Fisher 2502 Series Level-Trol Instruction Manual

Instruction Manual Form 1446 June 1994
2502 Series
250
2 S
erie
s L
evel-Trol C
Contents
Introduction
Scope of Manual 2. Description 2 Specifications 2 Controller Action 2.
Installation%2
249 Series Sensors 2. Uncrating 4 Controller Orientation 4. Mounting Caged Sensors 4. Mounting Cageless Sensors 5.
Side-Mounted Sensor 7. Top-Mounted Sensor 7.
Special Constructions 7.
Temperature-Compensated Displacer 7. Piezometer Ring 8.
Regulator Supply Pressure 8.
Prestartup Checks
Adjustments 10
Level Set Adjustment 10. Proportional Band Adjustment 10. Reset Adjustment 10. Differential Relief Adjustment 10.
Calibration
Precalibration Requirements 11.
Wet Calibration 11. Dry Calibration 11. Controller and Torque Tube Arm Disassembly 11 Determining Suspended Weight for Calibration 12
Calibration Procedure 12.
Startup
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.
W3121-3/IL
9.
Maintenance
Troubleshooting 16 Removing Controller from Sensor 16. Changing Mounting Method 18.
11
13
Installing Controller on Sensor 19. Changing Proportional, Reset, or
Differential Relief Valve 19. Testing Relay Dead Band 19. Changing Relay 20. Replacing Bellows 20. Reversing Action 20. Disassembling Relay 20.
Parts Ordering
TYPE 2502 CONTROLLER
TYPE 249B SENSOR
Figure 1. Type 2502 Controller Mounted on
Type 249B Sensor
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
15.
21.
Principle of Operation
Type 2502 Controller 15. Type 2502F Controller with Reset Relief Valve 15.
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
13.
Parts Kits Parts List
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
21.
21.
D200126X012
2502 Series
Introduction
Scope of Manual
This instruction manual provides installation, operat­ing, calibration, maintenance procedures for 2502 Se­ries pneumatic controllers (figure 1) used in combina­tion with 249 Series level sensors.
This manual does not include regulator or sensor installation or maintenance procedures. For this infor­mation, refer to the instruction manual for the appropri­ate regulator and 249 Series level sensor.
Only personnel qualified through training or experience should install, operate, and maintain this controller. If there are any questions concerning these instructions contact your Fisher Controls sales office or sales rep­resentative before proceeding.
Description
The Type 2502 Level-TrolR Controller described in this manual provides proportional-plus-reset and pro­portional-plus-reset-with-anti-reset-windup control. The controller output is a pneumatic signal that operates a final control element. These controllers are designed to control liquid level, the level of interface between two liquids, or density (specific gravity). Each unit con­sists of a 249 Series liquid level sensor and a 2502 Series pneumatic controller.
AMBIENT TEMPERATURE (_C)
–18 –10
1100
_
800
400
0
USE INSULATOR (CAUTION! IF AMBIENT DEWPOINT IS ABOVE PROCESS TEMPERATURE, ICE FORMATION MAY
PROCESS TEMPERATURE ( F)
CAUSE INSTRUMENT MALFUNCTION AND REDUCE INSULATOR EFFECTIVENESS.)
–20 –29
0 20 40 60 80 100 120 140 160
–18 –10
1100
_
800
400
NO INSULATOR NECESSARY
0
USE INSULATOR (CAUTION! IF AMBIENT DEWPOINT IS ABOVE PROCESS TEMPERATURE, ICE FORMATION MAY
PROCESS TEMPERATURE ( F)
CAUSE INSTRUMENT MALFUNCTION AND REDUCE INSULATOR EFFECTIVENESS.)
–20 –29
0 20 40 60 80 100 120 140 200
   
B1413-1/IL
NOTE: FOR SERVICE BELOW –20_F (–29_C) CONTACT FACTORY.
01020
HEAT INSULATOR REQUIRED
NO INSULATOR NECESSARY
AMBIENT TEMPERATURE (_F)
   
01020
HEAT INSULATOR REQUIRED
AMBIENT TEMPERATURE (_C)
AMBIENT TEMPERATURE (_F)
30 40 50 60 70
30 40 50 60 70
TOO HOT
71
593 500 400 300 200 100
0
80 90
TOO HOT
180160
Figure 2. Guidelines for Use of Optional
Heat Insulator Assembly
plied reverse-acting unit has the suffix letter R added to the type number.
_
PROCESS TEMPERATURE ( C)
93
593 500 400 300 200 100
0
Refer to the Principle of Operation section for a more comprehensive discussion of how the Type 2502 pneumatic controller operates.
Specifications
Table 1 gives general specifications for the Type 2502 Series Controllers.
Controller-Sensor Action
The following controller description is for right-hand mounting. Left-hand mounting produces an output sig­nal with the opposite action. Figure 4 shows cage head mounting positions.
For right-hand mounting:
S Direct Action--Increasing liquid or interface level, or density, increases the output signal.
S Reverse Action--Decreasing liquid or interface level, or density, increases the output signal. A factory-sup-
Installation
The 2502 Series controllers are used in combination with 249 Series sensors, and unless ordered separate­ly, the controller will be attached to the sensor.
249 Series Sensors
D The Type 249, 249B, 249C, 249K, 249L, and
249N, sensors side-mount on the vessel with the dis­placer mounted inside a cage (caged) outside the ves­sel.
D The Type 249BP and 249CP sensors top-mount
on the vessel with the displacer hanging down into the vessel (cageless).
D The Type 249V sensor side-mounts on the ves-
sel with the displacer hanging out into the vessel (cageless).
External sensors provide more stable operation than do internal sensors for vessels with internal obstruc­tions or considerable internal turbulence.
2
Table 1. Specifications
2502 Series
Available Configurations
Type 2502: A direct-acting controller which pro-
vides proportional-plus-reset control Type 2502C: A Type 2502 with a level indicator assembly Type 2502F: A Type 2502 with a differential relief valve
These type numbered products are also avail­able with reverse action. For example, Type 2502R, Type 2502CR, and 2502FR
Input Signal
(1)
Liquid Level or Liquid-to-Liquid Interface Level:
From 0 to 100 percent of displacer length—stan­dard lengths for all sensors are 14 inches (356 mm) or 32 inches (813 mm). Other lengths available de­pending on sensor construction Liquid Density: From 0 to 100 percent of displace­ment force change obtained with given displacer volume—standard volumes are 60 inches3 (980 cm3) for Types 249C and 249CP sensors, or 100 inches3 (1640 cm3) for most other 249 Series sen­sors; other volumes available depending on construction
Output Signal
(1)
3 to 15 psig (0.2 to 1.0 bar) or 6 to 30 psig (0.4 to
2.0 bar) Action: Field reversible between direct (increasing liquid or interface leel or specific gravity increases output pressure) and reverse (increasing liquid or interface level or specific gravity decreases output pressure)
band setting of 0 or 200 percent
Maximum:
27 scfh (0.72 m3/h) at proportional band
setting of 100 percent
At 35 psig (2.4 bar)
Minimum:
7 scfh (0.2 m3/h) at proportional band
setting of 0 or 200 percent
Maximum:
42 scfh (1.1 m3/h) at proportional band
setting of 100 percent
Performance
Hysteresis: 0.6 percent of output pressure change
at 100 percent of proportional band Repeatability(1): 0.2 percent of displacer length or displacement force change Dead Band(1): 0.05 percent of proportional band or span
Typical Frequency Response
(1)
: 4 Hz and 90-de-
gree phase shift at 100 percent of proportional band with output piped to typical instrument bellows using 20 feet (6.1 meters) of 1/4 inch (6.4 mm) tubing Ambient Temperature Error: 1.5 percent of out- put pressure change per 50_F (28_C) of tempera­ture change at 100 percent of proportional band when using sensor with standard-wall N05500 (K-Monel
Reset
(4)
) torque tube with 249 Series sensors
(1)
: Adjustable from 0.01 to 74 minutes per
repeat (100 to 0.01 repeats per minute)
Differential Relief (Type 2502F and 2502FR Con­trollers Only): Adjustable from 2 to 7 psi (0.1 to
0.48 bar differential) to relieve excessive difference between proportional and reset pressures. Differen­tial relief can be switched between rising output pressure and falling output pressure.
Area Ratio of Relay Diaphragms
3:1
Supply Pressure Requirement
(2)
20
psig (1.4 bar) for 3 to 15 psig (0.2 to 1.0 bar)
output signal or 35
(2)
psig (2.4 bar) for 6 to 30 psig
(0.4 to 2.0 bar) output signal
Maximum Supply Pressure
50 psig (3.4 bar)
Supply Pressure Consumption
At 20 Psig (1.4 bar)
Minimum:
1. Term defined in ISA Standard S51.1-1979.
2. Control and stability may be impaired if this pressure is exceeded.
3. Scfh=standard cubic feet per hour at 60_F and 14.7 psia (normal cubic meters per hour (m3/hr) at 0_C and 1.01325 bar).
4. K-Monel is a mark owned by Inco International.
4.2 scfh
(3)
(0.11 m3/h) at proportional
Standard Tubing Connections
1/4 inch (6.4 mm) NPT female
Maximum Working Pressures (Sensors Only)
Consistent with aplicable ANSI pressure/tempera­ture ratings
Operative Ambient Temperatures
Standard Construction: 40 to 160_F (40 to
71_C) High Temperature Construction: 0 to 220_F (18 to 104_C). See figure 2
3
2502 Series
WARNING
When replacing the sensor assembly, the displacer may retain process liquid or pressure. Personal injury or property damage due to sudden release of pres­sure, contact with hazardous liquid, fire, or explosion can be caused by punctur­ing, heating, or repairing a displacer that is retaining process pressure or liq­uid. This danger may not be readily ap­parent when disassembling the sensor or removing the displacer. Before disas­sembling the sensor or removing the displacer, observe the more specific warning provided in the sensor instruc­tion manual.
Uncrating
Unless ordered separately, the controller will be at­tached to the sensor when shipped. Carefully uncrate the assembly.
CAUTION
A thin-wall torque tube has a T stamped on the sensor end flange (not visible un­less the controller/transmitter is re­moved from the sensor). For sensors with a thin-wall torque tube, always sup­port the displacer if the travel stop must be removed.
Note
Caged sensors have a rod and block installed on each end of the displacer to protect the displacer in shipping. Re­move these parts before installing the sensor to allow the displacer to function properly.
Caged sensors will be shipped with the displacer installed in the cage. If the sensor is ordered with a tubular gauge glass, the gauge glass will be crated separately and must be installed at the site. Be certain that the cage equalizing connections are not plugged with foreign material.
ADJUSTING
PRESSURE REGULATOR
1/4”-18 NPT OUTPUT CONNECTION
CD1700-E A1909-1/IL
LOCKNUT
VENT
Figure 3. Pressure Connections
SCREW
1/4”-18 NPT SUPPLY CONNECTION
FILTER WELL
DRAIN VALVE
(12.7 mm) hexagon wrench to unscrew the damping plate. For flanged connections, use a screwdriver to pry the damping plate out of the flange.
A cageless sensor is shipped with the displacer sepa­rated from the sensor assembly. A displacer longer than 32 inches (813 mm) is crated separately. A short­er displacer is crated with the sensor, but is not at­tached to the displacer rod. Inspect the displacer and replace if it is dented. A dent may reduce the pressure rating of the displacer.
Controller Orientation
A controller is to be mounted with the vent opening pointing downward as shown in figure 3. This orienta­tion is necessary to ensure draining of accumulated moisture. The controller is attached to the sensor in one or the other of the mounting positions shown in figure 4: Right hand (with the case to the right of the displacer when looking at the front of the case) or left hand (with the case to the left of the displacer). The mounting position can be changed in the field if re­quired; refer to the appropriate sensor manual for in­structions. Changing this mounting position will change controller action from direct to reverse, or vice versa.
All caged sensors have a rotatable head. That is, the controller may be positioned at any of eight alternate positions around the cage as indicated by the numbers 1 through 8 in figure 4. To rotate the head, remove the head flange bolts and nuts and position the head as desired.
Mounting Caged Sensor
CAUTION
A caged sensor has a damping plate installed in the lower screwed or flanged connection to provide more stable operation. If the process liquid could clog the plate opening with sediment, then remove the damp­ing plate. For screwed connections, use a 1/2-inch
4
The cage must be installed plumb so that the displacer does not touch the cage wall. Should the displacer touch the cage wall, the unit transmits an erro­neous output signal.
2502 Series
AH9150–A A2613–2/IL
Figure
4. Cage Head Mounting Positions
Note
If the controller is not mounted on the sensor, refer to the Installing Controller on Sensor section. That section also provides instructions for adding a heat insulator to a unit. If a temperature-com­pensating displacer or piezometer ring is used, refer to the special installation procedures in this section before pro­ceeding.
Cage connections will normally be either 1-1/2 or 2-inch (38.1 to 50.8 mm) screwed or flanged. Figure 5 shows the combinations. It is recommended that a drain be installed between the cage and shutoff or hand valve whenever the bottom cage line has a liq­uid-trapping low point.
Mount the cage by running equalizing lines between the cage connections and the vessel (figure 6). On liquid or interface level applications, position the sen­sor so that the line marked FLOAT CENTER on the cage is located as close as possible to the center of the liquid level or interface level range being mea­sured.
A1271–2/IL
Figure 5. Cage Connection Styles
For liquid or interface level applications, it is advanta­geous to install a gauge glass either on the vessel, or on the sensor cage (if the cage is tapped for a gauge). With flanged connections, use standard gaskets or other flat-sheet gaskets compatible with the process liquid. Spiral wound gaskets without compression-con­trolling centering rings cannot be used for flanged con­nections.
Mounting Cageless Sensor
CAUTION
If a stillwell is used, it must be installed plumb so that the displacer does not touch the wall of the stillwell. Should the displacer touch the wall while the unit is in service, the unit will transmit an erroneous output signal.
Since the displacer hangs inside the vessel, it is advis­able to provide a stillwell around the displacer when the liquid is in a state of continuous agitation and ex­cessive turbulence can be expected.
5
2502 Series
CENTER
OF LIQUID OR INTERFACE LEVEL
SHUTOFF VALVES
VENT
EQUALIZING LINE
DRAIN
DF5379-A A6771/IL
Figure
6. Caged Sensor Mounting
CAUTION
Since a displacer used in an interface level or a density application must be completely submerged during opera­tion, obtaining desired controller sensi­tivity requires the use of either a thin­wall torque tube or an overweight displacer, or both. An overweight dis­placer cannot be used for any service except those conditions for which it was specified.
Note
W0645-1
  
TOP MOUNTED
If the controller is not mounted on the sensor, refer to the Installing Controller on Sensor section. That section also provides instructions for adding a heat insulator to a unit. If the sensor has a temperature-compensated displacer or piezometer ring, refer to the special constructions procedures in this sec­tion before proceeding.
Attach a cageless sensor to a flanged connection on the vessel as shown in figure 7. For interface or liquid level applications, install a gauge glass on the vessel.
6
CF5380-A A3893/IL
Figure
7. Cageless Sensor Mounting

CAUTION
If the displacer is to be inserted into the vessel before being attached to the dis­placer rod, provide a suitable means of
supporting the displacer to prevent it from dropping into the vessel and suf­fering damage.
To help support a Type 249BP or 249CP displacer, install the displacer stem and stem end piece, or a threaded rod, into the 1/4 inch-28 UNF threaded hole in the displacer spud or stem end piece (figure 8). On the Type 249BP with optional travel stop, the stem end piece pins will secure the displacer as long as the travel stop plate is installed and the sensor head is in position.
Side-Mounted Sensor
If a stillwell is required (figure 7), the displacer must be attached to the displacer rod from inside the vessel. Connect the displacer as shown in figure 8, locking the assembly with the cotter spring provided. If a stillwell is not required, the displacer can be attached to the displacer rod before mounting the sensor to the vessel connection. The displacer may then be swung out hor­izontally for insertion into the vessel. If an extension is used between the displacer spud and the displacer stem end piece, make sure the nuts are tight at each end of the displacer stem extension. Install and tighten suitable bolting or cap screws in the flanged connec­tion to complete the installation.
2502 Series
DISPLACER STEM END PIECE
DISPLACER STEM EXTENSION
W0229-1A/IL
DISPLACER SPUD
W0228-1A/IL
   
  
Figure 8. Displacer/Displacer Rod Connections
COTTER SPRING
LOCKING NUTS
DISPLACER SPUD
COTTER SPRING
DISPLACER ROD
DISPLACER ROD
Top-Mounted Sensor
Figure 7 shows the installation of a top-mounted cage­less sensor. The displacer may be attached to the dis­placer rod before installing the sensor on the vessel. Where the displacer diameter is small enough, it may be desirable to install a long or sectionalized displacer through the sensor head access hole after the sensor is installed on the vessel. Connect the displacer as shown in figure 8, locking the assembly with the cotter springs provided. If a stem is used between the dis­placer as shown in figure 8, lock the assembly with the cotter springs provided. If a stem is used between the displacer spud and the stem end piece, make sure the nuts are tight at each end of the stem. Install and tight­en suitable cap screws in the flanged connection to complete the installation.
Special Constructions
Temperature-Compensated Displacer
Some sensors use a temperature-compensated dis­placer (figure 9). This displacer is appropriate for den­sity applications that do not tolerate specific gravity changes due to temperature. The displacer must be filled with the liquid to be measured, or with a liquid of equal expansion coefficient. In service, the displacer
A0746–1/IL
Figure
9. Temperature-Compensated Displacer
7
2502 Series
expands and contracts the same amount as the mea­sured liquid to nullify signal changes that would be caused by temperature changes.
This type of displacer is shipped in a separate carton but crated with the rest of the assembly. See the ap­propriate sensor manual for filling instructions.
Piezometer Ring
A piezometer ring (figure 10) is used when it is desir­able to measure the specific gravity of a liquid in a flowing line, and when the liquid velocity exceeds two feet/minute (10 mm/second) past the displacer in the cage. The piezometer ring reduces the velocity effects caused by liquid passing through the displacer cage.
To install this type of sensor, connect a line to the cage inlet and outlet piping at each end of the cage. Use hand valves to balance the liquid flow through the cage and keep the displacer cage filled. It is advisable to provide a rotameter or sight flow gauge for measur­ing velocity through the cage. If the flow rates are properly balanced, the transmitter output will show little change when flow through the cage is shut off. If the flow rate through the cage is too high the turbu­lence may cause an erratic output pressure signal. Readjust hand valves to stabilize the output pressure signal.
Regulator Supply Pressure
WARNING
Do not overpressurize any system com­ponent. Personal injury or property damage may occur due to sudden pres­sure release or explosion. To avoid damage, provide suitable pressure-re­lieving or pressure limiting devices if supply pressure can exceed the maxi­mum supply pressure listed in table 1.
Personal injury or property danage may occur from an uncontrolled process if the supply medium is not clean, dry, oil­free, or non-corrosive gas. Industry in­strument air quality standards describe acceptable dirt, oil, and moisture con­tent. Due to the variability in nature of the problems these influences can have on pneumatic equipment, Fisher Con­trols has no technical basis to recom­mend the level of filtration equipment required to prevent performance degra­dation of pneumatic equipment. A filter or filter regulator capable of removing
A1317-1/IL
Figure
10. Piezometer-Ring Cage for Flow Line Mounting
particles 40 microns in diameter will suf­fice for most applications. Use of suit­able filtration equipment and the estab­lishment of a maintenance cycle to monitor its operation is recommended.
Standard 2502 Series controllers come complete with supply and output pressure gauges and an integrally mounted Type 67FR regulator to reduce supply pres­sure from a maximum of 250 psig (17.3 bar) to the 20 or 35 psig (1.4 or 2.4 bar) required. This regulator has built-in relief and a standard 40-micron to remove par­ticles from the supply source.
The output pressure connection is on the back of the controller case (figure 3). Pipe the supply pressure to the in connection of the regulator mounted to the case back. Provide a clean, dry, and noncorrosive air or gas supply to the controller as follows:
After pressure connections have been made, turn on the supply pressure and check all connections for leaks.
8
Loading...
+ 16 hidden pages