO ACTUATOR
HOLES FOR MOUNTING
POSITIONER TO PLATE
BF2635-B/DOC
Figure 5. Mounting Plates Used with 3582 Series Valve Positioners and 3583 Series Valve Stem Position Transmitters
6. Position the actuator to its mid-travel position using
a handwheel or manual loading regulator.
11. Check the travel pin setting using the following
procedures:
HOLES FOR MOUNTING
PLATE TO ACTUATOR
HOLES FOR MOUNTING
POSITIONER TO PLATE
SET NO. 4
7. Slip the round end of the travel pin (key 60) into the
rotary shaft arm (key 2) slot as shown in figure 4.
8. Slide the square end of the travel pin into the pin
holder and pin lock (keys 61 and 59). Place the pin
lock and holder into the slot in the connector arm (key
48). Screw the cap nut (key 62) onto the pin lock (key
59), but do not tighten.
9. With the actuator at its mid-travel position, lift the
rotary shaft arm so that the 0-degree index marks on
the rotary shaft arm are aligned with the case index
marks as shown in figure 7.
For standard travel pin setting (that is, with the
travel pin setting equal to total actuator travel). Stroke
the actuator to each end of its travel. At each end of
travel, the 30-degree index marks on the rotary shaft
arm should align with the case index marks. If the index marks are not in line, loosen the cap nut (key 62)
and slide the travel pin (key 60) in the rotary shaft arm
slot until the 30-degree index marks align with the
case index marks. Be sure the travel pin remains perpendicular to the connector arm. After making this adjustment, tighten the cap nut and re-check the arm at
the mid-travel position. If the 0-degree index marks do
CAUTION
not align, repeat this procedure.
Never set the travel pin at a setting that
is less than the actual actuator stroke.
Setting the travel pin at a setting that is
less than the actual actuator stroke will
cause the cam to rotate more than 60
degrees, causing damage to the cam or
other parts.
10. Position the travel pin so that it is perpendicular to
the connector arm and aligns with the correct actuator
stem travel index on the rotary shaft arm. Tighten the
cap nut (key 62 in figure 4).
8
For special travel pin setting (that is, with the
travel pin setting greater than total actuator travel).
Check the index marks using a procedure similar to
the standard settings procedure. The arm will not rotate a full 60 degrees as the actuator is stroked, and
the 30-degree index marks on the cam will be short of
aligning with the case index marks. If necessary, adjust the travel pin position so that the 30-degree marks
are the same distance from the respective case index
mark at each end of actuator travel.
3582 and 3583 Series
X
30_ MAX.
30_ MAX.
11B6520-C/DOC
Figure 6. Spacing for Mounting on Other Than Fisher Actuators
Changing Cam Position
Refer to figure 21 for a typical cam illustration and key
number locations.
STEM
TRAVEL
1-1/8 or less
1-1/2
2
2-1/2
3
3-1/2
4
29 or less
38
51
64
76
89
102
3/8-Inch
(9.5 mm) Stem
3.19
3.56
4.00
4.44
4.88
5.31
5.75
Millimeters
81
90
102
113
124
135
146
1/2-Inch
(12.7 mm) Stem
Inches
3.44
3.81
4.25
4.69
5.12
5.56
6.00
87
97
108
119
130
141
152
X
3/4-Inch
(19.1 mm) Stem
3.94
4.31
4.75
5.19
5.62
6.06
6.50
100
109
121
132
143
154
165
Note
D For Valve Positioners: The small
arrow on the cam must point in the direction of stem movement with increasing actuator diaphragm pressure.
D For Valve Stem Position Transmitters: If the arrow on the cam points up
toward the nozzle, output pressure increases with downward stem movement. If the arrow points down, output
pressure decreases with downward
stem movement.
If the arrow is pointing in the wrong direction, use the following procedure to
remove, reverse, and re-install the cam.
When mounting a valve positioner or valve stem position transmitter, check to see if the correct cam (key 4)
and cam position has been selected. To change the
cam or cam position, unhook the extension spring (key
38), and remove the cam bolt and locking nut (keys 6
and 45). Remove the cam and spring retainer bracket
(key 43).
To install the cam, screw the locking nut all the way
onto the cam bolt. Attach the cam and spring retainer
bracket to the shaft assembly with the cam bolt. Tighten the bolt to secure the cam. Then, tighten the locking nut against the spring retainer bracket. Hook the
spring into the spring retainer bracket.
70CA0750-C
A2452-2/IL
Figure 7. Rotary Shaft Arm and Case Index Marks
Details on cam characteristics can be found in the
cam information portion of the operating information
section.
Pressure Connections
WARNING
Valve positioners and valve stem position transmitters are capable of providing full supply pressure to connected
equipment. To avoid personal injury and
equipment damage, make sure the supply pressure never exceeds the maximum safe working pressure of any connected equipment.
9
3582 and 3583 Series
7.19
(182.6)
9.88
(251.0)
10.50
(266.7)
11.44
(290.6)
5.56
(141.2)
4.69
(119.1)
.31
(7.9)
5.56
(141.2)
5.00
(127.0)
.34 (8.6) ∅ HOLES
SPACED .69 (17.5) APART
.34 (8.6) ∅ HOLES
SPACED .69 (17.5) APART
.31
(7.9)
5.50
(139.7)
5.50
(139.7)
2.25
(57.1)
2.25
(51.1)
.50
(12.7)
.50
(12.7)
9.94
(252.5)
11B6519-F
11B6520-E
C0775/IL
(DIMENSIONS FOR TYPES 3582A, C, D, G, AND NS ARE THE SAME)
Figure 8. Typical Dimensions and Connections
Pressure connections are shown in figure 8. All pressure connections are 1/4-inch NPT female. Use
3/8-inch tubing for all pressure connections. After
making pressure connections, turn on the supply pressure and check all connections for leaks.
Supply Connection
WARNING
Personal injury or property damage may
occur from an uncontrolled process if
the supply medium is not clean, dry, oilfree air, or non-corrosive gas. Industry
TYPE 3582
INCH
(mm)
instrument air quality standards describe acceptable dirt, oil, and moisture
content. Due to the variability in nature
of the problems these influences can
have on pneumatic equipment, Fisher
Controls has no technical basis to recommend the level of filtration equipment
required to prevent performance degradation of pneumatic equipment. A filter
or filter regulator capable of removing
particles 40 microns in diameter should
suffice for most applications. Use of
suitable filtration equipment and the establishment of a maintenance cycle to
monitor its operation is recommended.
10
12B8045-A
A6077–1/IL
3582 and 3583 Series
STEM PROVIDED
WHEN GAUGE IS
SPECIFIED
12B8046-A
A6078–1/IL
Figure 9. Diagnostic Connections
Supply pressure must be clean, dry, oil-free
(2)
air or
noncorrosive gas. Use a Fisher Type 67AFR Filter
Regulator, or equivalent, to filter and regulate supply
air. Except for the Type 3582NS, the filter regulator
can be mounted on the positioner. For the Type
3582NS the regulator can be mounted on the mounting plate with the positioner but not on the postioner.
The supply pressure should be high enough to permit
setting the regulator 5 psi (0.3 bar) above the upper
limit of the appropriate pressure range, for example:
20 psig (1.4 bar) for a 3 to 15 psig (0.2 to 1.0 bar)
range. However, do not exceed the maximum allowable supply pressure of 50 psig (3.4 bar) nor the pressure rating of any connected equipment.
Connect the nearest suitable supply source to the
1/4-inch NPT IN connection on the filter regulator (if
furnished) or to the 1/4-inch NPT SUPPLY connection
on the positioner block assembly.
Output Connection
A factory mounted valve positioner has the valve positioner output piped to the supply connection on the
actuator. If mounting the valve positioner in the field,
connect 3/8-inch tubing between the 1/4-inch NPT
valve positioner connection marked OUTPUT and the
actuator supply pressure connection. Connect the
valve stem position transmitter connection marked
OUTPUT to an instrument that indicates valve stem
position.
Instrument Connection
For a 3582 Series pneumatic valve positioner connect
3/8-inch tubing from the control device to the 1/4-inch
NPT INSTRUMENT connection. If the control device
is mounted on the control valve assembly by the factory, this connection is made.
The Type 3582i electro-pneumatic valve positioner
requires a 4 to 20 milliampere dc current input signal
from the control device. A 1/2-inch NPT conduit connection is provided for properly wiring electrical installations. For more information, see the electrical connections section.
Diagnostic Connections
To support diagnostic testing of valve/actuator/positioner/accessory packages, special connectors and
hardware are available. The hardware used includes
1/8-inch NPT connector bodies and body protectors. If
the diagnostic connectors are ordered for a positioner
with gauges, 1/8-inch stems are also included.
Install the connectors on the 3582 block assembly or
Type 582i housing as shown in figure 9. Before installing the connectors on the positioner, apply sealant to
the threads. Sealant is provided with the diagnostic
connections and hardware.
2. Use a clean, dry, oil-free air supply with instruments containing EPDM components.
EPDM is subject to degradation when exposed to petroleum-based lubricants.
11
3582 and 3583 Series
Vent
WARNING
If a flammable, toxic, or reactive gas is
to be used as the supply pressure medium, personal injury or property damage could result from fire or explosion
of accumulated gas or from contact with
toxic, or reactive gas. The positioner/actuator assembly does not form a gastight seal, and when the assembly is enclosed, a remote vent line, adequate
ventilation, and necessary safety measures should be used. A remote vent
pipe alone cannot be relied upon to remove all hazardous gas. Vent line piping should comply with local and regional codes and should be as short as
possible with adequate inside diameter
and few bends to reduce case pressure
buildup.
A3875*/IL
Figure 10. Typical Field Wiring Diagram
Electrical Connections for Type 3582i
Valve Positioner
CAUTION
When installing a remote vent pipe, take
care not to overtighten the pipe in the
vent connection. Excessive torque will
damage the threads in the connection.
The vent opening at the back of the case marked
VENT should be left open to prevent pressure buildup
inside the case and to provide a drain hole for any
moisture that might collect inside the case. A screen is
normally installed in this opening to prevent blockage
from debris or insects.
If a remote vent is required, the vent line must be as
short as possible with a minimum number of bends
and elbows. The vent connection is 3/8-inch NPT female. To connect a remote vent, press out the screen
and use 3/8-inch tubing to provide a remote vent. The
582i has a 1/4-inch NPT female vent connection.
WARNING
For explosion-proof applications, disconnect power before removing the
converter housing cap.
For explosion-proof applications, install
rigid metal conduit and a conduit seal
no more than 18 inches (457 mm) from
the converter. Personal injury or property damage might result from explosion if
the seal is not installed.
For intrinsically safe installations, refer
to the loop schematics at the end of this
manual, factory drawings, or to instructions provided by the barrier manufacturer for proper wiring and installation.
Use the 1/2-inch NPT conduit connection on the Type
582i converter housing for installation of field wiring.
For Class I, Division I explosion-proof applications,
install rigid metal conduit and a seal no more than 18
inches (457 mm) from the converter. Also, install conduit according to local and national electrical codes
which apply to the application.
Also, be certain that the exhaust holes in the relay
(key 32 in figure 21) are kept open.
12
Refer to figures 10, 11 and 12 when connecting field
wiring from the control device to the converter. Connect the positive wire from the control device to the
Loading...
+ 28 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.