Fisher 2502 Series Level-Trol Instruction Manual

Page 1
Instruction Manual Form 1446 June 1994
2502 Series
250
2 S
erie
s L
evel-Trol C
Contents
Introduction
Scope of Manual 2. Description 2 Specifications 2 Controller Action 2.
Installation%2
249 Series Sensors 2. Uncrating 4 Controller Orientation 4. Mounting Caged Sensors 4. Mounting Cageless Sensors 5.
Side-Mounted Sensor 7. Top-Mounted Sensor 7.
Special Constructions 7.
Temperature-Compensated Displacer 7. Piezometer Ring 8.
Regulator Supply Pressure 8.
Prestartup Checks
Adjustments 10
Level Set Adjustment 10. Proportional Band Adjustment 10. Reset Adjustment 10. Differential Relief Adjustment 10.
Calibration
Precalibration Requirements 11.
Wet Calibration 11. Dry Calibration 11. Controller and Torque Tube Arm Disassembly 11 Determining Suspended Weight for Calibration 12
Calibration Procedure 12.
Startup
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.
W3121-3/IL
9.
Maintenance
Troubleshooting 16 Removing Controller from Sensor 16. Changing Mounting Method 18.
11
13
Installing Controller on Sensor 19. Changing Proportional, Reset, or
Differential Relief Valve 19. Testing Relay Dead Band 19. Changing Relay 20. Replacing Bellows 20. Reversing Action 20. Disassembling Relay 20.
Parts Ordering
TYPE 2502 CONTROLLER
TYPE 249B SENSOR
Figure 1. Type 2502 Controller Mounted on
Type 249B Sensor
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
15.
21.
Principle of Operation
Type 2502 Controller 15. Type 2502F Controller with Reset Relief Valve 15.
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
13.
Parts Kits Parts List
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
21.
21.
D200126X012
Page 2
2502 Series
Introduction
Scope of Manual
This instruction manual provides installation, operat­ing, calibration, maintenance procedures for 2502 Se­ries pneumatic controllers (figure 1) used in combina­tion with 249 Series level sensors.
This manual does not include regulator or sensor installation or maintenance procedures. For this infor­mation, refer to the instruction manual for the appropri­ate regulator and 249 Series level sensor.
Only personnel qualified through training or experience should install, operate, and maintain this controller. If there are any questions concerning these instructions contact your Fisher Controls sales office or sales rep­resentative before proceeding.
Description
The Type 2502 Level-TrolR Controller described in this manual provides proportional-plus-reset and pro­portional-plus-reset-with-anti-reset-windup control. The controller output is a pneumatic signal that operates a final control element. These controllers are designed to control liquid level, the level of interface between two liquids, or density (specific gravity). Each unit con­sists of a 249 Series liquid level sensor and a 2502 Series pneumatic controller.
AMBIENT TEMPERATURE (_C)
–18 –10
1100
_
800
400
0
USE INSULATOR (CAUTION! IF AMBIENT DEWPOINT IS ABOVE PROCESS TEMPERATURE, ICE FORMATION MAY
PROCESS TEMPERATURE ( F)
CAUSE INSTRUMENT MALFUNCTION AND REDUCE INSULATOR EFFECTIVENESS.)
–20 –29
0 20 40 60 80 100 120 140 160
–18 –10
1100
_
800
400
NO INSULATOR NECESSARY
0
USE INSULATOR (CAUTION! IF AMBIENT DEWPOINT IS ABOVE PROCESS TEMPERATURE, ICE FORMATION MAY
PROCESS TEMPERATURE ( F)
CAUSE INSTRUMENT MALFUNCTION AND REDUCE INSULATOR EFFECTIVENESS.)
–20 –29
0 20 40 60 80 100 120 140 200
   
B1413-1/IL
NOTE: FOR SERVICE BELOW –20_F (–29_C) CONTACT FACTORY.
01020
HEAT INSULATOR REQUIRED
NO INSULATOR NECESSARY
AMBIENT TEMPERATURE (_F)
   
01020
HEAT INSULATOR REQUIRED
AMBIENT TEMPERATURE (_C)
AMBIENT TEMPERATURE (_F)
30 40 50 60 70
30 40 50 60 70
TOO HOT
71
593 500 400 300 200 100
0
80 90
TOO HOT
180160
Figure 2. Guidelines for Use of Optional
Heat Insulator Assembly
plied reverse-acting unit has the suffix letter R added to the type number.
_
PROCESS TEMPERATURE ( C)
93
593 500 400 300 200 100
0
Refer to the Principle of Operation section for a more comprehensive discussion of how the Type 2502 pneumatic controller operates.
Specifications
Table 1 gives general specifications for the Type 2502 Series Controllers.
Controller-Sensor Action
The following controller description is for right-hand mounting. Left-hand mounting produces an output sig­nal with the opposite action. Figure 4 shows cage head mounting positions.
For right-hand mounting:
S Direct Action--Increasing liquid or interface level, or density, increases the output signal.
S Reverse Action--Decreasing liquid or interface level, or density, increases the output signal. A factory-sup-
Installation
The 2502 Series controllers are used in combination with 249 Series sensors, and unless ordered separate­ly, the controller will be attached to the sensor.
249 Series Sensors
D The Type 249, 249B, 249C, 249K, 249L, and
249N, sensors side-mount on the vessel with the dis­placer mounted inside a cage (caged) outside the ves­sel.
D The Type 249BP and 249CP sensors top-mount
on the vessel with the displacer hanging down into the vessel (cageless).
D The Type 249V sensor side-mounts on the ves-
sel with the displacer hanging out into the vessel (cageless).
External sensors provide more stable operation than do internal sensors for vessels with internal obstruc­tions or considerable internal turbulence.
2
Page 3
Table 1. Specifications
2502 Series
Available Configurations
Type 2502: A direct-acting controller which pro-
vides proportional-plus-reset control Type 2502C: A Type 2502 with a level indicator assembly Type 2502F: A Type 2502 with a differential relief valve
These type numbered products are also avail­able with reverse action. For example, Type 2502R, Type 2502CR, and 2502FR
Input Signal
(1)
Liquid Level or Liquid-to-Liquid Interface Level:
From 0 to 100 percent of displacer length—stan­dard lengths for all sensors are 14 inches (356 mm) or 32 inches (813 mm). Other lengths available de­pending on sensor construction Liquid Density: From 0 to 100 percent of displace­ment force change obtained with given displacer volume—standard volumes are 60 inches3 (980 cm3) for Types 249C and 249CP sensors, or 100 inches3 (1640 cm3) for most other 249 Series sen­sors; other volumes available depending on construction
Output Signal
(1)
3 to 15 psig (0.2 to 1.0 bar) or 6 to 30 psig (0.4 to
2.0 bar) Action: Field reversible between direct (increasing liquid or interface leel or specific gravity increases output pressure) and reverse (increasing liquid or interface level or specific gravity decreases output pressure)
band setting of 0 or 200 percent
Maximum:
27 scfh (0.72 m3/h) at proportional band
setting of 100 percent
At 35 psig (2.4 bar)
Minimum:
7 scfh (0.2 m3/h) at proportional band
setting of 0 or 200 percent
Maximum:
42 scfh (1.1 m3/h) at proportional band
setting of 100 percent
Performance
Hysteresis: 0.6 percent of output pressure change
at 100 percent of proportional band Repeatability(1): 0.2 percent of displacer length or displacement force change Dead Band(1): 0.05 percent of proportional band or span
Typical Frequency Response
(1)
: 4 Hz and 90-de-
gree phase shift at 100 percent of proportional band with output piped to typical instrument bellows using 20 feet (6.1 meters) of 1/4 inch (6.4 mm) tubing Ambient Temperature Error: 1.5 percent of out- put pressure change per 50_F (28_C) of tempera­ture change at 100 percent of proportional band when using sensor with standard-wall N05500 (K-Monel
Reset
(4)
) torque tube with 249 Series sensors
(1)
: Adjustable from 0.01 to 74 minutes per
repeat (100 to 0.01 repeats per minute)
Differential Relief (Type 2502F and 2502FR Con­trollers Only): Adjustable from 2 to 7 psi (0.1 to
0.48 bar differential) to relieve excessive difference between proportional and reset pressures. Differen­tial relief can be switched between rising output pressure and falling output pressure.
Area Ratio of Relay Diaphragms
3:1
Supply Pressure Requirement
(2)
20
psig (1.4 bar) for 3 to 15 psig (0.2 to 1.0 bar)
output signal or 35
(2)
psig (2.4 bar) for 6 to 30 psig
(0.4 to 2.0 bar) output signal
Maximum Supply Pressure
50 psig (3.4 bar)
Supply Pressure Consumption
At 20 Psig (1.4 bar)
Minimum:
1. Term defined in ISA Standard S51.1-1979.
2. Control and stability may be impaired if this pressure is exceeded.
3. Scfh=standard cubic feet per hour at 60_F and 14.7 psia (normal cubic meters per hour (m3/hr) at 0_C and 1.01325 bar).
4. K-Monel is a mark owned by Inco International.
4.2 scfh
(3)
(0.11 m3/h) at proportional
Standard Tubing Connections
1/4 inch (6.4 mm) NPT female
Maximum Working Pressures (Sensors Only)
Consistent with aplicable ANSI pressure/tempera­ture ratings
Operative Ambient Temperatures
Standard Construction: 40 to 160_F (40 to
71_C) High Temperature Construction: 0 to 220_F (18 to 104_C). See figure 2
3
Page 4
2502 Series
WARNING
When replacing the sensor assembly, the displacer may retain process liquid or pressure. Personal injury or property damage due to sudden release of pres­sure, contact with hazardous liquid, fire, or explosion can be caused by punctur­ing, heating, or repairing a displacer that is retaining process pressure or liq­uid. This danger may not be readily ap­parent when disassembling the sensor or removing the displacer. Before disas­sembling the sensor or removing the displacer, observe the more specific warning provided in the sensor instruc­tion manual.
Uncrating
Unless ordered separately, the controller will be at­tached to the sensor when shipped. Carefully uncrate the assembly.
CAUTION
A thin-wall torque tube has a T stamped on the sensor end flange (not visible un­less the controller/transmitter is re­moved from the sensor). For sensors with a thin-wall torque tube, always sup­port the displacer if the travel stop must be removed.
Note
Caged sensors have a rod and block installed on each end of the displacer to protect the displacer in shipping. Re­move these parts before installing the sensor to allow the displacer to function properly.
Caged sensors will be shipped with the displacer installed in the cage. If the sensor is ordered with a tubular gauge glass, the gauge glass will be crated separately and must be installed at the site. Be certain that the cage equalizing connections are not plugged with foreign material.
ADJUSTING
PRESSURE REGULATOR
1/4”-18 NPT OUTPUT CONNECTION
CD1700-E A1909-1/IL
LOCKNUT
VENT
Figure 3. Pressure Connections
SCREW
1/4”-18 NPT SUPPLY CONNECTION
FILTER WELL
DRAIN VALVE
(12.7 mm) hexagon wrench to unscrew the damping plate. For flanged connections, use a screwdriver to pry the damping plate out of the flange.
A cageless sensor is shipped with the displacer sepa­rated from the sensor assembly. A displacer longer than 32 inches (813 mm) is crated separately. A short­er displacer is crated with the sensor, but is not at­tached to the displacer rod. Inspect the displacer and replace if it is dented. A dent may reduce the pressure rating of the displacer.
Controller Orientation
A controller is to be mounted with the vent opening pointing downward as shown in figure 3. This orienta­tion is necessary to ensure draining of accumulated moisture. The controller is attached to the sensor in one or the other of the mounting positions shown in figure 4: Right hand (with the case to the right of the displacer when looking at the front of the case) or left hand (with the case to the left of the displacer). The mounting position can be changed in the field if re­quired; refer to the appropriate sensor manual for in­structions. Changing this mounting position will change controller action from direct to reverse, or vice versa.
All caged sensors have a rotatable head. That is, the controller may be positioned at any of eight alternate positions around the cage as indicated by the numbers 1 through 8 in figure 4. To rotate the head, remove the head flange bolts and nuts and position the head as desired.
Mounting Caged Sensor
CAUTION
A caged sensor has a damping plate installed in the lower screwed or flanged connection to provide more stable operation. If the process liquid could clog the plate opening with sediment, then remove the damp­ing plate. For screwed connections, use a 1/2-inch
4
The cage must be installed plumb so that the displacer does not touch the cage wall. Should the displacer touch the cage wall, the unit transmits an erro­neous output signal.
Page 5
2502 Series
AH9150–A A2613–2/IL
Figure
4. Cage Head Mounting Positions
Note
If the controller is not mounted on the sensor, refer to the Installing Controller on Sensor section. That section also provides instructions for adding a heat insulator to a unit. If a temperature-com­pensating displacer or piezometer ring is used, refer to the special installation procedures in this section before pro­ceeding.
Cage connections will normally be either 1-1/2 or 2-inch (38.1 to 50.8 mm) screwed or flanged. Figure 5 shows the combinations. It is recommended that a drain be installed between the cage and shutoff or hand valve whenever the bottom cage line has a liq­uid-trapping low point.
Mount the cage by running equalizing lines between the cage connections and the vessel (figure 6). On liquid or interface level applications, position the sen­sor so that the line marked FLOAT CENTER on the cage is located as close as possible to the center of the liquid level or interface level range being mea­sured.
A1271–2/IL
Figure 5. Cage Connection Styles
For liquid or interface level applications, it is advanta­geous to install a gauge glass either on the vessel, or on the sensor cage (if the cage is tapped for a gauge). With flanged connections, use standard gaskets or other flat-sheet gaskets compatible with the process liquid. Spiral wound gaskets without compression-con­trolling centering rings cannot be used for flanged con­nections.
Mounting Cageless Sensor
CAUTION
If a stillwell is used, it must be installed plumb so that the displacer does not touch the wall of the stillwell. Should the displacer touch the wall while the unit is in service, the unit will transmit an erroneous output signal.
Since the displacer hangs inside the vessel, it is advis­able to provide a stillwell around the displacer when the liquid is in a state of continuous agitation and ex­cessive turbulence can be expected.
5
Page 6
2502 Series
CENTER
OF LIQUID OR INTERFACE LEVEL
SHUTOFF VALVES
VENT
EQUALIZING LINE
DRAIN
DF5379-A A6771/IL
Figure
6. Caged Sensor Mounting
CAUTION
Since a displacer used in an interface level or a density application must be completely submerged during opera­tion, obtaining desired controller sensi­tivity requires the use of either a thin­wall torque tube or an overweight displacer, or both. An overweight dis­placer cannot be used for any service except those conditions for which it was specified.
Note
W0645-1
  
TOP MOUNTED
If the controller is not mounted on the sensor, refer to the Installing Controller on Sensor section. That section also provides instructions for adding a heat insulator to a unit. If the sensor has a temperature-compensated displacer or piezometer ring, refer to the special constructions procedures in this sec­tion before proceeding.
Attach a cageless sensor to a flanged connection on the vessel as shown in figure 7. For interface or liquid level applications, install a gauge glass on the vessel.
6
CF5380-A A3893/IL
Figure
7. Cageless Sensor Mounting

CAUTION
If the displacer is to be inserted into the vessel before being attached to the dis­placer rod, provide a suitable means of
Page 7
supporting the displacer to prevent it from dropping into the vessel and suf­fering damage.
To help support a Type 249BP or 249CP displacer, install the displacer stem and stem end piece, or a threaded rod, into the 1/4 inch-28 UNF threaded hole in the displacer spud or stem end piece (figure 8). On the Type 249BP with optional travel stop, the stem end piece pins will secure the displacer as long as the travel stop plate is installed and the sensor head is in position.
Side-Mounted Sensor
If a stillwell is required (figure 7), the displacer must be attached to the displacer rod from inside the vessel. Connect the displacer as shown in figure 8, locking the assembly with the cotter spring provided. If a stillwell is not required, the displacer can be attached to the displacer rod before mounting the sensor to the vessel connection. The displacer may then be swung out hor­izontally for insertion into the vessel. If an extension is used between the displacer spud and the displacer stem end piece, make sure the nuts are tight at each end of the displacer stem extension. Install and tighten suitable bolting or cap screws in the flanged connec­tion to complete the installation.
2502 Series
DISPLACER STEM END PIECE
DISPLACER STEM EXTENSION
W0229-1A/IL
DISPLACER SPUD
W0228-1A/IL
   
  
Figure 8. Displacer/Displacer Rod Connections
COTTER SPRING
LOCKING NUTS
DISPLACER SPUD
COTTER SPRING
DISPLACER ROD
DISPLACER ROD
Top-Mounted Sensor
Figure 7 shows the installation of a top-mounted cage­less sensor. The displacer may be attached to the dis­placer rod before installing the sensor on the vessel. Where the displacer diameter is small enough, it may be desirable to install a long or sectionalized displacer through the sensor head access hole after the sensor is installed on the vessel. Connect the displacer as shown in figure 8, locking the assembly with the cotter springs provided. If a stem is used between the dis­placer as shown in figure 8, lock the assembly with the cotter springs provided. If a stem is used between the displacer spud and the stem end piece, make sure the nuts are tight at each end of the stem. Install and tight­en suitable cap screws in the flanged connection to complete the installation.
Special Constructions
Temperature-Compensated Displacer
Some sensors use a temperature-compensated dis­placer (figure 9). This displacer is appropriate for den­sity applications that do not tolerate specific gravity changes due to temperature. The displacer must be filled with the liquid to be measured, or with a liquid of equal expansion coefficient. In service, the displacer
A0746–1/IL
Figure
9. Temperature-Compensated Displacer
7
Page 8
2502 Series
expands and contracts the same amount as the mea­sured liquid to nullify signal changes that would be caused by temperature changes.
This type of displacer is shipped in a separate carton but crated with the rest of the assembly. See the ap­propriate sensor manual for filling instructions.
Piezometer Ring
A piezometer ring (figure 10) is used when it is desir­able to measure the specific gravity of a liquid in a flowing line, and when the liquid velocity exceeds two feet/minute (10 mm/second) past the displacer in the cage. The piezometer ring reduces the velocity effects caused by liquid passing through the displacer cage.
To install this type of sensor, connect a line to the cage inlet and outlet piping at each end of the cage. Use hand valves to balance the liquid flow through the cage and keep the displacer cage filled. It is advisable to provide a rotameter or sight flow gauge for measur­ing velocity through the cage. If the flow rates are properly balanced, the transmitter output will show little change when flow through the cage is shut off. If the flow rate through the cage is too high the turbu­lence may cause an erratic output pressure signal. Readjust hand valves to stabilize the output pressure signal.
Regulator Supply Pressure
WARNING
Do not overpressurize any system com­ponent. Personal injury or property damage may occur due to sudden pres­sure release or explosion. To avoid damage, provide suitable pressure-re­lieving or pressure limiting devices if supply pressure can exceed the maxi­mum supply pressure listed in table 1.
Personal injury or property danage may occur from an uncontrolled process if the supply medium is not clean, dry, oil­free, or non-corrosive gas. Industry in­strument air quality standards describe acceptable dirt, oil, and moisture con­tent. Due to the variability in nature of the problems these influences can have on pneumatic equipment, Fisher Con­trols has no technical basis to recom­mend the level of filtration equipment required to prevent performance degra­dation of pneumatic equipment. A filter or filter regulator capable of removing
A1317-1/IL
Figure
10. Piezometer-Ring Cage for Flow Line Mounting
particles 40 microns in diameter will suf­fice for most applications. Use of suit­able filtration equipment and the estab­lishment of a maintenance cycle to monitor its operation is recommended.
Standard 2502 Series controllers come complete with supply and output pressure gauges and an integrally mounted Type 67FR regulator to reduce supply pres­sure from a maximum of 250 psig (17.3 bar) to the 20 or 35 psig (1.4 or 2.4 bar) required. This regulator has built-in relief and a standard 40-micron to remove par­ticles from the supply source.
The output pressure connection is on the back of the controller case (figure 3). Pipe the supply pressure to the in connection of the regulator mounted to the case back. Provide a clean, dry, and noncorrosive air or gas supply to the controller as follows:
After pressure connections have been made, turn on the supply pressure and check all connections for leaks.
8
Page 9
29A2834-C
30A8943-H A1933/IL
2502 Series
RESET ADJUSTMENT
W5637/IL/A
Prestartup Checks
WARNING
The following calibration procedure re­quires taking the controller out of ser­vice. To avoid personal injury and prop­erty damage caused by an uncontrolled process, provide some temporary means of control for the process before taking the controller out of service.
21A6447-A A1903/IL
Figure 11. Controller Adjustments
Adjustment locations are shown in figure 11 unless otherwise indicted. When performing the checks, open loop conditions must exist. One way to obtain an open loop is to ensure that there is no flow through the final control element. Another way to obtain an open loop is to disconnect the controller output signal line and plug the output connection.
During startup, it is necessary to change process lev­els to position the displacer from its maximum to its minimum range of operations. Provide a means to change the process level or interface. If the process variable cannot be varied sufficiently, follow the in-
1E8731-C 1E8732-C A1897-1/IL
9
Page 10
2502 Series
structions in the Calibration section to simulate the process variable changes required for these checks.
Make sure that the raise level dial on the controller is mounted with the correct side facing out. The dial is printed on both sides with the arrow on one side point­ing to the left and the arrow on the other side pointing to the right. Figure 11 shows the dial arrow positioned for a sensor that is mounted to the left of the control­ler; the arrow points to the left. If the sensor is to the right of the controller, remove the two mounting screws, turn the dial over so the arrow points to the right, then reinstall the mounting screws.
On a controller with optical mechanical indicator as­sembly, the travel indicator plate is printed on both sides. If the sensor is to the left of the controller (right­hand mounting), use the side of the plate that has the arrow pointing to the left. If displacer is to right of con­troller (left-hand mounting), use the side of the plate that has the arrow pointing to the right.
1. Turn on the supply pressure and check that the controller supply gauge reads 20 psig (1.4 bar) for a 3 to 15 psig (0.2 to 1.0 bar) output pressure range or 35 psig (2.4 bar) for a 6 to 30 psig (0.4 to 2.0 bar) output pressure range. If the pressure is incorrect, loosen the locknut of the filter/regulator (figure 3); turn the adjust­ing screw clockwise to increase or counterclockwise to decrease pressure. Tighten the locknut after setting the pressure.
2. Turn the reset control to .05 minutes per repeat.
3. Locate the process variable at its minimum value (on level applications, for instance, lower the liquid below the displacer). Zero the proportional band and raise level controls. Output pressure on direct-acting controllers should be greater than zero but less than 3 psig (0.2 bar) for the 3 to 15 psig (0.2 to 1.0 bar) range or 6 psig (0.4 bar) for the 6 to 30 psig (0.4 to 2.0 bar) range. For reverse-acting controllers, the output pres­sure should be greater than 15 psig (1.0 bar) and less than 20 psig (1.4 bar) for the 3 to 15 psig (0.2 to 1.0 bar) range or greater than 30 psig (2.0 bar) and less than 35 psig (3.4 bar) for the 6 to 30 psig (0.4 to 2.0 bar) range. On a controller with indicator assembly, the pointer should be over the low point on the indica­tor plate; slight adjustment might be necessary by loosening the bottom shaft nut (key 40, figure 16), shifting the pointer, and retightening the nut.
4. Set the raise level control as desired. Determine the dial setting by moving the nameplate slide until the specific gravity on scale B is opposite the displacer volume on scale A. Choose the percentage of displac­er length, as measured from the displacer bottom, that you desire the liquid or interface level to cover. Locate this percentage on scale D, and read up from this per­centage to find the raise level dial setting on scale C. For example, with a liquid level application, a specific
gravity of one (water service), and a 90-cubic-inch (1.5 L) displacer, move the slide so that 1.0 on scale B is over 90 on scale A. If it is desired to have water level cover 50 per cent of the displacer length at the control point, read up from 50 on scale D to find a 4.5 dial set­ting on scale C.
5. Relocate the process variable to the control point determined in step 4. If not, see if another setting on the raise level dial brings the output pressure into agreement with the process. For example, with water level at 50 percent of the height of the displacer, the output of a 3-15 psig (0.2 to 1.0 bar) unit should be aproximately 50 percent of the way between 3 and 15 psig (0.2 and 1.0 bar) or 9 psig (0.6 bar). If the new setting is more than one graduation away from the setting determined in step 4, the unit would appear to be out of calibration and recalibration may be desir­able. See Calibribration Procedure on page 12 steps 1 thru 10.
On a controller with level indicator, the pointer should reflect the magnitude of the process variable; for instance, with liquid or interface level covering 50 per­cent of the displacer, the pointer should be in the middle of the high-low scale. Slight plate adjustment might be necessary as described at the end of step 3.
6. If all prestartup checks are satisfactory proceed to the Startup section.
Adjustments
Controller adjustments are provided in this section. Refer to figure 11 for adjustment locations.
Level Set Adjustment
To perform the level adjustment, open the controller cover, loosen the knurled adjustment screw (see figure
11), and rotate the adjustment lever around the RAISE LEVEL dial. To raise the fluid or interface level, or in­crease density, rotate this knob in the direction of the arrows. To lower the level or decrease density, rotate the knob in the opposite direction. This procedure is the same for both direct and reverse action controllers. Tighten the knurled screw.
Note
The raise level dial does not reflect actu­al fluid level in the tank or fluid level position on the displacer.
Proportional Band Adjustment
Proportional band adjustment is made to change the amount of displacement force change required to ob­tain full output pressure change, by determining the
10
Page 11
2502 Series
percentage of pressure fed back to the proportional bellows. The adjustment is performed by opening the controller cover and turning the percent proportional band knob (just below the raise level dial).
Reset Adjustment
To adjust reset action (figure 11) turn the knob clock­wise to decrease the minutes per repeat. Turn the knob counterclockwise to increase the minutes per repeat. Increasing the minutes per repeat provides a slower reset action.
The reset rate adjustment dial is calibrated in minutes per repeat. By definition, this is the time in minutes required for the reset action to produce a correction which is equal to the correction produced by propor­tional control action. This is, in effect, the time in min­utes required for the controller to increase (or de­crease) its output pressure by an amount equal to a proportional increase (or decrease) caused by a change in control conditions.
Differential Relief Adjustment
The differential relief valve protrudes from the back of the controller case on a construction with an F in the type number. Although normally factory-set to relieve when the differential between the proportional and re­set bellows reaches 5 psi, the differential may be re­duced down to 2 psi by turning the adjustment screw clockwise or increased up to 7 psi by turning the screw counterclockwise. The minimum differential setting will yield the minimum set point overshoot during startup.
Depending on the characteristics of the process, the relief valve can be positioned so that the arrow cast on the case points either to the letters RE (reset) or to the letter P (proportional) on the back of the manifold. To reposition the arrow, see figure 11. Remove the mounting screws. Reposition the differential relief valve to RE or P and reinstall the mounting screws.
To calibrate a controller, it is necessary to place the device into operation. This may be done on the vessel with the actual service liquid. It may also be done in the shop, but other means of obtaining a displacement force change must be provided. It must be done in the shop if the process variable is not available for calibra­tion or if the process cannot be varied for calibration. There are two methods of adapting the calibration pro­cedure to shop calibration: wet and dry.
Wet Calibration
Remove the entire controller and sensor assembly from the vessel. For caged sensors, pour the liquid into the cage. For cageless sensors, suspend the dis­placer to an appropriate depth in a liquid having a spe­cific gravity equal to that of the process liquid.
If necessary, use water for wet calibration in the shop. However, this procedure requires compensation for the difference between the specific gravity of the water and that of the process liquids. For example, assume that the process liquid has a specific gravity of 0.7 and that wet calibration with water (specific gravity of 1.0) is desired. To simulate a process level of 50 percent of the input span, a water level of 35 percent is required (0.7/1.0 x 50 percent = 35 percent).
Dry Calibration
Remove the controller and torque tube arm, as a single unit, from the cage or vessel. Then, wherever the standard calibration instructions in this manual re­quire a specific process variable for input to the sen­sor, simulate that variable by suspending the proper weight (such as a can of sand) from the end of the displacer rod. Complete the following Controller and Torque Tube Arm Disassembly and the Determining Suspended Weight for Calibration sections before pro­ceeding to the calibration procedure.
Controller and Torque Tube Arm Disassembly
Calibration
Precalibration Requirements
Note
Calibration of a unit with a displacer de­signed for interface or density control must be conducted with the displacer completely submerged in a liquid of the specific gravity for which the unit was designed.
WARNING
To avoid personal injury from contact with the process liquid, lower the vessel level below the sensor torque tube arm, or shut off the cage equalizing valves and drain the cage before proceeding. For closed vessels, release any pres­sure that may be in the vessel before removing the sensor assembly.
When removing the displacer from the displacer rod or removing the controller and torque tube arm from the
11
Page 12
2502 Series
cage or vessel, refer to the appropriate sensor instruc­tion manual for assistance. The method of removing the displacer or torque tube arm and attached control­ler will vary with the type of sensor.
For a caged sensor with top equalizing connection, it may be appropriate to remove the entire cage from the vessel before disassembling.
CAUTION
If the displacer is to be disconnected from the displacer rod before the sensor assembly is removed from the cage or vessel, provide a means of supporting the displacer to prevent it from dropping and suffering damage. The spuds or stem end pieces on all displacers have holes suitable for inserting rods or other supports.
Additionally, a threaded rod may be installed into the 1/4-inch 28 UNF threaded hole in the displacer spud or stem end piece of top-mounted cageless and all caged sensors. For some top­mounted sensors with long displacers, it may also be possible to remove the sensor through the access hole in the sensor head.
For Type 249BP sensor with the travel stop, the stem end piece pins will se­cure the displacer as long as the travel stop plate is installed and the sensor head is in position.
Determining Suspended Weight for Calibration
where:
Ws = Total suspended weight in pounds (should
never be less than 0.5 pounds). For a unit with a horizontal displacer, make sure the center of gravity of the substitute weight is where it would be on the actual displacer.
Note
For liquid level control only, simulate the lower range limit of the input span by suspending the displacer from the displacer rod. For other values of input span, remove the displacer and suspend the appropriate weight as determined in the equation above.
Wd = Weight of the displacer, in pounds (determine
by weighing displacer).
0.0361 = Weight of one cubic inch of water (specific gravity = 1.0), in pounds.
V = Volume of the displacer in cubic inches, that
would be submerged at the level required by the calibration procedure. Or,
V = π/4 (displacer diameter)2 x (length of displacer
submerged)
SP GR = Specific gravity of the process liquid at
operating temperature.
For interface level measurement, the equation be­comes:
Ws = Wd - [(0.0361) (V1) (SP GR1) +
(0.0361) (Vh) (SP GRh)]
where:
CAUTION
To avoid overloading a torque tube sized for interface or density applica­tions under dry conditions, consult your Fisher Controls sales office or sales rep­resentative for the maximum allowable substitute weight Ws that can be used with your particular construction.
To determine the total weight that must be suspended from the displacer rod to simulate a certain condition of liquid level or specific gravity, solve the following equation:
Ws = Wd - [(0.0361) (V) (SP GR)]
12
V1 = Volume of the displacer submerged by the
lighter liquid, in cubic inches.
Or,
V = π/4 (displacer diameter)2 x (length of the dis-
placer submerged)
SP GR1 = Specific gravity of the lighter liquid at op-
erating temperature.
Vh = Volume of the displacer submerged by the
heavier liquid, in cubic inches.
Or,
V = π/4 (displacer diameter)2 x (length of the dis-
placer submerged)
Page 13
2502 Series
Table 2. Minimum and Maximum Limits for Setting Process Variables
Application Minimum Limit Maximum Limit
Liquid level Displacer must be completely out of liquid Displacer must be completely submerged in liquid
Interface
Density
Displacer must be completely submerged in the upper
of two process liquids
Displacer must be completely submerged in liquid having
highest specific gravity expected
Displacer must be completely submerged in the lower
of two process liquids
Displacer must be completely submerged in liquid
having the lowest specific gravity expected
SP GRh = Specific gravity of the heavier liquid at
operating temperature.
Calibration Procedure
WARNING
The following calibration procedure re­quires taking the controller out of ser­vice. To avoid personal injury and prop­erty damage caused by an uncontrolled process, provide some temporary means of control for the process before taking the controller out of service.
Figure 11 shows adjustment locations for the following steps, except as otherwise indicated. When calibrat­ing, open loop conditions must exist. One way to ob­tain an open loop is to place the final control element into manual control or bypass it. If there is no provision for manual control, shut down the process. It is recom­mended that a test pressure gauge be installed in the controller output line for subsequent calibration steps.
Several steps in these calibration procedures require setting the process variable at its minimum and maxi­mum limits according to table 2. Reverse-acting con­trollers produce the opposite response.
1. Connect a supply pressure source to the controller and provide a supply pressure suitable for the sensing element range: 20 psig (1.4 bar) for a 3 to 15 psig (0.2 to 1.0 bar) output pressure range or 35 psig (2.4 bar) for a 6 to 30 psig (0.4 to 2.0 bar) output pressure range.
2. Rotate the reset knob to 0.01 minutes per repeat.
3. Rotate the proportional band knob to zero.
4. Set the liquid at the minimum limit (dry displacer).
5. Turn the raise level knob to zero.
8. Turn the raise level knob until the out put pressure is 15 psig for a 3 to 15 psig signal range (1.0 bar for a 0.2 to 1.0 bar signal range) or 30 psig for a 6 to 30 psig sig­nal range (2. 0 bar for a 0.4 to 2.0 bar signal range).
9. The controller is within its calibration accuracy if the raise level knob is between the 9.0 and 10.0 positions.
10. If the controller is out of calibration, adjust the cal­ibration adjuster as follows:
Note
Loosen the two calibration adjuster screws (key 45, figure 16), and slide the calibration adjuster (key 100, figure 16) in the desired direction.
a. If output is below 15 psig for a 3 to 15 psig sig­nal range (1.0 bar for a 0.2 to 1.0 bar signal range) or 30 psig for a 6 to 30 psig signal range (2.0 bar for a 0.4 to 2.0 bar signal range) , move the adjus­tor a small distance away from the pivot to in- crease span. Then repeat steps 4 through 9.
b. If output is above 15 psig for a 3 to 15 psig sig­nal range (1.0 bar for a 0.2 to 1.0 bar signal range) or 30 psig for a 6 to 30 psig signal range (2.0 bar for a 0.4 to 2.0 bar signal range), move the adjustor a small distance toward the pivot to decrease span. Then repeat steps 4 through 9.
Note
If the controller cannot be calibrated, look for other problems as described in the Troubleshooting section, such as a nonperpendicular flapper-nozzle condi­tion, leaky connections, or a binding displacer rod. If none of these troubles is apparent, th e di spl acer or to rqu e tu be is probably sized for a different set of ser­vice conditions. Ensure that the displacer is sized correctly for the application.
6. Adjust the nozzle until output pressure is between 0 and 3 psig for a 3 to 15 psig signal range (0 and 0.2 bar for a 0.2 to 1.0 bar signal range) or 0 and 6 psig for a 6 to 30 psig signal range (0 and 0.4 bar for a 0.4 to 2.0 bar signal range).
7. Set the liquid at the maximum limit (covered dis­placer).
Startup
Adjustment locations are shown in figure 11.
1. Set the raise level control to the desired control point as determined in prestartup checks step 4.
13
Page 14
2502 Series
2. Set the percent proportional band control to 200.
3. Set the reset control to .05 minutes per repeat.
4. Slowly open the downstream and upstream manual control valves in the pipeline and close the manual bypass valve if one is used.
5. With the controller set at the desired control point, narrow the proportional band until a cycling condition exists. Then broaden the proportional band slightly until stable control is obtained.
6. Adjust the reset control to obtain the highest reset setting without introducing cycling.
7. To ensure that the optimum proportional band and reset settings have been obtained, momentarily create a load upset. If cycling occurs, broaden the proportion­al band slightly and repeat the load upset until stability is attained. In general, the narrowest proportional band and the highest reset setting that will not produce cycl­ing will provide the best control.
Principle of Operation
All 2502 Series controllers use the same basic pres­sure-balanced relay with a yoked double-diaphragm assembly (figure 12). This relay is connected so that supply pressure is fed to the inlet side of the relay valve and to the fixed restriction. From this restriction, the air pressure goes into the relay chamber on the side of the large diaphragm, and to the nozzle. As long as there is no pressure change on either diaphragm, the relay valve remains in equilibrium with both the inlet and exhaust ends closed.
Type 2502 Controller
As long as inflow and outflow of the vessel ar e equal, the beam and flapper remain mot ionless and allow sup­ply pressure to bleed through the nozzle as fast as it enters the relay thr ough the fixed rest rict ion. A level or density change either raises or lowers the displacer and pivots the beam and flapper with respect to the nozzle.
An increase in level or density with direct action, or a decrease with reverse action, moves the beam and flapper closer to the nozzle and restricts the escape of supply pressure. This builds up the loading differential on the side of the large diaphragm and opens the relay valve to supply pressure inflow.
On the other hand, a decrease in level or density with direct action, or an increase with reverse action, moves the beam and flapper away from the nozzle and permits supply pressure to bleed through the nozzle faster than it can enter through the fixed restric­tion. This builds up the loading differential on the side of the small diaphragm, and opens the relay valve to exhaust loading pressure.
The three-way proportional valve can be opened and adjusted to allow some or all of the output pressure change to feed back to the proportional bellows in or­der to change the proportional band of the controller. This pushes the beam and flapper opposite the way it is being pivoted by the torque tube shaft, counteract­ing the pressure change in the nozzle and again stabi­lizing the relay diaphragm pressure differential. The relay valve shuts off and maintains a new output pres­sure according to the change in sensed displacer posi­tion.
The area ratio of the large diaphragm to the small dia­phragm is 3 to 1. A 12 psig (0.8 bar) pressure change on the small diaphragm need only be balanced by a 4 psig (0.3 bar) change on the large diaphragm.
A change in liquid level, interface level, or density changes the buoyant force exerted on the sensor dis­placer, which in turn imparts a rotary motion through the torque tube shaft. The rotary motion is applied to the controller, which uses a nozzle, bellows, and pneu­matic relay to convert the rotary motion to a standard pneumatic output signal. The output signal is sent to a final control element. In conjunction with this control element, 2502-249 Series controller-sensors are capa­ble of bringing the controlled variable back to a specif­ic control point all the time.
The following descriptions show how the relay works in conjunction with the standard proportional-plus-reset controller, and how the reset relief valve construction works.
14
A wide-open proportional valve permits feedback of all the output change and produces 100 percent propor­tional response. Closing of this valve produces smaller proportional responses, since part of the output change is vented through the valve exhaust and only the remainder is available to reposition the bellows.
The reset valve can be adjusted to channel some or all of the proportional pressure into a reset bellows that opposes proportional bellows action. This automatical­ly dampens the effect of any proportional overcorrec­tion by a set amount per time interval, as long as there is a deviation from the control point.
Figure 12 illustrates these principles at work in a di­rect-acting right-hand-mounted construction controlling liquid inflow to a vessel, by means of a direct-acting diaphragm-actuated control valve. Nozzle positions and bellows connections would be reversed for direct action with left-hand mounting or reverse action with right-hand mounting.
Page 15
2502 Series
CD2114-A CJ4081-A C0313-1
Figure
12. Direct-Acting Right-Hand-Mounted 2502-249 Series Controller
Type 2502F Controller with Reset Relief Valve
This construction (figure 13) has a differential relief valve used to prevent proportional pressure from ex-
ceeding reset pressure by more than a set value, a feature useful for intermittent control applications. Pro­portional valve output registers in the outer chamber of the relief valve as well as in the proportional bellows.
15
Page 16
2502 Series
CJ4081-A CU7387-B C0311-2
Figure
13. Type 2502F Controller with Reset Relief Valve
A sudden increase in the output pressure will cause a rapid pressure increase in the proportional bellows and in the outer relief valve chamber. If the outer chamber pressure exceeds that in the inner relief valve cham­ber by the amount of the relief pressure setting, the relief diaphragm will move off the orifice in the relief valve, and the pressure in the outer chamber will bleed into the reset system. This action provides quick relief of excessive proportional pressure and reduces the time required by the system to return to the control point.
Maintenance
The 2502 Series controllers are used in combination with 249 Series sensors. Due to the care Fisher Con­trols takes in meeting all manufacturing requirements (heat treating, dimensional tolerances, etc.), use only replacement parts manufactured or furnished by Fish­er Controls.
WARNING
Personal injury or property damage due to sudden release of pressure, contact with hazardous liquid, fire, or explosion can be caused by puncturing, heating, or repairing a displacer that is retaining process pressure or liquid. This danger may not be readily apparent when disas­sembling the sensor or removing the displacer. Before disassembling the sensor or removing the displacer, ob­serve the more specific warning pro­vided in the sensor instruction manual.
Troubleshooting
When troubleshooting, open loop conditions must exist unless otherwise stated. When monitoring the process variable, use the most accurate level indicting device readily available. The output signal measuring device should have a corresponding accuracy.
16
Page 17
2502 Series
Table 3 lists some common operating faults, their probable causes, and corrective action.
Removing Controller from Sensor
WARNING
To avoid injury in the following steps, turn off the supply pressure and careful­ly release any pressure trapped in the controller before breaking any pressure connection. Provide a bypass for the control device if continuous operation is required during maintenance.
Refer to figure 16 for key number locations, unless otherwise indicated.
1. Disconnect the supply and output pressure tubing from the controller.
Changing Mounting Method
WARNING
To avoid injury from contact with the process liquid, lower the vessel level below the torque-tube arm before pro­ceeding. For closed vessels, release any pressure that may be above the liquid. Also, be careful to avoid overloading a thin-wall torque tube and/or overweight displacer.
Refer to figure 16 for key number locations.
1. Remove the controller as described previously.
2. A controller is attached to the sensor in one or the other of the mounting positions shown in figure 4. Right hand mount is with the case to the right of the displacer when looking at the front of the case. Left hand mount is with the case to the left of the displacer. For a 249 Series sensor, remove the torque tube arm from the sensor or vessel and reinstall the torque tube arm in the opposite position according to the appropri­ate instruction manual.
2. Loosen the hex nut (key 40) that secures the oper­ating arm base or pointer assembly (key 68 or 51) to the torque tube rotary shaft. Do not lose the two link bearings (key 87, not shown).
CAUTION
If the hex nut has not been loosened ac­cording to step 2, attempting to remove the controller from the sensor may bend the rotary shaft or operating arm and linkage. Be careful that the back of the controller case or the heat insulator does not drop down and bend the rotary shaft or shaft extension.
3. Remove any insulating tape from the joint between the controller case and the torque tube arm. Remove he four cap screws (key 39, figure 14) that hold the controller or heat insulator to the torque tube arm. Pull the case straight out from the torque tube arm, easing it over the shaft coupling (key 36, figure 14) if one is installed.
4. If the controller has a heat insulator, remove the button head cap screws (key 40). Remove four wash­ers (key 53) and the insulator assembly (key 35).
3. Check the desired control action to determine if it is also necessary to reverse the controller action. The nozzle block and bellows tubing should be arranged in the proper position as shown in figure 15.
4. Remove the raise level dial, turn it over, and install it in the desired position. The arrow on it under the word FLOAT should point toward the displacer. On a controller with indicator assembly, remove two screws (key 41, figure 16), turn the front plate (key 54, figure
16) to the side that will have the float arrow pointing toward the displacer, and secure the plate with the screws.
5. Install the controller according to the next section.
Installing Controller on Sensor
Note
If the installation is in a location that is not readily accessible and shop calibra­tion is required, remove the torque tube arm from the cage or vessel before mat­ing the controller to the sensor. Install the controller on the torque tube arm in the shop; then calibrate and return the controller and torque tube arm assem­bly to the installation.
17
Page 18
2502 Series
Fault Possible Cause Check Correction
1. Process wanders or cycles around setpoint.
2. Controller controlling off setpoint or switching point.
3. Controller cannot attain full output range.
4. Controller remains at full or zero output pressure.
Table
3. Troubleshooting Chart for 2502 Series Controllers
1.1 Proportional band or specific gravity adjsutment incorrect or improperly tuned control loop.
1.2 Supply pressure varying or incorrect supply pressure setting.
1.3 Sensor not plumb and is in contact with sidewall or leak in displacer.
1.4 Relay malfunction. 1.4 Check for relay malfunction by
2.1 Supply pressure not set correctly.
2.2 Leak in the controller loop. 2.2 Use soap and water to check
2.3 Leaking displacer. 2.3 Insure the displacer is not filling
2.4 Flapper adjustment. 2.4 Insure the flapper is not loose
2.5 Process variable changed. 2.5 Insure the process variable has
3.1 Supply pressure not set correctly.
3.2 Flapper adjustment. 3.2 Insure the flapper is not loose
3.3 Process variable changed. 3.3 Insure the process variable has
3.4 Relay malfunction. 3.4 Check for relay malfunction by
3.5 Leaking controller loop. 3.5 Use soap and water to check
4.1 Supply or output pressure gauge malfunction
4.2 Flapper adjustment. 4.2 Insure the flapper is not loose
1.1 Insure the prestartup procedures are completed correctly. Tune control loop.
1.2 Use input pressure gauge to monitor stability. Make sure regulator IN supply pressure is withlin limits.
1.3 Check cage vessel and stillwell installation, or for leaking displacer.
using the testing relay deadband procedure
2.1 Make sure regulator supply pressure is set correctly. Make sure regulator IN supply pressure is within limits.
for internal and external leaks.
with process fluid.
on the torque tube shaft and is centered on the nozzle.
not changed from original calibration settings or, displacer not design specific gravity of process.
3.1 Make sure supply pressure is set correctly. Make sure regulator IN supply pressure is within limits.
on the torque tube shaft and is centered on the nozzle.
not changed from original calibration settings or, from displacer design specific gravity.
using the testing relay deadband procedure.
for internal and external leaks.
4.1 Insure the pressure gauges are registering correctly.
on the torque tube shaft. Insure the flapper is centered on the nozzle.
1.1 If stable control cannot be attained and all other elements are functionally correct, examine other ossible causes related to the controller/transmitter.
1.2 Apply correct supply pressure. It is recommended to use one regulator per instrument.
1.3 Make sure the displacer and displacer rod hangs freely. Make sure linkage is tight. Replace displacer if leaking.
1.4 Depress plunger to clean out the fixed restriction. Replace or repair relay using the procedure in the Maintenance section.
2.1 Reset the supply regulator pressure. If the condition occurs again, rebuilld or replace regulator. Provide a regulator input pressure within regulator limits.
2.2 Replace or repair leaking parts as necessary.
2.3 Refer to sensor maintenance procedures in the appropriate sensor instruction manual.
2.4 Replace or tighten flapper assembly as necessary and/or center flapper on nozzle.
2.5 Change process variable back to original sepcification or recalibrate. If necessary, provide replacement displacer of correct size and recalibrate.
3.1 Reset the regulator pressure. If problem reoccurs, replace or rebuild the regulator. Insure regulator IN supply pressure is within limits at all operating levels.
3.2 Replace or tighten flapper assembly as necessary and/or center flapper on nozzle.
3.3 Change process variable back to original specificaton or recalibrate. If necessary, provide replacement displacer of correct size and recalibrate.
3.4 Depress plunger to clean out the fixed restriction. Replace or repair relay using the procedure in the Maintenance section.
3.5 Replace or repair leaking parts as necessary.
4.1 Replace pressure gauges. Use corrective action given in section 3 of this table.
4.2 Replace or tighten flapper assembly as necesary and/or center flapper on nozzle.
Perform step 1 only if adding a heat insulator to a unit that does not have one. Key numbers in this step are shown in figure 14.
18
1. To install the heat insulator, secure the shaft exten­sion (key 37) to the torque tube assembly rotary shaft with the shaft coupling (key 36). Tighten both set screws (key 38), with the coupling centered as shown
Page 19
2502 Series
20A7423-C/DOC
Figure
14. Heat Insulator Shown Installed on 249 Series
in the figure. Then mount the insulator assembly (key
35) on the controller case with four washers (key 53) and button-head cap screws (key 40). Tighten the screws.
CAUTION
In the following step, avoid bending the torque tube rotary shaft of the torque tube assembly. Bending or side loading of this shaft could cause erroneous readings. Additionally, make sure the ball bearing assembly (key 12, figure 16) is removed from the case (key 1, figure
16) to provide clearance when installing the case on the sensor.
2. Remove the bearing assembly (key 12) from the case (key 1).
3. Carefully slide the controller case straight in, guid­ing the bearing assembly (key 12), operating arm base or pointer assembly (key 68 or 51, figure 16) over the rotary shaft and easing an attached heat insulator over the shaft coupling (key 36, figure 14) if necessary. Se­cure the case or insulator to the torque tube arm with the four cap screws (key 39, figure 14).
AV2323-A AV2322-A B0995-2/IL
Figure
15. Nozzle, Flapper, and Tubing Arrangements
for Various Actions and Mountings
Note
If a heat insulator is used, do not insu­late its exterior.
4. On a unit without a heat insulator, tape the joint between the case and torque tube arm to minimize the entrance of atmospheric moisture around the torque tube rotary shaft.
19
Page 20
2502 Series
5. Install and tighten the bearing assembly (key 12) in the case (key1). Secure the operating arm base or point­er assembly to the rotary shaft by tightening the hex nut (key 40, figure 16). Connect the supply and output pr es­sure tubing and perform the calibrat ion procedure.
Changing Proportional, Reset, or Differential Relief Valve
1. Remove the proportional band valve assembly (key 36, figure 16) by unscrewing it from the relay base (key 23, figure 16). Install the desired replacement assembly, or a 1/8-inch (3.2 mm) NPT pipe plug into the proportional band tapping if testing relay dead band.
2. To change the reset restrict ion valve assembly (key
91), remove the two mounting screws (key 182) located on the back side of case. Install the replacement valve assembly, and reconnect the tubing connections.
3. Remove the differential relief valve assembly (key 186, figure 16) by removing the two mounting screws (figure 11) that anchor the valve to the manifold (key 184, figure 16). Install the valve with the arrow pointing to the same letter(s) as before removal, unless it is desired to change the relief action.
Testing Relay Dead Band
1. Replace the proportional band adjustment assem­bly with a 1/8-inch (3.2 mm) NPT pipe plug according to the Changing Proportional, Reset, or Differential Relief Valve section.
2. Turn on the supply pressure and set it to 20 or 35 psig (1.4 or 2.4 bar).
3. By changing the process variable and adjusting the raise level control, set the output pressure to 15 or 30 psig (1.0 or 2.0 bar). While monitoring the output pres­sure, slowly change the process until an output pres­sure change can just be detected, and record the val­ue of the process variable at the detection point.
4. Change the process variable in the opposite direc­tion until another output pressure change can be de­tected, and again record the value of the process vari­able. If the difference between the two recorded values (the dead band) is more than 0.2 percent of the maximum displacer length, the relay will have to be replaced or repaired according to the Changing Relay and the Disassembling Relay sections.
5. Turn off the supply pressure, remove the pipe plug, and install the proportional band adjustment assembly.
Changing Relay
The relay may be removed for cleaning or repair, and must be taken off to remove the lower bellows.
1. On a controller with indicator assembly, loosen the two lower screws (key 96, figure 17) of the relay case and slide out the indicator base plate (key 53, figure 16).
2. Disconnect the tubing (key 11, figure 16) from the relay.
3. Remove both mounting screws, the relay, and the relay gasket (keys 43, 34, and 22, figure 16).
4. Install a new gasket, the replacement relay if nec­essary, and both mounting screws. Reconnect the tub­ing. On a controller with indicator assembly, slide the base plate under the two lower screws of the relay case, align the plate so that the pointer will read prop­erly, and tighten the screws.
Replacing Bellows
Key numbers are shown in figure 16.
1. To gain access to the lower bellows, remove the relay according to the Changing Relay section.
2. Remove the upper and lower bellows frame screws (key 96) that hold both bellows assemblies to the bel­lows frame. Unscrew each bellows from the spacer (key 98), being careful not to lose the O-ring (key 57, not shown) from the spacer end of the bellows.
3. Inspect each bellows and O-ring and replace if nec­essary, using an unpainted bellows for a 3 to 15 psig (0.2 to 1.0 bar) range and a red bellows for a 6 to 30 psig (0.4 to 2.0 bar) range. Be sure to install the O-ring at the spacer end of the bellows.
4. Install each bellows by screwing it down over the stud (key 97, not shown) protruding from each end of the spacer. Secure with a bellows frame screw, and install the relay according to the Changing Relay sec­tion if it was removed.
5. Perform the calibration procedure and any other necessary part of the calibration sequence.
Reversing Action
Note
The following procedure will be neces­sary to restore previous action if the mounting method has been changed. Key numbers are shown in figure 16.
1. Remove two screws (keys 63 and 64), two seal rings (key 55), and the nozzle block (key 101). Check seal ring condition and replace rings as necessary.
2. Install the nozzle block, seal rings, and screws on the opposite side of the beam as shown in figure 15. Disconnect the proportional band tubing (key 76) and one of the two pieces of reset tubing (key 75) from the bellows frame (key 94) and reconnect them in the proper orientation as shown in figure 15.
20
Page 21
2502 Series
Note
Beam overtravel can jam the flapper against the nozzle if the following step is not performed.
3. Remove the flapper screw (key 93), lockwasher (key 84), and flapper (key 60). Invert the flapper so that the flapper hook is on the opposite side of the beam from the nozzle (key 58), and secure with the lockwasher and screw.
4. Perform the calibration procedure and any other necessary part of the calibration sequence.
Disassembling Relay
Disassembly can be accomplished in the following steps. Key numbers are shown in figure 17.
1. Remove the relay according to the Changing Relay section.
2. Remove the orifice assembly (key 88) and check for orifice plugging or damage. Replace the O-ring (key 90) before installing the orifice assembly.
3. Remove the casing screws (key 96) and washers (key 98), casing assembly (key 85), and top dia­phragm (key 91). On a high-temperature relay also remove the top gasket (key 100) that covers the top diaphragm.
4. Remove the spacer ring (key 84), diaphragm as­sembly (key 86), and relay spring (key 92) from the relay body (key 83). On a high-temperature relay also remove the bottom gasket (key 99) from underneath the diaphragm assembly.
5. Remove the screws (key 97), spring plate (key 95), spring plate gasket (key 94), spring (key 93), and valve plug (key 87).
6. Inspect the diaphragms and gaskets and replace if necessary. Also replace the spring and valve plug if they show signs of corrosion. The lower diaphragm comes as part of an assembly and must be installed as such. Clean all parts thoroughly before assembling.
7. Put the valve plug and its spring in the relay body. Replace the spring plate gasket and spring plate and secure with four screws.
8. Place the relay spring in the relay body and, on a high-temperature relay, install a bottom gasket. Install the diaphragm assembly, spacer ring, and top dia­phragm on the body so that all flow passage holes are lined up. On a high-temperature relay also install a gasket over the top diaphragm.
9. Put the casing assembly on the top diaphragm so that the lugs on the casing and spacer ring line up and are also lined up with the body lug.
10. Install the casing screws and tighten them slowly to ensure a good seal.
11. Install the assembled orifice assembly, and install the relay according to the Changing Relay section.
Parts Ordering
Whenever corresponding with the Fisher Controls sales office or sales representative about this equip­ment, always mention the controller type number and the serial number found on the unit nameplate (figure
11). When ordering replacement parts, also state the complete 11-character part number of each required part as found in the following parts list.
Parts Kits
Key Description Part Number
Controller Parts Kit
Contains keys 12, 15, 21, 24, 38, 55, 57, 58, 60, 62, 63, 64, 77, 79, 84, 86, 87, 93, 101, and 187
Standard Temperature High Temperature
Relay Parts Kit
Contains keys 22, 85, 86, 87, 88, 90, 91, 92, 93 and 94,
(99 and 100 high temp only)
Standard Temperature RRELAY X0L12 High Temperature
Relay Replacement Kit
Contains keys 22, 43, and the relay assembly
Standard Temperature RRELAY X0L22 High Temperature
Heat Insulator Parts Kit
Contains keys 35, 36, 37, 38, 39, 40, and 53
Parts
List
Heat Insulator (figure 14)
35 Heat Insulator Assembly, stainless steel 22A0033 X012 36 Shaft Coupling, stainless steel 37 Shaft Extension, K-Monel 38 Set Screw, stainless steel (2 req’d) 1E6234 X0022 39 Cap Screw, steel, pl (4 req’d) 40 Cap Screw, steel, pl (4 req’d) 53 Washer, carbon steel, pl (4 req’d)
Controller Common Parts (figure 16)
1 Pilot Case Back, zinc
Types 2502 and 2502C
Type 2502F 23A2073 X012 2 Pilot Case Cover, aluminum 50B9454 X012 3 Door Handle, steel, pl 4 Door Handle Shaft (not shown),
stainless steel 5 Machine Screw, stainless steel 6 Washer Spring, stainless steel 7 Door Hook, steel, pl 8 Elastic Stop Nut, steel, pl 9 Drive Pin, (2 req’d)
11 Relay Tubing
Copper 17A9100 X012
Stainless steel (2502 and 2502C only) 17A9100 X022
12* Ball Bearing Ass’y, brass, pl
R2502 X0L52
R2502 X0H52
RRELAY X0H12
RRELAY X0H22
R2500XH 0012
1A5779 35032 1B6815 40022
1A3816 24052 1V2395 28982 1B8659 28982
1J4157 44012
1C8972 25082
1C8984 14012
1C8958 X0022
1C8970 36032
1C8971 25082 1C8959 X0012 1C8991 X0022
1C8983 000A2
*Recommended spare part.
21
Page 22
2502 Series
30A8942-H/DOC
43A2366-H/DOC
30A8943-H/DOC
22
Figure 16. 2502 Series Controller Constructions
Page 23
2502 Series
Key Description Part Number
13 Retaining Ring, steel, pl (zinc case
cover only) (2 req’d) 14* Gauge Glass, glass, (2 req’d) 15* Gauge Glass Gasket, neoprene, (2 req’d) 18 Instruction Label, aluminum 29A2834 X012 19* Pressure Gauge (2 req’d)
Brass, triple scale
0-30 psig/0-0.2MPa/0-2.0 bar 11B8577 X012 0-60 psig/0-0.4MPa/0-4.0 bar 11B8577 X022
Stainless steel, triple scale
0-30 psig/0-0.2MPa/0-2.0 bar 11B8583 X012
0-60 psig/0-0.4MPa/0-4.0 bar 11B8583 X022 21* Cover Gasket, nitrile 22* Relay Gasket
Standard, neoprene
High-temperature, rubber 23 Relay Base, aluminum 47A0950 X012 24* Relay Base Gasket (not shown)
Standard, neoprene
High-temperature, rubber 29 Drive-lok Pin, stainless steel 31 Shaft Clamp Screw, stainless steel 34 Pilot Relay (parts shown under separate heading)
Standard 22B0463 X012
High-temperature 22B0462 X012 35 Level Adjustment Ass’y 10A8939 X0A2 36 Proportional Valve Ass’y 10A9122 X042 38* Filter Gasket (not shown)
Standard, neoprene
High-temperature, rubber 39 Cap Screw (not shown), steel, pl (2 req’d) 40 Hex Nut, stainless steel 41 Screw, steel, pl (4 req’d for Type
2502C and FC, 2 req’d for all others) 42 Machine Screw, stainless steel, (8 req’d) 1V7435 X0022 43 Machine Screw, stainless steel (2 req’d) 1A3776 X0012 44 Machine Screw, steel, pl (4 req’d) 1A5733 X0012 45 Machine Screw, stainless steel (2 req’d) 47 Spring (not shown), stainless steel 49 Machine Screw, stainless steel (13 req’d) 1B7839 X0012 50 Screen, stainless steel 51 Pointer Ass’y (Type 2502C and FC only),
stainless steel/brass, pl 53 Base Plate, aluminum
(Type 2502C and FC only) 54 Front Plate, aluminum
(Type 2502C and FC only) 55*
O-Ring, (3 req’d)
Standard, nitrile
High-temperature, fluoroelastomer 57* O-Ring (not shown)
Standard, nitrile
High-temperature, fluoroelastomer 58* Nozzle, stainless steel 59 Beam, steel, pl 60 Flapper, Invar 61 Flapper Base, stainless steel 62* Connecting Link, Monel 63 Sealing Screw, stainless steel 14A5721 X012 64 Screw, stainless steel 24A5720 X012 65* Bellows Ass’y, brass (2 req’d)
3 to 15 psig (0.2 to 1.0 bar) 14A5726 X012
6 to 30 psig (0.4 to 2.0 bar) 14A5726 X032 66 Level Set Arm, steel, pl 67 Operating Arm, steel, pl 68 Operating Arm Base, brass, pl
Types 2502 and 2502F only)
(1)
36
1A4658 28992 0T0192 06042 0T0191 04082
1C9198 06432
1C8974 03012 1N8738 04142
1C8973 03012 1N8739 04142 1C8989 X0012
1B4514 35172
1C8986 03012 1N8740 04142 1C3988 X0022
1L2863 38992
1C9419 X0012
1H2675 X0012
1J4234 37022
0L0783 43062
1R2425 X0012
1E8731 11992
1E8732 11992
1D6875 06992 1N4304 06382
1E2226 06992 1N8387 06382 1U6391 35132
1K8738 25072
1J4162 41132 1J4163 35032 1L3796 41012
1J4164 25072 1J4165 25072
1J4166 14022
Key Description Part Number
69 Level Set Pivot Pin, stainless steel 70 Pivot Base, steel, pl 19A9689 X012 71 Spring Washer, stainless steel 72 Washer, stainless steel
Types 2502 and 2502FC, (2 req’d) 1E8730 X0012
Type 2502C (4 req’d) 1E8730 X0012 74 Washer, stainless steel, (6 req’d) 75 Reset Tubing Ass’y (2 req’d),
copper 1J4169 000A2
stainless steel (2502 and 2502C only) 19A1887 X012 76 Proportional Band Tubing Ass’y
copper 1J4170 000A2
stainless steel (2502 and 2502C only) 1J4170 X0012 77* Bellows Frame Gasket (not shown)
Standard, neoprene
High-temperature, rubber 78 Spacer (not shown), brass 79* Bellows Gasket (2 req’d)
Standard, neoprene
High-temperature, rubber 80 Machine Screw, stainless steel, (4 req’d) 81 Machine Screw (not shown)
stainless steel, (2 req’d) 1P4373 X0012 82 Machine Screw, stainless steel, (4 req’d) 1B2752 X0022 83 Lock Washer, stainless steel (2 req’d) 84 Lock Washer, stainless steel 85 Cap Screw, stainless steel, not shown (4 req’d) 1A3816 K0012 86 Machine Screw, stainless steel (2 req’d) 1A8664 X00A2 87* Link Bearing (not shown)
stainless steel (2 req’d) 88 Machine Screw (not shown),
stainless steel, (4 req’d) 1J4159 X0012 89 Machine Screw, stainless steel, (2 req’d) 91 RESET Restriction Valve Ass’y
Types 2502 and 2502C
Standard 19A4357 X012 High-temperature 19A4357 X022
Type 2502F and 2502FC
Standard 19A4359 X012
High-temperature 19A4359 X032 93 Machine Screw, stainless steel 1B8776 X0012 94 Bellows Frame, aluminum 95 Bellows Frame Base (not shown), steel, pl 96 Bellows Screw, brass, pl (2 req’d) 97 Bellows Stud (not shown), brass 98 Spacer, zinc 99 Cross Spring, stainless steel (2 req’d)
100 Calibration Adjuster, zinc 101 Reversing Block, zinc 26A0975 X012 180 Pipe Nipple (not shown) Type 2502F
and 2502FC only), steel
181 Relief Tubing Ass’y (Type 2502F and
2502FC only), copper 13A2077 X012
182 Machine Screw, stainless steel, (2 req’d)
Types 2502 and 2502C (not shown) 1B7839 X0012 Type 2502F and 2502FC
183* O-Ring (2 req’d), Type 2502F and 2502FC only
Standard, nitrile
High temperature, fluoroelastomer
184 Manifold, aluminum, (Type 2502F and
2502FC only) 23A2072 X012 185 Manifold Nipple, aluminum (Type 2502F only) 13A2074 X012 186 Differential Relief Valve Ass’y (Type 2502F and 2502FC only)
Standard 21A6447 X0A2 High temperature 21A6447 X012
187 Sleeve, plastic 16A0976 X012
1J4167 35162
1H8851 X0012
6100057 0X12
1H2654 03012 1N8735 04142
1J6198 15122
1D3970 03012 1N8736 04142
1H2678 X0012
6100081 0X12
1C3162 X0012
1L3795 46202
1H8162 X0012
2H2653 08012
1J4160 25142 1D3976 14022 1H2658 14012 1H2659 44012 1H2660 37032 2H2662 44012
1C5599 26232
1C8969 X0012
1D6875 06992 1N4304 06382
*Recommended spare part.
1. Invar is a mark owned by Carpenter Technology Corp.
23
Page 24
2502 Series
22B0463-A/DOC
22B0462-A/DOC
  
Figure 17. Relay Constructions
Key Description Part Number
188* 0-Ring (Type 2502F and 2502FC only),
Standard High temperature
215 Nameplate, metal 12B6337 X0A2
1C8538 06992 1C8538 X0052
Relay (figure 17)
83 Relay Body, aluminum/brass 48A3776 X012 84 Spacer Ring, aluminum 38A3778 X012 85 Casing Ass’y, aluminum/steel 12B0460 X012 86* Diaphragm Ass’y
Standard, nitrile/nylon 18A2451 X012
High-temperature, polyacrylate/nylon 18A2451 X092 87* Valve Plug, brass 88* Orifice and Core Ass’y, brass 12B0468 X012 90* O-Ring, nitrile, (2 req’d)
Standard
High temperature
Level-Trol, Fisher, Fisher-Rosemount, and Managing The Process Better are marks owned by Fisher Controls International, Inc. or Fisher-Rosemount Systems, Inc. All other marks are the property of their respective owners.
EFisher Controls International, Inc. 1977, 1994; All Rights Reserved
                                                                 
For information, contact Fisher Controls:
Marshalltown, Iowa 50158 USA Cernay 68700 France Sao Paulo 05424 Brazil Singapore 128461
24
Printed in U.S.A.
0Y0617 14012
1D6875 06992 1N4304 06382
Key Description Part Number
91*
Top Diaphragm
Standard, nitrile
High-temperature, polyacrylate 1K6999 X0012 92 Relay spring, steel, pl 93 Valve Spring, stainless steel 94* Spring Plate Gasket
Standard, neoprene
High-temperature, rubber 95 Spring Plate, steel, pl 96 Machine Screw, stainless steel, (6 req’d) 1A3294 X0022 97 Machine Screw, stainless steel 98 Washer (standard only), stainless steel (6 req’d) 1P8261 X0012 99* Bottom Gasket (high-temperature only), rubber
100* Top Gasket (high-temperature only), rubber
*Recommended spare part.
(4 req’d)
1L5556 02042
1C8961 27012 0X0836 37022
1H2696 03012 1K7000 04142 1H2697 25072
1A8664 X00A2
1K7001 04142 1K7002 04142
Loading...