First Alert PC900V User Manual

STEP BY STEP GUIDE TO PROGRAMMING THIS ALARM
FOR FIRST TIME AND WHEN CHANGING BATTERIES
Action: Alarm Will Say:
1. Insert batteries (2, AA batteries).
2. Press & Hold Test Button if you would like to program the location or change the location of the Alarm. Release button after Alarm responds.
3. After you hear the location of where you are placing the Alarm, Press & Hold the Test Button.
Your Alarm has now been programmed for the location of your choice. Available locations: Basement, Hallway, Office, Child’s Bedroom, Kitchen, Utility Room, Dining Room, Living Room, Family Room, Master Bedroom, Guest Bedroom, No Location.
WHAT YOU WILL SEE AND HEAR WITH THIS ALARM
Under Normal Operations Voice: Silent Horn: Silent Power LED: Flashes Green once a minute
When You Test the Alarm Voice: “Testing.” “Warning, evacuate smoke in [Location, example: “Kitchen”]. Evacuate.” Horn: 3 beeps, pause, 3 beeps, voice Power LED: Flashes Red followed by Voice: “Warning, evacuate carbon monoxide in [Location, example: “Hallway”]. Evacuate.” Horn: 4 beeps, pause, 4 beeps, voice LED: Flashes Red
If Battery Becomes Low Voice: “Replace battery in [Location, example “Hallway”].” Repeated every 5 hours Horn: chirps once a minute Power LED: Flashes Green approximately once a minute
If Alarm is Not Operating Properly Voice: “Detector error in [Location, example “Hallway”], please see manual.” Repeated every 5 hours Horn: 3 chirps every minute Power LED: Three Green flashes approximately once a minute
Alarm has reached its End of Life Voice: “Detector error in [Location, example “Basement”], please see manual.” Repeated every 5 hours Horn: 5 chirps every minute Power LED: Five Green flashes approximately once a minute
Alarm Levels of CO are Detected Voice: “Warning, evacuate carbon monoxide in [Location, example: “Hallway”]. Evacuate.” “____ ppm.”
Horn: 4 beeps, pause, 4 beeps, voice* Power LED: Flashes Red
*NOTE: If unit goes into CO alarm, the regular 4 beeps-brief pause cycle will repeat for four minutes. After four minutes, the pause will increase to one minute. Smoke is Detected
Voice: “Warning, evacuate smoke in [Location, example: “Hallway”]. Evacuate.” Horn: 3 beeps, pause, 3 beeps, voice Power LED: Flashes Red
Smoke Alarm is Silenced Voice: Silent Horn: Off Power LED: Flashes Red
SUGGESTED AREAS FOR INSTALLING
USER’S MANUAL COMBINATION CARBON MONOXIDE
& SMOKE ALARM WITH VOICE & LOCATION
SEPARATE SENSORS TO DETECT SMOKE AND CO; THE TWO ALARM SYSTEMS WORK INDEPENDENTLY
VOICE WITH PROGRAMMABLE LOCATION SEPARATE AUDIBLE AND VISUAL SIGNALS TO INDICATE ALARM LEVELS
OF SMOKE OR CO
CONFORMS TO
UL STD 217 AND
UL STD 2034
Model PC900V
POWERED BY TWO “AA” BATTERIES SIDE ACCESS DRAWER FOR EASY BATTERY REPLACEMENT
This user’s manual contains important information about your Combination Carbon Monoxide & Smoke Alarm’s operation.
If you are installing this Alarm for use by others, you must leave this manual—or a copy of it—with the end user.
PARA EL MANUAL DEL USUARIO EN ESPAÑOL, POR FAVOR VISITE WWW.FIRSTALERT.COM.
IMPORTANT! PLEASE READ CAREFULLY AND SAVE.
INTRODUCTION
All First Alert® Smoke Alarms conform to regulatory requirements, including UL217 and are designed to detect particles of combustion. Smoke particles of varying number and size are produced in all fires.
Ionization technology is generally more sensitive than photoelectric technology at detecting small particles, which tend to be produced in greater amounts by flaming fires, which consume combustible materials rapidly and spread quickly. Sources of these fires may include paper burning in a wastebasket, or a grease fire in the kitchen.
Photoelectric technology is generally more sensitive than ionization technology at detecting large particles, which tend to be produced in greater amounts by smoldering fires, which may smolder for hours before bursting into flame. Sources of these fires may include cigarettes burning in couches or bedding.
For maximum protection, use both types of Smoke Alarms on each level and in every bedroom of your home.
___________________________________________________________________________________________________________________________
FIRE SAFETY TIPS
Follow safety rules and prevent hazardous situations: 1) Use smoking materials properly. Never smoke in bed. 2) Keep matches or lighters away from children; 3) Store flammable materials in proper containers; 4) Keep electrical appliances in good condition and don’t overload electrical circuits; 5) Keep stoves, barbecue grills, fireplaces and chimneys grease- and debris-free; 6) Never leave anything cooking on the stove unattended; 7) Keep portable heaters and open flames, like candles, away from flammable materials; 8) Don’t let rubbish accumulate. Keep alarms clean, and test them weekly. Replace alarms immediately if they are not working properly. Smoke Alarms that do not work cannot alert you to a fire. Keep at least one working fire extinguisher on every floor, and an additional one in the kitchen. Have fire escape ladders or other reliable means of escape from an upper floor in case stairs are blocked.
INSTALLATION
WHERE TO INSTALL THIS ALARM
MINIMUM COVERAGE FOR SMOKE ALARMS, as recommended by the National Fire Protection Association (NFPA), is one Smoke Alarm on every floor, in every sleeping area, and in every bedroom (See “Regulatory Information For Smoke Alarms” for details on the NFPA recommendations). For CO Alarms, the National Fire Protection Association (NFPA) recommends that a CO Alarm should be centrally located outside of each separate sleeping area in the immediate vicinity of the bedrooms. For added protection, install additional CO Alarms in each separate bedroom, and on every level of your home. NOTE: For added protection, install an additional Smoke/CO Alarm at least 15 feet (4.6 meters) away from the furnace or fuel burning heat source where possible. In smaller homes or in manufactured homes where this distance cannot be maintained, install the Alarm as far away as possible from the furnace or other fuel burning source. Installing the Alarm closer than 15 feet (4.6 meters) will not harm the Alarm, but may increase the frequency of unwanted alarms.
In general, install combination Smoke and Carbon Monoxide Alarms:
• On every level of your home, including finished attics and basements.
• Inside every bedroom, especially if people sleep with the door partly or completely closed.
• In the hall near every sleeping area. If your home has multiple sleeping areas, install a unit in each. If a hall is more than 40 feet (12 meters) long, install a unit at each end.
• At the top of first-to-second floor stairs.
• At the bottom of the basement stairs.
• For additional coverage, install Alarms in all rooms, halls, and storage areas, where temperatures normally remain between 40˚ F and 100˚ F (4.4˚ C and 37.8˚ C).
© 2015 BRK Brands, Inc. All rights reserved. Distributed by BRK Brands, Inc. First Alert® is registered trademark of The First Alert Trust
3901 Liberty Street Road, Aurora, IL 60504-8122 Consumer Affairs: (800) 323-9005 • www.firstalert.com www.brkelectronics.com • 2/15
W
Printed in Mexico • M08-0476-005
Installed on Replace by
STEP BY STEP GUIDE TO PROGRAMMING THIS ALARM
RECOMMENDED PLACEMENT
When installing on the wall, the top edge of Smoke Alarms should be placed between 4 inches (102 mm) and 12 inches (305 mm) from the wall/ceiling line.
When installing on the ceiling, place the alarm as close to the center as possible.
In either case, install at least 4 inches (102 mm) from where the wall and ceiling meet. See “Avoiding Dead Air Spaces” for more information.
NOTE: For any location, make sure no door or other obstruction could keep carbon monoxide or smoke from reaching the Alarm. Installing Smoke/CO Alarms in Mobile Homes
For minimum security install one Smoke/CO Alarm as close to each sleeping area as possible. For more security, put one unit in each room. Many older mobile homes (especially those built before 1978) have little or no insulation. If your mobile home is not well insulated, or if you are unsure of the amount of insulation, it is important to install units on inside walls only.
________________________________________________________________________________________________________________________
WHERE THIS ALARM SHOULD NOT BE INSTALLED
DO NOT LOCATE THIS SMOKE/CO ALARM:
In garages, furnace rooms, crawl spaces and unfinished attics. Avoid extremely dusty, dirty or greasy areas.
Where combustion particles are produced. Combustion particles form when something burns. Areas to avoid include poorly ventilated kitchens, garages, and furnace rooms. Keep units at least 20 feet (6 meters) from the sources of combustion particles (stove, furnace, water heater, space heater) if possible. In areas where a 20-foot (6 meter) distance is not possible – in modular, mobile, or smaller homes, for example – it is recommended the Smoke Alarm be placed as far from these fuel-burning sources as possible. The placement recommendations are intended to keep these Alarms at a reasonable distance from a fuel-burning source, and thus reduce “unwanted” alarms. Unwanted alarms can occur if a Smoke Alarm is placed directly next to a fuel-burning source. Ventilate these areas as much as possible.
Within 5 feet (1.5 meters) of any cooking appliance. In air streams near kitchens. Air currents can draw cooking smoke into the smoke sensor and cause unwanted alarms.
In extremely humid areas. This Alarm should be at least 10 feet (3 meters) from a shower, sauna, humidifier, vaporizer, dishwasher, laundry room, utility room, or other source of high humidity.
In direct sunlight.
In turbulent air, like near ceiling fans or open windows. Blowing air may prevent CO or smoke from reaching the sensors.
In areas where temperature is colder than 40˚ F (4.4˚ C) or hotter than 100˚F (37.8˚ C). These areas include non-airconditioned crawl spaces, unfinished attics, uninsulated or poorly insulated ceilings, porches, and garages.
In insect infested areas. Insects can clog the openings to the sensing chamber.
Less than 12 inches (305 mm) away from fluorescent lights. Electrical “noise” can interfere with the sensor.
In “dead air” spaces. See “Avoiding Dead Air Spaces”.
AVOIDING DEAD AIR SPACES
“Dead air” spaces may prevent smoke from reaching the Smoke/CO Alarm. To avoid dead air spaces, follow installation recommendations below. On ceilings, install Smoke/CO Alarms as close to the center of the ceiling as possible. If this is not possible, install the Smoke/CO Alarm at least 4 inches (102 mm) from the wall or corner. For wall mounting (if allowed by building codes), the top edge of Smoke/CO Alarms should be placed between 4 inches (102 mm) and 12 inches (305 mm) from the wall/ceiling line, below typical “dead air” spaces. On a peaked, gabled, or cathedral ceiling, install first Smoke/CO Alarm within 3 feet (0.9 meters) of the peak of the ceiling, measured horizontally. Additional Smoke/CO Alarms may be required depending on the length, angle, etc. of the ceiling’s slope. Refer to NFPA 72 for details on requirements for sloped or peaked ceilings.
SUGGESTED AREAS FOR INSTALLING
FOR FIRST TIME AND WHEN CHANGING BATTERIES
Action: Alarm Will Say:
1. Insert batteries (2, AA batteries).
2. Press & Hold Test Button if you would like to program the location or change the location of the Alarm. Release button after Alarm responds.
3. After you hear the location of where you are placing the Alarm, Press & Hold the Test Button.
Your Alarm has now been programmed for the location of your choice. Available locations: Basement, Hallway, Office, Child’s Bedroom, Kitchen, Utility Room, Dining Room, Living Room, Family Room, Master Bedroom, Guest Bedroom, No Location.
WHAT YOU WILL SEE AND HEAR WITH THIS ALARM
Under Normal Operations Voice: Silent Horn: Silent Power LED: Flashes Green once a minute
When You Test the Alarm Voice: “Testing.” “Warning, evacuate smoke in [Location, example: “Kitchen”]. Evacuate.” Horn: 3 beeps, pause, 3 beeps, voice Power LED: Flashes Red followed by Voice: “Warning, evacuate carbon monoxide in [Location, example: “Hallway”]. Evacuate.” Horn: 4 beeps, pause, 4 beeps, voice LED: Flashes Red
If Battery Becomes Low Voice: “Replace battery in [Location, example “Hallway”].” Repeated every 5 hours Horn: chirps once a minute Power LED: Flashes Green approximately once a minute
If Alarm is Not Operating Properly Voice: “Detector error in [Location, example “Hallway”], please see manual.” Repeated every 5 hours Horn: 3 chirps every minute Power LED: Three Green flashes approximately once a minute
Alarm has reached its End of Life Voice: “Detector error in [Location, example “Basement”], please see manual.” Repeated every 5 hours Horn: 5 chirps every minute Power LED: Five Green flashes approximately once a minute
Alarm Levels of CO are Detected Voice: “Warning, evacuate carbon monoxide in [Location, example: “Hallway”]. Evacuate.” “____ ppm.”
Horn: 4 beeps, pause, 4 beeps, voice* Power LED: Flashes Red
*NOTE: If unit goes into CO alarm, the regular 4 beeps-brief pause cycle will repeat for four minutes. After four minutes, the pause will increase to one minute. Smoke is Detected
Voice: “Warning, evacuate smoke in [Location, example: “Hallway”]. Evacuate.” Horn: 3 beeps, pause, 3 beeps, voice Power LED: Flashes Red
Smoke Alarm is Silenced Voice: Silent Horn: Off Power LED: Flashes Red
“Welcome, First Alert Carbon Monoxide and Smoke Alarm.” “No location programmed” if first time or “[Location, example: “Hallway”] location programmed” when changing batteries. “To select location, press and hold test button now.”
“To save location, press and hold test button after location is heard.” Alarm will speak list of locations (see below).
“[Location, example: “Hallway”] location saved.” If no location is chosen: “No location saved.”
CO Alarm is Silenced Voice: Silent Horn: Off Power LED: Flashes Red
RECOMMENDED PLACEMENT
SUGGESTED AREAS FOR INSTALLING
HOW TO INSTALL THIS ALARM
This combination Smoke/CO Alarm was designed to be mounted on the ceiling or wall. It is not a tabletop device. You must install this device on the ceiling or wall as outlined below. Read “Where To Install This Alarm” before starting.
Do not install this unit over an electrical junction box. Air currents around junction boxes can prevent smoke from reaching the sensing chamber and prevent the unit from alarming. Only AC powered units are intended for installation over junction boxes. NOTE: Be sure to mount the product in the orientation specified in the next steps as this provides the most stability for mounting the product to the wall or ceiling.
TOOLS YOU WILL NEED:
THIS UNIT IS DESIGNED TO BE MOUNTED ON THE CEILING, OR ON THE WALL IF NECESSARY.
Pencil
Drill with 3/16” (5 mm) drill bit
Standard flathead screwdriver
Hammer
THE PARTS OF THIS SMOKE/CO ALARM
1 Test/Silence Button 2 Power/Smoke and
CO Alarm LED
3 Speaker
1 Mounting bracket 2 Mounting slots 3 Battery door, install
batteries here
• When installing on the wall, the top edge of Smoke Alarms should be placed between 4 inches (102 mm) and 12 inches (305 mm) from the wall/ceiling line.
• When installing on the ceiling, place the alarm as close to the center as possible.
• In either case, install at least 4 inches (102 mm) from where the wall and ceiling meet. See “Avoiding Dead Air Spaces” for more information.
NOTE: For any location, make sure no door or other obstruction could keep carbon monoxide or smoke from reaching the Alarm. Installing Smoke/CO Alarms in Mobile Homes
For minimum security install one Smoke/CO Alarm as close to each sleeping area as possible. For more security, put one unit in each room. Many older mobile homes (especially those built before 1978) have little or no insulation. If your mobile home is not well insulated, or if you are unsure of the amount of insulation, it is important to install units on inside walls only.
________________________________________________________________________________________________________________________
SMOKE ALARMS, CO ALARMS, AND COMBO UNITS
KEY:
SMOKE ALARMS
SMOKE ALARM WITH SILENCE FEATURE
CO ALARMS
BOTH, OR COMBINATION SMOKE/CO ALARMS
Suggested locations are based on NFPA recommendations (NFPA 72 for Smoke Alarms and NFPA 720 for Carbon Monoxide Alarms). Always refer to national and local codes
In new construction AC and AC/DC smoke alarms MUST be interconnected to meet NFPA recommendations.
before beginning any installation.
WHERE THIS ALARM SHOULD NOT BE INSTALLED
DO NOT LOCATE THIS SMOKE/CO ALARM:
• In garages, furnace rooms, crawl spaces and unfinished attics. Avoid extremely dusty, dirty or greasy areas.
• Where combustion particles are produced. Combustion particles form when something burns. Areas to avoid include poorly ventilated kitchens, garages, and furnace rooms. Keep units at least 20 feet (6 meters) from the sources of combustion particles (stove, furnace, water heater, space heater) if possible. In areas where a 20-foot (6 meter) distance is not possible – in modular, mobile, or smaller homes, for example – it is recommended the Smoke Alarm be placed as far from these fuel-burning sources as possible. The placement recommendations are intended to keep these Alarms at a reasonable distance from a fuel-burning source, and thus reduce “unwanted” alarms. Unwanted alarms can occur if a Smoke Alarm is placed directly next to a fuel-burning source. Ventilate these areas as much as possible.
• Within 5 feet (1.5 meters) of any cooking appliance. In air streams near kitchens. Air currents can draw cooking smoke into the smoke sensor and cause unwanted alarms.
• In extremely humid areas. This Alarm should be at least 10 feet (3 meters) from a shower, sauna, humidifier, vaporizer, dishwasher, laundry room, utility room, or other source of high humidity.
• In direct sunlight.
• In turbulent air, like near ceiling fans or open windows. Blowing air may prevent CO or smoke from reaching the sensors.
• In areas where temperature is colder than 40˚ F (4.4˚ C) or hotter than 100˚F (37.8˚ C). These areas include non-airconditioned crawl spaces, unfinished attics, uninsulated or poorly insulated ceilings, porches, and garages.
• In insect infested areas. Insects can clog the openings to the sensing chamber.
• Less than 12 inches (305 mm) away from fluorescent lights. Electrical “noise” can interfere with the sensor.
• In “dead air” spaces. See “Avoiding Dead Air Spaces”.
AVOIDING DEAD AIR SPACES
“Dead air” spaces may prevent smoke from reaching the Smoke/CO Alarm. To avoid dead air spaces, follow installation recommendations below. On ceilings, install Smoke/CO Alarms as close to the center of the ceiling as possible. If this is not possible, install the Smoke/CO Alarm at least 4 inches (102 mm) from the wall or corner. For wall mounting (if allowed by building codes), the top edge of Smoke/CO Alarms should be placed between 4 inches (102 mm) and 12 inches (305 mm) from the wall/ceiling line, below typical “dead air” spaces. On a peaked, gabled, or cathedral ceiling, install first Smoke/CO Alarm within 3 feet (0.9 meters) of the peak of the ceiling, measured horizontally. Additional Smoke/CO Alarms may be required depending on the length, angle, etc. of the ceiling’s slope. Refer to NFPA 72 for details on requirements for sloped or peaked ceilings.
WEEKLY TESTING
• NEVER use an open flame of any kind to test this unit. You might accidentally damage or set fire to the unit or to your home. The built-in test switch accurately tests the unit’s operation as required by Underwriters Laboratories, Inc. (UL). NEVER use vehicle exhaust! Exhaust may cause permanent damage and voids your warranty.
DO NOT stand close to the alarm when the horn is sounding. Exposure at close range may be harmful to your hearing. When testing, step away when horn starts sounding.
It is important to test this unit every week to make sure it is working properly. Using the test button is the recommended way to test this Smoke/CO Alarm. You can test this Smoke/CO Alarm by pressing and holding the Test/Silence button on the Alarm cover until Alarm Voice says “Testing” (typically 3-5 seconds). During testing, you will see and hear the following sequence:
The Alarm Voice will say “Testing.” The Horn will sound 3 beeps, pause, 3 beeps. The Alarm Voice will say “Warning, evacuate smoke in [Location, example:
“Kitchen”]. Evacuate.” The Power LED flashes Red.
Next the Horn will sound 4 beeps, pause, 4 beeps. The Alarm Voice will say “Warning, evacuate carbon monoxide in [Location, example: “Kitchen”]. Evacuate.”
The LED flashes Red.
If the unit does not alarm, make sure the batteries are correctly installed, and test again. If the unit still does not alarm, replace it immediately.
________________________________________________________________________________________________________________________
REGULAR MAINTENANCE
This unit has been designed to be as maintenance free as possible, but there are a few simple things you must do to keep it working properly.
•Test it at least once a week.
Clean the Smoke/CO Alarm at least once a month; gently vacuum the outside of the Smoke/CO Alarm using your household vacuum’s soft brush attachment. A can of clean compressed air (sold at computer or office supply stores) may also be used. Follow manufacturer instructions for use. Test the Smoke/CO Alarm. Never use water, cleaners or solvents since they may damage the unit.
If the Smoke/CO Alarm becomes contaminated by excessive dirt, dust and/or grime, and cannot be cleaned to avoid unwanted alarms, replace the unit immediately
Relocate the unit if it sounds frequent unwanted alarms. See “Where This Alarm Should Not Be Installed” for details.
Choosing a replacement battery: Your Smoke/CO Alarm requires two standard AA alkaline batteries. The following batteries are acceptable as replacements: Eveready Energizer E91 or Duracell MN1500. These batteries are available at many local retail stores.
Always use the exact batteries specified by this User’s Manual. DO NOT use rechargeable batteries. Clean the battery contacts and also those of the device prior to battery installation. Install batteries correctly with regard to polarity (+ and -). Please dispose of or recycle used batteries properly, following any local regulations. Consult your local waste management authority or recycling organization to find an electronics recycling facility in your area. DO NOT DISPOSE OF BATTERIES IN FIRE. BATTERIES MAY EXPLODE OR LEAK.
Keep battery out of reach of children. In the event a battery is swallowed, immediately contact your poison control center, your physician, or the National Battery Ingestion hotline at 202-625-3333 as serious injury may occur.
Actual battery service life depends on the Smoke/CO Alarm and the environment in which it is installed. All the batteries specified above are acceptable replacement batteries for this unit. Regardless of the manufacturer’s suggested battery life, you MUST replace the battery immediately once the unit starts “chirping” (the “low battery warning”).
HOW TO INSTALL THIS ALARM
This combination Smoke/CO Alarm was designed to be mounted on the ceiling or wall. It is not a tabletop device. You must install this device on the ceiling or wall as outlined below. Read “Where To Install This Alarm” before starting.
Do not install this unit over an electrical junction box. Air currents around junction boxes can prevent smoke from reaching the sensing chamber and prevent the unit from alarming. Only AC powered units are intended for installation over junction boxes. NOTE: Be sure to mount the product in the orientation specified in the next steps as this provides the most stability for mounting the product to the wall or ceiling.
TOOLS YOU WILL NEED:
THIS UNIT IS DESIGNED TO BE MOUNTED ON THE CEILING, OR ON THE WALL IF NECESSARY.
• Pencil
• Drill with 3/16” (5 mm) drill bit
• Standard flathead screwdriver
• Hammer
THE PARTS OF THIS SMOKE/CO ALARM
1 Test/Silence Button 2 Power/Smoke and
CO Alarm LED
3 Speaker
1 Mounting bracket 2 Mounting slots 3 Battery door, install
batteries here
FOLLOW THESE SIMPLE STEPS
1. Turn alarm upside down so the circular shape is located in the upper left corner of the alarm.
2. Slide mounting bracket to the left and lift to separate it from the base.
3. Hold the mounting bracket against the ceiling (or wall) so the arrow located on the mounting plate is pointing to the left. (The circular shape will now be in upper right-hand corner). Trace around the insides of the mounting slots.
4. Put the unit where it won’t get covered with dust when you drill the mounting holes.
5. Using a 3/16” (5 mm) drill bit, drill a hole through the center of the oval outlines you traced in step #3.
6. Insert the plastic screw anchors (in the plastic bag with screws) into the holes. Tap the screw anchors gently with a hammer, if necessary, until they are flush with the ceiling or wall.
7. Attach the mounting bracket to the ceiling or wall.
8. Install the batteries (included). Open the battery door. Match the terminals on the ends of each battery with the terminals on the unit. Match “+” to “+” and “-” to “-.” Push the batteries in until they snap securely and cannot be shaken loose. If the batteries are not snapped in completely, the unit cannot receive battery power.
NOTE: After you install the batteries, the power indicator light may flash. (If the unit alarms, the light will blink rapidly, and the horn will repeatedly sound 3 beeps, pause, 3 beeps.)
9. Attach the Smoke/CO Alarm to the mounting bracket. Line up the arrow on the back of the unit to the arrow on the mounting bracket. When the units are lined up, slide the alarm to the right until it snaps into place.
NOTE: Once the Smoke/CO Alarm is snapped onto the mounting bracket, you can rotate the Smoke/CO Alarm to adjust the alignment.
10. Test the Alarm. See “Weekly Testing.”
Loading...
+ 8 hidden pages