Thank you for choosing First Alert®for your Smoke and Carbon
Monoxide Alarm needs. Y
Carbon Monoxide Alarm designed to provide you with early warning of a
e or Carbon Monoxide.
fir
Smoke & Carbon Monoxide Combination Alar
against two deadly household threats.
Spread Spectrum Horn Tone. Lower and varying horn frequency
makes it easier for elderly with normal age r
n. Sweeps through the 2200 – 3400 Hz range.
hor
t Interconnect
Smar
Heat Alarms. One interconnect wire carries both smoke and CO alarm
signals.
Optipath 360 T
the smoke sensor
Single Button Test/Silence eliminates confusion. Depending on what
mode the alarm is in, pushing the button provides different functions
such as testing the alarm, silencing the alarm, r
in silence and clearing the Latching features.
Two Silence Features. Temporarily silence low battery chirp for up to
eight hours before replacing low battery or silence an unwanted alarm
for several minutes.
wo Latching Features.
T
even after alarm condition has subsided. Low Battery Latch: Identifies
which unit is in low battery condition.
fect Mount System
Per
and a mounting bracket that keeps the alarm secur
rotation range to allow for perfect alignment.
echnology
Dust Cover is included to keep the alarm clean during construction.
Easy Installation/Maintenance featur
the mounting bracket for easy access to wiring. A battery pull tab that
keeps the battery fresh until the home is occupied. A Side Load Battery
Drawer allows for easy battery replacement without r
om the ceiling or wall.
fr
Improved UV Resistance keeps the alarm from discoloring over time.
ELECTRICAL SHOCK HAZARD. Turn off the power to the area
where the Smoke Alarm is installed before removing it from the
mounting bracket. Failure to turn off the power first may result in
serious electrical shock, injury or death.
• This unit will not alert hearing impaired residents.
It is recommended that you install special units which use
devices like flashing strobe lights to alert hearing impaired
residents.
• Installation of this unit must conform to the electrical
codes in your area; Article 210, 760 of NFPA 70 (NEC),
NFPA 72, NFPA 101; SBC (SBCCI); UBC (ICBO); NBC (BOCA);
OTFDC (CABO), and any other local or building codes that
may apply. Wiring and installation must be performed by a
licensed electrician. Failure to follow these guidelines may
result in injury or property damage.
• This unit must be powered by a 24-hour, 120VAC pure sine
wave 60Hz circuit. Be sure the circuit cannot be turned
off by a switch, dimmer, or ground fault circuit interrupter.
e to connect this unit to a 24-hour cir
Failur
prevent it from providing constant protection.
9
10
10
• This Alarm must have AC or battery power to operate.
If the AC power fails, battery back-up will allow the alarm
to sound for at least 4 minutes. If AC power fails and the
batter
y is weak, protection should last for at least 7 days.
If AC power fails and the batter
alarm cannot operate.
Never disconnect the power from an AC powered unit to
•
stop an unwanted alarm. Doing so will disable the unit and
remove your protection. In the case of a true unwanted
alarm open a window or fan the smoke away from the unit.
The alarm will reset automatically when it returns to normal
operation. Never r
operated unit to stop an unwanted alarm (caused by cooking
smoke, etc.). Instead open a window or fan the smoke away
from the unit. The alarm will reset automatically.
• Connect this unit ONLY to other compatible units. See
“How To Install This Smoke Alarm” for details. Do not
connect it to any other type of alar
Connecting anything else to this unit may damage it or
event it fr
pr
• This Smoke/CO Alarm has a battery drawer which resists
closing unless a battery is installed. This warns you the
unit will not operate under DC power without a battery.
• Do not stand too close to the unit when the alarm is
sounding. It is loud to wake you in an emergency. Exposure
to the hor
• Do not paint over the unit. Paint may clog the openings to
the sensing chambers and pr
properly.
1
ou have purchased a state-of-the-art Smoke &
Key featur
es include:
m.
One alarm pr
elated hearing loss to hear
can be inter
.
connected to BRK Smoke, CO, and
TM
ovides 360 degrees of direct access to
pr
e-testing the alarm when
Alarm Latch: Easily identifies initiating alarm
includes a gasketless base for easy installation
e over a wide
es include a large opening in
emoving the alarm
cuit may
y is dead or missing, the
emove the batteries fr
om a batter
m or auxiliar
om operating pr
n at close range may har
operly.
m your hearing.
event the unit fr
otects
y
y device.
om operating
INSTALLATION
SUGGESTED AREAS FOR INSTALLING
SMOKE ALARMS, CO ALARMS, AND COMBO UNITS
SMOKE ALARM WITH
SILENCE FEATURE
CO ALARMS
BOTH, OR COMBINATION
SMOKE/CO ALARMS
SMOKE ALARMS
KEY:
Suggested locations are based on
NFPA recommendations (NFPA 72
for Smoke Alarms and NFPA 720 for
Carbon Monoxide Alarms). Always
refer to national and local codes
before beginning any installation.
In new construction AC and AC/DC smoke alarms MUST
be interconnected to meet NFPA recommendations.
WHERE TO INSTALL THIS ALARM
Minimum coverage for Smoke Alarms, as r
National Fir
every floor, in every sleeping area, and in every bedroom (See
“Regulatory Information For Smoke Alarms” for details on the NFP
ecommendations).
r
For CO Alar
recommends that a CO Alarm should be centrally located outside of
each separate sleeping ar
For added pr
bedroom, and on every level of your home.
NOTE: For added pr
least 15 feet (4.6 meters) away fr
source where possible. In smaller homes or in manufactured homes
wher
possible fr
closer than 15 feet (4.6 meters) will not harm the Alarm, but may increase
the fr
In general, install combination Smoke and Carbon Monoxide Alar
•
•
• In the hall near every sleeping area. If your home has multiple
•
• At the bottom of the basement stairs.
• For additional coverage, install Alarms in all rooms, halls, and storage
RECOMMENDED PLACEMENT
e Protection Association (NFPA), is one Smoke Alarm on
ms,
the National Fir
otection, install additional CO Alarms in each separate
otection, install an additional Smoke/CO Alarm at
e this distance cannot be maintained, install the Alarm as far away as
om the furnace or other fuel burning source. Installing the Alarm
e Protection Association (NFPA)
ea in the immediate vicinity of the bedrooms.
om the furnace or fuel burning heat
equency of unwanted alarms.
On every level of your home, including finished attics and basements.
Inside every bedroom, especially if people sleep with the door partly
or completely closed.
sleeping areas, install a unit in each. If a hall is more than 40 feet
(12 meters) long, install a unit at each end.
At the top of first-to-second floor stairs.
eas, where temperatures normally remain between 40˚ F and 100˚ F
ar
(4˚ C and 38˚ C).
ecommended by the
A
ms:
WHERE THIS ALARM SHOULD NOT BE INST
Do NOT locate this Smoke/CO Alar
In garages, furnace rooms, crawl spaces and unfinished attics.
•
void extremely dusty, dirty or greasy areas.
A
Where combustion particles are produced. Combustion particles
•
form when something bur
kitchens, garages, and furnace rooms. Keep units at least 20 feet
(6 meters) fr
water heater
(6 meter) distance is not possible – in modular, mobile, or smaller
homes, for example – it is r
placed as far fr
placement recommendations are intended to keep these Alarms at
a r
“unwanted” alarms. Unwanted alarms can occur if a Smoke Alarm is
placed directly next to a fuel-burning source. Ventilate these areas
as much as possible.
Within 5 feet (1.5 meters) of any cooking appliance. In air streams
•
near kitchens. Air curr
sensor and cause unwanted alarms.
• In extremely humid areas. This Alarm should be at least 10 feet (3
meters) from a shower, sauna, humidifier, vaporizer, dishwasher,
laundry r
In direct sunlight.
•
• In turbulent air, like near ceiling fans or open windows. Blowing air
may pr
In areas where temperature is colder than 40˚ F (4˚ C) or hotter than
•
100˚ F (38˚ C). These areas include non-airconditioned crawl spaces,
unfinished attics, uninsulated or poorly insulated ceilings, porches,
and garages.
• In insect infested areas. Insects can clog the openings to the sensing
chamber
Less than 12 inches (305 mm) away from fluorescent lights. Electrical
•
“noise” can interfere with the sensor.
om the sources of combustion particles (stove, furnace,
, space heater) if possible. In areas where a 20-foot
om these fuel-burning sources as possible. The
easonable distance from a fuel-burning source, and thus reduce
ents can draw cooking smoke into the smoke
oom, utility room, or other source of high humidity.
event CO or smoke from reaching the sensors.
.
m:
ns. Areas to avoid include poorly ventilated
ecommended the Smoke Alarm be
ALLED
• In “dead air” spaces. See “Avoiding Dead Air Spaces”.
• When installing on the wall, the top edge of Smoke Alarms should
be placed between 4 inches (102 mm) and 12 inches (305 mm) from
the wall/ceiling line.
• When installing on the ceiling, place the alarm as close to the center
as possible.
• In either case, install at least 4 inches (102 mm) from where the
wall and ceiling meet. See “A
information.
NOTE: For any location, make sur
keep carbon monoxide or smoke from reaching the Alarm.
Installing Smoke/CO Alar
For minimum security install one Smoke/CO Alarm as close to each
sleeping area as possible. For more security, put one unit in each room.
Many older mobile homes (especially those built before 1978) have little
or no insulation. If your mobile home is not well insulated, or if you ar
unsure of the amount of insulation, it is important to install units on
inside walls only.
voiding Dead Air Spaces” for mor
e no door or other obstruction could
ms in Mobile Homes
e
e
AVOIDING DEAD AIR SPACES
“Dead air” spaces may prevent smoke from reaching the Smoke/CO
Alarm. To avoid dead air spaces, follow installation recommendations
below.
On ceilings, install Smoke/CO Alarms as close to the center of the
ceiling as possible. If this is not possible, install the Smoke/CO Alarm
at least 4 inches (102 mm) from the wall or corner.
For wall mounting (if allowed by building codes), the top edge of
Smoke/CO Alarms should be placed between 4 inches (102 mm) and
12 inches (305 mm) from the wall/ceiling line, below typical “dead air”
spaces.
On a peaked, gabled, or cathedral ceiling, install first Smoke/CO
Alarm within 3 feet (0.9 meters) of the peak of the ceiling, measured
horizontally. Additional Smoke/CO Alarms may be required depending
on the length, angle, etc. of the ceiling's slope. Refer to NFPA 72 for
details on requirements for sloped or peaked ceilings.
2
4
5
6
8
9
1
0
7
HOW TO INST
This Smoke/CO Alarm is designed to be mounted on any standar
by local codes). Read “Where to Install This Alarm” and “Where This Alarm Should Not Be Installed” before you begin installation.
ools you will need: • Needle-nose pliers or utility knife
T
ALL THIS SMOKE/CO ALARM
d wiring junction box up to a 4-inch (10 cm) size, on either the ceiling or wall (if allowed
• Standar
d flathead screwdriver
ire strippers.
• W
Make sur
from a generator or solar power, light dimmer on the same circuit or mounted near fluorescent lighting. Excessively noisy power may cause
damage to your Alar
e the Alarm is not receiving excessively noisy power. Examples of noisy power could be major appliances on the same circuit, power
m.
THE PARTS OF THIS ALARM
ts of This Unit
The Mounting Bracket:
o remove the mounting bracket from the Alarm
T
base, hold the Alarm base firmly and twist the
mounting bracket counter
bracket installs onto the junction box. It has a
variety of screw slots to fit most boxes.
The Power Connector:
The power connector plugs into a power input block
on the Alarm. It supplies the unit with AC power
• The black wir
• The white wire is neutral.
• The orange wire is used for interconnect.
If you need to remove the power connector, turn
POWER OFF first. Insert a flat scr
between the power connector and the security tab
inside the power input block. Gently pry back the tab
and pull the connector free.
clockwise. The mounting
.
e is “hot.”
ewdriver blade
The Par
1Mounting Bracket
2Mounting Slots
Locking Pins (break out of
3
bracket)
4Hot (Black) AC Wire
Neutral (White) AC Wire
5
Interconnect (Orange) Wire
6
7Quick-Connect Power
Connector
Turn this way to remove
8
from bracket
9Turn this way to attach to
bracket
10 Slide-Out Battery Drawer
3
FOLLOW
5
}
A
}
B
8
7
6
3
11
2
2
3
44
5
The basic installation of this Alarm is similar whether you want to
install one Alarm, or interconnect more than one Alarm. If you are
connecting more than one Alarm, you MUST read “Special
inter
ements For Interconnected Alarms” below before you begin
Requir
installation.
ELECTRICAL SHOCK HAZARD. T
you will install this unit at the cir
beginning installation. Failure to turn off the power before installa-
may result in serious electrical shock, injury or death.
tion
Remove the mounting bracket
1.
from the base, and attach it to
the junction box.
Using wire nuts, connect the
2.
power connector to the
household wiring.
AND-ALONE ALARM ONLY:
ST
• Connect the white wire on the power connector to the neutral
e in the junction box.
wir
Connect the black wire on the power connector to the hot wire
•
in the junction box.
• Tuck the orange wire inside the junction box. It is used for
interconnect only.
THESE INSTALLATION STEPS
urn off power to the area where
cuit breaker or fuse box before
INTERCONNECTED UNITS ONLY:
f about 1/2” (12 mm) of the plastic coating on the orange
Strip of
wire on the power connector.
• Connect the white wire on the power connector to the neutral
e in the junction box.
wir
• Connect the black wire on the power connector to the hot wire
in the junction box.
•
Connect the orange wire on the power connector to the
interconnect wire in the junction box. Repeat for each unit you
connecting. Never connect the hot or neutral wires in the
are inter
junction box to the orange interconnect wire. Never cross hot and
neutral wires between Alarms.
3. Plug the power connector into the back of the Alarm.
4. Activate the battery back-up by removing the “Pull to Activate
Battery Back-Up” tab. Or, install battery back-up. Battery back-up
cannot work until you install the battery in the correct position
(Match “+” to “+” and “-” to “-”).
Position the base of the Alarm over the mounting bracket, and turn
5.
the Alarm clockwise (right) until the unit is in place. If wall mounted,
adjust unit so words are level.
6. Check all connections.
Improper wiring of the power connector or the wiring leading to
the power connector will cause damage to the Alarm and may
lead to a non-functioning Alarm.
STAND-ALONE ALARM ONLY:
• If you are only installing one Alarm, restore power to the junction
box.
INTERCONNECTED UNITS ONL
• If you are interconnecting multiple Alarms, repeat steps
1-5 for each Alar
estore power to the junction box.
r
m in the series. When you ar
Y:
e finished,
Special Requirements For Interconnected Alarms
Failure to meet any of the above requirements could damage
•
the units and cause them to malfunction, r
protection.
AC and AC/DC Alarms can be interconnected. Under AC
•
, all units will alarm when one senses smoke or CO.
power
When power is interrupted, only the AC/DC units in the series
will continue to send and r
will not operate.
connected units can provide earlier warning of fire than stand-alone
Inter
units, especially if a fire starts in a remote area of the dwelling. If any unit
in the series senses smoke, all units will alarm. T
initiated an alarm, see table:
During an Alar
On Initiating Alarm(s)
m:
Red LED(s) flashes (flash) rapidly
eceive signals. AC powered Alarms
On All Other Alarms Red LED is Off
After an Alar
On Initiating Alarm(s)
On All Other Alarms
Compatible Inter
Inter
households will experience unwanted alarms when you test any unit
in the series. Interconnected units will only work if they are wired to
compatible units and all requirements are met. This unit is designed to
be compatible with:
9120B, SC9120B, 7010, 7010B, 4120, 4120B, 4120SB, 4919, 2002RAC,
100S, 5919, 5919TH; BRK Electronics®Heat Alarm Models HD6135F,
HD6135FB; BRK Electronics®CO Alarm Models CO5120BN,
CO5120PDBN; Smoke/CO Alarm Model SC6120B, SC7010BV, SC7010B;
and
SA4919B, SA100B.
m (Latching):
Red LED(s) On for 2 seconds/Off for 2 seconds
Green LED(s) On, Red LED(s) Off
connected Units
connect units within a single family residence only. Otherwise all
BRK Electronics®Smoke Alarm Models 9120,
First Alert®Smoke Alarm Models SA4120, SA4120B, SA4121B,
Interconnected units must meet ALL of the following requirements:
• A maximum of 18 compatible units may be interconnected
(Maximum of 12 Smoke Alarms).
• The same fuse or circuit breaker must power all interconnected
units.
• The total length of wire interconnecting the units should be
less than 1000 feet (300 meters). This type of wire is commonly
available at Hardware and Electrical Supply stores.
• All wiring must conform to all local electrical codes and NFPA 70
(NEC). Refer to NFPA 72, NFPA 101, and/or your local building
code for further connection requirements.
emoving your
o determine which Alarm
e power until all
ELECTRICAL SHOCK HAZARD. Do not r
Alarms are completely installed. Restoring power before installation
is complete may result in serious electrical shock, injury or death.
6. Make sure the Alarm is receiving AC power. Under normal
operation, the Green power indicator light will shine continuously.
7. If the Green power indicator light does not light,
POWER TO THE JUNCTION BOX
If all connections are correct and the Green power indicator still
does not light when you restore the power, the unit should be
eplaced immediately
r
est each Smoke Alarm. Pr
T
8.
until the unit alarms.
units you must test each unit individually. Make sure all units
alarm when each one is tested.
If any unit in the series does not alar
echeck connections. If it does not alar
r
replace it immediately.
.
ess and hold the T
When testing a series of interconnected
estor
TURN OFF
echeck all connections.
and r
est/Silence button
m, TURN OFF POWER and
m when you r
estor
e power
A. Unswitched 120VAC
60 Hz sour
1. Alarm
2. Ceiling or Wall
3. Power Connector
ce
B. To additional units; Maximum = 18 total
(Maximum 12 Smoke Alarms)
4. Wire Nut
5. Junction Box
6. Neutral Wire (Wht)
7. Interconnect Wire
(Orange)
e (Blk)
Hot Wir
8.
,
4
Loading...
+ 7 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.