FISCHER DE25 Operating Manual

Operating manual
DE25
Digital differential pressure transmitter
for gaseous media
09005155 • BA_EN_DE25 • Rev. ST4-A • 03/17
*09005155*
| Masthead FISCHER Mess- und Regeltechnik GmbH
Manufacturer:
Technical editorial team:
FISCHER Mess- und Regeltechnik GmbH
Bielefelderstr. 37a D-32107 Bad Salzuflen
Telefon: +49 5222 974 0 Telefax: +49 5222 7170
eMail: info@fischermesstechnik.de web: www.fischermesstechnik.de
Documentation representative: S. Richter Technical editor: R.Kleemann
All rights, also those to the translation, reserved. No part of these instructions may be reproduced or processed, duplicated or distributed using electronic sys­tems or any other form (print, photocopy, microfilm or another process) without the written consent of the company Fischer Mess- und Regeltechnik GmbH, Bad Salzuflen.
Reproduction for internal use is expressly allowed.
Brand names and procedures are used for information purposes only and do not take the respective patent situation into account. Great care was taken when compiling the texts and illustrations; nevertheless, errors cannot be ruled out. The company FISCHER Mess- und Regeltechnik GmbH will not accept any legal responsibility or liability for this.
Subject to technical amendments.
© FISCHER Mess- und Regeltechnik 2017

Version history

Rev. ST4-A 03/17 Version 1 (first edition) Rev. ST4-B 04/17 Version 2 (correction)
2 / 20 BA_EN_DE25
FISCHER Mess- und Regeltechnik GmbH Table of Contents

Table of Contents

1 Safety guidelines ............................................................................................................................................4
1.1 General .....................................................................................................................................................4
1.2 Personnel Qualification.............................................................................................................................4
1.3 Risks due to Non-Observance of Safety Instructions ...............................................................................4
1.4 Safety Instructions for the Operating Company and the Operator............................................................4
1.5 Unauthorised Modification ........................................................................................................................4
1.6 Inadmissible Modes of Operation .............................................................................................................5
1.7 Safe working practices for maintenance and installation work .................................................................5
1.8 Pictogram explanation ..............................................................................................................................5
2 Product and functional description ..............................................................................................................6
2.1 Delivery scope ..........................................................................................................................................6
2.2 Intended use .............................................................................................................................................6
2.3 Equipment versions ..................................................................................................................................6
2.4 Function diagram ......................................................................................................................................7
2.5 Design and mode of operation..................................................................................................................7
3 Assembly and Starting Operation.................................................................................................................8
3.1 Generalities...............................................................................................................................................8
3.2 Process connection ..................................................................................................................................8
3.3 Electrical connections ...............................................................................................................................9
3.4 Commissioning .........................................................................................................................................9
4 Maintenance..................................................................................................................................................11
4.1 Maintenance ...........................................................................................................................................11
4.2 Transport ................................................................................................................................................11
4.3 Service....................................................................................................................................................11
4.4 Accessories ............................................................................................................................................11
4.5 Disposal ..................................................................................................................................................11
5 Technical Data .............................................................................................................................................. 12
5.1 Generalities.............................................................................................................................................12
5.2 Input variables ........................................................................................................................................12
5.3 Output sizes............................................................................................................................................12
5.4 Measurement accuracy ..........................................................................................................................13
5.5 Auxiliary energy .....................................................................................................................................13
5.6 Application conditions .............................................................................................................................13
5.7 Construction design ................................................................................................................................14
6 Order Codes..................................................................................................................................................16
7 Annex.............................................................................................................................................................18
BA_EN_DE25 3 / 20
1 | Safety guidelines FISCHER Mess- und Regeltechnik GmbH

1 Safety guidelines

1.1 General

WARNING
This operating manual contains instructions fundamental to the installation, op­eration and maintenance of the device that must be observed unconditionally. It must be read by the assembler, operator and the specialized personnel in charge of the instrument before it is installed and put into operation.
This operating manual is an integral part of the product and therefore needs to be kept close to the instrument in a place that is accessible at all times to the re­sponsible personnel.
The following sections, in particular instructions about the assembly, commis­sioning and maintenance, contain important information, non-observance of which could pose a threat to humans, animals, the environment and property.
The instrument described in these operating instructions is designed and manu­factured in line with the state of the art and good engineering practice.

1.2 Personnel Qualification

The instrument may only be installed and commissioned by specialized person­nel familiar with the installation, commissioning and operation of this product.
Specialized personnel are persons who can assess the work they have been assigned and recognize potential dangers by virtue of their specialized training, their skills and experience and their knowledge of the pertinent standards.

1.3 Risks due to Non-Observance of Safety Instructions

Non-observance of these safety instructions, the intended use of the device or the limit values given in the technical specifications can be hazardous or cause harm to persons, the environment or the plant itself.
The supplier of the equipment will not be liable for damage claims if this should happen.

1.4 Safety Instructions for the Operating Company and the Operator

The safety instructions governing correct operation of theinstrument must be observed. The operating company must make them available to the installation, maintenance, inspection and operating personnel.
Dangers arising from electrical components, energy discharged by the medium, escaping medium and incorrect installation of the device must be eliminated. See the information in the applicable national and international regulations.
Please observe the information about certification and approvals in the Tech­nical Data section.

1.5 Unauthorised Modification

Modifications of or other technical alterations to the instrument by the customer are not permitted. This also applies to replacement parts. Only the manufacturer is authorised to make any modifications or changes.
4 / 20 BA_EN_DE25
FISCHER Mess- und Regeltechnik GmbH Safety guidelines | 1

1.6 Inadmissible Modes of Operation

The operational safety of this instrument can only be guaranteed if it is used as intended. The instrument model must be suitable for the medium used in the system. The limit values given in the technical data may not be exceeded.
The manufacturer is not liable for damage resulting from improper or incorrect use.

1.7 Safe working practices for maintenance and installation work

The safety instructions given in this operating manual, any nationally applicable regulations on accident prevention and any of the operating company's internal work, operating and safety guidelines must be observed.
The operating company is responsible for ensuring that all required mainten­ance, inspection and installation work is carried out by qualified specialized per­sonnel.

1.8 Pictogram explanation

DANGER
Type and source of danger
This indicates a direct dangerous situation that could lead to death or serious injury (highest danger level).
a) Avoid danger by observing the valid safety regulations.
WARNING
Type and source of danger
This indicates a potentially dangerous situation that could lead to death or ser­ious injury (medium danger level).
a) Avoid danger by observing the valid safety regulations.
CAUTION
Type and source of danger
This indicates a potentially dangerous situation that could lead to slight or seri­ous injury, damage or environmental pollution (low danger level).
a) Avoid danger by observing the valid safety regulations.
NOTICE
Note / advice
This indicates useful information of advice for efficient and smooth operation.
BA_EN_DE25 5 / 20
2 | Product and functional description FISCHER Mess- und Regeltechnik GmbH
Fixing lug
M12 plug
Cable screw connection
Nameplate
Process connection
Silicone-free
Item number Measuring range Electrical output
Operating voltage Pmax Prod. No.
sw
br
bl
DE2559K042CK00MW
0 ... 100 mbar
0 ... 10 V
24 V DC/AC
500 mbar
1710885.01.002
Special properties Order Codes
Circuit diagram
Technical data
Serial number
+Sig
U
b
+
U
b
-

2 Product and functional description

2.1 Delivery scope

• Differential pressure transmitter DE25 ## # 042 # K00 # W
• Operating Instructions

2.2 Intended use

The DE25 is a differential pressure transmitter for measuring over-pressure, un­der-pressure and differential pressure in neutral, non-aggressive gaseous me­dia.

2.3 Equipment versions

The appearance of the various models differs in terms of the electrical connec­tion type.
Illustration1: Equipment versions

2.3.1 Nameplate

This type plate serves as an example of the information that is stated. The data shown is purely fictive, but does correspond to the actual conditions. For more information, please see the order code at the end of these instructions.
Illustration2: Nameplate
6 / 20 BA_EN_DE25
FISCHER Mess- und Regeltechnik GmbH Product and functional description | 2
+
A
D
µC
D
A
+U
b
-U
b
+Sig

2.4 Function diagram

Illustration3: Function diagram

2.5 Design and mode of operation

The basis of this transmitter is a piezo-resistive sensor element. The pressure that is to be measured acts directly onto a silicon diaphragm equipped with piezo-resistive resistors. The active pressure generates changes in resistance that are evaluated by the device's electronics and transformed into an analogue signal. The output signal is usually available as a current or voltage signal.
BA_EN_DE25 7 / 20
3 | Assembly and Starting Operation FISCHER Mess- und Regeltechnik GmbH
+
Higher pressure
lower pressure
Pressure
open
open
Under-pressure

3 Assembly and Starting Operation

3.1 Generalities

The device is designed for installation onto flat assembly plates or walls. The casing has integrated assembly straps for this purpose. Ex-works, the device is set for vertical installation. The pressure connections must point downwards.
The protection type IP 65 is only guaranteed, if a suitable power supply cable is used (see accessories [}17]).
If the device is intended for outdoor use, we recommend permanently protecting the device against UV radiation and using a suitable enclosure or at least the erection of a sufficiently dimensioned canopy as a protection measure against constant rain or snow.

3.2 Process connection

• By authorized and qualified specialized personnel only.
• The pipes need to be depressurized when the instrument is being connec­ted.
• Appropriate steps must be taken to protect the device from pressure surges.
• Check that the device is suitable for the medium being measured.
• Maximum pressures must be observed (cf. Tech. data)
The pressure lines must be installed at an inclination so that when fluids are measured no air pockets are created or when measuring gases, no water pock­ets are created. If the required inclination is not reached, water or air filters must be installed at suitable places.
The pressure lines must be kept as short as possible and installed without any tight bends to avoid delays.
Pulsating pressure on the system side can lead to wear and functional prob­lems. To safeguard this, we recommend installing absorption elements in the pressure line.
The process connections are marked with (+) and (-) symbols on the device. The pressure lines must be mounted according to these symbols.
Illustration4: Process connection
1. Differential pressure measurement
2. Pressure measurement
3. Under-pressure measurement
8 / 20 BA_EN_DE25
FISCHER Mess- und Regeltechnik GmbH Assembly and Starting Operation | 3
Input
Output
AC
DC
Power supply
Sensor
Signal
+U
b
-Ub/ -Sig
+Sig
+U
b
-U
b
1 2 3

3.3 Electrical connections

• By authorized and qualified specialized personnel only.
• When connecting the unit, the national and international electro-technical regulations must be observed.
• Disconnect the system from the mains, before electrically connecting the device.
• Install the consumer-adapted fuses.
• Do not connect the connector if strained.
3-conductor circuit

3.3.1 Version with M12 plug

Illustration6: M12 connector 4­pin

3.3.2 Model with cable screw connection

Illustration7: Connection ter­minal
Illustration5: 3-conductor circuit
Pin Signal name Cable colour
1 Supply (+) +U
b
brown 2 n.c. white 3 Supply (-) / output signal (-) -Ub /-Sig blue 4 Output signal (+) +Sig black
A Coding
In case of the model with cable screw connection, the casing lid needs to be opened first.
Pin Signal name
1 Output signal (+) +Sig 2 Supply (-) / output signal (-) -Ub /-Sig 3 Supply (+) +U
b

3.4 Commissioning

A prerequisite for commissioning is correct installation of all electrical supply lines and the pressure lines. All connections are arranged so that there are no mechanical forces acting on the device.
CAUTION
Leak test
The pressure lines need to be checked for leaks before commissioning.
BA_EN_DE25 9 / 20
3 | Assembly and Starting Operation FISCHER Mess- und Regeltechnik GmbH
Zero-point button
Sensor element
+Sig
-Sig
+U
b
-U
b
AC
DC

3.4.1 Zero-point adjustment

The differential pressure transmitters of series DE25 are set in the factory be­fore delivery so that adjustment at the assembly site is usually unnecessary.
If the zero-point does need to be adjusted, this can be undertaken using the zero-point button. A prerequisite for this is a depressurized system. If this is not possible, the pressure lines must be released.
Proceed as follows:
• Switch off the auxiliary energy.
• Open the casing by releasing the four screws in the lid.
• Connect a current or voltage measuring unit to the output.
• Switch on the auxiliary energy.
• If the measured output signal deviates from the zero-point, keep the zero­point button pressed until the measuring unit shows the correct zero value in the output after approx. 5 seconds.
• Switch off the auxiliary energy.
• Remove the measuring device.
• Remount the lid of the casing.
• Switch on the auxiliary energy.
Illustration8: Zero-point adjustment
10 / 20 BA_EN_DE25
FISCHER Mess- und Regeltechnik GmbH Maintenance | 4

4 Maintenance

4.1 Maintenance

The instrument is maintenance-free. We recommend the following regular in­spection to guarantee reliable operation and a long service life:
• Check the function in combination with downstream components.
• Check the leak-tightness of the pressure connection lines.
• Check the electrical connections.
The exact test cycles need to be adapted to the operating and environmental conditions. In combination with other devices, the operating instructions for the other devices also need to be observed.

4.2 Transport

The measuring device must be protected against impacts. It should be transpor­ted in the original packaging or a suitable transport container.

4.3 Service

All defective or faulty devices should be sent directly to our repair department. Please coordinate all shipments with our sales department.
WARNING
Process media residues
Process media residues in and ondismantled devices can be a hazard to people, animals and the environment. Take adequate preventive measures. If required, the devices must be cleaned thoroughly.
Return the device in the original packaging or a suitable transport container.

4.4 Accessories

• M12 Connection lines of different lengths
• Connection set for intake and outlet channels
For the order numbers, please see the order code [}17].

4.5 Disposal

WARNING
Incorrect disposal may pose a risk to the environment.
Please help to protect the environment by always disposing of the work pieces and packaging materials in compliance with the valid national waste and recyc­ling guidelines or reuse them.
BA_EN_DE25 11 / 20
5 | Technical Data FISCHER Mess- und Regeltechnik GmbH

5 Technical Data

5.1 Generalities

Reference conditions (acc. to IEC 61298-1)
Temperature +15 … +25 °C Relative humidity 45 … 75 % Air pressure 86 … 106 kPa 860 … 1060 mbar Installation position User-defined

5.2 Input variables

Measuring variable
Differential pressure, positive and negative over-pressure
Measuring ranges
Measuring range Stat. operating pres-
sure max.
mbar mbar mbar
0 … 2.5 50 150
0 … 4 50 150
0 … 6 50 150 0 … 10 100 300 0 … 16 100 300 0 … 25 250 750 0 … 40 250 750 0 … 60 500 1500
0 … 100 500 1500
-2.5 … +2.5 50 150
-4 … +4 50 150
-6 … +6 50 150
-10 … +10 100 300
-16 … +16 100 300
-25 … +25 250 750
-40 … +40 250 750
-60 … +60 500 1500
Bursting pressure

5.3 Output sizes

Electricity Voltage
Output signal 0 … 20 mA 4 … 20 mA 0 … 10 V Admissible appar-
ent ohmic resist­ance
12 / 20 BA_EN_DE25
RL ≤ ((Ub-10V)*50Ω)+300Ω Ub < 15 V → RL ≥ 100 kΩ
Ub ≤ 15 V → RL ≥ 2 kΩ
FISCHER Mess- und Regeltechnik GmbH Technical Data | 5

5.4 Measurement accuracy

Measuring range 2.5 4 6 10 16 25 40 60 100 Characteristic curve deviation
Max. %FS 2.5 (1.0) Type %FS 1.5 (0.5) TK span
x)
Max. %FS 1.0 1.0 1.0 0.3 0.3 0.3 0.3 0.3 0.3 Type %FS 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 Tk zero-point
x)
Max. %FS / 10K 1.0 1.0 1.0 0.4 0.4 0.4 0.4 0.4 0.4 Type %FS / 10K 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2
Measuring range ± 2.5 ± 4 ± 6 ± 10 ± 16 ± 25 ± 40 ± 60 Characteristic curve deviation
Max. %FS 2.5 (1.0) Type %FS 1.5 (0.5) TK span
x)
Max. %FS / 10K 1.0 0.5 0.3 0.3 0.3 0.3 0.3 0.3 Type %FS / 10K 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 Tk zero-point
x)
Max. %FS / 10K 1.0 0.5 0.4 0.4 0.4 0.4 0.4 0.4 Type %FS / 10K 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2
+)
Characteristic curve deviation (non-linearity and hysteresis) at 25°C and rated
voltage.
A smaller deviation can be realised in certain measuring ranges (values in brackets). Please contact our sales department in this case.
x)
with respect to the measuring range (FS).
+)
+)

5.5 Auxiliary energy

Current output Voltage output
Rated Voltage 24 V AC/DC 24 V AC/DC Admissible operating voltage 12 … 32 V AC/DC 12 … 32 V AC/DC Limits ca. 23 mA approx. 13 V

5.6 Application conditions

Increase ambient temper­ature
Media temperature -10 … +50 °C Storage temperature -20 … +70 °C Enclosure protection class IP65 as per EN 60529 EMC EN 61326-1:2013
RoHS EN 50581:2012
-10 … +50 °C
EN 61326-2-3:2013
BA_EN_DE25 13 / 20
5 | Technical Data FISCHER Mess- und Regeltechnik GmbH

5.7 Construction design

5.7.1 Process connection

5.7.2 Electrical connection

M12 plug connection 4-pin, male, Coding A M12 connection cable
(see accessories)
4 x 0.34 mm sheath PUR Ø 5.2 mm
Bending radius (fixed) 5 x Ø Bending radius (mobile) 10 x Ø
Cable screw connection M16 x 1.5
min. terminal range 4.5 mm max. terminal range 10.0
Connection terminal Single-wire (rigid) 0.2 … 2.5 mm
Fine wire (flexible) 0.2 … 2.5 mm Fine-wire (flexible)
with ferrules
2
2
2
0.2 … 2.5 mm
2

5.7.3 Materials

Housing Polyamide PA 6.6 M12 plug Polyamide PA 6, brass, gold Cable screw connection Polyamide PA 6 Materials in contact with media Silicon, polyester glass-fibre rein-

5.7.4 Assembly

Integrated wall mounting straps
forced, polyamide PA 6.6, 1.4310, Ty­gon®, aluminium, NBR
14 / 20 BA_EN_DE25
FISCHER Mess- und Regeltechnik GmbH Technical Data | 5
91 48,5
76
+
Mounting lug
M12 Connector
Process connection
Cable gland M16 x 1,5
37
43
4,8
44
4,8
87
99

5.7.5 Dimensional drawings

All dimensions in mm unless otherwise stated
Illustration9: Front view
Illustration10: Rear view
BA_EN_DE25 15 / 20
6 | Order Codes FISCHER Mess- und Regeltechnik GmbH
Process connection
Output signal
Operating voltage
Characteristic curve deviation
Electrical connection
Assembly
Type
Measuring range
Code no.
0D E 2 5 4 2 K 0 0 W
1 2 5 6 7 8 9 10 11 123 4

6 Order Codes

Measuring range
[1.2] Measuring range Static operating pressure
98 0 … 2.5 mbar 50 mbar 52 0 … 4 mbar 50 mbar 53 0 … 6 mbar 50 mbar 54 0 … 10 mbar 100 mbar 55 0 … 16 mbar 100 mbar 56 0 … 25 mbar 250 mbar 57 0 … 40 mbar 250 mbar 58 0 … 60 mbar 500 mbar 59 0 … 100 mbar 500 mbar
A6 -2.5 … +2.5 mbar 50 mbar A7 -4 … +4 mbar 50 mbar A8 -6 … +6 mbar 50 mbar A9 -10 … +10 mbar 100 mbar B1 -16 … +16 mbar 100 mbar B2 -25 … +25 mbar 250 mbar C5 -40 … +40 mbar 250 mbar B3 -60 … +60 mbar 500 mbar
Characteristic curve deviation (relative pressure)
[3]
K Characteristic curve deviation 2.5%
M Characteristic curve deviation 1.0%
Process connection:
[5.6] (Code no.)
42 Plug nipple for 6/4 mm or 8 /6 mm hose
16 / 20 BA_EN_DE25
FISCHER Mess- und Regeltechnik GmbH Order Codes | 6
Output signal:
[7] (Code no.)
A 0 … 20 mA P 4 … 20 mA C 0 … 10 V
Operating voltage:
[8] (Code no.)
K 24 V DC
Electrical connection
[11] (Code no.)
M M12 plug connection E Cable screw connection
Assembly:
[12] (Code no.)
W Wall-mounting

6.1 Accessories

Order no. Planned measures No. of
Poles
06401993 Connection cable with M12 connector 4-pin 2 m 06401994 Connection cable with M12 connector 4-pin 5 m 06401563 Connection cable with M12 connector 4-pin 7 m 06401572 Connection cable with M12 connector 4-pin 10 m
Connection set
Order no. Planned measures hose Length
04005129 Plastic connection set 2 x 6/4 mm 1 m 04005148 Plastic connection set 2 x 6/4 mm 2.5 m 04005163 Plastic connection set 2 x 6/4 mm 5 m 04005216 Plastic connection set 2 x 6/4 mm 10 m 04005217 Plastic connection set 2 x 8/6 mm 1 m 04005218 Plastic connection set 2 x 8/6 mm 5 m
Length
BA_EN_DE25 17 / 20
7 | Annex FISCHER Mess- und Regeltechnik GmbH

7 Annex

Illustration11: CE_DE_DE25
18 / 20 BA_EN_DE25