FISCHER DE23 Series Instruction Manual

Page 1
Instruction Manual
DE23 Differential Pressure Transmitter
Table of Contents
1. Safety Instructions
2. Intended Applications
3. Product Description and Functions
4. Installation
5. Commissioning
6. Maintenance
7. Transport
8. Service
9. Accessories
10. Disposal
11. Specifications
12. Dimensions
13. Ordering Code
14. Declaration of Conformity
8.5.09 BA_GB_DE23.fm 09005097
1. Safety Instructions
1.1. General This manual contains detailed infor-
mation about the product, and in­structions for its installation, operation and maintenance. Opera-
tors and other technical personnel responsible for the equipment must read this thoroughly before at­tempting to install or operate this equipment. A copy of this manual must always be kept accessi­ble at the place of work for reference by concerned personnel.
Chapter 1 (sections 1.2 through 1.7) contains ge­neral as well as specific safety instructions. Chap­ters 2 through 10, covering topics ranging from intended purpose of the equipment to its final dis­posal, also include important points relating to safety. Overlooking or ignoring any of these safety points can endanger humans and animals, and possibly cause damage to other equipment.
1.2. Personnel Qualification Personnel responsible for installation, operation, maintenance and inspection of this product must
have the qualifications, training and experience necessary to carry out such work on this type of equipment.
1.3. Risks of Disregarding Safety Instruc­tions
Disregarding safety instructions, use of this pro­duct for purposes for which it is not intended, and/ or operation of this product outside the limits spe­cified for any of its technical parameters, can result in harm to persons, the environment, or the plant on which it is installed. Fischer Mess- und Regel­technik GmbH will not be responsible for conse­quences in such circumstances.
Page 2
1.4. Safety Instructions for Operators
Sensor element
Safety instructions for the proper use of this product must be followed. This information must be available at all times to by personnel responsible for installation, opera­tion, maintenance and inspection of this product. Ade­quate steps must be taken to prevent the occurrence of hazardous conditions that can be caused by electric en­ergy and
the convertible energy of the process media. Such con­ditions can, for example, be the result of improper electri­cal or process connections. Detailed information is available in relevant published norms (DIN EN, UVW in Germany; and equivalents in other countries), industrial standards such as DVWG, Ex-, GL-, VDE guidelines, as well as regulations of the local authorities (e.g., EVUs in Germany).
1.5. Modifications Forbidden Modification or other technical alteration of the product is
not permissible. This also applies to the use of unautho­rized spare parts for repair / maintenance of the product. Any modifications to this product, if and as necessary, should be done only by Fischer Mess- und Regeltechnik GmbH.
1.6. Operational Restrictions The operational reliability of the product is guaranteed only when used for intended purposes. The product must
be selected and configured for use specifically with defi­ned process media. The limiting values of operating pa­rameters, as given in the product specification sheet, must never be crossed.
3. Product Descriptions and Functions
3.1. Functional Scheme
3.2. Principles of Operation The instrument is based on a capacitance sensor ele-
ment and can measure positive gauge, negative gauge or differential pressure.
The pressure is measured directly by a micromachined silicon-on-glass differential capacitance sensor element.
Pressure changes cause capacitance changes interpre­ted by the integrated electronics.
4. Installation
The electronic module is mounted on a flat plate or panel, for which it has 4 holes at the rear for self-tapping screws 3.5 mm. A wall-mounting plate is available as an option (s. 13. Ordering Code).
The pressure transmitters are calibrated at the factory while mounted vertically, pressure ports downward. However, they can be mounted in any orientation.
IP65 protection for the housing is guaranteed only if sui­table connecting cable is used.
1.7. Safety Considerations during Installation and Maintenance
The safety instructions given in this manual, existing na­tional regulations relating to accident prevention, and the internal safety rules and procedures of the user organi­zation regarding safety during installation, operation and servicing must all be followed meticulously.
It is the responsibility of the users to ensure that only sui­tably qualified and experienced technical personnel are used for installation, operation and servicing of this equipment.
2. Intended Applications
The DE23 is a 2-wire transmitter. It is suitable for accura­te measurement of low positive / negative gauge pressu­re or differential pressure of air and gases.
If the instrument is intended for outdoor application, we highly recommend using an adequate protective housing (or at least a big enough shelter) as protection against UV-radiation on the membrane keyboard and against ex­posure of the instrument to rain or snow.
4.1. Process Connections
Only technicians who are qualified and authorized for this type of work should undertake installation.
Ensure that the process equipment and pressure li­nes are at atmospheric pressure before making pres­sure connections to the instrument.
The instrument should be provided with suitable pro­tection against pressure surges (e.g., snubber or pul­sation damper).
Ensure that the mechanical configuration and materi­als of construction of the instrument are compatible with the process media.
2
Page 3
Ensure that process pressure is always less than the
2-wire
specified safe pressure rating.
Carefully check the pressure-tightness of all pressure connections before start-up.
Do not blow into the pressure
connections!
Pressure lines must be kept as short as possible and must not have short bends to avoid measurement er­rors induced by pressure line delays.
5.1. Pressure Connections
The instruments pressure ports are marked by "+" and "-" symbols. For differential pressure applications the "+" port must be connected to the higher pressure and the "-" port should be connected to the lower pressure.
4.2. Electrical Connection
Only technicians who are qualified and authorized for this type of work should undertake installation.
Electrical connections must conform to relevant inter­national, national and local regulations and norms re­lating to electrical and instrumentation installations.
Switch off electrical power to the plant before attemp­ting electrical installation work of any kind.
Make electrical connections to the instrument through a suitable fuse.
4.3. Connection Scheme
Nominal supply voltage and the operating supply voltage range are indicated under 11. Specifications. The maxi­mum output signal loads are indicated under 11. Specifi­cations.
5. Commissioning
Power supply and pressure lines to the instrument must be correctly selected to meet operational requi­rements, and installed in way that does not cause physical stress to the instrument.
If pressure lines are used to connect the pressure in­strument and the process vessel / pipe, the pressure lines must have a downward gradient throughout, from the pressure instrument to the process vessel / pipe. This is to prevent formation of liquid plugs (for air / gas applications). If this continuous downward gra­dient cannot be provided for any reason, then suitable water separation devices must be inserted in the pressure lines.
6. Maintenance
The instrument is inherently maintenance-free.
However, to ensure reliable operation and maximize the operating life of the instrument, it is recommended that the instrument, its external electrical and process con­nections, and external connected devices be regularly in­spected, e.g.:
Check all pressure connections for leak-tightness.
Check the integrity of all electrical connections of the instruments.
Inspection and test schedules depend on operating and site conditions. The operating manuals of other equip­ment to which the level transmitter is connected must be read thoroughly to ensure that all of them work correctly when connected together.
7. Transport
The product must be protected against shock and vibra­tion during transport. It must therefore be properly pak­ked, preferably in the original factory packaging, whenever it is to be transported.
8. Service
Any defective devices or devices with missing parts should be retourned to Fischer Mess- und Regeltechnik GmbH. For quick service contact our service department.
Remaining medium in and on dismantled measuring instruments may cause danger to persons, environment and equipment. Take reasonable precautions! Clean the
instrument thoroughly if necessary.
9. Accessories
Wall mounting set (s. 13. Ordering Code)
M12 connector plug with cable (s. 13. Ordering Code)
3
Page 4
10. Disposal
Protect your environment! Use the product in accordance with relevant regulations. Please be aware of environmental conse­quences of disposal at the end of the product's life, and take care accordingly.
11. Specifications
General
Base mea-
suring range
Max. static
operating
pressure
Max. safe
pressure
Straight line
error (max.)°
Repeatability° %FS 0.1
TC span and
offset
max.°°
° Straight-line error = nonlinearity + hysteresis; at 25 °C °° Compensated temperature range 4 to 50 °C.
Operating temp. (ambient)
Operating temp. (media)
Protection class housing
Pa 0-25 0-50 0-100 0-250 0-500 0-1000 - 25...+ 25 - 50...+ 50 - 100...+ 100
bar 0.7
bar 1.7
%FS 1.0
%FS
10K
Storage temperature
-10 ... 70°C
-10 ... 70°C
-20 ... 70°C IP 65 acc. to DIN EN 60529
0.6
Nominal supply voltage
Operating supply voltage
Output signal
Output signal
Materials, media contact
load impedance
Electrical connection 1 round-shell connector M12 (5 pin, male)
Pressure connections Screw clamp connectors (aluminum) for 6/4 mm or 8/6 mm tube
Materials, housing
Electrical 24 V DC
12 ... 36 V DC 4 ... 20 mA 2-wire
(UB - 12 V) / 0.02 A
R
L
Connections, Materials, Mounting
Polyamide PA 6,6 Silicon, PVC, aluminium, brass
Mounting Rear mounting holes for back-panel mounting
Wall mounted with mounting plate If the instrument is intended for outdoor application, we highly recommend using an adequate protective housing (or at least a big enough shelter) as protection against UV-radiation on the membrane keyboard and against exposure of the instrument to rain or snow.
4
Page 5
12. Dimensions (all units in mm unless otherwise stated)
wall mounting plate (optional)
M12 connection
plug
3.5 Ø holes for
self tapping screws
Screw clamp connectors
for 6 or 8 mm tube
Rear view
without wall mounting plate
(standard)
5
Page 6
13. Ordering Code
#
##M9B
#
Differential Pressure Transmitter DE23
Range
0 . . . . 25 Pa..........................................................> D 1
0 . . . . 50 Pa..........................................................> J 6
0 . . . 100 Pa..........................................................> D 4
0 . . . 250 Pa..........................................................> D 6
0 . . . 500 Pa..........................................................> J 7
0 . . 1000 Pa..........................................................> D 9
- 25.0 . . . + 25.0 Pa ..................................................> L 5
- 50.0 . . . + 50.0 Pa ..................................................> L 2
- 100.0 . . . + 100.0 Pa ...................................................> L 7
Pressure Connection
Screw clamp connectors (aluminum) for 6/4 mm tube.................................. > 4 0
Screw clamp connectors (aluminum) for 8/6 mm tube.................................. > 4 1
Electrical Output Signal
4 - 20 mA linear, 2-wire .................................................................................................> B
Power Supply
24 V DC................................................................................................................................ > 9
Electrical Connection
M12 connection.............................................................................................................................................> M
Mounting
Standard (rear mounting holes).............................................................................................................................> 0
Mounting rail..........................................................................................................................................................> S
Wall mounting plate...............................................................................................................................................> W
Accessories
Ordering Code Description Pin Length
06401995 M12 connector plug with cable 5 pin 2 m
06401996 M12 connector plug with cable 5 pin 5 m
04005144 Wall mounting set
6
Page 7
14. Declaration of Conformity
7
Page 8
Technische Änderungen vorbehalten • Subject to change without notice • Changements techniques sous réserve
Fischer Mess- und Regeltechnik GmbH • Bielefelder Str. 37a • D-32107 Bad Salzuflen • Tel. +49 5222 9740 • Fax +49 5222 7170
eMail: info@fischermesstechnik.de • www.fischermesstechnik.de