Documentation representative: S. Richter
Technical editor: R.Kleemann
All rights, also those to the translation, reserved. No part of these instructions
may be reproduced or processed, duplicated or distributed using electronic systems or any other form (print, photocopy, microfilm or another process) without
the written consent of the company Fischer Mess- und Regeltechnik GmbH,
Bad Salzuflen.
Reproduction for internal use is expressly allowed.
Brand names and procedures are used for information purposes only and do
not take the respective patent situation into account. Great care was taken
when compiling the texts and illustrations; nevertheless, errors cannot be ruled
out. The company FISCHER Mess- und Regeltechnik GmbH will not accept any
legal responsibility or liability for this.
1.1 General .....................................................................................................................................................4
2.2 Intended use .............................................................................................................................................6
2.4 Function diagram ......................................................................................................................................7
2.5 Design and mode of operation..................................................................................................................7
3 Assembly and Starting Operation.................................................................................................................8
3.2 Process connection ..................................................................................................................................8
4.2 Transport ................................................................................................................................................11
5 Technical Data .............................................................................................................................................. 12
5.5 Auxiliary energy .....................................................................................................................................13
5.7 Construction design ................................................................................................................................14
6 Order Codes..................................................................................................................................................16
1 | Safety guidelinesFISCHER Mess- und Regeltechnik GmbH
1 Safety guidelines
1.1 General
WARNING
This operating manual contains instructions fundamental to the installation, operation and maintenance of the device that must be observed unconditionally. It
must be read by the assembler, operator and the specialized personnel in
charge of the instrument before it is installed and put into operation.
This operating manual is an integral part of the product and therefore needs to
be kept close to the instrument in a place that is accessible at all times to the responsible personnel.
The following sections, in particular instructions about the assembly, commissioning and maintenance, contain important information, non-observance of
which could pose a threat to humans, animals, the environment and property.
The instrument described in these operating instructions is designed and manufactured in line with the state of the art and good engineering practice.
1.2 Personnel Qualification
The instrument may only be installed and commissioned by specialized personnel familiar with the installation, commissioning and operation of this product.
Specialized personnel are persons who can assess the work they have been
assigned and recognize potential dangers by virtue of their specialized training,
their skills and experience and their knowledge of the pertinent standards.
1.3 Risks due to Non-Observance of Safety Instructions
Non-observance of these safety instructions, the intended use of the device or
the limit values given in the technical specifications can be hazardous or cause
harm to persons, the environment or the plant itself.
The supplier of the equipment will not be liable for damage claims if this should
happen.
1.4 Safety Instructions for the Operating Company and the Operator
The safety instructions governing correct operation of theinstrument must be
observed. The operating company must make them available to the installation,
maintenance, inspection and operating personnel.
Dangers arising from electrical components, energy discharged by the medium,
escaping medium and incorrect installation of the device must be eliminated.
See the information in the applicable national and international regulations.
Please observe the information about certification and approvals in the Technical Data section.
1.5 Unauthorised Modification
Modifications of or other technical alterations to the instrument by the customer
are not permitted. This also applies to replacement parts. Only the manufacturer
is authorised to make any modifications or changes.
4 / 20BA_EN_DE25
FISCHER Mess- und Regeltechnik GmbHSafety guidelines | 1
1.6 Inadmissible Modes of Operation
The operational safety of this instrument can only be guaranteed if it is used as
intended. The instrument model must be suitable for the medium used in the
system. The limit values given in the technical data may not be exceeded.
The manufacturer is not liable for damage resulting from improper or incorrect
use.
1.7 Safe working practices for maintenance and installation work
The safety instructions given in this operating manual, any nationally applicable
regulations on accident prevention and any of the operating company's internal
work, operating and safety guidelines must be observed.
The operating company is responsible for ensuring that all required maintenance, inspection and installation work is carried out by qualified specialized personnel.
1.8 Pictogram explanation
DANGER
Type and source of danger
This indicates a direct dangerous situation that could lead to death or serious
injury (highest danger level).
a) Avoid danger by observing the valid safety regulations.
WARNING
Type and source of danger
This indicates a potentially dangerous situation that could lead to death or serious injury (medium danger level).
a) Avoid danger by observing the valid safety regulations.
CAUTION
Type and source of danger
This indicates a potentially dangerous situation that could lead to slight or serious injury, damage or environmental pollution (low danger level).
a) Avoid danger by observing the valid safety regulations.
NOTICE
Note / advice
This indicates useful information of advice for efficient and smooth operation.
BA_EN_DE255 / 20
2 | Product and functional descriptionFISCHER Mess- und Regeltechnik GmbH
The DE25 is a differential pressure transmitter for measuring over-pressure, under-pressure and differential pressure in neutral, non-aggressive gaseous media.
2.3 Equipment versions
The appearance of the various models differs in terms of the electrical connection type.
Illustration1: Equipment versions
2.3.1 Nameplate
This type plate serves as an example of the information that is stated. The data
shown is purely fictive, but does correspond to the actual conditions. For more
information, please see the order code at the end of these instructions.
Illustration2: Nameplate
6 / 20BA_EN_DE25
FISCHER Mess- und Regeltechnik GmbHProduct and functional description | 2
+
A
D
µC
D
A
+U
b
-U
b
+Sig
2.4 Function diagram
Illustration3: Function diagram
2.5 Design and mode of operation
The basis of this transmitter is a piezo-resistive sensor element. The pressure
that is to be measured acts directly onto a silicon diaphragm equipped with
piezo-resistive resistors. The active pressure generates changes in resistance
that are evaluated by the device's electronics and transformed into an analogue
signal. The output signal is usually available as a current or voltage signal.
BA_EN_DE257 / 20
3 | Assembly and Starting OperationFISCHER Mess- und Regeltechnik GmbH
+
Higher pressure
lower pressure
Pressure
open
open
Under-pressure
3 Assembly and Starting Operation
3.1 Generalities
The device is designed for installation onto flat assembly plates or walls. The
casing has integrated assembly straps for this purpose. Ex-works, the device is
set for vertical installation. The pressure connections must point downwards.
The protection type IP 65 is only guaranteed, if a suitable power supply cable is
used (see accessories [}17]).
If the device is intended for outdoor use, we recommend permanently protecting
the device against UV radiation and using a suitable enclosure or at least the
erection of a sufficiently dimensioned canopy as a protection measure against
constant rain or snow.
3.2 Process connection
• By authorized and qualified specialized personnel only.
• The pipes need to be depressurized when the instrument is being connected.
• Appropriate steps must be taken to protect the device from pressure surges.
• Check that the device is suitable for the medium being measured.
• Maximum pressures must be observed (cf. Tech. data)
The pressure lines must be installed at an inclination so that when fluids are
measured no air pockets are created or when measuring gases, no water pockets are created. If the required inclination is not reached, water or air filters must
be installed at suitable places.
The pressure lines must be kept as short as possible and installed without any
tight bends to avoid delays.
Pulsating pressure on the system side can lead to wear and functional problems. To safeguard this, we recommend installing absorption elements in the
pressure line.
The process connections are marked with (+) and (-) symbols on the device.
The pressure lines must be mounted according to these symbols.
Illustration4: Process connection
1. Differential pressure measurement
2. Pressure measurement
3. Under-pressure measurement
8 / 20BA_EN_DE25
FISCHER Mess- und Regeltechnik GmbHAssembly and Starting Operation | 3
Input
Output
AC
DC
Power supply
Sensor
Signal
+U
b
-Ub/ -Sig
+Sig
+U
b
-U
b
123
3.3 Electrical connections
• By authorized and qualified specialized personnel only.
• When connecting the unit, the national and international electro-technical
regulations must be observed.
• Disconnect the system from the mains, before electrically connecting the
device.
• Install the consumer-adapted fuses.
• Do not connect the connector if strained.
3-conductor circuit
3.3.1 Version with M12 plug
Illustration6: M12 connector 4pin
3.3.2 Model with cable screw connection
Illustration7: Connection terminal
Illustration5: 3-conductor circuit
PinSignal nameCable colour
1Supply (+)+U
b
brown
2n.c.white
3Supply (-) / output signal (-)-Ub /-Sigblue
4Output signal (+)+Sigblack
ACoding
In case of the model with cable screw connection, the casing lid needs to be
opened first.
PinSignal name
1Output signal (+)+Sig
2Supply (-) / output signal (-)-Ub /-Sig
3Supply (+)+U
b
3.4 Commissioning
A prerequisite for commissioning is correct installation of all electrical supply
lines and the pressure lines. All connections are arranged so that there are no
mechanical forces acting on the device.
CAUTION
Leak test
The pressure lines need to be checked for leaks before commissioning.
BA_EN_DE259 / 20
3 | Assembly and Starting OperationFISCHER Mess- und Regeltechnik GmbH
Zero-point button
Sensor element
+Sig
-Sig
+U
b
-U
b
AC
DC
3.4.1 Zero-point adjustment
The differential pressure transmitters of series DE25 are set in the factory before delivery so that adjustment at the assembly site is usually unnecessary.
If the zero-point does need to be adjusted, this can be undertaken using the
zero-point button. A prerequisite for this is a depressurized system. If this is not
possible, the pressure lines must be released.
Proceed as follows:
• Switch off the auxiliary energy.
• Open the casing by releasing the four screws in the lid.
• Connect a current or voltage measuring unit to the output.
• Switch on the auxiliary energy.
• If the measured output signal deviates from the zero-point, keep the zeropoint button pressed until the measuring unit shows the correct zero value
in the output after approx. 5 seconds.
• Switch off the auxiliary energy.
• Remove the measuring device.
• Remount the lid of the casing.
• Switch on the auxiliary energy.
Illustration8: Zero-point adjustment
10 / 20BA_EN_DE25
FISCHER Mess- und Regeltechnik GmbHMaintenance | 4
4 Maintenance
4.1 Maintenance
The instrument is maintenance-free. We recommend the following regular inspection to guarantee reliable operation and a long service life:
• Check the function in combination with downstream components.
• Check the leak-tightness of the pressure connection lines.
• Check the electrical connections.
The exact test cycles need to be adapted to the operating and environmental
conditions. In combination with other devices, the operating instructions for the
other devices also need to be observed.
4.2 Transport
The measuring device must be protected against impacts. It should be transported in the original packaging or a suitable transport container.
4.3 Service
All defective or faulty devices should be sent directly to our repair department.
Please coordinate all shipments with our sales department.
WARNING
Process media residues
Process media residues in and ondismantled devices can be a hazard to
people, animals and the environment. Take adequate preventive measures. If
required, the devices must be cleaned thoroughly.
Return the device in the original packaging or a suitable transport container.
4.4 Accessories
• M12 Connection lines of different lengths
• Connection set for intake and outlet channels
For the order numbers, please see the order code [}17].
4.5 Disposal
WARNING
Incorrect disposal may pose a risk to the environment.
Please help to protect the environment by always disposing of the work pieces
and packaging materials in compliance with the valid national waste and recycling guidelines or reuse them.
BA_EN_DE2511 / 20
5 | Technical DataFISCHER Mess- und Regeltechnik GmbH
5 Technical Data
5.1 Generalities
Reference conditions (acc. to IEC 61298-1)
Temperature+15 … +25 °C
Relative humidity45 … 75 %
Air pressure86 … 106 kPa860 … 1060 mbar
Installation positionUser-defined
5.2 Input variables
Measuring variable
Differential pressure, positive and negative over-pressure
Characteristic curve deviation (non-linearity and hysteresis) at 25°C and rated
voltage.
A smaller deviation can be realised in certain measuring ranges (values in
brackets). Please contact our sales department in this case.
x)
with respect to the measuring range (FS).
+)
+)
5.5 Auxiliary energy
Current outputVoltage output
Rated Voltage24 V AC/DC24 V AC/DC
Admissible operating voltage12 … 32 V AC/DC12 … 32 V AC/DC
Limitsca. 23 mAapprox. 13 V
5.6 Application conditions
Increase ambient temperature
Media temperature-10 … +50 °C
Storage temperature-20 … +70 °C
Enclosure protection class IP65 as per EN 60529
EMCEN 61326-1:2013
RoHSEN 50581:2012
-10 … +50 °C
EN 61326-2-3:2013
BA_EN_DE2513 / 20
5 | Technical DataFISCHER Mess- und Regeltechnik GmbH
5.7 Construction design
5.7.1 Process connection
5.7.2 Electrical connection
M12 plug connection4-pin, male, Coding A
M12 connection cable
(see accessories)
4 x 0.34 mm
sheath PUR Ø 5.2 mm
Bending radius (fixed) 5 x Ø
Bending radius (mobile) 10 x Ø
Cable screw connectionM16 x 1.5
min. terminal range4.5 mm
max. terminal range10.0
Connection terminalSingle-wire (rigid)0.2 … 2.5 mm
Fine wire (flexible)0.2 … 2.5 mm
Fine-wire (flexible)
with ferrules
2
2
2
0.2 … 2.5 mm
2
5.7.3 Materials
HousingPolyamide PA 6.6
M12 plugPolyamide PA 6, brass, gold
Cable screw connectionPolyamide PA 6
Materials in contact with mediaSilicon, polyester glass-fibre rein-
FISCHER Mess- und Regeltechnik GmbHOrder Codes | 6
Output signal:
[7](Code no.)
A0 … 20 mA
P4 … 20 mA
C0 … 10 V
Operating voltage:
[8](Code no.)
K24 V DC
Electrical connection
[11](Code no.)
MM12 plug connection
ECable screw connection
Assembly:
[12](Code no.)
WWall-mounting
6.1 Accessories
Order no.Planned measuresNo. of
Poles
06401993Connection cable with M12 connector4-pin2 m
06401994Connection cable with M12 connector4-pin5 m
06401563Connection cable with M12 connector4-pin7 m
06401572Connection cable with M12 connector4-pin10 m
Connection set
Order no.Planned measureshoseLength
04005129Plastic connection set2 x 6/4 mm1 m
04005148Plastic connection set2 x 6/4 mm2.5 m
04005163Plastic connection set2 x 6/4 mm5 m
04005216Plastic connection set2 x 6/4 mm10 m
04005217Plastic connection set2 x 8/6 mm1 m
04005218Plastic connection set2 x 8/6 mm5 m
Length
BA_EN_DE2517 / 20
7 | AnnexFISCHER Mess- und Regeltechnik GmbH
7 Annex
Illustration11: CE_DE_DE25
18 / 20BA_EN_DE25
FISCHER Mess- und Regeltechnik GmbHAnnex | 7
BA_EN_DE2519 / 20
7 | AnnexFISCHER Mess- und Regeltechnik GmbH
20 / 20BA_EN_DE25