Thank you for choosing First Alert®for your Smoke and Carbon
Monoxide Alarm needs. Y
Carbon Monoxide Alarm designed to provide you with early warning of a
e or Carbon Monoxide.
fir
Smoke & Carbon Monoxide Combination Alar
against two deadly household threats.
Spread Spectrum Horn Tone. Lower and varying horn frequency
makes it easier for elderly with normal age r
n. Sweeps through the 2200 – 3400 Hz range.
hor
t Interconnect
Smar
Heat Alarms. One interconnect wire carries both smoke and CO alarm
signals.
Optipath 360 T
the smoke sensor
Single Button Test/Silence eliminates confusion. Depending on what
mode the alarm is in, pushing the button provides different functions
such as testing the alarm, silencing the alarm, r
in silence and clearing the Latching features.
Two Silence Features. Temporarily silence low battery chirp for up to
eight hours before replacing low battery or silence an unwanted alarm
for several minutes.
wo Latching Features.
T
even after alarm condition has subsided. Low Battery Latch: Identifies
which unit is in low battery condition.
fect Mount System
Per
and a mounting bracket that keeps the alarm secur
rotation range to allow for perfect alignment.
echnology
Dust Cover is included to keep the alarm clean during construction.
Easy Installation/Maintenance featur
the mounting bracket for easy access to wiring. A battery pull tab that
keeps the battery fresh until the home is occupied. A Side Load Battery
Drawer allows for easy battery replacement without r
om the ceiling or wall.
fr
Improved UV Resistance keeps the alarm from discoloring over time.
ELECTRICAL SHOCK HAZARD. Turn off the power to the area
where the Smoke Alarm is installed before removing it from the
mounting bracket. Failure to turn off the power first may result in
serious electrical shock, injury or death.
• This unit will not alert hearing impaired residents.
It is recommended that you install special units which use
devices like flashing strobe lights to alert hearing impaired
residents.
• Installation of this unit must conform to the electrical
codes in your area; Article 210, 760 of NFPA 70 (NEC),
NFPA 72, NFPA 101; SBC (SBCCI); UBC (ICBO); NBC (BOCA);
OTFDC (CABO), and any other local or building codes that
may apply. Wiring and installation must be performed by a
licensed electrician. Failure to follow these guidelines may
result in injury or property damage.
• This unit must be powered by a 24-hour, 120VAC pure sine
wave 60Hz circuit. Be sure the circuit cannot be turned
off by a switch, dimmer, or ground fault circuit interrupter.
e to connect this unit to a 24-hour cir
Failur
prevent it from providing constant protection.
9
10
10
• This Alarm must have AC or battery power to operate.
If the AC power fails, battery back-up will allow the alarm
to sound for at least 4 minutes. If AC power fails and the
batter
y is weak, protection should last for at least 7 days.
If AC power fails and the batter
alarm cannot operate.
Never disconnect the power from an AC powered unit to
•
stop an unwanted alarm. Doing so will disable the unit and
remove your protection. In the case of a true unwanted
alarm open a window or fan the smoke away from the unit.
The alarm will reset automatically when it returns to normal
operation. Never r
operated unit to stop an unwanted alarm (caused by cooking
smoke, etc.). Instead open a window or fan the smoke away
from the unit. The alarm will reset automatically.
• Connect this unit ONLY to other compatible units. See
“How To Install This Smoke Alarm” for details. Do not
connect it to any other type of alar
Connecting anything else to this unit may damage it or
event it fr
pr
• This Smoke/CO Alarm has a battery drawer which resists
closing unless a battery is installed. This warns you the
unit will not operate under DC power without a battery.
• Do not stand too close to the unit when the alarm is
sounding. It is loud to wake you in an emergency. Exposure
to the hor
• Do not paint over the unit. Paint may clog the openings to
the sensing chambers and pr
properly.
1
ou have purchased a state-of-the-art Smoke &
Key featur
es include:
m.
One alarm pr
elated hearing loss to hear
can be inter
.
connected to BRK Smoke, CO, and
TM
ovides 360 degrees of direct access to
pr
e-testing the alarm when
Alarm Latch: Easily identifies initiating alarm
includes a gasketless base for easy installation
e over a wide
es include a large opening in
emoving the alarm
cuit may
y is dead or missing, the
emove the batteries fr
om a batter
m or auxiliar
om operating pr
n at close range may har
operly.
m your hearing.
event the unit fr
otects
y
y device.
om operating
INSTALLATION
SUGGESTED AREAS FOR INSTALLING
SMOKE ALARMS, CO ALARMS, AND COMBO UNITS
SMOKE ALARM WITH
SILENCE FEATURE
CO ALARMS
BOTH, OR COMBINATION
SMOKE/CO ALARMS
SMOKE ALARMS
KEY:
Suggested locations are based on
NFPA recommendations (NFPA 72
for Smoke Alarms and NFPA 720 for
Carbon Monoxide Alarms). Always
refer to national and local codes
before beginning any installation.
In new construction AC and AC/DC smoke alarms MUST
be interconnected to meet NFPA recommendations.
WHERE TO INSTALL THIS ALARM
Minimum coverage for Smoke Alarms, as r
National Fir
every floor, in every sleeping area, and in every bedroom (See
“Regulatory Information For Smoke Alarms” for details on the NFP
ecommendations).
r
For CO Alar
recommends that a CO Alarm should be centrally located outside of
each separate sleeping ar
For added pr
bedroom, and on every level of your home.
NOTE: For added pr
least 15 feet (4.6 meters) away fr
source where possible. In smaller homes or in manufactured homes
wher
possible fr
closer than 15 feet (4.6 meters) will not harm the Alarm, but may increase
the fr
In general, install combination Smoke and Carbon Monoxide Alar
•
•
• In the hall near every sleeping area. If your home has multiple
•
• At the bottom of the basement stairs.
• For additional coverage, install Alarms in all rooms, halls, and storage
RECOMMENDED PLACEMENT
e Protection Association (NFPA), is one Smoke Alarm on
ms,
the National Fir
otection, install additional CO Alarms in each separate
otection, install an additional Smoke/CO Alarm at
e this distance cannot be maintained, install the Alarm as far away as
om the furnace or other fuel burning source. Installing the Alarm
e Protection Association (NFPA)
ea in the immediate vicinity of the bedrooms.
om the furnace or fuel burning heat
equency of unwanted alarms.
On every level of your home, including finished attics and basements.
Inside every bedroom, especially if people sleep with the door partly
or completely closed.
sleeping areas, install a unit in each. If a hall is more than 40 feet
(12 meters) long, install a unit at each end.
At the top of first-to-second floor stairs.
eas, where temperatures normally remain between 40˚ F and 100˚ F
ar
(4˚ C and 38˚ C).
ecommended by the
A
ms:
WHERE THIS ALARM SHOULD NOT BE INST
Do NOT locate this Smoke/CO Alar
In garages, furnace rooms, crawl spaces and unfinished attics.
•
void extremely dusty, dirty or greasy areas.
A
Where combustion particles are produced. Combustion particles
•
form when something bur
kitchens, garages, and furnace rooms. Keep units at least 20 feet
(6 meters) fr
water heater
(6 meter) distance is not possible – in modular, mobile, or smaller
homes, for example – it is r
placed as far fr
placement recommendations are intended to keep these Alarms at
a r
“unwanted” alarms. Unwanted alarms can occur if a Smoke Alarm is
placed directly next to a fuel-burning source. Ventilate these areas
as much as possible.
Within 5 feet (1.5 meters) of any cooking appliance. In air streams
•
near kitchens. Air curr
sensor and cause unwanted alarms.
• In extremely humid areas. This Alarm should be at least 10 feet (3
meters) from a shower, sauna, humidifier, vaporizer, dishwasher,
laundry r
In direct sunlight.
•
• In turbulent air, like near ceiling fans or open windows. Blowing air
may pr
In areas where temperature is colder than 40˚ F (4˚ C) or hotter than
•
100˚ F (38˚ C). These areas include non-airconditioned crawl spaces,
unfinished attics, uninsulated or poorly insulated ceilings, porches,
and garages.
• In insect infested areas. Insects can clog the openings to the sensing
chamber
Less than 12 inches (305 mm) away from fluorescent lights. Electrical
•
“noise” can interfere with the sensor.
om the sources of combustion particles (stove, furnace,
, space heater) if possible. In areas where a 20-foot
om these fuel-burning sources as possible. The
easonable distance from a fuel-burning source, and thus reduce
ents can draw cooking smoke into the smoke
oom, utility room, or other source of high humidity.
event CO or smoke from reaching the sensors.
.
m:
ns. Areas to avoid include poorly ventilated
ecommended the Smoke Alarm be
ALLED
• In “dead air” spaces. See “Avoiding Dead Air Spaces”.
• When installing on the wall, the top edge of Smoke Alarms should
be placed between 4 inches (102 mm) and 12 inches (305 mm) from
the wall/ceiling line.
• When installing on the ceiling, place the alarm as close to the center
as possible.
• In either case, install at least 4 inches (102 mm) from where the
wall and ceiling meet. See “A
information.
NOTE: For any location, make sur
keep carbon monoxide or smoke from reaching the Alarm.
Installing Smoke/CO Alar
For minimum security install one Smoke/CO Alarm as close to each
sleeping area as possible. For more security, put one unit in each room.
Many older mobile homes (especially those built before 1978) have little
or no insulation. If your mobile home is not well insulated, or if you ar
unsure of the amount of insulation, it is important to install units on
inside walls only.
voiding Dead Air Spaces” for mor
e no door or other obstruction could
ms in Mobile Homes
e
e
AVOIDING DEAD AIR SPACES
“Dead air” spaces may prevent smoke from reaching the Smoke/CO
Alarm. To avoid dead air spaces, follow installation recommendations
below.
On ceilings, install Smoke/CO Alarms as close to the center of the
ceiling as possible. If this is not possible, install the Smoke/CO Alarm
at least 4 inches (102 mm) from the wall or corner.
For wall mounting (if allowed by building codes), the top edge of
Smoke/CO Alarms should be placed between 4 inches (102 mm) and
12 inches (305 mm) from the wall/ceiling line, below typical “dead air”
spaces.
On a peaked, gabled, or cathedral ceiling, install first Smoke/CO
Alarm within 3 feet (0.9 meters) of the peak of the ceiling, measured
horizontally. Additional Smoke/CO Alarms may be required depending
on the length, angle, etc. of the ceiling's slope. Refer to NFPA 72 for
details on requirements for sloped or peaked ceilings.
2
4
5
6
8
9
1
0
7
HOW TO INST
This Smoke/CO Alarm is designed to be mounted on any standar
by local codes). Read “Where to Install This Alarm” and “Where This Alarm Should Not Be Installed” before you begin installation.
ools you will need: • Needle-nose pliers or utility knife
T
ALL THIS SMOKE/CO ALARM
d wiring junction box up to a 4-inch (10 cm) size, on either the ceiling or wall (if allowed
• Standar
d flathead screwdriver
ire strippers.
• W
Make sur
from a generator or solar power, light dimmer on the same circuit or mounted near fluorescent lighting. Excessively noisy power may cause
damage to your Alar
e the Alarm is not receiving excessively noisy power. Examples of noisy power could be major appliances on the same circuit, power
m.
THE PARTS OF THIS ALARM
ts of This Unit
The Mounting Bracket:
o remove the mounting bracket from the Alarm
T
base, hold the Alarm base firmly and twist the
mounting bracket counter
bracket installs onto the junction box. It has a
variety of screw slots to fit most boxes.
The Power Connector:
The power connector plugs into a power input block
on the Alarm. It supplies the unit with AC power
• The black wir
• The white wire is neutral.
• The orange wire is used for interconnect.
If you need to remove the power connector, turn
POWER OFF first. Insert a flat scr
between the power connector and the security tab
inside the power input block. Gently pry back the tab
and pull the connector free.
clockwise. The mounting
.
e is “hot.”
ewdriver blade
The Par
1Mounting Bracket
2Mounting Slots
Locking Pins (break out of
3
bracket)
4Hot (Black) AC Wire
Neutral (White) AC Wire
5
Interconnect (Orange) Wire
6
7Quick-Connect Power
Connector
Turn this way to remove
8
from bracket
9Turn this way to attach to
bracket
10 Slide-Out Battery Drawer
3
FOLLOW
5
}
A
}
B
8
7
6
3
11
2
2
3
44
5
The basic installation of this Alarm is similar whether you want to
install one Alarm, or interconnect more than one Alarm. If you are
connecting more than one Alarm, you MUST read “Special
inter
ements For Interconnected Alarms” below before you begin
Requir
installation.
ELECTRICAL SHOCK HAZARD. T
you will install this unit at the cir
beginning installation. Failure to turn off the power before installa-
may result in serious electrical shock, injury or death.
tion
Remove the mounting bracket
1.
from the base, and attach it to
the junction box.
Using wire nuts, connect the
2.
power connector to the
household wiring.
AND-ALONE ALARM ONLY:
ST
• Connect the white wire on the power connector to the neutral
e in the junction box.
wir
Connect the black wire on the power connector to the hot wire
•
in the junction box.
• Tuck the orange wire inside the junction box. It is used for
interconnect only.
THESE INSTALLATION STEPS
urn off power to the area where
cuit breaker or fuse box before
INTERCONNECTED UNITS ONLY:
f about 1/2” (12 mm) of the plastic coating on the orange
Strip of
wire on the power connector.
• Connect the white wire on the power connector to the neutral
e in the junction box.
wir
• Connect the black wire on the power connector to the hot wire
in the junction box.
•
Connect the orange wire on the power connector to the
interconnect wire in the junction box. Repeat for each unit you
connecting. Never connect the hot or neutral wires in the
are inter
junction box to the orange interconnect wire. Never cross hot and
neutral wires between Alarms.
3. Plug the power connector into the back of the Alarm.
4. Activate the battery back-up by removing the “Pull to Activate
Battery Back-Up” tab. Or, install battery back-up. Battery back-up
cannot work until you install the battery in the correct position
(Match “+” to “+” and “-” to “-”).
Position the base of the Alarm over the mounting bracket, and turn
5.
the Alarm clockwise (right) until the unit is in place. If wall mounted,
adjust unit so words are level.
6. Check all connections.
Improper wiring of the power connector or the wiring leading to
the power connector will cause damage to the Alarm and may
lead to a non-functioning Alarm.
STAND-ALONE ALARM ONLY:
• If you are only installing one Alarm, restore power to the junction
box.
INTERCONNECTED UNITS ONL
• If you are interconnecting multiple Alarms, repeat steps
1-5 for each Alar
estore power to the junction box.
r
m in the series. When you ar
Y:
e finished,
Special Requirements For Interconnected Alarms
Failure to meet any of the above requirements could damage
•
the units and cause them to malfunction, r
protection.
AC and AC/DC Alarms can be interconnected. Under AC
•
, all units will alarm when one senses smoke or CO.
power
When power is interrupted, only the AC/DC units in the series
will continue to send and r
will not operate.
connected units can provide earlier warning of fire than stand-alone
Inter
units, especially if a fire starts in a remote area of the dwelling. If any unit
in the series senses smoke, all units will alarm. T
initiated an alarm, see table:
During an Alar
On Initiating Alarm(s)
m:
Red LED(s) flashes (flash) rapidly
eceive signals. AC powered Alarms
On All Other Alarms Red LED is Off
After an Alar
On Initiating Alarm(s)
On All Other Alarms
Compatible Inter
Inter
households will experience unwanted alarms when you test any unit
in the series. Interconnected units will only work if they are wired to
compatible units and all requirements are met. This unit is designed to
be compatible with:
9120B, SC9120B, 7010, 7010B, 4120, 4120B, 4120SB, 4919, 2002RAC,
100S, 5919, 5919TH; BRK Electronics®Heat Alarm Models HD6135F,
HD6135FB; BRK Electronics®CO Alarm Models CO5120BN,
CO5120PDBN; Smoke/CO Alarm Model SC6120B, SC7010BV, SC7010B;
and
SA4919B, SA100B.
m (Latching):
Red LED(s) On for 2 seconds/Off for 2 seconds
Green LED(s) On, Red LED(s) Off
connected Units
connect units within a single family residence only. Otherwise all
BRK Electronics®Smoke Alarm Models 9120,
First Alert®Smoke Alarm Models SA4120, SA4120B, SA4121B,
Interconnected units must meet ALL of the following requirements:
• A maximum of 18 compatible units may be interconnected
(Maximum of 12 Smoke Alarms).
• The same fuse or circuit breaker must power all interconnected
units.
• The total length of wire interconnecting the units should be
less than 1000 feet (300 meters). This type of wire is commonly
available at Hardware and Electrical Supply stores.
• All wiring must conform to all local electrical codes and NFPA 70
(NEC). Refer to NFPA 72, NFPA 101, and/or your local building
code for further connection requirements.
emoving your
o determine which Alarm
e power until all
ELECTRICAL SHOCK HAZARD. Do not r
Alarms are completely installed. Restoring power before installation
is complete may result in serious electrical shock, injury or death.
6. Make sure the Alarm is receiving AC power. Under normal
operation, the Green power indicator light will shine continuously.
7. If the Green power indicator light does not light,
POWER TO THE JUNCTION BOX
If all connections are correct and the Green power indicator still
does not light when you restore the power, the unit should be
eplaced immediately
r
est each Smoke Alarm. Pr
T
8.
until the unit alarms.
units you must test each unit individually. Make sure all units
alarm when each one is tested.
If any unit in the series does not alar
echeck connections. If it does not alar
r
replace it immediately.
.
ess and hold the T
When testing a series of interconnected
estor
TURN OFF
echeck all connections.
and r
est/Silence button
m, TURN OFF POWER and
m when you r
estor
e power
A. Unswitched 120VAC
60 Hz sour
1. Alarm
2. Ceiling or Wall
3. Power Connector
ce
B. To additional units; Maximum = 18 total
(Maximum 12 Smoke Alarms)
4. Wire Nut
5. Junction Box
6. Neutral Wire (Wht)
7. Interconnect Wire
(Orange)
e (Blk)
Hot Wir
8.
,
4
LOCKING FEATURES
The locking featur
single-family households where unauthorized battery or Alarm removal is not a concern.
These Alarms have two separate locking featur
the mounting bracket. Y
Tools you will need: • Needle-nose pliers • Standard Flathead screwdriver.
Both locking features use locking pins, which are molded into the mounting bracket. Using needle-nose pliers, remove
one or both pins fr
To permanently remove either lock, insert a flathead screwdriver between the locking pin and the lock, and pry the pin out of the lock.
es are designed to discourage unauthorized removal of the batteries or Alarm. It is not necessary to activate the locks in
ou can choose to use either feature independently, or use them both.
om the mounting bracket, depending on how many locking features you want to use.
es: one to lock the battery compartment, and the other to lock the Alarm to
TO LOCK THE BATTERY COMPARTMENT
Do not lock the battery compartment until you have installed the
battery and tested the battery back-up.
1. Push and hold Test/Silence button until the alarm sounds.
If the unit does not alar
compartment! Install a new battery and test again. If the Alarm still
does not alar
Using needle-nose pliers, detach one locking pin from the mounting
2.
bracket.
3. Push the locking pin through the hole near the battery drawer on
the back of the Alarm.
m, replace it immediately.
m during testing, DO NOT lock the battery
TO LOCK THE MOUNTING BRACKET
1. Using needle-nose pliers, detach one locking pin from mounting
bracket.
TO UNLOCK THE BATTERY COMPARTMENT
Once the Alarm is installed, you must disconnect it from the AC power
e unlocking the battery compartment.
befor
ELECTRICAL SHOCK HAZARD. Turn off the power to the area where
m is installed before removing it from the mounting bracket.
the Alar
e to turn off the power first may result in serious electrical
Failur
shock, injury or death.
Always dischar
m. First, turn off the AC power at the circuit breaker or fuse box.
Alar
Next, remove the battery from Alarms with battery back-up. Finally,
ess and hold the Test/Silence button for 5-10 seconds to discharge
pr
the branch cir
1. Remove the Alarm from the mounting bracket.
If the unit is locked to the bracket, see the
section “T
2. Disconnect the power connector by gently
prying it away from the back of the Alarm.
3. Insert a flathead screwdriver under the head
of the locking pin, and gently pry it out of the
battery compartment lock. (If you plan to
relock the battery compartment, save the
locking pin.)
4. To relock the battery compartment, close the battery door and
reinsert locking pin in lock.
5. Reconnect the power connector to the back of the Alarm, reattach
the Smoke Alarm to the mounting bracket, and restore the power.
When replacing the batteries, always test the Alarm before relocking the
battery compartment.
ge the branch circuit before servicing an AC or AC/DC
cuit.
o Unlock the Mounting Bracket.”
TO UNLOCK THE MOUNTING BRACKET
ELECTRICAL SHOCK HAZARD. Turn off the power to the area where
the Alarm is installed before removing it from the mounting bracket.
Failure to turn off the power first may result in serious electrical
shock, injury or death.
Insert the locking pin into the lock located
2.
opposite from the battery drawer as shown
in the diagram.
When you attach the Alarm to the mounting bracket, the locking
3.
s head will fit into a notch on the bracket.
pin’
Always discharge the branch circuit before servicing an AC or AC/DC
m. First, tur
Alar
emove the batter
Next, r
press and hold the Test/Silence button for 5-10 seconds to discharge
the branch circuit.
1. Insert a flathead screwdriver between the
mounting bracket pin and the mounting
bracket.
2. Pry the Alarm away from the bracket by
turning both the screwdriver and the Alarm
counterclockwise (left) at the same time.
5
f the AC power at the circuit breaker or fuse box.
n of
y from Alarms with battery back-up. Finally,
A
B
WEEKLY TESTING
1
REGULAR MAINTENANCE
•
NEVER use an open flame of any kind to test this unit. Y
might accidentally damage or set fir
home. The built-in test switch accurately tests the unit’
operation as r
NEVER use vehicle exhaust! Exhaust may cause per
damage and voids your warranty.
If the Alarm ever fails to test properly, replace it immediately.
•
Products under warranty may be returned to the manufacturer
eplacement. See “Limited Warranty” at the end of this
for r
manual.
It is impor
sure it is working properly. Using the test button is
the recommended way to test this Smoke/CO Alarm.
Y
holding the T
During testing, you will see and hear the following
sequence:
If the unit does not alar
installed, and test again. If the unit still does not alar
immediately.
tant to test this unit every week to make
ou can test this Smoke/CO Alarm bypressing and
• The
Horn will sound 3 beeps, pause, 3 beeps. The Power/Smoke
LED
flashes Red and the CO LED will be Off.
• Next the
Smoke LED will be Of
equired by Underwriters Laboratories, Inc. (UL).
est/Silence button on the Alarm cover.
Horn will sound 4 beeps, pause, 4 beeps. The Power/
f and the
m, make sure the batteries are correctly
e to the unit or to your
CO LED flashes Red.
m, replace it
s
manent
WHAT YOU WILL SEE AND HEAR WITH THIS ALARM
Under Nor
When You Test the Alarm
If Battery Becomes Low or is Missing
If Alarm is Not Operating Properly
Alarm Levels of CO are Detected
*NOTE: If unit goes into CO alarm, the regular 4 beeps-brief pause
cycle will repeat for fifteen minutes. After fifteen minutes, the pause
will incr
Smoke is Detected
Smoke Alar
mal Operations
n:
Hor
SilentPower/Smoke LED: Constant Gr
Horn:3 beeps, pause, 3 beeps
Power/Smoke LED: Flashes Red in sync with the hor
CO LED: Off, followed by
Horn: 4 beeps, pause, 4 beeps
Power/Smoke LED: Off
CO LED: Flashes Red in sync with the horn pattern
chirps once a minute
Horn:
Power/Smoke LED: Flashes Green On for 2 seconds/Off for
2 seconds. Low Battery Latch is now engaged.
CO LED: Off
Horn: Three rapid chirps every minute
Power/Smoke LED: Flashes approximately once a minute
CO LED: Off
Horn: 4 beeps, pause, 4 beeps*
Power/Smoke LED: Off
CO LED: During Alarm: Flashes Red in sync with the horn pattern.
Horn:
Power/Smoke LED: During Alarm: Flashes Red in sync with the
CO LED: Of
Horn: Off
Power/Smoke LED: Flashes
CO LED: Off
After Alarm: Flashes Red On for 2 seconds/Off for 2
seconds. CO Alarm Latch is now engaged.
ease to one minute.
3 beeps, pause, 3 beeps
n. After Alarm: Flashes Red On for 2
n patter
hor
seconds/Off for 2 seconds. Smoke Alarm Latch is now
engaged.
f
m is Silenced
Red
CO LED: Off
m is Silenced
CO Alar
Horn: Off
Power/Smoke LED: Off
CO LED: Flashes Red
n pattern
ou
een
Use only the r
operate pr
batteries since they may not pr
This unit has been designed to be as maintenance-free as possible, but
e are a few simple things you must do to keep it working properly:
ther
• Test it at least once a week.
• Clean the Smoke/CO Alarm at least once a month; gently vacuum
the outside of the Smoke/CO Alarm using your household vacuum’s
soft brush attachment. T
cleaners or solvents since they may damage the unit.
If the Smoke/CO Alarm becomes contaminated by excessive dirt,
•
dust and/or grime, and cannot be cleaned to avoid unwanted
alarms, r
• Relocate the unit if it sounds frequent unwanted alarms. See “Where
This Alarm Should Not Be Installed” for details.
When the battery back-up becomes weak, the Alarm will “chirp”
•
about once a minute (the low battery war
last 7 days, but you should replace the battery immediately to
continue your pr
engaged. The Gr
Off for 2 seconds.
Choosing a r
our Smoke/CO Alarm requires two “AA” Energizer E91 batteries.
Y
batteries ar
Actual battery service life depends on the Alarm and the environment
in which it is installed. All the batteries specified above ar
replacement batteries for this unit. Regardless of the manufacturer’s
suggested battery life,
once the unit star
To replace the batteries (without removing Alarm from the ceiling
or wall):
1. Open the battery compartment.
2. Press tabs A and B as shown in the
diagram and remove each battery.
3. Insert the new batteries, making sure
they snap completely into the battery
compartment. Match the terminals on
the ends of the batteries with the
terminals on the unit.
4. Close the battery compartment, and
then test the unit by pressing the
Test/Silence button.
eplacement batteries listed below. The unit may not
operly with other batteries. Never use rechargeable
eplace the unit immediately.
otection. The Low Battery Latch feature will be
een Power/Smoke LED will flash On for 2 seconds/
eplacement battery:
e available at many local retail stores.
you MUST replace the battery immediately
ts “chirping” (the “low battery warning”).
ovide a constant charge.
est the Smoke/CO Alarm. Never use water,
ning). This warning should
e acceptable
These
IF YOUR SMOKE/CO ALARM SOUNDS
WHAT TO DO FIRST–
IDENTIFY THE TYPE OF ALARM SIGNAL
Type of Alarm
Carbon Monoxide (CO)
Smoke
What You See and Hear
4 beeps, pause, 4 beeps
Horn:
Power/Smoke LED: Of
CO LED: Flashes Red
Horn:3 beeps, pause, 3 beeps
Power/Smoke LED: Flashes Red
CO LED: Off
f
Continued...
6
IF YOUR SMOKE/CO ALARM SOUNDS, Continued
IF THE CO ALARM SOUNDS
“ALARM-MOVE TO FRESH AIR”
If you hear the CO alar
Actuation of your CO Alar
monoxide (CO) which can kill you. In other words, when your CO
m sounds, you must not ignore it!
Alar
IF THE CO ALARM SIGNAL SOUNDS:
Operate the Test/Silence button.
1.
Call your emergency services, fire department or 911. Write down the
3. Immediately move to fresh air—outdoors or by an open door or
window. Do a head count to check that all persons are accounted
for
or window until the emergency services responder has arrived, the
premises have been aired out, and your CO Alarm remains in its
normal condition.
After following steps 1-3, if your CO Alarm reactivates within a 24-
4.
hour period, r
technician to investigate for sources of CO from fuel-burning
equipment and appliances, and inspect for pr
equipment. If pr
equipment serviced immediately. Note any combustion equipment
not inspected by the technician, and consult the manufactur
instructions, or contact the manufacturers directly, for more information about CO safety and this equipment. Make sure that motor
vehicles are not, and have not, been operating in an attached
garage or adjacent to the residence. Write down the number of a
qualified appliance technician here:
NOTE: A qualified appliance technician is defined as “a person, firm,
corporation, or company that either in person or through a representative,
is engaged in and responsible for the installation, testing, servicing, or
replacement of heating, ventilation, air conditioning (HVAC) equipment,
combustion appliances and equipment, and/or gas fireplaces or other
decorative combustion equipment.”
move ever
. Do not re-enter the premises, or move away from the open door
epeat steps 1-3 and call a qualified appliance
m horn and the CO red light is flashing,
yone to a source of fresh air.
DO NOT remove the batteries!
m indicates the presence of carbon
oblems are identified during this inspection have the
oper operation of this
ers’
IF THE SMOKE ALARM SOUNDS
RESPONDING TO AN ALARM
• If the unit alarms and you are not testing the unit, it is warning
you of a potentially dangerous situation that requires your
immediate attention. NEVER ignore any alarm. Ignoring the
alarm may result in injury or death.
• Never remove the batteries from a battery operated Smoke/CO
Alarm to stop an unwanted alarm (caused by cooking smoke,
etc.). Removing batteries disables the alar
smoke, and r
fan the smoke away from the unit. The alarm will reset automatically.
• If the unit alarms get everyone out of the house immediately.
T TO DO IN CASE OF FIRE
WHA
Don’
•
Get out of the house as quickly as possible. Don’
•
dressed or collect anything.
• Feel doors with the back of your hand before opening them.
If a door is cool, open it slowly. Don’t open a hot door. Keep doors
and windows closed, unless you must escape thr
• Cover your nose and mouth with a cloth (preferably damp).
Take short, shallow breaths.
Meet at your planned meeting place outside your home,
•
and do a head count to make sur
• Call the Fire Department as soon as possible from outside.
Give your address, then your name.
• Never go back inside a burning building for any reason.
Contact your Fir
•
emoves your protection. Instead open a window or
t panic; stay calm. Follow your family escape plan.
e everybody got out safely.
e Department for ideas on making your home safer
m so it cannot sense
t stop to get
ough them.
USING THE SILENCE FEA
emove the batteries to quiet an unwanted alarm. Removing
Never r
the batteries disables the alar
The Silence Featur
you identify and corr
emergency situations. It will not correct a CO problem or extinguish a
e.
fir
The Silence Featur
minutes. You can silence this Smoke/CO Alarm by pressing the
Test/Silence button on the alarm cover for at least 3-5 seconds.
After the Test/Silence button is released, the Red LED blinks during the
silence mode.
When the Smoke Alarm is
Silenced
The Smoke Alarm will r
silent for up to 15 minutes, then
return to normal operation.
If the smoke has not cleared–or
continues to incr
will go back into alarm.
e is intended to temporarily silence the horn while
ect the problem. Do not use the Silence Feature in
e can temporarily quiet an unwanted alarm for several
emain
ease–the device
TURES
m and removes your protection.
When the CO Alarm is
Silenced
The CO alarm will r
for up to 4 minutes.
After 4 minutes, if CO levels
remain potentially dangerous the
n will start sounding again.
hor
emain silent
SILENCING THE LOW BATTERY WARNING
This Silence Featur
“chirp” for up to 8 hours if AC power is present. Press the Test/Silence
button on the Alarm cover until you hear the acknowledge “chirp”.
Once the low battery war
continues to flash the green light once a minute for 8 hours. After 8
hours, the low battery “chirp” will resume. The Alarm will continue to
operate as long as AC power is supplied. However,
as soon as possible,
o deactivate this feature: Press the Test/Silence button again. The unit
T
will go into Test Mode and the low battery warning will resume (LED
flashes and unit sounds “chirp” once a minute).
To silence Alarms in an interconnected series:
To silence an interconnected series of Smoke/CO Alarms, you must
press the Test/Silence button on the initiating alarm (The unit with the
flashing red light; the red light will be off on all other Alarms.). If you
press the Test/Silence on any other Alarm, it will only silence that unit,
not the whole interconnected series.
e can temporarily quiet the low battery warning
ning “chirp” silence featur
to maintain protection in event of a power outage.
e is activated, the unit
replace the batteries
LATCHING FEATURES
Alarm Latch is activated after an Alarm is exposed to alarm levels of
smoke or carbon monoxide. This feature will only work with AC power.
After smoke or CO levels drop below alarm levels, the
or “CO” Red LED will begin to flash once every few seconds. It will
continue to flash or “latch” until you clear it by testing the alarm.
This feature helps emergency responders, investigators, or service
technicians identify which unit(s) in your home were exposed to alarm
levels of smoke or carbon monoxide. This can help investigators
pinpoint the source of smoke or CO.
Interconnected Alarms. Latching Alarm Indicator shows which Alarm(s)
in the series were exposed to alarm levels of smoke or carbon monoxide.
The Latching Alarm Indicator stays ON until you clear it, so it can alert
you to an alarm that occurred while you were away from home, even
though smoke or CO present in the air has dropped below alarm levels.
Low Battery Latch is activated when the Alarm is in the "low battery
condition". When this occurs, the
for 2 seconds/Of
identify which Alarm needs to have the battery replaced. Although, the
Alarm will sound the low battery chirp approximately once every minute,
sometimes during the initial stages of "low battery", the Alarm will chirp
eater intervals than one minute, sometimes up to several hours, until
in gr
the battery reaches a steady low battery level. This innovative feature
eliminates the frustration of waiting for and/or identifying which unit is
chirping.
f for 2 seconds. This featur
Smoke/Power LED flashes Green On
“Smoke/Power”
e is designed to help you
“SMART INTERCONNECT” FEATURE
This Alarm includes "Smart Interconnect" which enables the Alarm to be
connected with other First Alert
inter
connect" CO Alarms. When smoke is detected, all Alarms will sound
Inter
the smoke horn pattern. When CO is detected, "Smart Interconnect"
.
Alarms will sound the CO horn pattern. Alarms that do not have the
"Smart Interconnect" feature will remain silent during a CO alarm.
®
and BRK Smoke, Heat, and "Smart
ms have various limitations. See "General Limitations of
Alar
Smoke/CO Alarms" for details.
7
WHAT YOU NEED TO KNOW ABOUT CO
WHAT IS CO?
CO is an invisible, odorless, tasteless gas pr
do not burn completely, or are exposed to heat (usually fire). Electrical
appliances typically do not pr
These fuels include: W
osene, and propane.
ker
Common appliances ar
maintained, are improperly ventilated, or malfunction, CO levels can rise
quickly. CO is a real danger now that homes are more energy efficient.
-tight” homes with added insulation, sealed windows, and other
“Air
weatherproofing can “trap” CO inside.
oduce CO.
ood, coal, charcoal, oil, natural gas, gasoline,
e often sources of CO. If they are not properly
SYMPTOMS OF CO POISONING
These symptoms are related to CO POISONING and should be
discussed with ALL household members.
heart rate.
Extreme Exposure: Convulsions, unconsciousness, heart and lung
e. Exposure to Carbon Monoxide can cause brain damage, death.
failur
This CO Alarm measures exposure to CO over time. It alarms if CO
levels are extremely high in a short period of time, or if CO levels reach
a certain minimum over a long period of time. The CO Alarm generally
sounds an alarm before the onset of symptoms in average, healthy
adults. Why is this important? Because you need to be warned of a
potential CO pr
cases of CO exposure, victims may be aware that they are not feeling
well, but become disoriented and can no longer react well enough to
exit the building or get help. Also, young childr
fected. The average healthy adult might not feel any symptoms
first af
when the CO Alarm sounds. However, people with cardiac or respiratory
oblems, infants, unborn babies, pregnant mothers, or elderly people
pr
can be more quickly and severely affected by CO. If you experience
even mild symptoms of CO poisoning, consult your doctor immediately!
obbing headache, drowsiness, confusion, fast
oblem while you can still react in time. In many reported
FINDING THE SOURCE OF CO AFTER AN ALARM
Carbon monoxide is an odorless, invisible gas, which often makes it
difficult to locate the source of CO after an alarm. These are a few of the
factors that can make it difficult to locate sources of CO:
• House well ventilated before the investigator arrives.
• Problem caused by “backdrafting.”
• Transient CO problem caused by special circumstances.
Because CO may dissipate by the time an investigator arrives, it may
be difficult to locate the source of CO.
obligated to pay for any carbon monoxide investigation or service
call.
oduced when fossil fuels
en and pets may be the
BRK Brands, Inc. shall not be
POTENTIAL SOURCES OF CO IN THE HOME
ning appliances like:
Fuel-bur
fireplace, gas kitchen range or cooktop, gas clothes dryer.
Damaged or insuf
heater vent pipe, leaking chimney pipe or flue, or cracked heat exchanger
blocked or clogged chimney opening.
oper use of appliance/device:
Impr
in an enclosed area (like a garage or screened porch).
ransient CO Problems:
T
can be caused by outdoor conditions and other special cir
The following conditions can r
Excessive spillage or reverse venting of fuel appliances caused by
1.
outdoor conditions such as:
• Wind direction and/or velocity, including high, gusty winds.
Heavy air in the vent pipes (cold/humid air with extended periods
between cycles).
• Negative pressure dif
• Several appliances running at the same time competing for limited
fresh air.
• Vent pipe connections vibrating loose from clothes dryers,
furnaces, or water heaters.
• Obstructions in or unconventional vent pipe designs which can
3. Temperature inversions, which can trap exhaust close to the ground.
4. Car idling in an open or closed attached garage, or near a home.
These conditions are dangerous because they can trap exhaust in your
home. Since these conditions can come and go, they are also hard to
recreate during a CO investigation.
ficient venting:
portable heater
corr
operating a barbecue grill or vehicle
“transient” or on-again-of
esult in transient CO situations:
ferential resulting from the use of exhaust fans.
, gas or wood burning
oded or disconnected water
f-again CO problems
cumstances.
,
HOW CAN I PROTECT MY FAMILY FROM
CO POISONING?
A CO Alarm is an excellent means of protection. It monitors the air and
sounds a loud alarm before Carbon Monoxide levels become thr
for average, healthy adults.
A CO Alarm is not a substitute for proper maintenance of home
appliances.
To help prevent CO problems and reduce the risk of CO poisoning:
• Clean chimneys and flues yearly. Keep them free of debris, leaves,
and nests for proper air flow. Also, have a professional check for
rust and corrosion, cracks, or separations. These conditions can
pr
or cover a chimney in any way that would block air flow.
• Test and maintain all fuel-burning equipment annually. Many local
gas or oil companies and HVAC companies offer appliance
inspections for a nominal fee.
• Make regular visual inspections of all fuel-burning appliances.
Check appliances for excessive rust and scaling. Also check the
flame on the burner and pilot lights. The flame should be blue.
A yellow flame means fuel is not being bur
may be present. Keep the blower door on the furnace closed.
Use vents or fans when they are available on all fuel-burning
appliances. Make sur
not grill or barbecue indoors, or in garages or on scr
Check for exhaust backflow fr
•
hood on an operating furnace for a backdraft. Look for cracks on
fur
Check the house or garage on the other side of shar
•
Keep windows and doors open slightly
•
is escaping into your home, open a window or a door. Opening
windows and doors can significantly decrease CO levels.
In addition, familiarize yourself with all enclosed materials. Read
this manual in its entirety, and make sure you understand what to
do if your CO Alar
oper air movement and cause backdrafting. Never “cap”
event pr
ned completely and CO
e appliances ar
nace heat exchangers.
m sounds.
e vented to the outside. Do
om CO sour
ces. Check the draft
. If you suspect that CO
eatening
een porches.
ed wall.
8
REGULATORY INFORMATION FOR
SMOKE/CO ALARMS
REGULATORY INFORMATION FOR CO ALARMS
T LEVELS OF CO CAUSE AN ALARM?
WHA
Underwriters Laboratories Inc. Standar
Alarms to sound when exposed to levels of CO and exposur
described below. They are measured in parts per million (ppm) of CO
over time (in minutes).
UL2034 Requir
• If the alarm is exposed to 400 ppm of CO, IT MUST ALARM
• If the alarm is exposed to 150 ppm of CO, IT MUST ALARM
• If the alarm is exposed to 70 ppm of CO, IT MUST ALARM
* Approximately 10% COHb exposure at levels of 10% to 95% Relative
Humidity (RH).
The unit is designed not to alarm when exposed to a constant level
of 30 ppm for 30 days.
ed Alarm Points*:
BETWEEN 4 and 15 MINUTES.
BETWEEN 10 and 50 MINUTES.
BETWEEN 60 and 240 MINUTES.
d UL2034 requires residential CO
e times as
RECOMMENDED LOCA
TIONS FOR SMOKE ALARMS, Continued
CO Alarms ar
eat. Since you cannot see or smell CO, never assume it’s not present.
thr
An exposure to 100 ppm of CO for 20 minutes may not affect
•
average, healthy adults, but after 4 hours the same level may cause
headaches.
• An exposure to 400 ppm of CO may cause headaches in average,
healthy adults after 35 minutes, but can cause death after 2 hours.
Standar
carbon monoxide alarms UL2034.
According to Underwriters Laboratories Inc. UL2034, Section 1-1.2:
“Carbon monoxide alarms covered by these r
espond to the presence of carbon monoxide from sources such as,
to r
but not limited to, exhaust fr
operation of fuel-fired appliances, and fireplaces. CO Alarms are intended
to alarm at carbon monoxide levels below those that could cause a loss
of ability to react to the dangers of Carbon Monoxide exposure.” This CO
Alarm monitors the air at the Alarm, and is designed to alarm before CO
levels become life threatening. This allows you precious time to leave
the house and correct the problem. This is only possible if Alarms are
located, installed, and maintained as described in this manual.
Gas Detection at Typical Temperature and Humidity Ranges: The
CO Alarm is not formulated to detect CO levels below 30 ppm typically.
UL tested for false alarm resistance to Methane (500 ppm), Butane (300
ppm), Heptane (500 ppm), Ethyl Acetate (200 ppm), Isopropyl Alcohol
(200 ppm) and Carbon Dioxide (5000 ppm). Values measure gas and
vapor concentrations in parts per million.
Audible Alarm: 85 dB minimum at 10 feet (3 meters).
e designed to alarm before there is an immediate life
ds:
Underwriters Laboratories Inc. Single and Multiple Station
equirements are intended
om internal-combustion engines, abnormal
REGULATORY INFORMATION FOR SMOKE ALARMS
RECOMMENDED LOCATIONS FOR SMOKE ALARMS
Installing Smoke Alar
The National Fire Protection Association (NFPA), recommends one Smoke
Alarm on every floor, in every sleeping area, and in every bedroom. In new
construction, the Smoke Alarms must be AC powered and interconnected.
See “Agency Placement Recommendations” for details.
coverage, it is r
halls, storage areas, finished attics, and basements, where temperatures
normally remain between 40˚ F (4˚ C) and 100˚ F (38˚ C). Make sure no
door or other obstruction could keep smoke from reaching the Smoke
Alarms.
e specifically
Mor
• On every level of your home, including finished attics and basements.
• Inside every bedroom, especially if people sleep with the door partly
or completely closed.
• In the hall near every sleeping area. If your home has multiple
sleeping areas, install a unit in each. If a hall is more than 40 feet
long (12 meters), install a unit at each end.
• At the top of the first-to-second floor stairway, and at the bottom
of the basement stairway.
ms in Single-Family Residences
ecommended that you install a Smoke Alarm in all r
, install Smoke Alar
ms:
For additional
ooms,
INSTALLING SMOKE ALARMS IN MOBILE HOMES
For minimum security install one Smoke Alarm as close to each
sleeping area as possible. For more security, put one unit in each room.
Many older mobile homes (especially those built before 1978) have little
or no insulation. If your mobile home is not well insulated, or if you ar
unsure of the amount of insulation, it is important to install units on
inside walls only. Smoke Alarms should be installed where temperatures
normally r
AGENCY PLACEMENT RECOMMENDA
Standards: Underwriters Laboratories Inc. Single and Multiple Station
Smoke Alarms 217.
NFPA 72 (National Fire Code) Chapter 11
“For your information, the National Fir
Standard 72, reads as follows:”
“11.5.1 One- and Two-Family Dwelling Units.”
“11.5.1.1 Smoke Detection.
or standards for the specified occupancy, approved single- and multiplestation Smoke Alarms shall be installed as follows: (1) In all sleeping
rooms Exception: Smoke Alarms shall not be required in sleeping rooms
in existing one- and two-family dwelling units. (2) Outside of each
separate sleeping area, in immediate vicinity of the sleeping rooms.
(3) On each level of the dwelling unit, including basements Exception:
In existing one- and two family dwelling units, approved Smoke Alarms
powered by batteries are permitted.”
“A.11.8.3 Are More Smoke Alarms Desirable?
The required number of Smoke Alarms might not provide reliable early
warning protection for those areas separated by a door from the areas
protected by the required Smoke Alarms. For this reason, it is recommended that the householder consider the use of additional Smoke
Alarms for those areas for increased protection. The additional areas
include the basement, bedrooms, dining room, furnace room, utility
room, and hallways not protected by the required Smoke Alarms. The
installation of Smoke Alarms in kitchens, unfinished attics, or garages is
not normally recommended, as these locations occasionally experience
conditions that can result in improper operation.”
Califor
Early war
detection equipment in all rooms and areas of the household as follows:
A Smoke Alarm installed in each separate sleeping area (in the vicinity,
but outside bedrooms), and Heat or Smoke Alarms in the living rooms,
dining r
rooms, closets, utility and storage rooms, basements, and attached
garages.
emain between 40˚ F (4˚ C) and 100˚ F (38˚ C).
TIONS
e Protection Association's
Where required by applicable laws, codes,
nia State Fire Marshal (CSFM)
ning detection is best achieved by the installation of fir
Specific requirements for Smoke Alarm installation vary from state to
state and from region to region. Check with your local Fire Department
for curr
units be interconnected for added protection.
ent r
equir
ements in your ar
ea.
ecommended AC or AC/DC
It is r
9
ABOUT SMOKE ALARMS
Battery (DC) operated Smoke Alarms: Provide protection even when
electricity fails, pr
e easy to install, and do not require professional installation.
Units ar
However, they do not provide interconnected functionality.
AC powered Smoke Alarms: Can be interconnected so if one unit
senses smoke, all units alarm. They do not operate if electricity fails.
AC with batter
the batteries are fresh and correctly installed. AC and AC/DC units must
be installed by a qualified electrician.
ireless Interconnected Alarms:Offer the same interconnected
W
functionality as with har
to install and do not require professional installation. They provide
otection even when electricity fails, provided the batteries are fresh
pr
and correctly installed.
Smoke/CO Alar
backup power systems: AC powered Smoke/CO Alarms should only
be operated with true or pur
with most battery-powered UPS (uninterruptible power supply) products
or square wave or “quasi sine wave” inverters
If you ar
the manufacturer to verify.
Smoke Alarms for the hearing impaired: Special purpose Smoke
Alarms should be installed for the hearing impaired. They include a
visual alarm and an audible alarm hor
the Americans With Disabilities Act. Can be interconnected so if one
unit senses smoke, all units alarm.
Smoke alarms are not to be used with detector guards unless the
combination has been evaluated and found suitable for that purpose.
All these Smoke Alarms ar
located, installed and car
smoke r
to install, r
72 (National Fire Alarm Code) and NFPA 101 (Life Safety Code).
National Fir
02269-9101. Local building codes may also require specific units in new
construction or in different areas of the home.
ovided the batteries are fresh and correctly installed.
y (DC) back-up:
ms for Solar or Wind Energy users and battery
e not sure about your inverter or UPS type, please consult with
eaches the Alarm. If you are unsure which type of Smoke Alarm
efer the National Fire Protection Association (NFPA) Standard
e Protection Association, One Batterymarch Park, Quincy, MA
will operate if electricity fails, pr
dwired alarms, without wires. Units are easy
e sine wave inverters. Operating this Alarm
will damage the Alarm.
n, and meet the requirements of
e designed to provide early warning of fires if
ed for as described in the user’s manual, and if
ovided
SPECIAL COMPLIANCE CONSIDERATIONS
This unit alone is not a suitable substitute for complete fir
systems in places housing many people—like apar
condominiums, hotels, motels, dor
health car
homes of any kind—even if they wer
It is not a suitable substitute for complete fire detection systems
in war
special-purpose non-r
fire detection and alarm systems. Depending on the building codes
in your ar
in these facilities.
The following information applies to all five types of buildings listed
below:
In new construction, most building codes r
power
Smoke Alarms can be used in existing construction as specified by
local building codes. Refer to NFP
NFP
Department for detailed fire protection requirements in buildings not
defined as “households.”
1. Single-Family Residence:
Single family home, townhouse. It is recommended this unit be installed
on every level of the home, in every bedroom, and in each bedroom
hallway
2. Multi-Family or Mixed Occupant Residence:
Apartment building, condominium. This unit is suitable for use in
individual apartments or condos, pr
system alr
areas like lobbies, hallways, or porches. Using this unit in common areas
may not pr
protection ordinances/regulations.
3. Institutions:
Hospitals, day car
suitable for use in individual patient sleeping/resident rooms, provided
a primary fire detection system already exists to meet fire detection
r
this unit in common areas may not provide sufficient warning to all
residents or meet local fire protection ordinances/regulations.
4. Hotels and Motels:
Also boarding houses and dormitories. This unit is suitable for use inside
individual sleeping/resident rooms, provided a primary fire detection
system already exists to meet fire detection requirements in common
areas like lobbies, hallways, or porches. Using this unit in common areas
may not provide sufficient warning to all residents or meet local fire
protection ordinances/regulations.
5. Warehouses/Commercial Buildings:
DO NOT use this Smoke/CO Alarm in warehouses, industrial or
commercial buildings, special-purpose non-residential buildings, RVs,
boats, or airplanes. This Smoke/CO Alarm is specifically designed
for residential use, and may not provide adequate protection in nonresidential applications.
e facilities, nursing homes, day care facilities, or group
ehouses, industrial facilities, commercial buildings, and
ea, this unit may be used to provide additional protection
ed Smoke Alarms only. AC, AC/DC, DC or Wireless DC powered
A 101 (Life Safety Code), local building codes, or consult your Fire
.
eady exists to meet fire detection requirements in common
ovide sufficient warning to all residents or meet local fire
equirements in common areas like lobbies, hallways, or porches. Using
esidential buildings which require special
e facilities, long-term health care facilities. This unit is
mitories, hospitals, long-term
e once single-family homes.
equire the use of AC or AC/DC
A 72 (National Fire Alarm Code) and
ovided a primary fire detection
e detection
tment buildings,
GENERAL LIMITATIONS OF SMOKE/CO ALARMS
This Smoke/CO Alarm is intended for residential use. It is not intended
for use in industrial applications where Occupational Safety and Health
Administration (OSHA) r
be met. The Smoke Alarm portion of this device is not intended to alert
hearing impaired residents. Special purpose Smoke Alarms should be
installed for hearing impaired residents (CO Alarms are not yet available
for the hearing impaired).
Smoke/CO Alarms may not waken all individuals. Practice the
escape plan at least twice a year
– from kids to grandparents. Allow children to master fire escape
planning and practice before holding a fire drill at night when they are
sleeping. If childr
Smoke/CO Alarm, or if ther
limitations, make sure that someone is assigned to assist them in fire
drill and in the event of an emergency. It is recommended that you hold
a fire drill while family members are sleeping in order to determine their
response to the sound of the Smoke/CO Alarm while sleeping and
to determine whether they may need assistance in the event of an
emergency.
Smoke/CO Alarms cannot work without power. Battery operated
units cannot work if the batteries are missing, disconnected or dead, if
the wrong type of batteries are used, or if the batteries are not installed
ectly
corr
(open fuse or circuit breaker, failure along a power line or at a power
station, electrical fire that burns the electrical wires, etc.). If you are
concerned about the limitations of battery or AC power, install both
types of units.
This Smoke/CO Alar
reach the sensors.
or CO may be pr
affect the rate at which CO or smoke reaches the sensors. If bedroom
doors are usually closed at night, we recommend you install an alarm
device (Combination CO and Smoke Alarm, or separate CO Alarms and
Smoke Alarms) in each bedroom and in the hallway between them.
This Smoke/CO Alarm may not sense smoke or CO on another
level of the home. Example: This alarm device, installed on the second
floor, may not sense smoke or CO in the basement. For this reason, one
en or others do not r
. AC units cannot work if the AC power is cut of
esent in other areas. Doors or other obstructions may
ements for Carbon Monoxide Alarms must
equir
, making sur
e infants or family members with mobility
e ar
m will not sense smoke or CO that does not
It will only sense smoke or CO at the sensor. Smoke
e that everyone is involved
eadily waken to the sound of the
f for any reason
alarm device may not give adequate early warning. Recommended
minimum protection is one alarm device in every sleeping area, every
oom, and on every level of your home. Some experts r
bedr
battery powered Smoke and CO Alarms be used in conjunction with
interconnected AC powered Smoke Alarms. For details, see “About
Smoke Alarms” for details.
Smoke/CO Alarms may not be heard. The alarm horn loudness
meets or exceeds curr
However, if the Smoke/CO Alarm is installed outside the bedroom, it
may not wake up a sound sleeper or one who has recently used drugs
or has been drinking alcoholic beverages. This is especially true if the
door is closed or only partly open. Even persons who are awake may
not hear the alarm horn if the sound is blocked by distance or closed
doors. Noise from traffic, stereo, radio, television, air conditioner, or other
appliances may also prevent alert persons from hearing the alarm horn.
This Smoke/CO Alarm is not intended for people who are hearing
ed.
impair
m may not have time to alar
The Alar
damage, injury, or death, since smoke from some fires may not
reach the unit immediately. Examples of this include persons
smoking in bed, children playing with matches, or fires caused by
violent explosions r
This Smoke/CO Alar
this Smoke/CO Alarm warns against increasing CO levels or the presence
of smoke, BRK Brands, Inc. does not warrant or imply in any way that they
will protect lives. Homeowners and renters must still insure their lives.
This Smoke/CO Alarm has a limited life. Although this Smoke/CO
Alarm and all of its parts have passed many stringent tests and ar
designed to be as reliable as possible, any of these parts could fail at
any time. Ther
replaced immediately if it is not operating properly.
This Smoke/CO Alarm is not foolproof. Like all other electronic
devices, this Smoke/CO Alarm has limitations. It can only detect smoke
or CO that r
sour
alarm device.
10
eaches the sensors. It may not give early war
ce of smoke or CO is in a remote part of the home, away from the
ent UL standar
esulting fr
m is not a substitute for life insurance.
e, you must test this device weekly. The unit should be
efor
ds of 85 dB at 10 feet (3 meters).
e the fir
m befor
om escaping gas.
ecommend
e itself causes
Though
e
ning of the
TROUBLESHOOTING GUIDE
If the Alarm...Problem...You should...
n "chirps" about once per minute;
Hor
Green "Smoke/CO" LED flashes Green On for
2 seconds/Of
Latch is engaged.)
n does three rapid "chirps" every minute;
Hor
LED has 3 rapid flashes with "chirps".
Carbon Monoxide Alar
CO Alarm goes back into alarm 4 minutes after
you Silence it.
CO Alarm sounds frequently even though no
high levels of CO are revealed in an investigation.
Smoke Alarm ONLY:
Smoke Alarm sounds when no smoke is visible.
*For a list of acceptable replacement batteries, see “Regular Maintenance.”
If you have questions that cannot be answered by reading this manual, call Consumer Affairs at 1-800-323-9005, M-F 7:30 a.m. to 5:00 p.m. (CST)
f for 2 seconds. (Low Battery
m ONLY:
Low battery war
MALFUNCTION SIGNAL. Device is not working
properly, and needs to be replaced.
CO levels indicate a potentially dangerous
situation.
The CO Alarm may be improperly located. Refer
to “Where to Install This Alarm” for details.
Unwanted alarm may be caused by nonemergency source like cooking smoke.
ning.Install two new AA batteries
Units under warranty should be r
manufacturer for replacement. See “Limited
arranty” for details.
W
IF YOU ARE FEELING SYMPTOMS OF CO
POISONING, EV
or the Fire Department. Refer to "If The CO
Alarm Sounds" for details.
Relocate your Alarm. If frequent alarms
continue, have home rechecked for potential
oblems. You may be experiencing an
CO pr
intermittent CO problem.
Silence Alarm using manual button; clean the
Alarm’s cover with a soft, clean cloth. If frequent
unwanted alarms continue, relocate your Alarm.
Alarm may be too close to a kitchen, cooking
appliance, or steamy bathr
ACUATE your home and call 911
*.
eturned to
oom.
LIMITED WARRANTY
BRK Brands, Inc., ("BRK") the maker of First Alert®brand products
warrants that for a period of five years from the date of purchase, this
product will be free from defects in material and workmanship. BRK, at
its option, will repair or replace this product or any component of the
product found to be defective during the warranty period. Replacement
will be made with a new or remanufactured product or component.
If the product is no longer available, replacement may be made with a
similar product of equal or greater value. This is your exclusive warranty.
This warranty is valid for the original retail purchaser from the date of
initial retail purchase and is not transferable. Keep the original sales
receipt. Proof of purchase is required to obtain warranty performance.
BRK dealers, service centers, or retail stores selling BRK products do
not have the right to alter, modify or any way change the terms and
conditions of this warranty.
This warranty does not cover normal wear of parts or damage resulting
from any of the following: negligent use or misuse of the product,
use on improper voltage or current, use contrary to the operating
instructions, disassembly, repair or alteration by anyone other than
BRK or an authorized service center. Further, the warranty does not
cover Acts of God, such as fir
any batteries that are included with this unit.
e, flood, hurricanes and tor
nadoes or
BRK shall not be liable for any incidental or consequential damages
caused by the breach of any express or implied warranty. Except to
the extent prohibited by applicable law, any implied warranty of
merchantability or fitness for a particular purpose is limited in duration
to the duration of the above warranty. Some states, provinces or
jurisdictions do not allow the exclusion or limitation of incidental or
consequential damages or limitations on how long an implied warranty
lasts, so the above limitations or exclusion may not apply to you.
This warranty gives you specific legal rights, and you may also have
other rights that vary from state to state or province to province.
How to Obtain Warranty Service
If service is required, do not return the product to your retailer.
Service:
In order to obtain warranty service, contact the Consumer Affairs
Division at 1-800-323-9005, 7:30 AM - 5:00 PM Central Standard Time,
Monday through Friday. To assist us in serving you, please have the
model number and date of purchase available when calling.
For Warranty Service return to:
BRK Brands, Inc., 25 Spur Drive, El Paso, TX 79906
Battery: BRK Brands, Inc. make no warranty, express or implied,
written or oral, including that of merchantability or fitness for any
particular purpose with respect to battery.
For your records, please record:
Date Purchased: _______________________________
e Purchased: __________________________________________
Wher
Date Installed: ____________/____________Month/Year
Replacement date is five years after installation: ________/______
NOTE: End of Life Signal — Once the unit r
lifecycle, the MALFUNCTION SIGNAL will sound once a minute to
indicate the need to immediately replace the Alarm.
Month/Year
eaches the end of its
First Alert®is a registered trademark of the First Alert Trust.
Printed in Mexico M08-0182-000 K1 03/07
11
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.