Fisher 2516, 2516F Instruction Manual

Instruction Manual
Form 1041 November 2005
2506 Series Receiver/Controllers
2506 Series Multi-TrolR Receiver/Controllers (Type 2506, 2516, 2516F)
Contents
Introduction 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Specifications 2. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Educational Services 4. . . . . . . . . . . . . . . . . . . . . .
Installation 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mounting the Controller 5. . . . . . . . . . . . . . . . . . . .
Actuator Yoke Mounting 5. . . . . . . . . . . . . . . . . .
Wall Mounting 5. . . . . . . . . . . . . . . . . . . . . . . . . . .
Actuator Diaphragm Case Mounting 6. . . . . . . .
Pipestand Mounting 7. . . . . . . . . . . . . . . . . . . . . .
2500 Series Controller/Transmitter
and 2506 Series Receiver/Controller
Mounting 7. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connections 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Supply Connection 8. . . . . . . . . . . . . . . . . . . . . . .
Output Connections 9. . . . . . . . . . . . . . . . . . . . . .
Instrument Connection 10. . . . . . . . . . . . . . . . . .
Vents 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Remote Set Point Connection 11. . . . . . . . . . . .
Startup 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Adjustments 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Set Point Adjustment 12. . . . . . . . . . . . . . . . . . . . .
Remote Set Point Adjustment 12. . . . . . . . . . . . . .
Proportional Band Adjustment 12. . . . . . . . . . . . .
Reset Adjustment
(Type 2516 Receiver/Controller Only) 13. . . .
Anti-Reset Windup Valve Adjustment
(Type 2516F Receiver/Controller Only) 13. . .
Calibration 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Principle of Operation 14. . . . . . . . . . . . . . . . . . . . . .
Type 2506 Receiver/Controllers 15. . . . . . . . . . .
Types 2516, 2516F Receiver/Controllers 15. . . .
Maintenance 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Changing Controller Action 16. . . . . . . . . . . . . . . .
Troubleshooting 17. . . . . . . . . . . . . . . . . . . . . . . . .
Testing Relay Deadband 17. . . . . . . . . . . . . . . . . .
Replacing Receiver/Controller Parts 17. . . . . . . .
Bellows Replacement 17. . . . . . . . . . . . . . . . . . .
Changing the Relay 18. . . . . . . . . . . . . . . . . . . . .
Changing Proportional or Reset Valve 19. . . . .
Parts Ordering 19. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parts Kits 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
W4687 / IL
Figure 1. Type 2506 Multi-TrolR Receiver-Controller
W4688 / IL
Figure 2. Type 2516 Multi-TrolR Receiver-Controller
www.Fisher.com
D200129X012
2506 Series Receiver/Controllers
Instruction Manual
Form 1041
November 2005
Contents (Continued)
Parts List 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Receiver/Controller Common Parts 19. . . . . . . . .
Anti-Reset Windup Valve for
Type 2516F Only 22. . . . . . . . . . . . . . . . . . . . . .
Type 2516F Reset and Anti-Reset Windup
Valve Assembly 22. . . . . . . . . . . . . . . . . . . . . . .
Mounting Parts 23. . . . . . . . . . . . . . . . . . . . . . . . . .
Yoke Mounting 23. . . . . . . . . . . . . . . . . . . . . . . . .
Wall Mounting 23. . . . . . . . . . . . . . . . . . . . . . . . . .
Case Mounting 23. . . . . . . . . . . . . . . . . . . . . . . . .
Pipestand Mounting 24. . . . . . . . . . . . . . . . . . . . .
2500 Series Controller/Transmitter
and 2506 Series Receiver/Controller
Mounting 24. . . . . . . . . . . . . . . . . . . . . . . . . . .
Introduction
Scope of Manual
This manual provides installation, startup, calibration, maintenance, and parts ordering information for 2506 Series Multi-Trol receiver/controllers. Figure 1 shows a Type 2506 receiver/controller. Figure 2 shows a Type 2516 receiver/controller.
A 2506 Series receiver/controller is often used with a 2502 Series Level-Trol® controller/transmitter. For information about 2502 Series controller/transmitters or associated equipment such as pressure regulators, sensors, accessories, or related control devices, see the appropriate instruction manual, or contact your Fisher® sales office.
No person may install, operate, or maintain a 2506 Series Multi-Trol receiver/controller without first D being fully trained and qualified in valve, actuator and accessory installation, operation and maintenance and D carefully reading and understanding the contents of the manual. If you have any questions about these instructions, contact your Fisher sales office.
R
Description
See table 2.
The receiver/controllers described in this manual provide:
D Proportional-only control: Type 2506 (with snap
action: Type 2506S)
D Proportional-plus-reset control (Type 2516)
D Proportional-plus-reset-plus-anti-reset windup
control (Type 2516F)
See figures 9, 10, and 11.
The receiver/controller takes a pneumatic input signal from either a 2500 Series controller/transmitter or a control device. The unit then provides a pneumatic output signal that operates a final control element.
When a Type 2506 receiver/controller is used to provide proportional-only control, the pneumatic output signal from the unit can also be piped to a remote receiving indicator or recording device. This provides a visual indication of receiver/controller action.
The INCREASE OUTPUT PRESSURE adjustment is used to increase or decrease the output pressure in relationship to the input pressure. Changing this adjustment changes the position of the nozzle in relationship to the beam/flapper assembly. In turn, the amount of supply pressure released by the relay is changed and the pneumatic output signal that operates a final control element is affected.
If a remote set point signal is used, it is piped to the remote set point connection and into remote set point bellows. The remote signal expands the bellows and moves the beam/flapper assembly. This affects the controller output in the same way a change in the INCREASE OUTPUT PRESSURE adjustment affects the output.
Specifications
Specifications are shown in table 1.
2
Instruction Manual
Form 1041 November 2005
2506 Series Receiver/Controllers
Table 1. Specifications
Available Configurations
For additional information, refer to table 2
Type 2506: A receiver/controller
(1)
that is set for either proportional or snap action (S) control or for either direct or reverse (R) action
Type 2516: A Type 2506 that also provides proportional-plus-reset control
Type 2516F: A Type 2516 that also provides anti-reset windup control
Input Signal Range
(2)
From a transmitter or control device, a signal of
0.2 to 1.0 bar (3 to 15 psig) or 0.4 to 2.0 bar (6 to 30 psig) is required depending on receiver/controller range
Refer to the receiver/controller nameplate for specific range.
Output Signal Range
(2,3)
See table 3
Proportional Band
(2)
Reset
(2)
, and Anti-Reset
Windup
See table 2 and the Changing Controller Action procedure
Performance
Hysteresis: 0.6 percent of output pressure
change at 100 percent of proportional band for Type 2506 proportional receiver/controllers only
Standard Supply and Output Pressure Gauge Indications
See table 3
Standard Tubing Connections
All connections are 1/4-inch NPT female
Hazardous Area Classification
2506 Series receiver/controllers comply with the requirements of ATEX Group II Category 2 Gas and Dust
Output Action
Direct Action: An increasing fluid, interface level,
or density increases output pressure or,
Reverse Action: An increasing fluid, interface level, or density decreases output pressure
Remote Set Point Signal Range
From a control device, provide a remote set point signal that is 0.2 to 1.0 bar (3 to 15 psig) or 0.4 to
2.0 bar (6 to 30 psig) that matches the receiver/controller input signal range
Operative Ambient Temperature Limits
Standard: 40 to 71°C (40 to 160°F)
High Temperature: 18 to 104°C (0 to 220°F)
Approximate Weight
4.54 kg (10 Pounds)
Declaration of SEP
(4)
Fisher Controls International LLC declares this
Supply Pressure
(2,4)
Normal Operating Pressure: See table 3
Maximum Pressure to Prevent Internal Part Rupture: 3.4 bar (50 psig)
Steady State Air Consumption
(3)
See table 3
1. Receiver/controllers are field adjustable between direct or reverse action. If the receiver/controller is set for reverse action at the factory, an R suffix will appear in the type number. Receiver/controllers are field-adjustable between proportional and snap action. If the receiver/controller is set for snap action at the factory, an S suffix appears in the type number.
2. These terms are defined in ISA Standard S51.1.
3. Normal m3/hr at 0°C, 1.01325 bar absolute (Scfh at 60°F, 14.7 psia).
4. The pressure/temperature limits in this document, and any applicable standard or code limitation should not be exceeded.
product to be in compliance with Article 3 paragraph 3 of the Pressure Equipment Directive (PED) 97 / 23 / EC. It was designed and manufactured in accordance with Sound Engineering Practice (SEP) and cannot bear the CE marking related to PED compliance.
However, the product may bear the CE marking to indicate compliance with other applicable EC Directives.
3
2506 Series Receiver/Controllers
Instruction Manual
Form 1041
November 2005
Control Mode
Proportional control (Type 2506)
Snap action control (Type 2506S)
Proportional-plus-reset control (Type 2516)
Proportional-plus-reset with differential relief control (Type 2516F)
1. Proportional control is continuously active between 0 and 100 percent of the transmitter signal span. Differential gap provides snap action between 0 and 100 percent of the transmitter signal. Do not use reset controllers in snap action.
(1)
Proportional Band: Adjustable from 0 to 100% of transmitter signal.
Snap Action: Control output is at 0 or 100% of input supply pressure. Switching depends on position of sensor and is adjustable.
Proportional Band: Adjustable from 0 to 200% of transmitter signal. Recommended setting is from 20 to 200%. Reset: Adjustable form 0.01 to 74 minute per repeat with standard reset valve setting.
Proportional Band: Adjustable from 0 to 200% of transmitter signal. Recommended setting is from 20 to 200%. Reset: Adjustable from 0.01 to 74 minute per repeat with standard reset valve setting. Differential Relief: Provides relief when output pressure falls or when output pressure rises depending on valve adjustment.
Action (Full Output Change) Output Signal
0.2 to 1.0 bar (3 to 15 psig) or
0.4 to 2.0 bar (6 to 30 psig)
0 to 1.4 bar (0 to 20 psig) or 0 to 2.4 bar (0 to 35 psig)
0.2 to 1.0 bar (3 to 15 psig) or
0.4 to 2.0 bar (6 to 30 psig)
Table 3. Supply Pressure Data
Table 2. Additional Information
OUTPUT SIGNAL
RANGE
0.2 to 1.0 bar (3 to 15 psig) 0 to 30 psig 1.4 20 4.2 scfh
0.4 to 2.0 bar (6 to 30 psig) 0 to 60 psig 2.4 35 7 scfh
1. Consult your Fisher sales office for gauges calibrated in other units of measurement.
2. Control and stability may be impaired if this pressure is exceeded.
3. At zero or maximum proportional band or span setting.
4. At setting in middle of proportional band or span range.
5. If air consumption is desired in normal m3/hr at 0°C and 1.01325 bar, multiply scfh by 0.0268.
STANDARD SUPPLY
AND OUTPUT
PRESSURE GAUGE
INDICATIONS
(1)
NORMAL
OPERATING
SUPPLY
PRESSURE
Bar Psig Minimum
(2)
AIR CONSUMPTION AT
NORMAL OPERATING
SUPPLY PRESSURE
(3)
(5)
(5)
Maximum
27 scfh
42 scfh
(4)
(5)
(5)
Educational Services
For information on available courses for Type 2506 Series receiver/controllers as well as a variety of other products, contact:
Emerson Process Management Educational Services, Registration P.O. Box 190; 301 S. 1st Ave. Marshalltown, IA 501582823 Phone: 8003388158 or Phone: 6417543771 FAX: 6417543431 e-mail: education@emersonprocess.com
Note
Neither EmersonR, Emerson Process Management, Fisher, nor any of their affiliated entities assumes responsibility for the selection, use, and maintenance of any product. Responsibility for the selection, use, and maintenance of any product remains with the purchaser and end-user.
Installation
WARNING
To avoid personal injury or property damage resulting from the sudden release of pressure:
D Always wear protective clothing, gloves, and eyewear when performing any installation procedures to avoid personal injury.
D Check with your process or safety engineer for any additional measures that must be taken to protect against process media.
D If installing into an existing application, also refer to the WARNING at the beginning of the Maintenance section in this instruction manual.
4
Instruction Manual
Form 1041 November 2005
2506 Series Receiver/Controllers
235 (9.25)
171 (6.76)
232 (9.12)
FRONT VIEW
AD4913-H A3844-1 / IL
BOTTOM VIEW
Figure 3. Dimensions and Location of Connections
Mounting the Controller
Note
If a separate receiver/controller unit has been ordered for field installation with an existing valve/actuator assembly or 2500 Series controller/transmitter, additional mounting parts may be required. Find the mounting description in the parts list at the end of this manual. Then, order any additional parts.
Figures 3 through 8 show dimensions and connection locations used when you install a receiver/controller.
BELLOWS VENT OR REMOTE SET POINT CONNECTION
OUTPUT CONNECTION (MARKED DIAPHRAGM)
70 (2.75)
44 (1.75)
SUPPLY CONNECTION
57 (2.25)
70 (2.75)
REAR VIEW
MOUNTING HOLES (2 PLACES) 5/16-18 UNC
41 (1.62)
INSTRUMENT CONNECTION
CASE VENT
TAPPED VENT FOR VENT LINE (OPTIONAL)
mm
(INCH)
2. Place the two cap screws (key 48) through the mounting plate from “back to front”. Engage the cap screw threads in the mounting holes in the receiver/controller case and tighten the cap screws to attach the mounting plate to the back of the receiver/controller.
3. Place cap screws (key 39) through the yoke mounting holes in the mounting plate from “front to back”. Place a spacer (key 174) over the threads of the cap screws extending from the mounting plate to properly separate the mounting plate and the lower yoke boss of the actuator (figure 5).
4. Attach the mounting plate with receiver/controller to the lower yoke boss of the actuator yoke. Be sure the spacers support the mounting plate. Be sure the receiver/controller is parallel with the actuator yoke and then tighten the cap screws into the yoke boss.
Actuator Yoke Mounting
See figure 4 for a typical mounting plate. Key numbers are shown in figure 5.
1. Locate the mounting plate (key 164, figure 5). Select appropriate mounting holes in the mounting plate for the receiver/controller. Then, align the mounting holes in the mounting plate with the mounting holes in the receiver/controller case.
5. If supply pressure is piped through a filter/regulator, bolt the regulator directly to the upper yoke boss using the cap screws (key 85). Provide appropriate piping from the filter/regulator output connection to the receiver/controller supply connection.
Wall Mounting
See figure 6 for key number locations. The mounting plate is shown in figure 5.
5
2506 Series Receiver/Controllers
83
13
8 HOLES 11/16 DIAMETERS (17)
(0.50)
35 (1.38)
(3.25)
57 (2.25)
38 (1.50)
17 (0.69)
13 (0.50)
14 (0.58)
17 (0.69 )
102 (4.00)
MOUNTING BRACKET (KEY 164)
Instruction Manual
November 2005
121 (4.75)
CAP HEAD SCREW (KEY 39)
CAP HEAD SCREW (KEY 48)
Form 1041
IC2218-E / IL
14 (0.56)
mm
(INCH)
Figure 4. Mounting Plate for Yoke Mounting, Wall Mounting
SPACER (KEY 174)
CAP SCREW AND LOCKWASHER (KEYS 39 AND 83)
38b39604-A / IL AD44913-H A3848-1 / IL
REGULATOR OUTPUT (SUPPLY CONNECTION ON OPPOSITE SIDE)
MOUNTING PLATE (KEY 164)
CAP HEAD SCREW (KEY 48)
Figure 5. Yoke Mounting
MOUNTING PLATE (KEY 164)
194 (7.62)
SPACER (KEY 78)
CAP SCREW AND LOCKWASHER (KEYS 39 AND 83)
SPACER (KEY 174)
AD4913-H A3846-1 / IL
86 (3.38)
mm
(INCH)
Figure 7. Case Mounting
1. Install lock washers (key 83) on the cap screws (key 39). Then, insert the cap screws through the mounting plate from “back to front”. Place a spacer (key 174) over the threads of each cap screw as it extends from the mounting plate. The spacers are required to properly separate the receiver/controller from the mounting plate. Then, thread the cap screws into the mounting holes in the receiver/controller case and tighten.
2. Install lock washers (key 83) on the cap screws (key 48). Then, insert the cap screws through the mounting plate from ‘‘front to back’’. Place a spacer (key 174) over the threads of each cap screw as it extends from the mounting plate. The spacers are required to properly separate the mounting plate from the wall mounting position. Then, thread the cap screws into holes prepared at the wall mounting position and tighten.
3. Provide appropriate piping from the filter/regulator output connection to the receiver/controller supply connection.
Actuator Diaphragm Case Mounting
To mount a receiver/controller to the diaphragm casing of a standard Fisher diaphragm actuator, remove two hex nuts and hex head cap screws securing the upper and lower diaphragm casings. If necessary, refer to the appropriate actuator instruction manual to locate the hex head cap screws and nuts.
See figure 7 for key number locations.
AD4913-H A3847-1 / IL
SIDE VIEW
Figure 6. Wall Mounting
6
mm
(INCH)
1. Locate the receiver/controller mounting holes in mounting bracket (key 164, figure 7).
2. Place the two cap screws (key 48) through the receiver/controller mounting plate holes from ‘‘back
Instruction Manual
Form 1041 November 2005
2506 Series Receiver/Controllers
to front’’. Engage the threads in the receiver/controller mounting holes and tighten the cap screws to attach the mounting plate to the back of the receiver/controller.
3. Locate the receiver/controller mounting position on the horizontal edge of the diaphragm case. A typical Fisher diaphragm actuator features upper and lower diaphragm casings held together with hex head cap screws and hex nuts. Remove the hex nuts from two hex head cap screws joining the upper and lower casing. Then, remove the cap screws.
4. Place the mounting bracket over the empty casing holes. Insert the casing cap screws through the mounting bracket, upper casing, and lower casing. Add the nuts and tighten to secure the mounting bracket with receiver/controller to the casing.
5. If supply pressure is piped through a filter/regulator, the regulator may be attached in one of two locations:
D Attach the regulator directly to the upper yoke boss using the cap screws (key 85) for yoke mounting.
D Attach the regulator to the casing using a mounting bracket (key 177). The mounting bracket for the regulator is the same as the mounting bracket for the receiver/controller. Follow steps 1 through 4 to mount the regulator.
MOUNTING PLATE
2
NOTES:
1
PIPE CLAMP INCLUDES NUTS FILTER/REGULATOR MOUNTING AREA
2
AD4913-H A3845-1 / IL
(KEY 164)
SPACE SPOOL (KEY 78)
157 (61.9)
Figure 8. Pipestand Mounting
CAP SCREW AND LOCKWASHER (KEYS 39 AND 83)
PIPE CLAMP (KEY 175)
51 j PIPE (2.00)
mm
(INCH)
3. Engage the cap screw threads in the mounting holes in the receiver/controller case and tighten the cap screws to attach the mounting plate to the back of the receiver/controller.
4. Attach the mounting plate with receiver/controller to a 2-inch (nominal) pipe with pipe clamps (key
175). Each pipe clamp includes two nuts. Tighten clamp nuts.
5. If supply pressure is piped through a filter/regulator, the regulator may be attached to the mounting plate using cap screws (key 85), lock washers (key 84), and hex nuts (key 40).
1
6. Connect the filter/regulator output connection to the receiver/controller supply connection.
Pipestand Mounting
See figure 8 for key number locations.
1. Locate the mounting plate (key 164). Select appropriate mounting holes in the mounting plate for
the receiver/controller. Then, align the mounting holes in the mounting plate with the mounting holes in the receiver/controller case.
2. Place the two cap screws (key 48) through the mounting plate from ‘‘back to front’’. Place a spacer (key 174) over the threads of each cap screw as it extends from the mounting plate. The spacers are required to properly separate the receiver/controller from the mounting plate.
6. Provide appropriate piping from the filter/regulator output connection to the receiver/controller supply connection.
2500 Series Controller/Transmitter and 2506 Series Receiver/Controller Mounting
If the controller/transmitter and receiver/controller are ordered simultaneously, the factory will mount them together before shipment (figure 9). For examples of typical transmitter/receiver mounting arrangements, see figures 10 and 11.
If the receiver/controller is ordered separately for use with a 2500 Series controller/transmitter, it may not have the required mounting parts. If mounting parts are required, consult the parts list under the specific mounting application.
See figure 9 for key number locations.
7
2506 Series Receiver/Controllers
235 (9.25)
TUBING (KEY 169)
406
AR5748-B 3V7594-B B2115-1 / IL
(16.00)
60 (2.37)
FRONT VIEW
TRANSMITTER OUTPUT
TUBING (KEY 168)
OUTPUT CONNECTION (MARKED DIAPHRAGM)
REAR VIEW
Instruction Manual
1/4 NPT SUPPLY (ON REGULATOR)
MOUNTING PLATE (KEY 164)
CAP SCREW AND LOCKWASHER (KEYS 39 AND 83)
BELLOW VENTS OR REMOTE SETPOINT CONNECTION
INSTRUMENT INPUT CONNECTION
SUPPLY CONNECTION
1/4 NPT REMOTE LEVEL INDICATOR
Form 1041
November 2005
mm
(INCH)
Figure 9. 2500 Series Controller-Transmitter and 2506 Series Receiver-Controller Mounting
1. Install lock washers (key 83) on the cap screws (key 39). Then, insert the cap screws through the mounting plate from ‘‘back to front’’. Thread the cap screws into the mounting holes in the receiver/controller case and tighten.
2. Install lock washers (key 83) on the cap screws (key 48). Then, insert the cap screws through the mounting plate from ‘‘back to front’’. Thread the cap screws into the mounting holes in the controller/transmitter.
3. If supply pressure is piped through a filter/regulator, bolt the regulator to the back of the controller/transmitter.
4. Provide appropriate piping connections between the units as shown in figures 10 or 11.
Connections
WARNING
exceeds the maximum safe working pressure of any connected equipment.
To complete the installation of a receiver/controller, make connections with tubing and fittings between the receiver/controller and the actuator. The fittings, tubing, and mounting parts required depend on the type number and optional equipment such as filter, regulator, and bypass valve.
All pressure connections on the 2506 Series receiver/controllers are 1/4-inch NPT female fittings (figures 3 and 9). Use 1/4-inch piping or 3/8-inch tubing to these connections.
If remote venting is required, see the Vents subsection below.
Supply Connection
WARNING
The controller is capable of providing full supply pressure to connected equipment. To avoid personal injury or property damage caused by parts bursting from system overpressure, make sure the supply pressure never
8
Severe personal injury or property damage may occur if the instrument air supply is not clean, dry and oil free or non-corrosive gas. While use and regular maintenance of a filter that
Instruction Manual
Form 1041 November 2005
2506 Series Receiver/Controllers
NOTE:
SEE FIGURE 9 FOR REAR VIEW
1
DF5357-A A3701-2 / IL
SUPPLY
2500 SERIES CONTROLLER/ TRANSMITTER
2506 SERIES RECEIVER/ CONTROLLER
FROM DIAPHRAGM CONNECTION TO ACTUATOR
1
DIAPHRAGM ACTUATOR
CONTROL VALV E
1
1
Figure 10. Typical Transmitter with Receiver and Control Valve Installation Assembly
remove particles larger than 40 microns in diameter will suffice in most applications, check with a Fisher Field office and Industry Instrument air quality standards for use with corrosive gas or if you are unsure about the proper amount or method of air filtration or filter maintenance.
If the existing supply is corrosive, make sure the tubing and instrument components that contact the corrosive medium are of suitable corrosion-resistant materials, or change to a noncorrosive supply medium.
WARNING
Personal injury or property damage may occur from bursting parts due to overpressuring any system component. To avoid injury or
damage, provide pressure-relieving or pressure-limiting devices if supply or input pressure could exceed the maximum allowable pressures listed in table 3.
It is recommended that supply pressure pass through a filter/regulator combination such as a 67CFR. See table 3 for recommended supply pressures to the receiver/controller.
Typical supply pressure for the 67CFR is clean dry air or a gas at a pressure of 2.5 bar (35 psig) to a maximum of 17 bar (250 psig). For specific regulator limits, see the appropriate regulator instruction manual.
Output Connections
See figure 3.
Use 3/8-inch tubing between the actuator and the receiver/controller. Connect the output (diaphragm) connection to the appropriate actuator connection.
9
2506 Series Receiver/Controllers
CONTROLLER/ TRANSMITTER SUPPLY
RECEIVER/
4
CONTROLLER SUPPLY
2500 SERIES CONTROLLER/ TRANSMITTER
2
INDICATOR
1
PANEL LOADER REMOTE SET POINT ADJUSTMENT
SUPPLY
3
CONTROLLER OUTPUT PIPING
2506 SERIES REMOTE RECEIVER/CONTROLLER
DIAPHRAGM ACTUATOR
Instruction Manual
November 2005
CENTRALIZED CONTROL PANEL
4
Form 1041
NOTES:
1
PIPING FROM TRANSMITTER OUTPUT TO PANEL INDICATOR
2
PIPING FROM TRANSMITTER OUTPUT TO PANEL RECEIVER/CONTROLLER
INSTRUMENT INPUT. SEE FIGURE 3 FOR CONNECTION LOCATION
PIPING FROM PANEL LOADER TO RECEIVER/CONTROLLER REMOTE SET POINT
3
CONNECTION. SEE FIGURE 3 FOR CONNECTION LOCATION.
SEE FIGURE 3 FOR CONNECTION LOCATION.
4
DF5379-A A3702-2 / IL
Figure 11. Typical Transmitter and Receiver Installation with an Indicator and Remote Set Point Connection
Instrument Connection
See figure 3.
Use 3/8-inch tubing to connect the output from the control device to the INSTRUMENT connection on the receiver/controller.
Vents
WARNING
If a flammable or hazardous gas is used as supply pressure medium, personal injury or property damage could result from fire or explosion caused by the accumulated gas. Injury or property damage could also result
CONTROL VALVE
from contact with the flammable or hazardous gas.
The case and cover assembly does not form a gas-tight seal and flammable or hazardous gas could leak from this unit. Therefore, if the receiver/controller unit is enclosed, install a remote vent line to remove part of the exhaust gas to a properly ventilated area. However, a remote vent line cannot be relied upon to remove all hazardous gas. Vent line piping should comply with local and regional codes and should be as short as possible. Select vent line piping with adequate inside diameter and install with few bends to reduce case pressure buildup.
10
Instruction Manual
Form 1041 November 2005
2506 Series Receiver/Controllers
See figure 3 for vent locations.
A receiver/controller may be ordered with one of two vent configurations:
D Standard, with 1/4-inch case vent open. The standard receiver/controller case (key 1, p/n 4D396044012) is not drilled and tapped for the optional tapped vent.
D Optional, with tapped vent, for applications requiring vent line attachment to receiver/controller case. The optional receiver/controller case (key 1, p/n 2E355544012) features a tapped vent for applications requiring a remote vent line. The standard case vent should be sealed with a machine screw.
An air vent plug (key 137) with gasket (key 138) and hex nut (key 139) can be added to the tapped vent. The air vent plug provides a 1/4-Inch NPT female fitting.
D Receiver/controllers feature an open bellows vent/remote set point connection. An external vent assembly (key 128) is recommended if the remote set point connection is not made. The external vent assembly can be driven into the open bellows vent.
Protect all vents against the entrance of any foreign material that could plug them. Check the vents periodically to be certain they are not plugged.
Remote Set Point Connection
WARNING
Severe personal injury or property damage may occur if the instrument air supply is not clean, dry and oil free or non-corrosive gas. While use and regular maintenance of a filter that remove particles larger than 40 microns in diameter will suffice in most applications, check with a Fisher Field office and Industry Instrument air quality standards for use with corrosive gas or if you are unsure about the proper amount or method of air filtration or filter maintenance.
See figure 3.
The remote set point connection is made at the tapped bellows vent/remote set point connection on the rear of the receiver/controller case. A vent assembly (key 128) is recommended if the remote set point connection is not made.
To make a remote set point connection, remove the vent assembly from the connection. Install piping from the remote set point loader or regulator.
When a panel loader or regulator is used for remote set point adjustment, as shown in figure 11, an adjustable output range of 0.2 to 1 bar (3 to 15 psig) or 0.4 to 2 bar (6 to 30) is required to match the receiver/controller output range.
Use clean, dry air or a non-corrosive gas for supply pressure to the remote set point bellows.
Startup
It is important that the output range of the transmitter or other device used as the input to the receiver/controller be adjusted so that its output range corresponds to the input signal range of the receiver/controller. Be sure the receiver/controller action (direct or reverse) is correct for the application.
To start the system:
D For all receiver/controllers, perform steps 1
and 2.
1. See table 3 for specific pressure limits. Be sure the correct supply pressure is available. If necessary, adjust the regulator to 1.4 bar (20 psig) for a 0.2 to 1 bar (3 to 15 psig) or 2.4 bar (35 psig) for a 0.4 to 2 bar (6 to 30 psig) receiver/controller range.
2. Turn on the supply pressure to the receiver/controller.
D To make the proper level or output pressure setting for a Type 2506 receiver/controller, go to step 3. To make the proper level or output pressure setting for a Type 2516 receiver/controller, go to step 9.
D For the Type 2506 receiver/controller:
3. Set the proportional band adjustment at 15 percent (1.5 on the adjustment dial). At this setting, a
0.1 bar (1.8 psig) input pressure causes a 12 psig
11
2506 Series Receiver/Controllers
Instruction Manual
Form 1041
November 2005
output pressure change. Operate the receiver/controller with the proportional band setting as small as possible.
4. Provide an input pressure equal to the output pressure of the transmitter at a value desired or halfway between the transmitter output range. For example, on a receiver/controller, if the desired control point is halfway between the ends of the displacer, provide an input of 0.6 bar (9 psig) which is halfway between 0.2 and 1 bar (3 and 15 psig) transmitter output range.
5. Set the output pressure adjustment to give a controller output that is halfway between its output range.
6. Vary the input pressure to be sure the full controller output pressure range is produced within the specified input pressure range.
7. Lock the output pressure adjustment and connect the receiver/controller to the final control element.
8. If the proportional band setting is too narrow, causing instability, widen the proportional band just enough to stabilize control. After making this adjustment, it may be necessary to reset the output pressure slightly to produce the proper control range.
D For the Type 2516 receiver/controller:
9. Set the proportional band adjustment dial at 0 percent (minimum proportional band).
10. Set the reset adjustment to the fastest speed (0.005 minutes-per-repeat).
11. Provide an input pressure equal to the output pressure of the transmitter at a value desired or halfway between the transmitter output range. For example, on a receiver/controller, if the desired control point is halfway between the ends of the displacer, provide an input of 0.6 bar (9 psig) which is halfway between 0.2 and 1 bar (3 and 15 psig) transmitter output range.
12. Adjust the output pressure dial to give a controller output somewhere within the output range of the receiver/controller.
13. Lock the output pressure dial and connect to the final control element.
14. If the proportional band is too narrow causing instability, widen the proportional band or slow the reset just enough to stabilize control.
Adjustments
To adjust the receiver/controller, open the cover and locate the appropriate adjustment. See figures 14, 15, and 16 for the location of adjustments.
Set Point Adjustment
To adjust the level set point, loosen the knurled knob and rotate the knob around the INCREASE OUTPUT PRESSURE or RAISE LEVEL dial. To raise fluid or interface level or increase density, rotate the knob in the direction of the arrow.
To lower level or decrease density, rotate the knob in the opposite direction. The INCREASE OUTPUT PRESSURE or RAISE LEVEL dial is graduated (in percent) to show approximate indications of the receiver/controller set point. When making adjustments, do not rely only on the dial setting. Monitor the process fluid level to be sure the receiver/controller attains the desired set point.
For differential gap receiver/controllers, the level setting adjustment determines the location of the gap within the range of the sensing element.
Remote Set Point Adjustment
On a receiver/controller with remote set point adjustment capability, adjust the set point by changing the pressure to the remote set point connection. Increase the remote set point signal pressure to decrease the receiver/controller set point (for a direct acting receiver/controller) or increase the receiver/controller set point (for a reverse acting receiver/controller).
Proportional Band Adjustment
For proportional and proportional-plus-reset receiver/controllers, the proportional band adjustment determines the amount of change in the input pressure required to change the controller output signal from one limit of the output signal range to the other limit (without the effect of reset action).
Proportional band is expressed as a percent of the sensing element range. That is, with a proportional band of 100 percent, an input pressure change equal to the sensing element span would change the controller output from one limit to the other. With a proportional band of 50 percent, an input pressure change equal to one half the sensing element range
12
Instruction Manual
Form 1041 November 2005
2506 Series Receiver/Controllers
would change the controller output from one limit to the other.
The proportional valve dial is graduated from 0 to 10. A setting of 10 on the dial represents a proportional band of 100 percent; 5 represents a proportional band of 50 percent.
The receiver/controller is designed for a maximum proportional band of 200 percent. The effective band is determined by the location of the adjustable nozzle assembly (key 17, figure 14) in the slot in the level set arm (key 28). Most applications require a maximum band of 100 percent so, at the factory, a receiver/controller unit is set to the 100 percent value. This setting places the nozzle at a point that is halfway between the bellows assemblies. To adjust the proportional band, rotate the adjustment counterclockwise to broaden the setting. Rotate the adjustment clockwise to narrow the setting.
In some applications, a 200 percent proportional band range may be required. To obtain the 200 percent range, move the nozzle assembly to the extreme right end of the slot in the level set arm.
The factory sets this valve to relieve when the differential pressure between the proportional and reset bellows reaches 5 psi. To set the valve to relieve when the differential pressure is as low as 2 psig, turn the adjustment screw clockwise. To set the valve to relieve when the differential pressure is as high as 7 psig, turn the adjustment screw counterclockwise. The minimum differential setting yields the minimum differential set point overshoot during startup.
Depending on the characteristics of the process, the anti-reset windup valve can be positioned so that the arrow on the case points to the letters RE or, to the letter P on the back of the manifold. If the arrow points to P, the valve opens when receiver/controller output pressure rises. If the arrow points to RE, the valve opens when receiver/controller output pressure falls.
Calibration
WARNING
For differential gap receiver/controllers, the proportional band adjustment determines the width of the differential gap. This is the difference between the input pressures at which the controller output switches from zero to full supply pressure and back to zero.
Reset Adjustment (Type 2516 Receiver/Controller Only)
On proportional-plus-reset receiver/controllers, the reset adjustment determines the time in minutes required for the reset action to produce a change in output pressure equal to the change that has occurred due to proportional band action.
To adjust the reset action, rotate the adjustment clockwise to decrease, or counterclockwise to increase the minutes per repeat. Increasing the minutes per repeat provides a slower reset action.
Anti-Reset Windup Valve Adjustment (Type 2516F Receiver/Controller Only)
The anti-reset windup valve provides differential pressure relief. Its adjustment control extends from the back of the receiver/controller case (figure 16).
The following calibration procedures require taking the controller out of service. To avoid personal injury and property damage caused by an uncontrolled process, provide some temporary means of control for the process before taking the receiver/controller out of service. Also refer to the Warning at the beginning of the Maintenance section.
See figure 14 for key number and adjustment locations.
When performing the following calibration procedures, open loop conditions must exist and make provisions to monitor the output pressure. One way to obtain an open loop is to disconnect the controller output signal line and install a pressure gauge.
Note
When calibrating a combined controller arrangement such as the Type 2500 with the Type 2506 or 2516 (figure 9), calibrate the Type 2500 controller/transmitter first.
13
2506 Series Receiver/Controllers
Instruction Manual
Form 1041
November 2005
For a direct action receiver/controller:
1. Adjust the INCREASE OUTPUT PRESSURE adjustment to mid-range on the scale.
2. Turn the proportional band adjustment to 100 percent of the scale range.
3. For Type 2516 only, turn the reset valve adjustment fully clockwise.
4. Adjust the input pressure to 0.6 bar (9 psig) for a
0.2 to 1 bar (3 to 15 psig) or 1.2 bar (18 psig) for a
0.4 to 2 bar (6 to 30 psig) receiver/controller.
5. For Type 2516 only, turn the reset valve adjustment fully counterclockwise (to the CLOSED position). This locks 0.6 bar (9 psig) or 1.2 bar (18 psig) in the reset bellows.
6. If the output pressure is 0.6 bar (9 psig) for a 0.2 to 1 bar (3 to 15 psig) or 1.2 bar (18 psig) for a 0.4 to 2 bar (6 to 30 psig) receiver/controller, go to step 8. If not, continue with step 7.
7. If the output pressure span is too low, move the nozzle down towards the flapper, if output pressure is too high, move the nozzle up. Continue by trial and error until the desired setting is obtained.
TRANSMITTER INPUT
SENSING BELLOWS
RESTRICTION
SUPPLY
SUPPLY PRESSURE
RELAY LOADING PRESSURE
TRANSMITTER INPUT
OUTPUT PRESSURE
BD2388-F A3849 / IL
Figure 12. Type 2506 Multi-Trol
Receiver/Controller Schematic
REVERSING SWITCH
BELLOWS VENT OR REMOTE SETPOINT CONNECTION
NOZZLE BEAM/FLAPPER ASSEMBLY
VENT
RELAY INNER VALV E
OUTPUT PRESSURE TO CONTROL VALVE
RELAY BLEED PRESSURE
PROPORTIONAL PRESSURE
®
Direct Action
PROPORTIONAL BELLOWS
8. Adjust the input pressure to 1 bar (15 psig) for a
0.2 to 1 bar (3 to 15 psig) or 2 bar (30 psig) for a 0.4 to 2 bar (6 to 30 psig) receiver/controller.
9. The output pressure should be 1 bar (15 psig) for a 0.2 to 1 bar (3 to 15 psig) or 2 bar (30 psig) for a
0.4 to 2 bar (6 to 30 psig) receiver/controller. If output pressure is within application tolerance, proceed to step 12. If not, continue with step 10.
10. If the output pressure span is narrow, move the nozzle slightly to the left or, if the output pressure span is too wide, move it to the right and repeat steps 4 and 6 through 10.
11. Repeat the steps until the receiver/controller is within application requirements.
12. Reconnect the receiver/controller to the control loop and see the Adjustment section.
Principle of Operation
The 2506 Series uses a basic pressure balance relay system (figure 12). The relay is connected so that supply pressure is fed to the inlet side of the relay valve and the fixed restriction. From this restriction, the air pressure bleeds into the relay chamber on one side of the large diaphragm and also to the nozzle. As long as there is no pressure change on either diaphragm, the relay valve remains in equilibrium with both inlet and exhaust ends closed. The area ratio of the large diaphragm to the small diaphragm is 3 to 1. A 12 psi pressure change on the small diaphragm is balanced by a 4 psi change in the large diaphragm.
The following descriptions show how the relay works with the standard proportional, proportional-plus-reset, and proportional-plus-reset with anti-reset windup receiver/controllers.
14
Instruction Manual
Form 1041 November 2005
TRANSMITTER INPUT
REMOTE SETPOINT BELLOWS
REVERSING SWITCH
BELLOWS VENT OR REMOTE SETPOINT CONNECTION
PROPORTIONAL BELLOWS
2506 Series Receiver/Controllers
RESET RELIEF VALVE SPRING
BEAM/FLAPPER ASSEMBLY
ADJUSTING SCREW
SENSING BELLOWS
RESTRICTION
SUPPLY
TYPE 2516 RECEIVER/CONTROLLER
SUPPLY PRESSURE
RELAY LOADING PRESSURE
TRANSMITTER INPUT
B2116 / IL
BEAM/ FLAPPER ASSEMBLY
OUTPUT PRESSURE TO CONTROL VALVE
OUTPUT PRESSURE
RELAY BLEED PRESSURE
PROPORTIONAL VALV E
Figure 13. Type 2516 and 2516F Multi-Trol®Direct Action Receiver-Controller Schematic
Type 2506 Receiver/Controllers
See figure 12.
As long as the process level remains constant, the transmitter input pressure to the receiver/controller remains constant. Inside the receiver/controller, the bellows beam/flapper assembly remains in a steady-state position.
RESET BELLOWS
RESET BELLOWS
RESET VALV E
OUTPUT PRESSURE
PROPORTIONAL PRESSURE
RESET PRESSURE
A decrease in transmitter input pressure decreases the pressure in the input bellows assembly by moving the beam away from the nozzle. This allows the supply pressure to bleed through the nozzle faster than it can enter through the fixed restriction in the relay. The relay valve opens, exhausting the output pressure which vent through the relay exhaust port. This action decreases output pressure to the control valve.
RESET VALV E
PROPORTIONAL VALV E
TYPE 2516F RECEIVER/CONTROLLER
RELIEF VALVE DIAPHRAGM
DIFFERENTIAL RELIEF VALVE
The position of the bellows beam allows the supply pressure to bleed through the nozzle as fast as it enters the relay through the fixed restriction. A change in transmitter input pressure repositions the beam/flapper assembly with respect to the nozzle.
On a direct action receiver/controller, an increase in transmitter input pressure causes a pressure increase in the sensing bellows assembly, tending to push the beam toward the nozzle. This restricts the escape of supply pressure through the nozzle, thus increasing the pressure on the large diaphragm in the relay. This opens the relay valve to the supply pressure allowing an increase in output pressure to the control valve.
Type 2516, 2516F Receiver/Controllers
The action of a proportional-plus-reset controller (figure 13) is similar to that of a proportional controller except that feedback from the controller output pressure is piped to a reset bellows as well as to the proportional bellows.
Users can adjust the reset valve on the Type 2516 and 2516F to channel some or all of the proportional pressure into the reset bellows that opposes the proportional bellows action. This arrangement automatically reduces the effect of any proportional overcorrection by a set amount per time interval, as long as there is a deviation from the control point.
15
2506 Series Receiver/Controllers
Instruction Manual
Form 1041
November 2005
The Type 2516F receiver/controller also features an anti-reset windup valve. This valve provides differential pressure relief to prevent proportional pressure from exceeding reset pressure by more than a set value. The proportional valve output pressure registers on one side of the diaphragm chamber and the reset valve output pressure registers on the other side diaphragm. A sudden increase in the output pressure causes a rapid pressure increase in the proportional bellows and in the proportional side of the diaphragm chamber. If the diaphragm pressure of the relief valve exceeds that of the spring side by the amount of the relief pressure setting, the relief diaphragm moves off the orifice in the differential relief valve. This allows the pressure on the proportional side of the diaphragm to bleed into the reset system. This action provides quick relief of excessive proportional pressure and reduces the time required by the system to return to the control point. A user can reverse the differential relief action to relieve on decrease output pressure.
Maintenance
Receiver/controller parts are subject to normal wear and may require inspection or replacement. The frequency of inspection and parts replacement depends upon the severity of the service conditions. When inspection or repairs are needed, disassemble only those parts necessary to accomplish the job.
Select the appropriate maintenance procedures and perform the appropriate steps. Each procedure requires that supply pressure and process pressure be shut off before beginning maintenance.
any maintenance operations to avoid personal injury.
D Provide some temporary means of controlling the process before taking the receiver/controller out of service.
D Release any trapped pressure from the controller and vent supply pressure before disassembly.
D Check with your process or safety engineer for any additional measures that must be taken to protect against process media.
Changing Controller Action
See figure 14 for key number locations, unless otherwise directed.
Note
Do not switch the Type 2516 receiver/controller to snap (S) action.
To change controller action, reposition one or both switch plates (key 132), which are mounted on the left or right bellows assemblies (key 134 or 133 respectively). When either switch plate (key 132) is removed, the raised letters D, R, S, and P are visible on the bellows frame located under the switch plate (figure 14).
These letters correspond to: direct (D), reverse (R), snap (S), and proportional (P) control action. To obtain the type of control desired, position the switch plates so that the proper letter appears in the cut-out corner, as explained below:
Establish a maintenance cycle to regularly clean the vents (figure 3). Also, establish a maintenance cycle to clear the relay orifice (key 88, not shown) by pushing in the plunger of the core assembly (key
89).
WARNING
The following maintenance procedures require taking the controller out of service. To avoid personal injury and property damage caused by an uncontrolled process:
D Always wear protective clothing,
gloves, and eyewear when performing
16
D The bellows assembly on the left provides either direct or reverse action. The receiver/controller (Type 2506 or 2516) can be changed between direct and reverse action by repositioning the switch plate (key 132) on the left. Direct action (D) is when increasing transmitter input pressure increases receiver/controller output pressure. To obtain direct action, position the switch plate so the D is visible. Reverse action (R) is when decreasing transmitter input pressure increases receiver/controller output pressure. To obtain reverse action, position the switch plate so the R is visible.
D The bellows assembly on the right provides either proportional (P) or snap (S) action depending
Instruction Manual
Form 1041 November 2005
2506 Series Receiver/Controllers
on the switch plate position. For all types of receiver/controllers, to obtain proportional action, position the switch plate so the P is visible. For Type 2506 receiver/controllers, to obtain snap action, position the switch plate so the S is visible.
Troubleshooting
As an aid to troubleshooting, see table 4 for a listing of some common operating faults, their probable cause, and suggested procedures for correcting the faults.
Testing Relay Deadband
1. Replace the PROPORTIONAL BAND adjustment assembly with a 1/8-inch NPT pipe plug according to the sections for changing proportional, reset, or anti-reset windup valves.
2. Turn on the supply pressure and set it to 1.4 bar or 2.4 bar (20 or 35 psig) according to supply pressure requirements of the receiver/controllers.
3. By changing the process variable and adjusting the INCREASE OUTPUT PRESSURE control, set the output pressure to 15 or 30 psig. While monitoring the output pressure, slowly change the process until an output pressure change just begins. Record the value of the process variable at this detection point.
4. Change the process variable in the opposite direction until another output pressure change just begins. Again, record the value of the process variable. If the difference between the two values (the deadband) is more than 0.2 percent of the maximum displacer length, the relay must be repaired or replaced.
5. See the relay removal and replacement procedures and, if necessary, the relay disassembly and assembly procedures if the relay is to be repaired.
6. Turn off the supply pressure, remove the pipe plug, and install the PROPORTIONAL BAND adjustment assembly.
Replacing Receiver/Controller Parts
See figure 14 for key number locations, unless otherwise indicated.
Bellows Replacement
Use the following bellows replacement procedure to replace defective bellows or change the output signal range.
Removal
1. Remove the relay tubing assembly (key 11), the INCREASE OUTPUT PRESSURE plate (key 35), and the attached restriction plug orifice assembly (key 11).
2. Take out the four bellows screws (key 96). These are special screws with air passages in them so, be careful not to lose them.
3. Compress the bellows (both are key 65) slightly and slip them out of the bellows frame (keys 133 or
134).
4. Unscrew the bellows from the beam (key 59). A gasket (key 79) fits between the end of the bellows and the bellows frame.
5. Inspect each bellows and gasket and, if necessary, replace them.
Replacement
1. First install the bellows gasket (key 79), then install each bellows (key 59) by screwing it onto the beam (key 59).
2. Compress the bellows slightly and slip them into the bellows frame (key 133 or 134).
17
2506 Series Receiver/Controllers
Table 4.Troubleshooting Chart
Fault Possible Cause Check Correction
1. Process wanders or cycles around setpoint.
Note: 1.2 is for Type 2500 and 2506/16 combination.
2. Receiver/controller controlling off setpoint or switching point.
3. Receiver/controller cannot obtain full output range.
4. Receiver/controller remains at full or zero output pressure.
3. Secure the screws (key 96) and replace the tubing.
4. Check all tubing connections and the bellows screws for leaks. Tighten as necessary and proceed to the Calibration section.
1.1 Proportional band or specific gravity adjustment incorrect, or improperly tuned control loop.
1.2 Input signal varying to the Type 2506/16.
1.3 Supply pressure varying, or incorrect supply pressure setting.
1.4 Relay malfunction. 1.4 Check for relay malfunction by
2.1 Supply pressure not set correctly.
2.2 Leak in the receiver/controller loop.
3.1 Supply pressure not set correctly.
3.2 Nozzle adjustment. 3.2 Insure the nozzle is not loose. 3.2 Perform calibration procedures.
3.3 Relay malfunction. 3.3 Check for relay malfunction by
3.4 Leaking controller/transmitter loop.
4.1 Supply or output pressure gauge malfunction.
4.2 Flapper adjustment. 4.2 Insure the flapper is not loose on
4.3 Relay malfunction. 4.3 Check for relay malfunction by
1.1 Insure that the prestartup procedures are completed correctly. Tune control loop.
1.2 Use a pressure gauge to monitor input stability.
1.3 Use input pressure gauge to monitor stability. Make sure regulator supply pressure is within limits.
using the testing relay deadband procedure.
2.1 Make sure regulator supply pressure is set correctly. Make sure regulator supply pressure is within limits.
2.2 Use soap and water to check for internal and external leaks.
3.1 Make sure supply pressure is set correctly. Make sure regulator supply pressure is within limits.
using the testing relay deadband procedure.
3.4 Use soap and water to check for internal and external leaks.
4.1 Insure the pressure gauges are registering correctly.
the torque tube shaft. Insure the flapper is centered on the nozzle.
using the testing relay deadband procedure.
Instruction Manual
Form 1041
November 2005
1.1 If stable control cannot be attained, and all other elements are functionally correct, examine other possible causes related to the controller/transmitter.
1.2 Apply stable input pressure source. Tune the 2500 controller/transmitter.
1.3 Apply correct supply pressure. It is recommended to use one regulator per instrument.
1.4 Depress plunger to clean out the fixed restriction. Replace relay using the procedure in the maintenance section.
2.1 Reset the regulator pressure. If the problem recurs, replace or rebuild the regulator. Provide a regulator input pressure within regulator limits.
2.2 Replace or repair leaking parts as necessary.
3.1 Reset the regulator pressure. If problem recurs, replace or rebuild the regulator. Provide a regulator input pressure within regulator limits.
3.3 Depress plunger to clean out the fixed restriction. Replace or repair relay using the procedure in the maintenance section.
3.4 Replace or repair leaking parts as necessary.
4.1 Replace pressure gauges. Use corrective action given for section 3 of this table.
4.2 Replace or tighten flapper assembly as necessary and/or center flapper on nozzle.
4.3 Depress plunger to clean out the fixed restriction. Replace or repair relay using the procedure in the maintenance section.
Removal
1. Disconnect the tubing (key 11) from the relay.
2. Remove two relay mounting screws, the relay, and the relay gasket (keys 43, 34, and 22).
5. If a bellows assembly (key 65) with a different range is installed, replace the gauges (key 20 or
135) with those with an appropriate measurement capability.
Changing the Relay
Remove the relay to replace it.
18
Replacement
1. Install a new gasket (key 22), the replacement relay (key 34), and secure with two mounting screws (key 43).
2. Connect the tubing (key 11) to the relay.
3. See the testing relay deadband procedures in this section.
Instruction Manual
Form 1041 November 2005
2506 Series Receiver/Controllers
4. If the deadband is within tolerance, see the Calibration section.
Changing Proportional or Reset Valve
1. Disconnect the appropriate tubing(s) from the proportional or reset valve.
2. Removing the valve assembly:
a. Remove the proportional valve assembly by unscrewing it from the relay base. Install the replacement assembly.
b. Remove the reset valve assembly by unscrewing the two machine screws (key 182, not shown) located behind the reset valve on the back of the case. Install the replacement assembly.
Parts Ordering
Whenever corresponding with your Fisher sales office, include the receiver/controller type number and the serial number. The serial number can be found on the nameplate. When ordering replacement parts, also state the complete 11-character part number of each part required as found in the following parts list.
Note
Use only genuine Fisher replacement parts. Components that are not supplied by Fisher should not, under any circumstances be used in any Fisher instrument. The use of components not manufacture by Fisher will void your warranty, might adversely affect the performance of the instrument, and might jeopardize worker and workplace safety.
Note
Neither Emerson, Emerson Process Management, Fisher, nor any of their affiliated entities assumes responsibility for the selection, use, and maintenance of any product. Responsibility for the selection, use, and maintenance of any product remains with the purchaser and end-user.
Parts Kits
Key Description Part Number
Receiver/Controller Repair Kits
Contains keys 17, 19, 21, 24, 38, and 45
Standard Temperature R2506X00L12 High Temperature R2506X00H12
Relay Replacement Kit
Contains key 22 (43 for Type 2500 and 2502) and the relay assembly
Standard Temperature RRELAYX0L22 High Temperature RRELAYX0H22
Parts List
Receiver/Controller Common Parts (figure 14)
Note
Case Vent Options
D The standard receiver/controller case (key 1, p/n 4D396044012) features an open case vent. The case is not drilled for the optional tapped vent.
D All receiver/controller cases feature an open bellows vent/remote set point connection. A external vent assembly (key 128) is recommended if the remote set point connection is not made.
D The optional receiver/controller case (key 1, p/n 2E355544012) features a tapped vent for applications requiring a remote vent line. The standard case vent is sealed w/a machine screw. An external connection (air vent plug, key 137) w/gasket (key 138) and hex nut (key 139) can be added to the tapped vent.
1 Controller case (controller back), die cast aluminum
for Types 2506, 2516
Std: W/open case vent (no optional
tapped vent for vent line) 4D396044012
Optional: W/tapped vent for vent line
(case vent sealed with machine screw) 2E355544012
Additional option: Case pressure-tested
to 0.1 bar (2 psig). Contact your
Fisher sales office to order pressure testing.
Label (key 179) is added to the case. 2E355544012
1 Controller case (controller back), die cast Aluminum
for Type 2516F, w/open case vent (no optional
tapped vent for vent line) 15A7611X012
2 Controller cover, die cast 4D396144012
19
2506 Series Receiver/Controllers
Instruction Manual
Form 1041
November 2005
Key Description Part Number
3 Door handle, steel pl 1C897225082
4 Door handle shaft, stainless steel
(not shown) 1C898414012 5 Machine screw, steel pl 1C895828982 6 Washer, stainless steel 1C897036032 7 Door hook, steel pl 1C897125082
8 Elastic stop nut, steel pl 1C895928992 9 Hinge pin, stainless steel, (2 req’d) 1C8991X0022
10* Compensator tubing assembly, proportional,
stainless steel 1K674838072
11 Relay tubing assembly,
Type 2506 and 2516, stainless steel 1K674738072
17 Orifice cap, brass 0X0843X0012
Note
Gauges
See key 135 for input (instrument) gauge or pipe plug.
20* Output (diaphragm) gauge
Triple scale
0 to 30 psig/0-0.2 MPa/0-2 bar 11B8582X012 0 to 60 psig/0-0.4 MPa/0-4 bar 11B8582X022
Dual scale
0 to 30 psig/0-2 kg/cm 21* Cover gasket, nitrile 1D398706062 22* Relay gasket,
Standard temperature, neoprene 1C897403012 High temperature, silicone 1N873804142
23 Relay base, die cast zinc 2D396244012 24* Relay base gasket (not shown)
Standard temperature, neoprene 1D396703012
High temperature, silicone rubber 1N874204142 25 Flexure strip, stainless steel 1C897836012 26 Flexure strip nut, steel (2 req’d) 1C897525082
27 Flexure strip base, steel 1C897725082 28 Level set arm, steel 1D398025082 29 Latch pin, steel 1C898928982 31 Nut, brass (2 req’d) 1A9463X0012
32 Flapper, Invar 1D398341132 34 Relay assembly
Standard temperature 22B0463X012
High temperature 22B0462X012 35 Level adjustment assembly 10A8939X0A2
2
11B8582X042
Key Description Part Number
35C Level adjustment dial (not shown), aluminum
Std, clockwise adjustment 1D397411032 Optional, counter-clockwise adjustment
For use w/2500 controller 1E235318992
36 Proportional band assembly 10A9122X012 41 Screw, steel pl (2 req’d) 1C941928982 42 Machine screw, steel pl (2 req’d) 1A684928992 43 Machine screw, steel pl (2 req’d) 1D713224192
44 Machine screw, steel pl (6 req’d) 1A573328982 46 Machine screw, stainless steel (4 req’d) 1C899028982 47 Spring (not shown) 1J423437022 56 Bellows stud, brass (2 req’d) (not shown) 1D397814012
59 Bellows beam, steel pl 1D397925082
Note
Bellows Assembly
Select specific bellows assembly by application pressure range.
65* Bellows assembly
Brass
Range:
0.2 to 1 bar (3 to 15 psig) Gray color code 14A5726X072
0.4 to 2 bar (6 to 30 psig) Green color code 14A5726X082
Stainless steel
Range:
0.2 to 1 bar (3 to 15 psig) Gray color code 14A5726X102
0.4 to 2 bar (6 to 30 psig) Green color code 14A5726X092
75 Reset tubing assembly
Type 2516 and 2516F, copper 1D3988000A2 Type 2516, stainless steel 1K674638072
77* Bellows frame gasket (2 req’d) (not shown)
Standard temperature, neoprene 1D396803012 High temperature, silicone 1N874304142
79* Bellows gasket (4 req’d)
Standard temperature, neoprene 1D397003012 High temperature, silicone 1N873604142
91 Reset restriction valve assembly
Type 2516
Standard temperature 19A4357X012 High temperature 19A4357X022
Type 2516F
Standard temperature 19A4359X012
20
*Recommended spare parts
Instruction Manual
Form 1041 November 2005
2506 Series Receiver/Controllers
30A8956-B
USE W/THREADED
CASE VENT
VIEW A
WITH SWITCH
PLATE REMOVED
RESET VALVE ADJUSTMENT
TYPE 2506
SETPOINT ADJUSTMENT
PROPORTIONAL BAND VALVE ADJUSTMENT
C0670-2 / IL
Figure 14. Types 2506 and 2516 Receiver-Controller Assemblies
TYPE 2516
21
2506 Series Receiver/Controllers
Key Description Part Number
96 Bellows screw (4 req’d)
brass 1D3976X0012 stainless steel 1D3976X0022
128 External vent assembly (not shown)
for bellows vent opening when remote set point connection is not made plastic/stainless steel 27A5516X012
129* Switch plate gasket (2 req’d) (not shown)
Standard temperature, nitrile 1D397103012
High temperature, silicone 1N874104142 130 Machine screw, steel pl 1B275128992 132 Switch plate, die cast zinc (2 req’d) 1D396444012 133 Right bellows frame, die cast zinc 1D396544012
134 Left bellows frame, die cast zinc 2D396344012
Note
Gauges
See key 20 for output (diaphragm) gauge.
135 Input (instrument) gauge
Triple Scale
0 to 30 psig/0-0.2 MPa/0-2 bar 11B8582X012 0 to 60 psig/0-0.4 MPa/0-4 bar 11B8582X022
Dual Scale
0 to 30 psig/0-2 kg/cm
135 Pipe plug (not shown), brass
Use instead of input gauge 1A6495X0052 136 Machine screw, steel pl (18 req’d) 1B783928982 137 Air vent plug, brass
For use w/optional case (key 1) featuring
tapped vent 1C442414012
138 Vent plug gasket, neoprene
For use w/key 137 1C442704082 139 Hex nut, steel pl
For use w/key 137 1A352424112 179 Label, paper
For case (back), if pressure-tested.
See key 1 12A9842X012
2
11B8582X042
21A6447-A / DOC
Instruction Manual
Form 1041
November 2005
ADJUSTMENT SCREW
SECTION A-A
186 Anti-reset windup valve assembly
See following list for individual parts 215 Nameplate 12B6338X0A2
Anti-Reset Windup Valve for Type 2516F Only (figure 15)
192 Lower valve body assembly 1V7410X0012 193* O-ring, nitrile (3 req’d) 1D134606992 194 Diaphragm assembly, rubber 1V7408X0012 195 Spring, steel 1V740627012
196 Upper body half, aluminum 2V740208012 197 Adjustment screw, brass 1V740414022 198 Spring seat, aluminum 1V740509022 199 Machine screw, stainless steel (4 req’d) 1N3336X0012
200 Machine screw, stainless steel (2 req’d) 1V7451X0012
22
Figure 15. Type 2516F Anti-Reset Windup Valve Assembly
Type 2516F Reset and Anti-Reset Windup Valve Assembly (figure 16)
181 Relief tubing assembly 13A2077X012 182 Machine screw, steel pl (2 req’d) 1A329428992 183 O-ring, Nitrile 1C853806992 184 Manifold, aluminum 25A7606X012
185 Manifold nipple, aluminum 13A2074X012 186 Differential relief valve 21A6447X0A2
*Recommended spare parts
Instruction Manual
Form 1041 November 2005
2506 Series Receiver/Controllers
RESET VALVE ADJUSTMENT
RECEIVER/ CONTROLLER BACK
15A7608-B A3841 / IL
Figure 16. Type 2516F Reset and Anti-Reset Windup Valve Assembly
Key Description Part Number
Mounting Parts
Yoke Mounting (figures 3 and 4)
39 Cap screw (2 req’d) 1A553424052 48 Cap screw (2 req’d)
For Types 513, 657, 667 1C631224052
For Type 480 1A352624052
78 Spacer (2 req’d)
For Type 480 1F906724092 164 Mounting bracket 1C221825022 174 Spacer Spool (2 req’d) 1C559024092
Regulator mounting. To upper yoke boss
85 Cap screw (2 req’d) T14109T0012
Wall Mounting (figure 6)
ANTI-RESET WINDUP ADJUSTMENT
Key Description Part Number
Regulator mounting
165 Nipple, to join regulator to
receiver/controller supply connection 1C210026232
178 Street Elbow, for supply connection
to regulator 1A913221992
Case Mounting (figure 7)
39 Cap screw (2 req’d) 1A368324052 48 Cap screw (2 req’d) 1C631224052
164 Mounting bracket, steel pl 1F401225072
Regulator mounting. To actuator case (not shown)
39 Cap screws, (2 req’d) 1K747624052 78 Spacer, (2 req’d) 1J830724092 83 Lock washer (2 req’d) 1E830628992
164 Mounting plate, steel pl 1C221825022
174 Spacer, (2 req’d) 1L200624092
40 Hex nut (2 req’d) 1E944024112 84 Lock washer (2 req’d) 1C225728982 85 Cap screw (2 req’d) T14109T0012
176 Cap screw (2 req’d) 1A353024052
177 Bracket 1F401225072
23
2506 Series Receiver/Controllers
Instruction Manual
Form 1041
November 2005
Key Description Part Number
Pipestand Mounting (figure 8)
39 Cap screw, (2 req’d) 1B762424052 78 Spacer, (2 req’d) 1J958824092 83 Lock washer (2 req’d) 1C225728982
164 Mounting plate, steel pl 3R228725022
175 Pipe clamp (2 req’d)
(includes 2 hex nuts for each clamp) 1P427028982
Regulator mounting. To mounting plate (not shown)
40 Hex nut (2 req’d) 1E944024112 84 Lock washer (2 req’d) 1C225728982 85 Cap screw (2 req’d) T14109T0012
Key Description Part Number
2500 Series Controller/Transmitter and 2506 Series Receiver/Controller Mounting (figure 9)
39 Cap screw (4 req’d) 1C631224052 83 Lock washer (4 req’d) 1E830628992
164 Mounting plate, steel pl 1C221825022
Regulator mounting on Types 2506, 2516. W/separate
supply sources and separate regulators
165 Nipple, to join regulator to receiver/controller
supply connection 1B218826232
Regulator mounting on Types 2506, 2516. W/common supply source and separate regulators
165 Nipple, to join regulator to receiver/controller
supply connection 1B218826232
166 Nipple, to join tee (key 167) to
controller/transmitter regulator 1C488226232
167 Tee (common supply connection at
controller/transmitter regulator) 172 Connector to tee (key 167) 173 Street Elbow, for receiver/controller
regulator supply connection
Multi-Trol, Level-Trol and Fisher are marks owned by Fisher Controls International LLC, a member of the Emerson Process Management business division of Emerson Electric Co. Emerson and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.
Neither Emerson, Emerson Process Management, Fisher, nor any of their affiliated entities assumes responsibility for the selection, use and maintenance of any product. Responsibility for the selection, use and maintenance of any product remains with the purchaser and end-user.
Emerson Process Management
Fisher
Marshalltown, Iowa 50158 USA Cernay 68700 France Sao Paulo 05424 Brazil Singapore 128461
www.Fisher.com
24
EFisher Controls International LLC 1978, 2005; All Rights Reserved Printed in USA
Loading...