First Alert FA570CR Installation And Setup Manual

Page 1
K14030-2CF 9/08 Rev. B
FA570CR
FA570CR
FA570CRFA570CR
Commercial
Commercial Fire
R
Fire Keypad
FireFire
Keypad
Keypad Keypad
INSTALLATION AND SETUP GUIDE
Keypad Features
Programmable function keys (see note 1)
Built-in sounder
ARMED, READY, POWER, FIRE ALARM, SILENCED,
SUPERVISORY, TROUBLE LEDs (see note 2)
RED keypad for Commercial Fire applications
Notes: 1. Function key applications are control-dependent and may differ from one control to another (see control’s
instructions for details).
2. Trouble and Supervisory LED operation are supported only in the panels listed above.
3. Supervised by control panel, if supported (must be enabled for Commercial Fire installations).
GENERAL INFORMATION
The FA570CR is an addressable, remote keypad that is intended for use in commercial applications with First Alert Professional control panels, as listed above. The FA570CR’s address is set locally, via the keypad’s keys, depending on the control being used (see note 3, above). The keys are continuously backlit for convenience. The LCD display is backlit only when a key is depressed, or when the system is in alarm or trouble condition. Note: On some controls, the LCD may be programmed to remain on at all times (see control’s instructions for details).
KEYPAD LED INDICATIONS
The keypad’s LEDs will light under the following conditions:
ARMED (Red)
READY (Green)
POWER (Green)
FIRE ALARM (Red)
SILENCED (Yellow)
SUPERVISORY (Yellow)
ON
System is Armed
OFF
System is Disarmed
ON
System is ready to be armed
OFF
System is not ready
ON
AC power is applied
OFF
AC power is removed
ON
Fire Alarm active
OFF
Normal
ON
Fire Alarm has been silenced
OFF
Normal
ON
Supervisory condition exists (see control’s instructions for details)
OFF
Normal TROUBLE (Yellow)
ON
Trouble condition exists
controls instructions for details)
OFF
Normal
(see
SPECIAL FUNCTION KEYS
The keypad also features programmable function keys labeled A, B, C, and D. These keys may be programmed to initiate panic, fire, or emergency alarms as well as other special functions such as macros, paging, and single-button arming. (Not all controls support these special functions. Refer to the individual control panel’s instructions for details.)
These keys must be held down for at least 2 seconds to initiate the assigned function.
Supported Control Panels
FA1670C
FA1700C
WIRING AND INSTALLATION
The keypad may be surface-mounted directly to a dry wall or to a single- or double-gang electrical box.
1. To remove the case back, insert a small screwdriver blade at a downward angle into Slot 1 and twist, (the right side pops up). Insert the screwdriver blade at a downward angle into Slot 2 and twist, (the left side pops up). Insert the screwdriver blade into right side narrow Slot 3 and twist. Separate the case back from upper case. Refer to Figure 1 for location of the case back Slots.
2. Route wiring going to the keypad through the large rectangular opening in the case back.
3. Mount the case back to the wall or electrical box.
4. Wire directly from the keypad’s terminal block (see Figure
2) to the terminal block on the control panel (see control’s Summary of Connections label for correct terminal connections).
NOTE: No more than one wire per terminal may be connected. If daisy­chained configuration is required, pig-tail wires together so that only one wire is terminated under the screw. Use 16-24 AWG wire only!
TABLE 1 - Wiring Table
Terminal Description Wire Color
Y Keypad Data In Yellow + + Aux. Pwr Red – – Aux Pwr (GND) Black G
Keypad Data Out Green
5. Reattach the keypad to its case back. Attach the top of
the keypad first, then press the bottom section down until it snaps into place securely.
Display
Special
Function
Keys
A
B
xxxxxx
xxxxxx
xxxxxx
xxxxxx
xxxxxx
xxxxxx
xxxxxx
Case Back
Slot 3
C
D
Slot 1
Slot 2
Figure 1 – Removing the Case Back
FA570CR-001-V0
Page 2
BLACK
RED
+
YG
+
+
+
+
+
+
+
+
6160CR-004-V1
Figure 2 – FA570CR Wiring Details
SETTING THE KEYPAD ADDRESS
The keypad address must be set according to the control panel being used (refer to the individual control panel’s instructions for details). Available addresses are 00 through 30. The keypad is shipped with a default address of 31 (non-addressable mode). To change the address, do the following:
1. Enter keypad address mode: Power up the keypad. Within 60 seconds of power-up, press and hold down the [1] and [3] keys together for 3­seconds. The current address will be displayed and the cursor will be under the “tens” digit (3
1).
Notes:
If the system has been powered up for more than 60
seconds, you must power the keypad down, and then power it up again in order to change the keypad’s address.
The keypad will not enter the address mode if the
system is in the program mode.
If 10 seconds have passed with no key entry, the keypad
automatically exits the address mode.
FOR WARRANTY INFORMATION AND LIMITATIONS OF THE ENTIRE SYSTEM, REFER TO THE INSTALLATION INSTRUCTIONS FOR THE CONTROL PANEL WITH WHICH THIS DEVICE IS USED.
2. Set the desired address: Enter the desired address. For example, for address 12, enter 1, then 2. Display shows (12).
3. Exit the address mode: Press the “star” key (
✻) to save the displayed address
and exit the address mode. The current address may be viewed at any time by pressing and holding [1] and [3] keys together.
KEYPAD LABELS
Function key labels: A set of adhesive-backed labels with some typical function symbols (e.g., fire, police, emergency, etc.) is provided. These labels come in four colors (red, blue, green, and white) and may be placed on the appropriate function keys (A, B, C, or D) for ease of identifying the individual key’s function (as determined by the control panel’s capability and programming).
OPERATING THE KEYPAD
For operating instructions, see the User Guide for the control panel used with this keypad.
SPECIFICATIONS
Physical: 5.25” H x 7.437” W x 1.312” D
Display: Alphanumeric, 32-character (2 lines x 16
characters), LCD back-lit
LEDs: ARMED (red), READY (green), POWER
(green), FIRE ALARM (red) *SUPER­VISORY (yellow) and *TROUBLE (yellow)
* Refer to the control panel’s instructions
for specific applications regarding Trouble and Supervisory LEDs.
Sounder: High-quality speaker Electrical: Voltage: +12VDC (from power-limited
source) Current: 50mA standby;
160mA in alarm (sounder, back
light and LEDs on)
NFPA-72 Compliant
ÊK14030-2CFwŠ
K14030-2CF 9/08 Rev. B
2 CORPORATE CENTER DRIVE, MELVILLE, NY 11747
www.firstalertprofessional.com
Copyright © 2009 Honeywell International Inc.
Loading...