Fisher, Fisher-Rosemount, and Managing The Process Better are marks
owned by Fisher Controls International, Inc. or Fisher-Rosemount Systems, Inc.
All other marks are the property of their respective owners.
Fisher Controls International, Inc. 1977, 1997; All Rights Reserved
D200124X012
Page 2
Type 2500
Contents
Principle of Operation
Type 2500 Controller or Type 2500T
Transmitter21.
Proportional Valve21.
Type 2500S Controller21.
Type 2503 Controller21.
Maintenance
Troubleshooting23
Removing Controller/Transmitter from
Sensor23.
Changing Mounting Methods25.
Installing Controller/Transmitter on Sensor26.
Replacing the Bourdon Tube26.
Changing Action26.
Relay Deadband Testing (Type 2500 Controller
or 2500T Transmitter Only)27.
Replacing the Proportional Valve27.
Changing Relay28.
These instruments control or transmit the fluid level,
the level of interface between two fluids, or the density
20.
(specific gravity). Each unit consists of a 249 Series
displacer-type fluid level sensor and a 2500 or 2503
Series pneumatic controller or transmitter. Figure 1
shows a typical controller-sensor combination.
Specifications
22
Refer to table 1 for specifications.
Installation
The 2500 and 2503 Series controller/transmitters work
in combination with 249 Series displacer-type sensors.
The factory attaches the controller/transmitter to the
sensor, unless it is ordered separately.
Sensor Assembly
29.
Table 2 lists sensors recommended for use with controller/transmitters. For sensor installation and mainte-
29.
nance, refer to the appropriate sensor instruction
manual.
Introduction
Scope of Manual
This manual provides installation, operating, calibration, maintenance, and parts ordering information for
the 2500 and 2503 Series pneumatic controllers and
transmitters used in combination with 249 Series displacer sensors.
Note
This manual does not include installation or maintenance procedures for the
supply pressure regulator, sensor, or
other devices. For that information, refer
to the appropriate instruction manual
for the other device.
Only qualified personnel should install, operate, and
maintain these controller/transmitters. If you have any
questions concerning these instructions, contact your
Fisher Controls sales office or sales representative
before proceeding.
WARNING
When replacing the sensor assembly,
the displacer may retain process fluid or
pressure. Personal injury or property
damage may occur due to sudden release of the pressure. Contact with hazardous fluid, fire, or explosion can be
caused by puncturing, heating, or repairing a displacer retaining process
pressure or fluid. This danger may not
be readily apparent when disassembling
the sensor assembly or removing the
displacer. Before disassembling the
sensor or removing the displacer, observe the more specific warning provided in the sensor instruction manual.
Uncrating
Unless ordered separately, the controller/transmitter is
attached to the sensor when shipped. Carefully uncrate the assembly.
2
Page 3
Table 1. Specifications
Type 2500
Available Configurations
(1)
Type 2500—Proportional-Only controller
Type 2500C—Proportional-Only controller with indi-
cator (see figure 12)
Type 2500R—Reverse acting proportional-only
controller
Type 2500S—Differential gap (snap acting) controller. See changing controller action procedure and
figure 17.
Type 2500T—Transmitter
Type 2503—Differential gap controller without pro-
portional valve; for applications requiring very little
adjustment.
Input Signal
(2)
Fluid Level or Fluid-to-Fluid Interface Level:
From 0 to 100% of displacer length—standard
lengths for all sensors are 14 inches or 32 inches
(356 mm or 812 mm). Other lengths available depending on sensor construction.
Fluid Density: From 0 to 100% of displacement
force change obtained with given displacer volume.
Standard volume for displacers are listed in table 2.
Output Signal
(2)
Type 2500 Controller and 2500T Transmitter: 3
to 15 psig (0.2 to 1 bar) or 6 to 30 psig (0.4 to 2 bar)
Type 2500S and 2503 Differential Gap Controllers: 0 psig (0 bar) when switched off and full sup-
ply [20 or 35 psig (1.4 or 2.4 bar) nominal depending on controller output pressure range] when
switched on.
Area Ratio of Relay Diaphragms
3:1
Supply Pressure Data
See table 3
Maximum Supply Pressure
(3)
(3)
45 psig (3 bar) to the controller or transmitter. If
controller or transmitter is equipped with an integrally mounted Type 67FR filter/regulator, typical supply pressure to the regulator is from 35 psig (2.5
bar) to 250 psig (17 bar), maximum. For supply
pressures to the filter/regulator, refer to the appropriate regulator instruction manual.
Steady-State Air Consumption
2500 Series Controllers and Transmitters (2500,
2500C, 2500R, 2500S, and 2500T): See Table 3.
Type 2503 Controller: Vents only when relay is
exhausting.
Proportional Band
(2)
Adjustment (Proportional-
Only Controllers)
Full output pressure change adjustable over 10 to
100% of displacer length.
Differential Gap
(2)
Adjustment (Differential Gap
(5)
Controllers)
Type 2500S Controller: Full output pressure
change adjustable from 20 to 100% of displacer
length.
(5)
Type 2503 Controller: Full output pressure change
adjustable over approximately 25 to 40% of displacer length.
Span
Full output pressure change adjustable from 20 to
100% of displacer length.
Set Point
(5)
(2)
Adjustment (Type 2500T Transmitter)
(5)
(2)
(controllers only) or Zero
ters only) Adjustment
For proportional-only controllers or transmitters,
level adjustment positions the set point or zero for
the fluid level, interface level, or displacer force
change (density) within the displacer length.
For differential gap controllers, level adjustment simultaneously positions both ends of the gap within
the displacer length.
Performance
Independent Linearity
(2)
(transmitters only): 1%
of output pressure change for 100% span.
Hysteresis: 0.6% of output pressure change at
100% proportional band, differential gap, or span.
Repeatability
placement force change.
Deadband
(4)
lers
): 0.05% of proportional band or span.
(2)
: 0.2% of displacer length or dis-
(2)
(except differential gap control-
Typical Frequency Response
gree phase shift at 100% proportional band with
output piped to typical instrument bellows using 20
feet of 1/4-inch tubing.
Ambient Operating Temperature Limits
For ambient temperature ranges and guidelines for
use of the optional heat insulator assembly, see
figure 2. Relay temperature limits are:
Standard Construction: -40 to 160F (-40 to
71C)
High-Temperature Construction: 0 to 220F (-18
to 104C)
(continued)
(2)
(transmit-
(2)
: 4 Hz and 90 de-
3
Page 4
Type 2500
PRESSURE GAUGE
SUPPLY PRESSURE
Table 1. Specifications (Continued)
Typical Ambient Temperature Operating Influence
Output pressure changes 1.5% per 50F
(10C)change in temperature at 100% proportional
band when using a standard wall torque tube with
249 Series sensors.
1. Controllers are field adjustable between direct or reverse action. The letter R in the type number indicates that the controller/transmitter shipped from the factory set for reverse action (see
changing controller action procedures). The letter C in the type number indicates that a pointer is attached to the torque tube shaft providing visual monitoring of torque tube motion.
2. This term is defined in ISA Standard S51.1-1979.
3. Control and stability may be impaired if the maximum pressures are exceeded.
4. Adjusting the span of the differential gap controller is equivalent to adjusting the deadband.
5. These statements apply only to units sized to produce a full output change for a 100% level change at the maximum proportional band dial setting.
1. With standard 12-inch (305 mm) flange-face-to-displacer centerline dimension only.
STANDARD VOLUME,
Cubic Inches
Supply and Output Connections
1/4-inch NPT female
Maximum Working Pressure (sensors only)
Refer to the appropriate sensor instruction manual.
100
60
120
80
STANDARD VOLUME,
(1)
Liters
1.6
1.0
1.9
(1)
1.3
Table 3. Supply Pressure Data
STANDARD SUPPLY
OUTPUT SIGNAL RANGE
3 to 15 psig (0.2 to 1 bar)0 to 30 psig201.44.2 scfh
6 to 30 psig (0.4 to 2 bar)0 to 60 psig352.47 scfh
1. Consult your Fisher Controls representative about gauges in other units.
2. Control and stability may be impaired if this pressure is exceeded.
3. At zero or maximum proportional band or specific gravity setting.
4. At setting in middle of proportional band or specific gravity range.
5. If air consumption is desired in normal m3/hr at 0C and 1.01325 bar, multiply scfh by 0.0258.
AND OUTPUT
PRESSURE GAUGE
INDICATIONS
NORMAL OPERATING
SUPPLY PRESSURE
(1)
PsigBarMinimum
(2)
AIR CONSUMPTION AT
NORMAL OPERATING
SUPPLY PRESSURE
(3)
(5)
(5)
Maximum
27 scfh
42 scfh
MAXIMUM
(4)
(5)
(5)
SUPPLY PRESSURE
45 psig (3 bar)
45 psig (3 bar)
4
Page 5
Type 2500
AMBIENT TEMPERATURE (C)
01020
–10
–18
1100
800
400
–20
–40
PROCESS TEMPERATURE ( F)
HEAT INSULATOR
REQUIRED
0
NO INSULATOR NECESSARY
USE INSULATOR (CAUTION! IF AMBIENT DEWPOINT IS ABOVE
PROCESS TEMPERATURE, ICE FORMATION MAY CAUSE INSTRUMENT MALFUNCTION AND REDUCE INSULATOR EFFECTIVENESS.)
020406080100120140160
AMBIENT TEMPERATURE (F)
3040506070
TOO
HOT
71
NOTE:
FOR APPLICATIONS BELOW –20F (–29C), BE SURE THE SENSOR
MATERIALS OF CONSTRUCTION ARE APPROPRIATE FOR THE SERVICE
TEMPERATURE.
CV6190–E
B1413-2/IL
Figure 2. Guidelines for Use of Optional Heat Insulator Assembly
CAUTION
Sensors used for interface or density
control may be so large and heavy that
the torque tube cannot fully support
their weight in air. On the 249V, a travel
stop is used to prevent damage. Do not
remove this travel stop assembly without first removing the displacer from the
displacer rod. Refer to the instruction
manual for cageless 249 Series sensors.
593
500
400
300
200
100
–18
–29
–40
PROCESS TEMPERATURE ( C)
–18
–10
1100
800
400
PROCESS TEMPERATURE ( F)
–20
HEAT INSULATOR
REQUIRED
NO INSULATOR NECESSARY
0
USE INSULATOR (CAUTION! IF AMBIENT DEWPOINT IS ABOVE PROCESS
TEMPERATURE, ICE FORMATION MAY CAUSE INSTRUMENT MALFUNCTION
AND REDUCE INSULATOR EFFECTIVENESS.)
020406080100120 140200
AMBIENT TEMPERATURE (C)
0
1020
3040506070
AMBIENT TEMPERATURE (F)
W2141–1B/IL
8090
180160
DISPLACER
CAGE
100
TOO
HOT
105
220
593
500
400
300
200
100
0
PROCESS TEMPERATURE ( C)
Note
Caged sensors have rods and blocks
installed at each end of the displacers to
protect the displacers in shipping. Remove these parts before you install the
sensor to allow the displacer to function
properly.
Caged sensors come with the displacer installed in the
cage. If a tubular gauge glass is ordered with the sensor, the gauge glass is crated separately and must be
installed at the site. A damping plate is installed in the
lower screwed or flanged connection (see figure 3) to
provide more stable operation. Be certain that the
cage equalizing connections and the damping plate
are not plugged by foreign material.
W0144–1/IL
DAMPING PLATE
Figure
SCREWED
CONNECTION
FLANGED
CONNECTION
3. Damping Plate Location
5
Page 6
Type 2500
tion changes the control action from direct to reverse,
or vice versa.
All caged sensors have a rotatable head. That is, the
controller/transmitter may be positioned at any of eight
alternate positions around the cage as indicated by the
numbers 1 through 8 in figure 4. To rotate the head,
remove the head flange bolts and nuts and position
the head as desired.
Mounting Caged Sensor
CAUTION
Install the cage so that it is plumb; the
displacer must not touch the cage wall.
If the displacer touches the cage wall,
the unit will transmit an erroneous output signal.
Note
AH9150–A
A2613–1/IL
Figure
4. Cage Head Mounting Positions
A cageless sensor comes with its displacer separated
from the sensor assembly. Displacers longer than 32
inches (813 mm) come in a separate crate. Shorter
displacers come in the same crate as the sensor, but
are not attached to their displacer rods. Inspect the
displacer to insure it is not dented. A dent may reduce
the pressure rating of the displacer. If a displacer is
dented, replace it.
Controller/Transmitter Orientation
The controller/transmitter attaches to the sensor in
one of the mounting positions shown in figure 4. Right
hand mounting is with the controller or transmitter
case to the right of the displacer when you look at the
front of the case; left hand mounting is with the case
to the left of the displacer. The mounting position can
be changed in the field. Changing this mounting posi-
If the controller/transmitter is not
mounted on the sensor, refer to the
Installing Controller/Transmitter on Sensor procedures in the Maintenance section. That section also provides instructions for adding a heat insulator to a
unit.
If a temperature-compensated displacer
or piezometer ring is used, refer to the
Special Installation procedures in this
section before proceeding.
Cage connections normally are either 1-1/2 or 2-inch,
screwed or flanged. Figure 5 shows the combinations.
With flanged connections, use standard gaskets or
other flat-sheet gaskets compatible with the process
fluid. Spiral-wound gaskets without compression-controlling centering rings cannot be used for flange connections.
As shown in figure 6, mount the cage by running
equalizing lines between the cage connections and the
vessel. A shutoff or hand valve with a 1-1/2 inch diameter or larger port should be installed in each of the
equalizing lines. Also install a drain between the cage
and shutoff or hand valve whenever the bottom cage
line has a fluid-trapping low point.
On fluid or interface level applications, position the
sensor so that the center line on the cage (see figure
6) is as close as possible to the center of the fluid level
or interface level range being measured. Also consider
installing a gauge glass on the vessel, or on the sensor cage (if the cage is tapped for a gauge).
6
Page 7
Type 2500
Mounting Cageless Sensor
CAUTION
If a stillwell is used, install it plumb so
that the displacer does not touch the
wall of the stillwell. If the displacer
touches the wall, the unit will transmit
an erroneous output signal.
Since the displacer hangs inside the vessel, provide a
stillwell around the displacer if the fluid is in a state of
continuous agitation to avoid excessive turbulence
around the displacer.
CAUTION
Displacers used in an interface level application must be completely submerged during operation. To obtain the
desired controller or transmitter sensitivity may require using either a thinwall torque tube, an oversized displacer,
or both.
A1271–2/IL
CENTER OF
LIQUID OR
INTERFACE LEVEL
DF5379-A
A1883-2/IL
Figure
5. Cage Connection Styles
SHUTOFF
VALVES
EQUALIZING LINE
Figure 6. Caged Sensor Mounting
EQUALIZING LINE
DRAIN VALVE
Note
If the controller/transmitter is not
mounted on the sensor, refer to the
Installing Controller/Transmitter on Sensor procedures in the Maintenance section. That section also provides instructions for adding a heat insulator to a
unit. If the sensor has a temperaturecompensated displacer or piezometer
ring, refer to the Special Installations
procedures in this section before proceeding.
Attach a cageless sensor to a flanged connection on
the vessel as shown in figure 7. For interface or fluid
level applications, install a gauge glass on the vessel.
Side-Mounted Sensor
If a stillwell is required (see figure 7), attach the displacer to the displacer rod from inside the vessel.
Connect the displacer as shown in figure 8, locking the
assembly with the cotter spring provided. If a stillwell
is not required, attach the displacer rod before mounting the sensor on the vessel. Then, you can swing the
displacer out horizontally for insertion into the vessel.
However, once the sensor is installed and the displacer drops to a vertical position, the displacer may not
be capable of being withdrawn for servicing later. Be
sure there is another access to the displacer to permit
swinging it to a horizontal position or to permit disconnecting it from the displacer rod.
7
Page 8
Type 2500
SIDE
MOUNTED
TOP
MOUNTED
W0645–1/IL
Figure
7. Cageless Sensor Mounting
If an extension is used between the displacer spud
and the displacer stem end piece, make sure the nuts
are tight at each end of the displacer stem extension.
Install and tighten suitable bolting or cap screws in the
flanged connection to complete the installation.
Top-Mounted Sensor
CAUTION
If inserting the displacer into the vessel
before attaching to the displacer rod,
provide a means of supporting the displacer to prevent it from dropping into
the vessel and suffering damage.
Figure 7 shows an example of a top-mounted cageless sensor. You may attach the displacer to the displacer rod before installing the sensor on the vessel. If
the displacer diameter is small enough, you may desire to install a long or sectionalized displacer through
the sensor head access hole after the sensor is
installed on the vessel. Connect the displacer as
shown in figure 8, locking the assembly with the cotter
springs provided. If a stem extension is used between
the displacer spud and the stem end piece, make sure
the nuts are tight at each end of the stem. Install and
tighten suitable cap screws in the flanged connection
to complete the installation.
A special travel stop may be provided on top-mounted
sensors to aid in servicing of the sensor. This option
prevents dropping the displacer and stem when the
displacer rod is disconnected
Special Installations
Temperature-Compensated Displacer
CAUTION
The bellows style temperature compensating displacers are relatively fragile
and must be protected from all physical
damage.
Some sensor assemblies use a temperature-compensated displacer shown in figure 9. This displacer is
appropriate only for density applications that measure
fluid composition regardless of temperature. The displacer must be filled completely with the fluid to be
measured, or with a fluid of equal volumetric expan-
8
Page 9
DISPLACER
STEM
END PIECE
DISPLACER
STEM
EXTENSION
COTTER SPRING
LOCKING NUTS
DISPLACER SPUD
DISPLACER ROD
DISPLACER
SPUD
Type 2500
COTTER SPRING
W0229-1A/IL
Figure
8. Displacer and Displacer Rod Connections
Piezometer Ring
A piezometer ring, shown in figure 10, is used when
measuring the specific gravity of a flowing fluid in a
line. The piezometer ring reduces the velocity effects
caused by fluid passing through the displacer cage.
However, the fluid velocity through the cage should
not exceed two feet per minute (10 mm/second).
To install this type of sensor, connect a line to the
cage inlet and outlet piping at each end of the cage.
Use hand valves to balance the fluid flow through the
cage and keep the displacer cage filled. Provide a
rotameter or sight flow gauge for measuring velocity
through the cage. If the flow rates are properly balanced, the transmitter output shows little change when
flow through the cage is shut off. If the flow rate
through the cage is too high, the turbulence may
cause an erratic output pressure signal. Readjust the
hand valves to stabilize the output pressure signal.
W0228-1A/IL
DISPLACER ROD
A0746–1/IL
Figure 9. Temperature-Compensated Displacer
sion coefficient. In service, the displacer expands and
contracts the same amount as the measured fluid to
nullify signal changes that would be caused by temperature changes.
This type of displacer comes in a separate carton, but
is in the same crate as the rest of the assembly. See
the appropriate sensor manual for displacer filling
instructions.
Supply and Output Pressure
Connections
WARNING
To avoid personal injury or property
damage resulting from the sudden release of pressure, do not install any system component where service conditions could exceed the limits given in
this manual. Use pressure-relieving devices as required by government or accepted industry codes and good engineering practices.
9
Page 10
Type 2500
10A1211–A
22A9197–B
CD1700–E
A2708–1/IL
Figure
11. Controller/Transmitter Dimensions and Connections
A6620/IL
Figure
10. Piezometer-Ring Cage for Flow Line Mounting
Figure 11 shows dimensions, locations, and connections for controller/transmitter installation. All pressure
connections to the controller/transmitter are 1/4-inch
NPT female.
Supply Pressure
WARNING
Personal injury or property damage may
occur from an uncontrolled process if
the supply medium is not clean, dry, oilfree, or a noncorrosive gas. Industry
instrument air quality standards describe acceptable dirt, oil, and moisture
content. Due to the variability in nature
of the problems these influences can
have on pneumatic equipment, Fisher
Controls has no technical basis to rec-
ommend the level of filtration equipment
required to prevent performance degradation of pneumatic equipment. A filter
or filter regulator capable of removing
particles 40-microns in diameter should
suffice for most applications. Use of
suitable filtration equipment and the establishment of a maintenance cycle to
monitor its operation is recommended.
Supply pressure must be clean, dry air or noncorrosive
gas that meets the requirements of ISA Standard
S7.3-1975 (R1981). Use a suitable supply pressure
regulator to reduce the supply pressure to the normal
operating supply pressure shown in table 3. As shown
in figure 11, a Type 67FR filter/regulator mounts on
the back of the controller/transmitter case and mates
with the supply pressure connection on the controller/
transmitter case. Pipe the supply pressure to the IN
connection of the regulator. Typically, the Type 67FR
filter/regulator accepts supply pressures between 35
and 250 psig (2.5 and 17 bar). For specific regulator
limits, refer to the appropriate regulator instruction
manual.
If operating the controller or transmitter from a high
pressure source [up to 2000 psig (138 bar)], use a
high pressure regulator system, such as the Type
1367 High Pressure Instrument Supply System. For
Type 1367 system installation, adjustment. and maintenance information, see the separate instruction
manual.
10
Page 11
Type 2500
Controller/Transmitter Output Connection
As shown in figure 11, the output pressure connection
is on the back of the controller/transmitter case. After
connecting the output pressure line, turn on the supply
pressure, adjust the filter/regulator to the appropriate
supply pressure required for the controller/transmitter
and check all connections for leaks.
Prestartup Checks
Adjustments are shown in figure 12 unless otherwise
indicated. Open-loop conditions must exist when performing the prestartup checks. To obtain open-loop
conditions:
make sure there is no process flow through the
final control element, or
disconnect the controller/transmitter output signal
line and connect it to a pressure gauge.
During prestartup, the displacer must be positioned
from its maximum to its minimum range of operation.
Provide a means to change the process variable (the
process level or interface). If the process variable cannot be varied sufficiently, use the precalibration procedures in the Calibration section to simulate the process variable changes required for these checks.
Make sure the RAISE LEVEL dial on the controller is
mounted with the correct side facing out. The dial is
marked on both sides with an arrow. The arrow points
to the left on one side and to the right on the other.
When the sensor is mounted to the left of the controller/transmitter, the arrow on the raise level dial should
point to the left, as shown in figure 12. If the sensor is
to the right, the arrow should point to the right. If necessary, remove the two mounting screws, turn the dial
over so the arrow points correctly, and reinstall the
mounting screws. The level directions shown on the
dial will be correct for both direct-acting and reverseacting controllers. For a transmitter, use the same side
of the ZERO ADJUSTMENT dial for both right- and
left-hand sensor mountings.
On a controller or transmitter with an optional mechanical indicator assembly, the travel indicator plate is
also marked with an arrow on both sides. If the sensor
is to the left of the controller/transmitter, the arrow on
the plate should point to the left. If the sensor is to the
right, the arrow should point to the right. If necessary,
reinstall the plate so that the arrow points in the correct direction.
Set the PROPORTIONAL BAND control on a Type
2500 or 2500S controller, or the SPECIFIC GRAVITY
control on a Type 2500T transmitter, as follows:
Sensor with Both Standard Torque Tube and
Standard Volume Displacer—If the torque tube is
standard and the displacer volume is close to that
listed in table 2, use figure 13 to find the PROPORTIONAL BAND or SPECIFIC GRAVITY setting. Locate the specific gravity of the process fluid on fluid
level applications, or the difference between minimum
and maximum specific gravity on interface level or
density applications, on the vertical axis of the chart.
From this location, trace horizontally to the curve with
the desired percentage of displacer used, then trace
vertically up or down to determine the proper dial setting on the horizontal axis.
Sensor with Nonstandard Torque Tube and/
or Displacer with Other than Standard Volume—If
the construction does not have a standard wall torque
tube or has a displacer volume that deviates significantly from the volume listed in table 2, or both, the
PROPORTIONAL BAND or SPECIFIC GRAVITY dial
setting does not necessarily indicate the actual proportional band or specific gravity. To determine the correct dial setting, solve the following equation:
Corrected
Dial Setting
Required
where:
L
= percentage of displacer length desired for full
output pressure change (e.g., if 80% of displacer is used, L = 80)
SP GR = specific gravity of
face level control, use the difference between the specific gravity of the two fluids;
for specific gravity control, use the difference between the upper and lower range
limits of specific gravity).
Va = actual displacer volume, cubic inches listed
on the sensor nameplate.
Vr = standard displacer volume, cubic inches, from
table 2.
X = torque tube factor (1.0 for standard torque
tubes, 2.0 for thin-wall torque tubes, or 0.5
for heavy-wall torque tubes).
(
L
)(SP GR)
100
the process fluid (for inter
V
a
(X)
V
r
-
11
Page 12
Type 2500
LEVEL SET ARM
MOUNTING SCREWS
LEVEL SET
ARM
W0671–1/IL
RIGHT-HAND MOUNTED TYPE 2503R
W0641–1B/IL
BOURDON TUBE DETAIL OF
TYPE 2500S ON-OFF
CONTROLLER
3–WAY VALVE
FLAPPER ALIGNMENT SCREW
SHAFT CLAMP NUT
VENT
ON-OFF CONTROLLER
W0656–1/IL
NOZZLE
PLUNGER
1C9283–B/DOC
RAISE LEVEL DIAL FOR
LEFT-HAND MOUNTING
LEVEL ADJUSTMENT
PROPORTIONAL
BAND ADJUSTMENT
FLAPPERRELAY
SPAN ADJUSTMENT
RIGHT-HAND MOUNTED TYPE 2500
PROPORTIONAL CONTROLLER
12
SPECIFIC GRAVITY
ADJUSTMENT
W0647–2B/IL
ZERO
ADJUSTMENT
DETAIL OF TRANSMITTER
ADJUSTMENTS
W0648–1B/IL
INDICATOR ASSEMBLY WITH
RIGHT-HAND MOUNTING
Figure
12. Adjustment Locations
POINTER
ASSEMBLY
1E8731
1E8732
A1897–1/IL
TRAVEL INDICATOR PLATE
FOR LEFT-HAND MOUNTING
Page 13
NOTE:
EACH CURVE MARKED WITH PERCENTAGE OF DISPLACER USED.
1C9259–G
A3891–1/IL
Figure 13. Proportional Band and Specific Gravity
Setting Chart (chart assumes standard wall torque tube and
displacer volume in table 2)
Type 2500 Controller or 2500T
Transmitter
Note
Type 2500
necessary, extrapolation may be used to determine an
appropriate RAISE LEVEL or ZERO ADJUSTMENT
setting.
Note
The raise level dial does not reflect actual fluid level in the tank or fluid level
position on the displacer.
4. The OUTPUT gauge on a 3 to 15 psig (0.2 to 1
bar) range should read 3 psig (0.2 bar) for direct or 15
psig (1 bar) for reverse action. On a 6 to 30 psig (0.4
to 2 bar) range the OUTPUT gauge should read 6 psig
(0.4 bar) for direct or 30 psig (2 bar) for reverse action.
5. On a controller or transmitter with a mechanical
indicator assembly, the pointer should be over the
LOW point on the indicator plate. If a slight adjustment
is necessary, loosen the side hex clamp nut (key 40,
figure 19), shift the pointer, and retighten the nut.
6. Increase the process variable to the level desired
for full output change. The OUTPUT gauge on a 3 to
15 psig (0.2 to 1 bar) range should read 15 psig (1
bar) for direct or 3 psig (0.2 bar) for reverse action. On
a 6 to 30 psig (0.4 to 2 bar) range the OUTPUT gauge
should read 30 psig (2 bar) for direct or 6 psig (0.4
bar) for reverse action. On a controller or transmitter
with an indicator assembly, the pointer should be over
the HIGH point on the indicator plate; slight plate adjustment may be necessary, as described at the end
of step 5.
7. If all prestartup checks are satisfactory, go to the
startup procedure. If performance is unsatisfactory,
proceed to the Calibration section.
In the following steps the output pressure can go as high as the controller
supply pressure.
1. Turn on the supply pressure and check that the
supply pressure gauge reads 20 psig (1.4 bar) for a 3
to 15 psig (0.2 to 1 bar) or 35 psig (2.4 bar) for a 6 to
30 psig (0.4 to 2 bar) output pressure range. If the
pressure is incorrect, loosen the locknut of the Type
67FR filter/regulator (figure 11); turn the adjusting
screw clockwise to increase the pressure or, counterclockwise to decrease the pressure. Tighten the locknut after setting the regulator pressure.
2. Set the process variable to its minimum value.
3. Make sure that the PROPORTIONAL BAND or
SPECIFIC GRAVITY control is at the setting determined earlier in this section. Then, set the RAISE
LEVEL or ZERO ADJUSTMENT control at an appropriate value according to table 4. This table gives
recommended settings based on maximum and minimum possible PROPORTIONAL BAND and SPECIFIC GRAVITY settings. If an intermediate PROPORTIONAL BAND or SPECIFIC GRAVITY setting is
Type 2500S Controller
Note
In the following steps the output pressure can go as high as the controller
supply pressure.
1. Turn on the supply pressure and check that the
SUPPLY pressure gauge reads 20 psig (1.4 bar) for a
0 to 20 psig (0 to 1.4 bar) output pressure range or 35
psig (2.4 bar) for a 0 to 35 psig (0 to 2.4 bar) output
pressure range. If the pressure is incorrect, loosen the
locknut of the Type 67FR filter/regulator (figure 11);
turn the adjusting screw clockwise to increase the
pressure or counterclockwise to decrease pressure.
Tighten the locknut after setting the pressure.
2. Set the process variable to its minimum value.
3. On a controller with a mechanical indicator assembly, the pointer should be over the LOW point on the
indicator plate. If a slight adjustment is necessary,
loosen the hex clamp nut (key 40, figure 19), shift the
pointer and retighten the nut.
13
Page 14
Type 2500
Table
4. Recommended Settings For Pre-Startup Checks
RECOMMENDED RAISE LEVEL SETTING
FOR TYPE 2500 CONTROLLER
MOUNTINGACTION
-
Right-hand
-
Left-hand
1. For proportional band dial settings between 10 and 0 or for specific
gravity dial settings between 1.0 and 0, interpolate the value.
Direct3.0 to 3.54.0 to 4.51.5 to 2.0 to right0.5 to 1.0 to right
Reverse6.5 to 7.00.5 to 1.01.5 to 2.0 to left4.0 to 4.5 to right
Direct3.0 to 3.54.0 to 4.51.5 to 2.0 to left0.5 to 1.0 to left
Reverse6.5 to 7.00.5 to 1.01.5 to 2.0 to right4.0 to 4.5 to left
For Predetermined
PROPORTIONAL BAND
Dial Setting of 10
For Predetermined
PROPORTIONAL BAND
Dial Setting of 0
RECOMMENDED ZERO ADJUSTMENT SETTING FOR
For Predetermined
SPECIFIC GRAVITY Dial
TYPE 2500T TRANSMITTER
Setting of 1.0
For Predetermined
SPECIFIC GRAVITY Dial
Setting of 0
Note
Adjustment of the RAISE LEVEL control
can set the switching points anywhere
within the length of the displacer. Be
careful not to set the switching points
so that one is off the displacer.
4. Make sure that the PROPORTIONAL BAND control is at the setting determined in the previous procedures. Set the RAISE LEVEL control to 0, then set it
to 1.0 for a direct-acting or 4.0 for a reverse-acting
controller.
5. The OUTPUT gauge should read 0 psig (0 bar) for
direct or supply pressure for reverse action.
6. Increase the process variable until the OUTPUT
gauge changes to either supply pressure for direct or 0
psig (0 bar) for reverse acting. The process variable
should be at the desired high trip value. On a controller with an indicator assembly, the pointer should be
over the HIGH point on the indicator plate; slight adjustment may be necessary, as described at the end
of step 3.
7. Decrease the process variable until the OUTPUT
gauge changes to 0 psig for direct or supply pressure
for reverse action (depending on controller range). The
process variable should be at the desired low trip value.
8. If all prestartup checks are satisfactory, proceed to
the Startup section. If performance is unsatisfactory,
proceed to the Calibration section.
Type 2503 Controller
Note
In the following steps the output pressure can go as high as the controller
supply pressure.
Note
Since the Type 2503 controller has no
proportional valve, the differential gap
between switching points is adjusted by
varying the supply pressure. This gap
can be varied from approximately a
3.5-inch (88.9 mm) level change at 15
psig (1 bar) to a 6.0-inch level change at
25 psig (1.7 bar) with a standard volume
displacer and a fluid with a specific
gravity of 1.0. The gap also varies inversely according to density; a fluid
with 0.8 specific gravity produces a
4.4-inch (112 mm) level change at 15
psig to a 7.5-inch change at 25 psig (1.7
bar). Set the gap at a pressure low
enough to be compatible with the limitations of the diaphragm control valve or
other final control element.
1. Turn on the supply pressure. If necessary, adjust
the Type 67FR regulator to produce the desired differential gap by loosening the locknut (figure 11) and
turning the adjusting screw clockwise to increase or
counterclockwise to decrease pressure. Tighten the
locknut.
2. Locate the process variable at its minimum value.
Note
Adjustment of the RAISE LEVEL control
can set the switching points anywhere
within the length of the displacer. Be
careful not to set the switching points
so that one is off the displacer.
3. Set the RAISE LEVEL control to 0 and then reset it
as follows:
a. For direct-acting controllers, set it between 1.0
and 1.5.
b. For reverse-acting controllers, set it between 3.5
and 4.0.
4. The OUTPUT gauge should read 0 psig (0 bar) for
direct or full supply pressure for reverse action.
14
Page 15
Type 2500
5. Increase the process variable until the OUTPUT
gauge changes to full supply pressure for direct or 0
psig (0 bar) for reverse action. The process variable
should be at the desired high trip value.
6. Decrease the process variable until the OUTPUT
gauge changes to 0 psig for direct or full supply pressure for reverse action. The process variable should
be at the desired low trip value.
7. If all prestartup checks are satisfactory, proceed to
the Startup section. If performance is unsatisfactory,
proceed to the Calibration section.
Adjustments
This section explains controller/transmitter action and
adjustments. Figure 12 shows adjustment locations.
Control Action
The following is a definition of control action.
Direct Action—Increasing fluid level, interface
level, or density, increases the output signal.
Reverse Action—Increasing fluid level, interface
level, or density, decreases the output signal. Controller/transmitters factory-set for reverse-acting have the
suffix letter R added to their type number.
Zero Adjustment (Transmitters Only)
To make a zero adjustment, open the transmitter cover, loosen the adjustment screw and rotate the adjustment lever around the ZERO ADJUSTMENT dial. This
adjustment sets the output pressure to correspond to
a specific level on the displacer. Tighten the knurled
screw.
Proportional Band Adjustment (Except
Transmitters and 2503 Series Controllers)
The proportional band adjustment varies the amount
of process variable change required to obtain a full
output pressure change. To perform this adjustment,
open the controller cover and turn the PROPORTIONAL BAND adjustment (see figure 12). Refer to the
prestartup check procedures to determine the proper
setting.
Specific Gravity Adjustment (Transmitters
Only)
This adjustment also varies the amount of process
variable change required to obtain a full output pressure change. To perform this adjustment, open the
transmitter cover and turn the SPECIFIC GRAVITY
adjustment (see figure 12). Refer to the prestartup
check procedures to determine the proper setting.
The control action is determined by the cage head
mounting position and by the Bourdon tube-flapper
arrangement in the controller/transmitter. Refer to figure 4 for mounting positions and to figure 17 for Bourdon tube-flapper arrangements. To change the action,
refer to the changing action procedure in the Maintenance section.
Level Adjustment (Controllers Only)
To make a level adjustment, open the controller cover,
loosen the knurled adjustment screw, and rotate the
adjustment lever around the RAISE LEVEL dial. To
raise the fluid or interface level, or increase density,
rotate this knob in the direction of the arrows. To lower
the level or decrease density, rotate the knob in the
opposite direction. This procedure is the same for either direct or reverse action. Tighten the knurled
screw.
Note
The raise level dial does not reflect actual fluid level in the tank or fluid level
position on the displacer.
Calibration
Precalibration Requirements
The controller/transmitter can be calibrated in the field,
mounted on the vessel containing the process fluid. It
may also be done in the shop, but other means of obtaining a displacement force change must be provided.
There are wet and dry methods of adapting the calibrating procedure.
Wet Calibration
Remove the entire controller/transmitter and sensor
assembly from the vessel. For caged sensors, pour
the fluid into the cage. For cageless sensors, suspend
the displacer to an appropriate depth in a fluid having
a specific gravity equal to that of the process fluid.
If necessary, you may use water for wet calibration in
the shop. You must compensate for the difference between the specific gravities of water and the process
fluid, however. As an example, assume the process
fluid has a specific gravity of 0.7. The specific gravity
of water is 1.0. To simulate a process level of 50 percent of the input span, would require a water level of
35 percent (0.7/1.0 x 50 percent = 35 percent).
15
Page 16
Type 2500
Dry Calibration
Remove the controller/transmitter and torque tube
arm, as a single unit, from the cage or vessel. Then,
wherever the standard calibration procedures in this
manual require a specific process variable input to the
sensor, simulate the process variable by suspending
the proper weight (such as a can of sand) from the
end of the displacer rod. Complete the following procedures (Controller/Transmitter and Torque Tube Arm
Disassembly) and (Determining the Amount of Suspended Weight) before proceeding to the Calibrating
Procedure.
Controller/Transmitter and Torque Tube
Arm Disassembly
WARNING
To avoid personal injury from contact
with the process fluid, lower the vessel
level below the sensor torque tube arm,
or shut off the cage equalizing valves
and drain the cage before proceeding.
For closed vessels, release any pressure that may be in the vessel before
removing the sensor assembly.
When removing the displacer from the displacer rod or
removing the controller/transmitter and torque tube
arm from the cage or vessel, refer to the appropriate
249 Series instruction manual for assistance. The
method of removing the displacer or torque tube arm
and attached controller/ transmitter varies with the
type of sensor.
For a caged sensor with top equalizing connection, it
may be appropriate to remove the entire cage from the
vessel before disassembling.
CAUTION
the sensor may be removed through the
access hole in the sensor head.
For Type 249BP sensors with travel
stop, the stem end piece pins will secure the displacer on the travel stop as
long as the travel stop plate is installed
and the sensor head is in position.
Determining the Amount of Suspended
Weight
CAUTION
Avoid overloading a torque tube sized
for interface or density applications.
Consult your Fisher Controls sales office or sales representative for the maximum allowable substitute weight, Ws,
that may be used with your particular
construction.
To determine the total weight that must be suspended
from the displacer rod to simulate a certain condition
of fluid level or specific gravity, solve the following
equation:
Ws Wd–[(0.0361)(V)(SP GR)]
where:
Ws = Total suspended weight in pounds (should never
be
less
than 0.5 pounds). For a unit with a hori
zontal displacer, make sure the center of grav
ity of the substitute weight
on the actual displacer.
is where it would be
-
-
If the displacer is to be disconnected
from the displacer rod before the sensor
assembly is removed from the cage or
vessel, provide a means of supporting
the displacer to prevent it from dropping
and suffering damage. The spuds or
stem end pieces on all displacers have
holes suitable for inserting rods or other
supports.
Additionally, a threaded rod may be
installed into the 1/4-inch 28 UNF
threaded hole in the displacer spud or
stem end piece of top-mounted cageless
and all caged sensors. For some topmounted sensors with long displacers,
16
Note
For liquid level control only, simulate
the lower range limit of the input span
by suspending the displacer from the
displacer rod. For other values of input
span, remove the displacer and suspend
the appropriate weight as determined in
the equation above.
Wd = Weight
of the displacer, in pounds (determine by
weighing displacer).
Page 17
Type 2500
Table 5. Minimum and Maximum Limits for Setting Process Variables
APPLICATIONMINIMUM LIMITMAXIMUM LIMIT
Liquid LevelDisplacer must be completely out of liquidDisplacer must be completely submerged in liquid
InterfaceDisplacer must be completely submerged in lighter of two
process liquids
DensityDisplacer must be completely submerged in liquid having
specific gravity of lowest range point
Displacer must be completely submerged in
heavier of two process liquids
Displacer must be completely submerged in liquid having
specific gravity of highest range point
0.0361 = Weight of one cubic inch of water
(specific gravity = 1.0), in pounds.
V
= Volume, in cubic inches, of the portion
of the dis
placer submerged. Or,
V = (π/4) (displacer diameter)2 (length of displacer
submerged)
SP
GR = Specific gravity of
the process fluid at operating
temperature.
For interface level measurement, the equation becomes:
Ws+Wd–[(0.0361)(Vt)(SP GRl)
) (0.0361)(Vh)(SP GRh* SP GRl)]
where:
Vt = Total volume, in cubic inches, of the displacer.
SP
GRl = Specific gravity of the lighter of the fluids at oper
ating temperature.
Vh = Volume, in cubic inches, of the portion of the
displacer submerged in the heavier of the
fluids.
before taking the controller/transmitter
out of service.
Figure 12 shows adjustment locations, except as
-
otherwise indicated. In order to calibrate, open-loop
conditions must exist. One way to obtain an open loop
is to ensure that there is no flow through the final control element. Another way to obtain an open loop is to
disconnect the controller/transmitter output signal line
and plug the output connection with a test pressure
gauge.
Several steps in these calibrating procedures require
setting the process variable at its minimum and maximum limits, according to table 5.
Note
If the process cannot be varied readily
or the Wet Calibration method cannot be
used in the following steps, be sure to
use the proper sequence of correct
weights as found in the Determining
Amount of Suspended Weight proce-
-
dure. Whenever the following steps require particular prestartup checks, refer
to the appropriate procedures for: Type
2500 Controller or 2500T Transmitter,
Type 2500S Controller, or Type 2503
Controller.
Or,
V
= (π/4) (displacer diameter)2 (length
er submerged)
SP
GRh = Specific gravity of the heavier
erating temperature.
Calibration Procedure
WARNING
The following calibration procedures
require taking the controller/transmitter
out of service. To avoid personal injury
and property damage caused by an uncontrolled process, provide some temporary means of control for the process
of the displac
of the fluids at op
Type 2500 Controller and 2500T
Transmitter
-
1. Turn on the supply pressure and check that it is set
according to the appropriate prestartup checks proce-
-
dure.
2. Make sure that the PROPORTIONAL BAND or
SPECIFIC GRAVITY adjustment is at the setting determined according to the appropriate prestartup
check procedure.
3. Adjust the RAISE LEVEL (Type 2500) or ZERO
ADJUSTMENT (Type 2500T) to the appropriate value
per table 4. This table gives recommended settings
based on maximum and minimum possible PROPORTIONAL BAND (Type 2500) or SPECIFIC GRAVITY
(Type 2500T) settings. If an intermediate PROPORTIONAL BAND or SPECIFIC GRAVITY setting is necessary, extrapolation may be used to determine a new
RAISE LEVEL or SPECIFIC GRAVITY setting.
17
Page 18
Type 2500
4. Set the process variable to the minimum value of
the input range as shown in Table 5. For constructions
with an indicator assembly, make sure that the pointer
is over the LOW mark.
Note
In the following step, the alignment
screw (key 33, figure 19) always must
remain screwed in far enough to provide
spring tension on the underside of the
alignment screw head.
5. Adjust the flapper (key 32, figure 19) to obtain the
appropriate pressure listed below. For coarse flapper
adjustment, loosen the hex nut (key 40, figure 19) and
rotate the flapper assembly about the torque tube
shaft. For fine flapper adjustment, turn the flapper
alignment screw (key 33, figure 19).
For Direct Acting Type 2500, 2500T, 3 psig (0.2
bar) for a 3 to 15 psig (0.2 to 1.0 bar) output or 6 psig
(0.4 bar) for a 6 to 30 psig (0.4 to 2.0 bar)output.
For Reverse Acting Type 2500, 2500T, 15 psig
(1.0 bar) for a 3 to 15 psig (0.2 to 1.0 bar) output or 30
psig (2.0 bar) for a 6 to 30 psig (0.4 to 2.0 bar) output.
the indicator plate screws (key 41, figure 19, detail of
indicator assembly), slide the plate until the HIGH
mark is under the pointer. Tighten the plate screws
and go to the Startup section.
Note
Any sliding of the level set arm (key 28,
figure 19) in the following step changes
the zero as well as the output pressure
span.
11. To adjust the output pressure span, loosen the
two level set mounting screws (see figure 19) and
slide the flexure strip base (key 27) right or left along
the elongated slotted hole as follows:
To increase the output pressure span, slide the
flexure strip base away from the torque tube shaft.
To decrease the output pressure span, slide the
flexure strip base toward the torque tube shaft.
Retighten the screws. If the flexure strip base has
been moved as far as possible and the output pressure span is still too large or too small, proceed to step
13.
6. Visually examine the nozzle and flapper to ensure
the nozzle is as square as possible with the flapper.
The nozzle can be realigned by loosening the Bourdon
tube mounting screws (key 45, figure 19) and rotating
the Bourdon tube slightly. If the nozzle is realigned,
tighten the mounting screws and repeat step 5.
7. Set the process variable to the maximum value of
the input range as shown in table 5.
8. The output pressure should be:
For Direct Acting Type 2500, 2500T, 15 psig
1.0 bar) for a 3 to 15 psig (0.2 to 1.0 bar) output or 30
psig (2.0 bar) for a 6 to 30 psig (0.4 to 2.0 bar) output.
For Reverse Acting Type 2500, 2500T, 3 psig
(0.2 bar) for a 3 to 15 psig (0.2 to 1.0 bar) output or 6
psig (0.4 bar) for a 6 to 30 psig (0.4 to 2.0 bar) output.
9. If the output pressure agrees with that shown in
step 8, proceed to step 10. If the output pressure does
not agree, go to step 11.
10. If the unit does not contain an indicator assembly,
go to the Startup section. If the unit contains an indicator assembly, change the pointer span by loosening
12. Repeat the procedure from step 4 until the required calibration points are obtained.
Note
Any change of the PROPORTIONAL
BAND or SPECIFIC GRAVITY adjustment in the following step changes the
zero as well as the output pressure
span.
13. If the flexure strip base has been moved as far as
possible and the output pressure span is still too large
or too small, slightly adjust the PROPORTIONAL
BAND or SPECIFIC GRAVITY adjustment as follows:
If the output pressure span is too large, slightly
increase the PROPORTIONAL BAND or SPECIFIC
GRAVITY setting.
If the output pressure span is too small, slightly
decrease the PROPORTIONAL BAND or SPECIFIC
GRAVITY setting.
14. Repeat the procedure from step 4 until the required calibration points are obtained.
18
Page 19
Type 2500
Note
If you cannot calibrate the controller or
transmitter, look for other problems as
described in the Troubleshooting procedures, such as leaking connections, or a
binding displacer rod. If none of these
troubles are apparent, ensure that the
displacer is sized correctly for the application.
Type 2500S and 2503 Controllers
1. Turn on the supply pressure and check that it is set
according to the appropriate prestartup checks procedure.
2. Make sure that the PROPORTIONAL BAND adjustment (Type 2500S only) is at the setting determined according to the appropriate prestartup check
procedure.
3. Perform one or the other of the following:
For direct acting controllers, set the RAISE
LEVEL adjustment between 1.0 and 1.5.
For reverse acting controllers, set the RAISE
LEVEL adjustment between 3.5 and 4.0.
4. Set the process variable at the minimum value of
the input range as shown in table 5. For constructions
with an indicator assembly, make sure that the pointer
is over the LOW mark.
For Reverse Acting Controllers, move the flap-
per away from the nozzle until the output pressure
switches to 0 psig, then carefully adjust the flapper
toward the nozzle until the output pressure switches to
full supply pressure.
7. Slowly increase the process variable until the output pressure switches:
For Direct Acting Controllers, slowly increase
the process variable until the output pressure switches
to full supply pressure. The process variable should be
at the maximum value of input range as shown in table
5. If the process variable agrees with table 5, proceed
with step 8. If the process variable does not agree with
table 5, proceed to step 9.
For Reverse Acting Controllers, slowly in-
crease the process variable until the output pressure
switches to 0 psig. The process variable should be at
the maximum value of input range as shown in table 5.
If the process variable agrees with table 5, proceed
with step 8. If the process variable does not agree with
table 5, proceed to step 9.
8. If the unit does not contain an indicator assembly,
go to the startup section. If the unit contains an indicator assembly, change the pointer span by loosening
the indicator plate screws (key 41, figure 19, indicator
assembly detail), slide the plate until the HIGH mark is
under the pointer. Tighten the plate screws and go to
the startup section.
Note
In the following step, the alignment
screw (key 33, figure 19) always must
remain screwed in far enough to provide
spring tension on the underside of the
alignment screw head.
5. Be sure the flapper is centered over the nozzle. If
not, loosen the hex nut (key 40, figure 19) and reposition the flapper, tighten the hex nut.
6. Adjust the flapper (key 32, figure 19) as described
below. For coarse flapper adjustment, loosen the hex
nut (key 40, figure 19) and rotate the flapper assembly
about the torque tube shaft. For fine flapper adjustment, turn the flapper alignment screw (key 33, figure
19).
For Direct Acting Controllers, move the flapper
toward the nozzle until the output pressure switches to
full supply pressure, then carefully adjust the flapper
away from the nozzle until the output pressure
switches to 0 psig.
Note
Any sliding of the level set arm (key 28,
figure 19) in the following step changes
the zero as well as the differential gap.
9. To adjust the differential gap, loosen the two level
set mounting screws (see figure 19) and slide the flexure strip base (key 27) right or left along the elongated
slotted hole as follows:
To decrease the differential gap, slide the flexure
strip base away from the torque tube shaft.
To increase the differential gap, slide the flexure
strip base toward the torque tube shaft.
Retighten the screws. For the Type 2500S only, if the
flexure strip base has been moved as far as possible
and the differential gap is still too low, proceed to
step 11.
10. Repeat the procedure from step 4 until the required calibration points are obtained.
19
Page 20
Type 2500
Note
Any change in the PROPORTIONAL
BAND adjustment in the following step
changes the zero as well as the differential gap.
11. If the flexure strip base has been moved as far as
possible and the differential gap is still too large or too
small, adjust the PROPORTIONAL BAND as follows:
If the differential gap is too large, slightly de-
crease the PROPORTIONAL BAND setting.
If the differential gap is too small, slightly in-
crease the PROPORTIONAL BAND setting.
12. Repeat the procedure from step 4 until the re-
quired calibration points are obtained.
Note
If you cannot calibrate the controller,
look for other problems as described in
the Troubleshooting procedures, such
as a nozzle that is not perpendicular to
the flapper, leaky connections, or a
binding displacer rod. If none of these
troubles are apparent, ensure the displacer is sized correctly for the application.
Startup
Adjustment locations are shown in figure 12. The prestartup or calibration procedures must be completed
prior to startup.
Type 2500 Controller
1. Slowly open the upstream and downstream manual
control valves in the pipeline. If the pipeline has a bypass valve, close the valve.
2. If desired, adjust the proportional band to the nar-
rowest (lowest) setting that maintains stable control.
Proportional band adjustments will affect the process
level and may require a level adjustment. If adjusting
proportional band, make the adjustments in small increments.
3. To confirm the optimum proportional band setting,
momentarily create a load upset. If cycling occurs,
broaden (increase) the proportional band until process
oscillations diminish rapidly. In general, the narrowest
proportional band that does not produce cycling provides the best control.
Type 2500T Transmitter
1. Make sure that the SPECIFIC GRAVITY and
ZERO ADJUSTMENT controls are set according to
the Type 2500 Controller or 2500T Transmitter portion
of the pre-startup checks procedures.
2. Slowly open the upstream and downstream manual
control valves in the pipeline. If the pipeline has a
manual bypass valve, close the valve.
Type 2500S Controller
1. Set the switching points according to the Type
2500S Controller portion of the prestartup checks procedures.
2. Slowly open the upstream and downstream manual
control valves in the pipeline. If the pipeline has a
manual bypass valve, close the valve.
3. If necessary, the proportional band may be adjusted to increase or decrease the differential gap. Adjust the RAISE LEVEL adjustment to reposition the
differential gap. After readjustment, confirm the controller is still switching correctly at both switching
points.
Type 2503 Controller
1. Set the switching points according to the Type
2503 Controller portion of the prestartup checks procedures.
2. Slowly open the upstream and downstream manual
control valves in the pipeline. If the pipeline has a
manual bypass valve, close the valve.
3. If necessary, reposition the switching points by adjusting the RAISE LEVEL control. For example, if the
differential gap is set for 4-inches (102 mm) of level
change, this 4-inches (102 mm) can be set anywhere
within the length of the displacer. After readjustment,
confirm the controller is still switching correctly at both
switching points.
Principle of Operation
The controller/transmitter receives the change in fluid
level, fluid-to-fluid interface level, or density from the
change in the buoyant force the fluid exerts on the
sensor displacer. The displacer, through a mechanical
linkage, imparts a rotary motion to the torque tube
shaft. This rotary motion positions the flapper according to the level position of the displacer; the nozzle/
Bourdon tube arrangement sends a pneumatic signal
to the relay valve.
All 2500 and 2503 Series controller/transmitters use
the same basic pressure-balanced relay assembly.
20
Page 21
Type 2500
The following descriptions explain how the relay action
produces the output signal with the various controller/
transmitter constructions.
Type 2500 Controller or 2500T
Transmitter
Full supply pressure comes to the relay from the regulator, as shown in figure 14. The relay has a fixed restriction through which supply pressure bleeds before
entering the large diaphragm area and the inner Bourdon tube channel. In a steady-state condition, the process level holds the torque tube and attached flapper
steady in relation to the nozzle. This allows pressure
to escape between the nozzle and flapper at the same
rate it bleeds into the large diaphragm area. The large
diaphragm holds the inlet end of the relay valve slightly open to compensate for the venting of output pressure through the proportional valve as it maintains a
steady-state position of the final control element. The
output pressure, through the three-way proportional
valve, affects the Bourdon tube outer channel, holding
the Bourdon tube in a steady-state position.
A process level change raises or lowers the displacer,
moving the flapper with respect to the nozzle. If the
process level change increases nozzle pressure, the
large diaphragm moves down; this closes the exhaust
end and opens the inlet end of the relay valve (see
figure 14). This action of the relay valve increases the
output pressure to the final control element. Since the
area ratio of the large diaphragm to the small diaphragm is three-to-one, the small diaphragm action
amplifies the output pressure change. The three-way
proportional valve lets the increase in output pressure
apply to the Bourdon tube outer channel. The expansion of the Bourdon tube moves the nozzle away from
the flapper slowing the response of the pneumatic circuit.
If the process level change decreases the nozzle pressure, the large diaphragm moves up. This action
closes the inlet end and opens the exhaust end of the
relay valve which allows output pressure to exhaust.
This relay valve action reduces the output pressure to
the final control element and is the reverse of the previous explanation.
The proportional valve varies the reaction of the Bourdon tube to changes in the output pressure. For additional information on the proportional valve action, refer to the following proportional valve subsection.
Proportional Valve
The three-way proportional valve is adjustable to allow
some or all of the output pressure change to feed back
to the Bourdon tube outer channel, providing proportional band control (see figure 14). The Bourdon tube
moves to counteract the pressure changes in the
nozzle, equaling the relay diaphragm pressure differential. The relay valve maintains a new output pressure according to the change in the process variable.
A wide-open proportional valve (fully counterclockwise) permits feedback of the output pressure signal
change and produces 100 percent proportional response. A closed (fully clockwise) proportional valve
produces smaller proportional responses, because
part of the output pressure change vents through the
proportional valve exhaust.
Type 2500S Controller
This construction has the same flapper, relay, and proportional valve as the Type 2500 controller. However,
the nozzle is connected (figure 14) in such a way that
output pressure feedback (from the movement of the
Bourdon tube) moves the nozzle in the opposite direction of the flapper. This action completely opens the
relay valve for full output pressure or completely
closes the relay valve for full exhaust of the output
pressure, allowing no in-between throttling.
Type 2503 Controller
This construction has the same flapper and sensor
arrangement as the Type 2500 controller, but its Bourdon tube has a three way valve operated by a plunger
(see figure 15). Note that the switch point adjustment
changes the position of the moveable arm and attached Bourdon tube assembly; this in turn changes
the switch point in relationship to the process level.
The differential gap of the 2503 either completely
opens the relay valve for full output pressure or completely closes the relay valve for full exhaust of the
output pressure, allowing no in-between throttling.
For a direct-acting controller, as long as the process
variable remains above the switch point, the flapper
does not depress the plunger of the Bourdon tube
valve. In this condition, the Bourdon tube valve remains closed, providing full loading pressure to the
Bourdon tube. This loading pressure moves the Bourdon tube away from the flapper. Also, in this condition,
full loading pressure is on the upper diaphragm of the
relay. The loading pressure moves the diaphragm
down, closing the exhaust end and opening the inlet
end of the relay valve, allowing full output pressure.
When the process level sufficiently decreases, the
flapper pushes in the plunger of the Bourdon tube
valve enough to release the loading pressure and seal
the inner Bourdon tube channel (see figure 15). This
decrease in the loading pressure moves the Bourdon
tube toward the flapper, producing the snap action.
Also, this decrease in loading pressure allows relay
spring pressure to move the large diaphragm up, closing the inlet end and opening the exhaust end of the
relay valve,
21
Page 22
Type 2500
CD2114–E
BO998–1/IL
Figure
14. Direct-Acting, Right-Hand-Mounted 2500-249 Series Controller/Transmitter
allowing full exhaust of the output pressure. This control action continues until a sensor level change moves
the flapper away from the plunger, permitting the
Bourdon tube valve to close, restoring loading pressure to the pneumatic circuit. Reverse-acting controllers produce the opposite effect.
22
Maintenance
The 2500 and 2503 Series controllers/transmitters
work in combination with 249 Series displacers. Refer
to figure 19 for key number locations, unless otherwise
indicated.
Due to the care Fisher Controls takes in meeting all
manufacturing requirements (heat treating, dimension-
Page 23
Type 2500
BD4466–A
CD2114–E
A1890–1/IL
Figure
15. Direct-Acting Left-Hand-Mounted Type 2503 Controller
al tolerances, etc.), use only replacement parts
manufactured or furnished by Fisher Controls.
WARNING
When replacing the sensor assembly,
the displacer may retain process fluid or
pressure. Personal injury or property
damage may occur due to sudden release of the pressure. Contact with hazardous fluid, fire, or explosion can be
caused by puncturing, heating, or repairing a displacer that is retaining process pressure or fluid. This danger may
not be readily apparent when disassembling the sensor assembly or removing
the displacer. Before disassembling the
sensor or removing the displacer, observe the more specific warning provided in the sensor instruction manual.
Troubleshooting
When troubleshooting, open loop conditions must exist
unless otherwise stated. When monitoring the process
variable, use the most accurate level indicating device
available. The output signal measuring device should
have corresponding accuracy.
Table 6 lists some common operating faults, their
probable causes, and corrective action.
Removing Controller/Transmitter from
Sensor
WARNING
To avoid injury in the following steps,
turn off the supply pressure and carefully release any pressure trapped in the
controller/transmitter before breaking
any pressure connection. Provide a bypass for the control device if continuous
operation is required during maintenance.
1. Disconnect the supply and output pressure tubing
from the controller or transmitter. For a controller/
transmitter with an indicator, remove the pointer assembly by referring to the section entitled Replacing
the Bourdon Tube.
23
Page 24
Type 2500
FAULTPOSSIBLE CAUSECHECKCORRECTION
1. Process wanders or cycles
around set point.
2. Controller/transmitter
controlling off set point or
switching point.
3. Controller/transmitter cannot
attain full output range.
4. Controller/transmitter remains
at full or zero output pressure.
Table
6. Troubleshooting Chart for 2500 Series Controller/Transmitters
1.1 Proportional band or specific
gravity adjustment incorrect or
improperly tuned control loop.
1.2 Supply pressure varying or
incorrect supply pressure setting.
1.3 Sensor not plumb and is in
contact with sidewall or leak in
displacer.
1.4 Relay malfunction.Check for relay malfunction by
2.1 Supply pressure not set
correctly.
2.2 Leak in the
controller/transmitter loop.
2.3 Leaking displacer.Ensure the displacer is not filling
2.4 Flapper adjustment.Ensure the flapper is not loose on
2.5 Process variable changed.Ensure the process variable has
3.1 Supply pressure not set
correctly.
3.2 Flapper adjustment.Ensure the flapper is not loose on
3.3 Process variable changed.Ensure the process variable has
3.4 Relay malfunctionCheck for relay malfunction by
3.5 Leak in the
controller/transmitter loop.
4.1 Supply or output pressure
gauge malfunction.
4.2 Flapper adjustment.Ensure the flapper is not loose on
Ensure the prestartup procedures
are completed correctly. Tune
control loop.
Use input pressure gauge to
monitor stability. Make sure
regulator IN supply pressure is
within limits.
Check cage vessel and stillwell
installation, or for leaking
displacer.
using the testing relay deadband
procedure.
Make sure regulator supply
pressure is set correctly. Make
sure regulator IN supply pressure
is within limits.
Use soap and water to check for
internal and external leaks.
with process fluid.
the torque tube shaft and is
centered on the nozzle.
not changed from original
calibration settings, or displacer
not designed for specific gravity of
process.
Make sure supply pressure is set
correctly. Make sure regulator IN
supply pressure is within limits.
the torque tube shaft and is
centered on the nozzle.
not changed from original
calibration settings, or from
displacer’s designed specific
gravity.
using the testing relay deadband
procedure.
Use soap and water to check for
internal and external leaks.
Ensure the pressure gauges are
registering correctly.
the torque tube shaft and is
centered on the nozzle.
If stable control cannot be attained
and all other elements are
functionally correct, examine other
possible causes related to the
controller/transmitter.
Apply correct supply pressure.
Use one regulator per instrument.
Make sure the displacer and
displacer rod hangs freely. Make
sure linkage is tight. Replace
displacer if leaking.
Depress plunger to clean out the
fixed restriction. Replace or repair
relay using the procedure in the
Maintenance section.
Reset the supply regulator
pressure. If the condition occurs
again, rebuild or replace regulator.
Provide a regulator input pressure
within regulator limits.
Replace or repair leaking parts as
necessary.
Refer to sensor maintenance
procedures in the appropriate
sensor instruction manual.
Replace or tighten flapper
assembly as necessary and/or
center flapper on nozzle.
Change process variable back to
original specification or
recalibrate. If necessary, provide
replacement displacer of correct
size and recalibrate.
Reset the regulator pressure. If
problem reoccurs, replace or
rebuild the regulator. Ensure
regulator IN supply pressure is
within limits at all operating levels.
Replace or tighten flapper
assembly as necessary and/or
center flapper on nozzle.
Change process variable back to
original specification or
recalibrate. If necessary, provide
replacement displacer of correct
size and recalibrate.
Depress plunger to clean out the
fixed restriction. Replace or repair
relay using the procedure in the
Maintenance section.
Replace or repair leaking parts as
necessary.
Replace pressure gauges. Use
corrective action given in section 3
of this table.
Replace or tighten flapper
assembly as necessary and/or
center flapper on nozzle.
24
Page 25
2. Loosen the top hex clamp nut (key 40, figure 19)
and remove the flapper base (key 30, figure 19) from
the torque tube rotary shaft.
CAUTION
If the hex clamp nut has not been loosened or the pointer removed according
to step 2, attempting to remove the controller/transmitter from the sensor may
bend the flapper or rotary shaft. Be careful that the back of the controller/transmitter case or the heat insulator does
not drop down and bend the rotary shaft
or shaft extension.
3. Remove any insulating tape from the joint between
the controller/transmitter case and the torque tube
arm. Remove the four cap screws (key 39, figure 16)
that hold the controller/transmitter or heat insulator to
the torque tube arm. Pull the case straight out from
the torque tube arm, easing it over the shaft coupling
(key 36, figure 16) if one is installed.
Type 2500
4. If the controller/transmitter has a heat insulator,
remove the four button head cap screws and washers
(keys 40 and 53, figure 16) and remove the insulator
assembly.
Changing Mounting Methods
WARNING
To avoid personal injury from contact
with the process fluid, lower the vessel
fluid level below the torque-tube arm before proceeding. For closed vessels, release any pressure that may be above
the fluid. Also, be careful to avoid overloading a thin-wall torque tube with an
overweight displacer.
Refer to figure 19 for key number locations.
1. Remove the controller/transmitter as described pre-
viously.
2. A controller/transmitter is attached to the sensor in
one of the mounting positions shown in figure 4. Righthand mounting is with the controller/transmitter case
(key 1) to the right of the displacer (FLOAT), as you
look at the front of the case, left-hand mounting is with
with the case to the left of the displacer. For a 249 Series sensor, remove the torque tube arm from the sensor or vessel and reinstall the torque tube arm in the
20A7423–C/DOC
Figure
16. Heat Insulator for 249 Series Sensor
opposite position according to the appropriate instruction manual. Note that the term FLOAT is marked on
the RAISE LEVEL dial and the indicator plate, if one is
used.
3. Check the desired control action. If the control action is not correct, refer to the changing action procedures to change it. Mount the Bourdon tube in one of
the positions shown in figure 17.
4. The arrow on the RAISE LEVEL dial under the
word FLOAT should point toward the displacer. If not,
remove the dial from the controller, turn it over, and
install it in the correct position.
5. For a controller/transmitter with an indicator assembly, the arrow near the word FLOAT on the indicator
plate should point toward the displacer. If it does not,
remove the two screws (key 41, see detail of indicator
assembly in figure 19), turn the front plate (key 54) to
the side with the FLOAT arrow pointing toward the
displacer, and secure the plate with the screws.
6. Install the controller/transmitter according to the
next section.
25
Page 26
Type 2500
Installing Controller/Transmitter on
Sensor
Note
If the installation is in a location that is
not readily accessible and shop calibration is required, remove the torque tube
arm from the cage or vessel before
installing the controller or transmitter to
the sensor. Install the controller/transmitter on the torque tube arm in the
shop; then calibrate and return the controller/transmitter with the torque tube
arm assembly attached for installation.
Perform step 1 only if adding a heat insulator to a unit that does not have one.
Key numbers in this step are shown in
figure 16.
1. To install the heat insulator, secure the shaft exten-
sion (key 37) to the torque tube assembly rotary shaft
with the shaft coupling (key 36). Tighten both set
screws (key 38), with the coupling centered as shown
in figure 16. Then mount the insulator assembly (key
35) on the controller/transmitter case with four button
head cap screws and washers (keys 40 and 53).
Tighten the screws.
CAUTION
In the following step, avoid bending the
rotary shaft of the torque tube assembly. Bending or side loading of this
shaft could cause erroneous readings.
Additionally, make sure the ball bearing
assembly (key 12, figure 19) is removed
from the case (key 1, figure 19) to provide clearance when installing the case
on the sensor.
5. Install the flapper base (key 30, figure 19) on the
torque tube rotary shaft, making sure the flapper is
centered over the nozzle or Bourdon tube valve. Secure the base with the hex nut (key 40, figure 19). For
a controller/transmitter with an indicator assembly,
install the pointer assembly according to the section
entitled Replacing the Bourdon Tube.
6. Connect the supply and output pressure tubing and
perform the calibration procedure.
Replacing the Bourdon Tube
Refer to figure 19 for key number locations.
1. Disconnect the tubing (key 10 for Type 2503 and
key 11 for Type 2500) from the Bourdon tube base.
For a controller/transmitter with indicator assembly,
loosen the side hex clamp nut (key 40) and remove
the pointer assembly (key 51) from the torque tube
rotary shaft.
2. Remove the mounting screws (key 45) and Bourdon tube assembly (key 16).
3. Inspect the Bourdon tube. Replace it if necessary,
using a tube with a black color code for a 3 to 15 psig
or 0 to 20 psig (0.2 to 1 bar or 0 to 1.4 bar) range. Use
a tube with a red color code for a 6 to 30 psig or 0 to
35 psig (0.4 to 2 bar or 0 to 2.4 bar) range. The range
is stamped at the Bourdon tube base.
4. Mount the Bourdon tube on the level set arm (key
28). Secure it with the mounting screws, using the
proper orientation as shown in figure 17. Connect the
tubing to the tube base, with tubing from the R connection on the relay (key 34) going to the marked base
connection. The other tubing goes to the unmarked
base connection. With an indicator assembly, install
the pointer assembly on the rotary shaft and tighten
the hex nut.
5. Perform the calibration procedure.
Changing Action
Note
2. Remove the bearing assembly (key 12, figure 19)
from the case (key 1, figure 19).
3. Carefully slide the controller/transmitter case
straight in. Secure the case on the torque arm or insulator with the four cap screws (key 39).
Note
If a heat insulator is used, do not insulate its exterior.
4. Slide the bearing assembly (key 12, figure 19) onto
the shaft or shaft extension of the insulator, and install
the bearing assembly (key 12, figure 19) into the case
(key 1, figure 19).
26
The following procedure is necessary to
restore previous action if the mounting
method has been changed. Figure 19
shows key numbers.
1. Reposition the Bourdon tube (and indicator assembly, if used) according to steps 1 through 4 of the section entitled Replacing the Bourdon Tube.
2. Loosen the hex nut (key 40) and remove the flapper base (key 30) from the torque tube rotary shaft.
Turn the flapper base over and install it on the rotary
shaft, using the proper orientation as shown in figure
17 and making sure the flapper is centered over the
nozzle or Bourdon tube valve.
3. Perform the calibration procedure.
Page 27
Type 2500
AC9554
AR8148
BO996–1/IL
Figure
17. Bourdon Tube-Flapper Arrangements for Various Actions and Mountings
Relay Deadband Testing (Type 2500
Controller or 2500T Transmitter Only)
1. Replace the appropriate (proportional or specific
gravity) adjustment assembly with the 1/8-inch NPT
pipe plug according to the section entitled Replacing
the Proportional Valve.
2. Turn on the supply pressure and set it to 20 or 35
psig (1.4 to 2.4 bar), depending on the controller/transmitter operating range.
3. By changing the process variable and adjusting the
RAISE LEVEL or ZERO ADJUSTMENT control, set
the output pressure to 15 or 30 psig (1.0 or 2.0 bar).
While monitoring the output pressure, slowly change
the process variable until the output pressure just
changes, and record the value of the process variable
at the detection point.
4. Change the process variable in the opposite direc-
tion until the output pressure just changes and again
record the value of the process variable. If the differ-
ence between the two recorded values (the deadband)
is more than 0.2% of the maximum displacer length,
the relay must be replaced or repaired according to
the Changing Relay section.
5. Turn off the supply pressure, remove the pipe plug,
and install the appropriate adjustment assembly.
Replacing the Proportional Valve
Note
The following procedure, to convert to
or from the pipe plug or the desired adjustment assembly, can be used for any
type number covered in this manual.
1. Remove the tubing (key 10) from the proportional
band valve assembly.
2. Unscrew the base of the PROPORTIONAL BAND
or SPECIFIC GRAVITY adjustment assembly (key 36
27
Page 28
Type 2500
or 90, figure 19), or the 1/8-inch NPT pipe plug (key
73, not shown), from the relay base (key 23, figure
19).
3. Install the pipe plug or the desired adjustment as-
sembly into the relay base.
4. Replace the tubing (key 10) to the proportional
band valve assembly.
Changing Relay
The relay may be removed for cleaning, repair, or replacement.
Removal
1. For a controller or transmitter with indicator assem-
bly, loosen the two lower relay screws (key 96) and
slide out the indicator base plate (key 53).
2. Disconnect the tubing (key 10 or 11) from the relay.
3. Remove both mounting screws, relay, and relay
gasket (keys 43, 34, and 22).
Replacement
1. Install a new gasket (key 22), the replacement
relay (key 34), and secure with two mounting screws
(key 43). On a controller or transmitter with an indicator assembly, slide the base plate under the two lower
screws of the relay case, align the plate so the pointer
will read properly, and tighten the screws.
2. Connect the tubing (key 10 or 11) to the relay.
3. Test the relay deadband, according to the Relay
Deadband Testing procedure in this section.
4. If the deadband is within tolerance, go to the Cal-
ibration section. If the deadband is not within tolerance, perform the Relay Assembly Maintenance procedure
Relay Assembly Maintenance
The alignment tool shown in figure 18 is not essential
for assembly of the relay, but its use does prevent excessive air consumption and deadband. If low air consumption and minimum deadband are required, make
or purchase the alignment tool before disassembling
the relay.
Refer to figures 20 and 21 for key number locations.
Disassembly
1. Remove the relay according to the Changing Relay
procedure in this section.
2. Remove the orifice assembly or connector (key
88), check to see if the orifice is plugged or damaged,
and inspect the O-ring (key 90).
3. Remove six casing screws and washers (keys 96
and 98) and, remove the top diaphragm (key 91). For
15A3519–B
A6016
Figure
18. Relay Alignment Tool
a high temperature relay, also remove the gasket (key
100, figure 21) that covers the diaphragm.
4. Remove the spacer ring (key 84), diaphragm assembly (key 86), and relay spring (key 92) from the
relay body (key 83). On a high temperature relay, also
remove the gasket (key 99, figure 21) from underneath
the diaphragm assembly.
5. Remove the four screws (key 97), spring plate (key
95), spring plate gasket (key 94), spring (key 92), and
inner valve (key 87).
6. Inspect the valve seats for roughness due to corrosion. One seat is in the diaphragm assembly; the other
is in the relay body (key 83). If necessary, replace the
parts.
7. Inspect the diaphragms and gaskets, and replace
them if necessary. Also, replace the spring and inner
valve (keys 92 and 87) if they show signs of corrosion.
The lower diaphragm comes as part of an assembly; it
must be installed as an assembly.
8. Clean all parts thoroughly before assembly.
Assembly
1. Place the relay spring in the relay body and, for a
high temperature relay, install a bottom gasket. Install
the diaphragm assembly, spacer ring, and top diaphragm on the body so that all flow passage holes are
in line. For a high temperature relay, also install a gasket over the top diaphragm.
2. Place the casing assembly on the top diaphragm
so that the lugs on the casing and spacer ring line up
and are also in line with the body lug.
28
Page 29
Type 2500
3. Install the machine screws (key 96) and, for stan-
dard relays, the washers (key 98), but do not tighten
the screws.
4. If the optional alignment tool (figure 18) is available,
insert the small end of the tool into the opening in the
relay body. If the tool does not engage in the hole of
the diaphragm assembly, move the parts slightly to
reposition the diaphragm so the alignment tool does
engage the hole in the diaphragm assembly. Do not
remove the alignment tool until the machine screws
(key 96) are tightened.
5. Tighten the machine screws (key 96) evenly. Re-
move the alignment tool, if one is used.
6. Install the inner valve, spring, gasket, and cover
plate (keys 87, 92, 94, and 95). Secure them with the
four machine screws (key 97).
7. Install the O-ring (key 90) on the orifice assembly
(key 88), and install the orifice assembly into the relay
casing.
8. Install the relay according to the Changing Relay
procedure.
9. Install a new gasket (key 22, figure 19), the re-
placement relay (key 34, figure 19), and secure them
with two mounting screws (key 43, figure 19).
10. Connect the tubing (key 11, figure 19) to the relay.
11. Test the relay deadband according to procedures
in this section.
12. If the deadband is within tolerance, go to the Cal-
ibration section.
Parts Ordering
Whenever corresponding with the sales representative
about this equipment, use the controller/transmitter
type number and the serial number. The serial number
is found on the nameplate (key 215, figure 19). When
ordering replacement parts, also state the complete
11-character part number of each part required as
found in the following parts list.
Parts
KeyDescriptionPart Number
Controller Parts Kits
List
Type 2500 Controller Repair Kits
Contains keys 12, 15, 21, 24, 38, and
the flapper assembly
Standard temperature
High temperature
R2500 X00L32
R2500 X00H32
KeyDescriptionPart Number
Type 2503 Controller and Relay Repair Kit
Standard temperature only
For the controller, the kit contains
keys 12, 21, 22, 24, 38, and the
flapper assembly. For the relay, the
kit contains keys 86, 90, 91, and 94
Relay Repair Kits
Contains keys 22, 85, 86, 87, 88, 90, 91, 92,
93, 94, (99 and 100 high temperature only)
and the plug and wire assembly
Standard temperatureRRELAYX0L12
High temperatureRRELAYX0H12
Relay Replacement Kit
Contains keys 22, 43, and the relay assembly
Standard temperatureRRELAYX0L22
High temperatureRRELAYX0H22