K3590-OM 4/01
FA260KP-OM, FA560KP-OM
REMOTE KEYPADS
INSTALLATION INSTRUCTIONS
The FA260KP-OM and FA560KP-OM are addressable remote keypads intended for use with the FA408C and
FA848C control panels. They have the following features:
•
Option for continuous or timed backlit display
•
Dedicated Function Keys
•
Built-in Sounders
•
Keypad addresses set via the keypad keys (no DIP switches required).
KEYPAD DISPLAYS AND LEDs
The keypads have the following display features:
Model
FA260KP-OM
FA560KP-OM* X X
Use the FA560KP-OM with the red color insert (provided for fire
*
installations) as required by the local authority having jurisdiction.
Fixed-Word
Display
XX
2-Line Alpha
Display
2-Digit Zone
Identifier
Custom Zone
Descriptors
The following table shows the LEDs and their functions:
LED Function
Red Lights when the system is armed in any mode.
Green
Lights when the system is "ready" to be armed.
TURNING BACKLIGHT TIMER ON and OFF
FA260KP-OM
Press and hold down the INSTANT and CODE keys at the
same time for about three seconds.
Press the [1] key that toggles a zero or one in the display:
0 = Backlight always on
1 = Backlight on a 120-second timeout.
✱
Press [
] key to exit this Backlight menu.
FA560KP-OM
Press and hold down the INSTANT and CODE keys at the
same time for about three seconds.
Press the [1] key to toggle the display between:
0 = Backlight always on
and
1 = Backlight on a 120-second timeout.
WIRING AND INSTALLATION
The keypads can be surface-mo unted directly to a drywall, o r
to a single- or double-gang electical box.
Remove the case back
1.
tabs. Pry apart the case back as each tab is depressed.
See diagram below.
Route wiring from the control panel
2.
opening in the case back.
Mount the case back
3.
Wire directly
4.
from the keypad’s terminal block to the
terminal block on the control panel (see control’s
Summary of Connections label for correct terminal
connections).
Wiring Table (all Keypads)
Keypad Control Panel Terminals
DO GRN
RED
−
BLK
DI YEL
by pushing against each of two
through the
to a wall or electrical box.
✱
Press [
] key to exit this Backlight menu.
Remove case back by pushing in
the 2 tabs along keypad's bottom
edge and pulling case apart.

SETTING THE KEYPAD ADDRESS
The keypad can be set for an address of 1-8. The keypad's
default address is 8.
To change the keypad's address, do the following:
Enter Address mode: Power up the keypad. Within 60
1.
seconds of power-up, press and hold down the Stay and
Code keys at the same time for 3 seconds. (If unable to
enter Address mode, power up and try again.)
The current keypad address will be displayed. If 10
seconds have passed with no key entry, the keypad
automatically exits Address mode. If this happens, you
must power down, power up and enter Address mode
again.
2. If the panel does not send a valid command to the
keypad, the display will remain blank.
3. Exit Address mode:
Press [✱] to save the displayed address and exit Address
mode.
USING THE SOUNDER MENU (FA560KP-OM only)
1. Press the BYPASS and CODE keys at the same time
and hold down for two seconds. This accesses the
Sounder Menu.
2. Press the [1] key to toggle through the four modes listed
above (stop at desired mode).
3. Press the [2] key to toggle through the sounder volume
choices (high or low appears on the display).
4. Press the [3] key to adjust the sound of the key acknowledge (Ack H or L appears on the display).
5. Press the
[✱] key to exit the Sounder Menu.
SPECIFICATIONS
Physical:
FA260KP-OM: 6-5/8'H x 4-7/8"W x 1-5/16"D
FA560KP-OM: 7-5/16'H x 5-3/8"W x 1-3/8"D
VIEWING THE KEYPAD ADDRESS
Press and hold down the STAY and CODE keys at the
same time for about 3 seconds. The current address is
displayed. No ke y entry i s al lo we d. Pres s an y key to e xi t or
wait 10 seconds to exit viewing mode.
TURNING THE SOUNDER ON/OFF
FA260KP-OM:
Press the BYPASS and CODE keys at the same time
and hold down for two seconds until you hear a beep.
Press any key to toggle the sounder on or off.
0 = Sounder off
1 = Sounder on.
FA560KP-OM
There are four modes available in the Sounder Menu. They
are as follows:
• Off – No Sounds at all
• Key – Only Key Clicks
• Fire – Only Fire Sounder (temporal sounder – not
supported by all panels)
•
On – Normal Sounder Keys (all sounds on)
REFER TO INSTALLATION INSTRUCTIONS FOR THE CONTROL PANEL WITH WHICH THIS DEVICE IS USED FOR
:
WARRANTY INFORMATION AND LIMITATIONS OF THE ENTIRE ALARM SYSTEM.
Displays:
FA260KP-OM: Fixed-Word LCD (backlit)
FA560KP-OM: 2 x 16 alphnumeric LCD (backlit)
Sounder:
FA260KP-OM: Speaker
FA560KP-OM: Speaker
Current:
FA260KP-OM: 150mA (backlight and sounder on).
75mA standby mode (backlight on)
FA560KP-OM: 150mA (backlight and sounder on).
80mA standby mode (backlight on)
¬.20Al
K3590-OM 4/01
175 Eileen Way, Syosset, New York 11791
C