Thank you for choosing BRK Brands, Inc. for your Smoke Alarm needs.
You have purchased a state-of-the-art Smoke Alarm designed to provide
you with early warning of a fire.
Key features include:
Smart Technology
Single Button Test/Silence eliminates confusion. Depending on what
mode the alarm is in, pushing the button pr
as testing the alarm, silencing the alarm, re-testing the alarm when in
silence and clearing the Latching feature.
Latching Alarm Indicator easily identifies initiating alarm even after the
alarm condition has subsided.
Perfect Mount System includes a gasketless base for easy installation and
a new mounting bracket that keeps the alarm secure over a wide rotation
range to allow for perfect alignment.
Dust Cover is included to keep the alarm clean during construction.
Easy Installation/Maintenance features include a large opening in the
mounting bracket for easy access to wiring. A battery pull tab keeps the
esh until the home is occupied. A Side Load Battery Drawer allows
battery fr
for easy battery r
wall (Model 9120B only).
Improved UV Resistance keeps the alarm from discoloring over time.
designed to help reduce unwanted or nuisance alarms.
ovides different functions such
eplacement without r
emoving the alarm fr
om the ceiling or
Models 9120
9120B
.
All First Alert®and BRK®Smoke Alarms conform to regulatory
equirements, including UL217 and are designed to detect particles of
r
combustion. Smoke particles of varying number and size are produced
in all fires.
Ionization technology is generally more sensitive than photoelectric
technology at detecting small particles, which tend to be produced
in greater amounts by flaming fires, which consume combustible
materials rapidly and spread quickly. Sources of these fires may include
paper burning in a wastebasket, or a grease fire in the kitchen.
Photoelectric technology is generally more sensitive than ionization
technology at detecting large particles, which tend to be produced in
greater amounts by smoldering fires, which may smolder for hours
before bursting into flame. Sources of these fires may include cigarettes
burning in couches or bedding.
For maximum protection, use both types of Smoke Alarms on each level
and in every bedroom of your home.
FIRE SAFETY TIPS
Follow safety rules and prevent hazardous situations: 1) Use smoking
materials properly. Never smoke in bed. 2) Keep matches or lighters away from
children; 3) Store flammable materials in proper containers;
4) Keep electrical appliances in good condition and don’t overload electrical
cuits; 5) Keep stoves, barbecue grills, fir
cir
debris-free; 6) Never leave anything cooking on the stove unattended;
7) Keep portable heaters and open flames, like candles, away from flammable
materials; 8) Don’t let rubbish accumulate.
Keep alarms clean, and test them weekly
are not working properly. Smoke Alarms that do not work cannot alert you to
a fire. Keep at least one working fire extinguisher on every floor, and an additional one in the kitchen. Have fire escape ladders or other reliable means of
om an upper floor in case stairs are blocked.
escape fr
eplaces and chimneys gr
. Replace alarms immediately if they
ease- and
BEFORE YOU INSTALL THIS SMOKE ALARM
IMPORTANT! Read “Recommended Locations for Smoke Alarms” and
“Locations to Avoid for Smoke Alarms” before beginning. This unit monitors
the air
, and when smoke reaches its sensing chamber, it alarms. It can give
e time to escape befor
you mor
early warning of developing fires if it is installed, maintained and located
where smoke can reach it, and where all residents can hear it, as described
in this manual. This unit will not sense gas, heat, or flame. It cannot prevent
or extinguish fir
Understand The Different Type of Smoke Alarms
Battery powered or electrical? Different Smoke Alarms provide
different types of protection. See “About Smoke Alarms” for details.
Know Where To Install Your Smoke Alarms
Fir
level of your home, in every bedr
separate sleeping area. See “Recommended Locations For Smoke Alarms”
and “Locations To Avoid For Smoke Alarms” for details.
Know What Smoke Alar
A Smoke Alarm can help alert you to fire, giving you precious time to
escape. It can only sound an alarm once smoke reaches the sensor. See
“Limitations of Smoke Alarms” for details.
Check Your Local Building Codes
This Smoke Alarm is designed to be used in a typical single-family home.
It alone will not meet requirements for boarding houses, apartment buildings,
hotels or motels. See “Special Compliance Considerations” for details.
1
es.
e Safety Professionals recommend at least one Smoke Alarm on every
ms Can and Can’
eads. This unit can ONLY give an
e spr
e fir
oom, and in every bedr
t Do
oom hallway or
1
2
3
5
6
4
2
3
9
7
8
BEFORE YOU INSTALL THIS SMOKE ALARM, Continued
ELECTRICAL SHOCK HAZARD. Turn off the power to the area where the
Smoke Alar
Failur
injury or death.
m is installed before removing it from the mounting bracket.
e to turn off the power first may result in serious electrical shock,
•
This unit will not alert hearing impaired residents. It is recommended
that you install special units which use devices like flashing str
lights to aler
•
Installation of this unit must confor
area; Articles 210, 760 of NFPA 70 (NEC), NFPA 72, NFPA 101; ICC;
SBC (SBCCI); UBC (ICBO); NBC (BOCA); OTFDC (CABO), and any
other local or building codes that may apply
must be performed by a licensed electrician. Failure to follow these
guidelines may r
This unit must be powered by a 24-hour, 120V AC pure sine wave
•
60 Hz circuit.
dimmer, or ground fault circuit interrupter. Failure to connect this unit
to a 24-hour cir
Unit may be connected to an arc fault circuit interrupter.
•
This Smoke Alarm must have AC or battery power to operate.
If the AC power fails, battery back-up will allow the alarm to sound
for at least 4 minutes. If AC power fails and the batter
protection should last for up to 7 days. If AC power fails and the
battery is dead or missing, the alarm cannot operate.
•
Never disconnect the power from an AC powered unit to stop an
unwanted alar
protection. In the case of a true unwanted alarm open a window or
fan the smoke away fr
when it r
a batter
smoke, etc.). Instead open a window or fan the smoke away from the
unit. The alar
•
Connect this unit ONL
Install This Smoke Alarm” for details. Do not connect it to any other
type of alarm or auxiliary device. Connecting anything else to this unit
may damage it or prevent it from operating properly.
• The battery compartment resists closing unless a battery is
installed. This warns you the unit will not operate under DC power
without a battery.
• Do not paint over the unit. Paint may clog the openings to the
sensing chamber and prevent the unit from operating properly.
t hearing impaired residents.
m to the electrical codes in your
. Wiring and installation
esult in injury or property damage.
Be sure the circuit cannot be turned off by a switch,
cuit may prevent it from providing constant protection.
y is weak,
m. Doing so will disable the unit and remove your
eturns to normal operation. Never remove the batteries from
y operated unit to stop an unwanted alarm (caused by cooking
om the unit. The alarm will reset automatically
m will reset automatically.
Y to other compatible units. See “How To
obe
HOW TO INSTALL THIS SMOKE ALARM
This Smoke Alarm is designed to be mounted on any standard wiring junction box to a 4-inch (10 cm) size, on either the ceiling or wall. Read “Recommended
Locations For Smoke Alarms” and “Locations to Avoid For Smoke Alarms” before you begin installation.
Tools you will need: • Needle-nose pliers or utility knife • Standard Flathead screwdriver.
Make sure the Alarm is not receiving excessively noisy power. Examples of noisy power could be major appliances on the same circuit, power from a
generator or solar power, light dimmer on the same circuit or mounted near fluorescent lighting. Excessively noisy power may cause damage to your
m.
Alar
TS OF THIS SMOKE ALARM
AR
THE P
The Mounting Bracket:
emove the mounting bracket fr
o r
T
Alarm base, hold the Smoke Alarm base firmly and
twist the mounting bracket counterclockwise.
The mounting bracket installs onto the junction box.
It has a variety of screw slots to fit most boxes.
The Power Connector:
The power connector plugs into a power input block on
the Smoke Alarm. It supplies the unit with AC power.
• The black wir
• The white wire is neutral.
• The orange wire is used for interconnect.
If you need to r
flat screwdriver blade between the power connector
and the security tab inside the power input block.
Gently pry back the tab and pull the connector fr
e is “hot.”
emove the power connector, insert a
om the Smoke
ee.
The Parts of This Unit
Mounting Bracket
1
2Mounting Slots
Locking Pins (br
3
eak out of bracket)
4Hot (Black) AC Wire
5Neutral (White) AC Wire
6Interconnect (Orange) Wire
7Latch to Open Battery Compartment
8Swing-Out Battery Compartment
Quick-Connect Power Connector
9
2
6
7
8
4
3
1
5
4
3
1
5
2
A
B
}
}
FOLLOW THESE INSTALLATION STEPS
The basic installation of this Smoke Alarm is similar whether you want
to install one Smoke Alarm, or interconnect more than one Smoke Alarm.
f you are interconnecting more than one Smoke Alarm, you MUST read
I
“Special Requir
you begin installation.
ELECTRICAL SHOCK HAZARD. T
will install this unit at the circuit breaker or fuse box before beginning
installation. Failur
in serious electrical shock, injur
Using wire nuts, connect the power connector to the household wiring.
1.
oper wiring of the power connector or the wiring leading to the
Impr
power connector will cause damage to the Alar
non-functioning Alarm.
STAND-ALONE ALARM ONLY:
• Connect the white wire on the power connector to the neutral wire
in the junction box.
Connect the black wire on the power connector to the hot wire in
•
the junction box.
• Tuck the orange wire inside the junction box. It is used for
inter
INTERCONNECTED UNITS ONL
Strip of
wire on the power connector.
• Connect the white wire on the power connector to the neutral wire
in the junction box.
Connect the black wire on the power connector to the hot wire in
•
the junction box.
•
Connect the orange wir
wire in the junction box. Repeat for each unit you are interconnecting.
Never connect the hot or neutral wires in the junction box to the orange
interconnect wire. Never cross hot and neutral wires between Alarms.
2. Remove the mounting bracket from the base, and attach it to the
junction box.
3. Plug the power connector into the back of the Smoke Alarm.
Position the base of the Smoke Alarm over the mounting bracket and
4.
turn. The Alarm will remain secure over a wide rotation range to allow for
perfect alignment. When wall mounting, this will allow fine-tuning on the
positioning to compensate for misaligned wall studs and to keep the
wording level. The Alarm can be positioned over the bracket every 120°.
Rotate the Alarm until aligned properly.
5. Check all connections.
STAND-ALONE ALARM ONLY:
• If you are only installing one Smoke Alarm, restore power to the
junction box.
INTERCONNECTED UNITS ONLY:
• If you are interconnecting multiple Smoke Alarms, repeat steps
1-5 for each Smoke Alarm in the series. When you are finished,
restore power to the junction box.
ements For Interconnected Smoke Alarms” below before
urn off power to the area where you
e to turn off the power before installation may result
y or death.
m and may lead to a
connect only.
Y:
f about 1/2” (12 mm) of the plastic coating on the orange
e on the power connector to the interconnect
9. For new construction, place supplied dust cover over Alarm to prevent
damage fr
plete, r
Smoke will not be able to r
Cover must be removed!
om dust and construction debris. When construction is com-
emove cover.
each smoke sensor while cover is in place.
SPECIAL REQUIREMENTS FOR INTERCONNECTED SMOKE ALARMS
Failure to meet any of the above requirements could damage the
•
units and cause them to malfunction, removing your protection.
AC and AC/DC Smoke Alarms can be interconnected. Under AC
•
, all units will alarm when one senses smoke. When power is
power
interrupted, only the AC/DC units in the series will continue to send
eceive signals. AC powered Smoke Alarms will not operate.
and r
Interconnected units can provide earlier warning of fire than stand-alone units,
especially if a fir
series senses smoke, all units will alarm. To determine which Smoke Alarm
initiated an alarm, see table:
During an Alar
On Initiating Alarm(s)
e starts in a remote area of the dwelling. If any unit in the
m:
Red LED(s) flashes (flash) rapidly
On All Other Alarms Red LED is Off
After an Alarm (Latching):
On Initiating Alarm(s)
Green LED(s) On for 2 seconds/Off for 2 seconds
On All Other Alarms Green LED(s) On, Red LED(s) is Off
Compatible Interconnected Units
Interconnect units within a single family residence only. Otherwise all households will experience unwanted alarms when you test any unit in the series.
Interconnected units will only work if they are wired to compatible units and
all requirements are met. This unit is designed to be compatible with:
First Alert®Smoke Alarm Models SA4120, SA4121B, SA100B and BRK
Electronics®Smoke Alarm Models 9120, 9120B, SC6120B, SC9120B, 7010,
Interconnected units must meet ALL of the following requirements:
• A maximum of 18 compatible units may be interconnected
(Maximum of 12 Smoke Alarms).
• The same fuse or circuit breaker must power all interconnected units.
• The total length of wire interconnecting the units should be less than
1000 feet (300 meters). This type of wire is commonly available at
Hardware and Electrical Supply stores.
All wiring must conform to all local electrical codes and NFPA 70 (NEC).
•
Refer to NFPA 72, NFPA 101, and/or your local building code for further
connection r
equirements.
®
ELECTRICAL SHOCK HAZARD. Do not restore power until all Smoke
Alarms are completely installed. Restoring power before installation is
complete may r
Make sur
6.
operation, the Green power indicator light will shine continuously.
7. If the Green power indicator light does not light, TURN OFF POWER TOTHE JUNCTION BOX and recheck all connections. If all connections
e corr
ar
estore the power, the unit should be replaced immediately.
r
Single Station Alarms: Test each Smoke Alarm. Press and hold the
8.
Test/Silence button until the unit alarms.
Interconnected Alarms: Press and hold the Test/Silence button until
the unit alarms. All inter
Alarms sounding only tests the interconnect signal between Alarms.
It does not test each Alarm’s operation. You must test each Alarm
individually to check if the Alar
If any unit in the series does not alarm, TURN OFF POWER and r
connections. If it does not alarm when you r
immediately.
esult in serious electrical shock, injur
e the Smoke Alarm is r
ect and the Gr
een power indicator still does not light when you
eceiving AC power
connected Alarms should sound. The other
m is functioning pr
estor
y or death.
. Under normal
e power
.
operly
, replace it
echeck
Unswitched 120V
A.
60 Hz source
1. Smoke Alarm
2. Ceiling or Wall
3. Power Connector
AC
B. To additional units; Maximum = 18 total
(Maximum 12 Smoke Alarms)
4. Wire Nut
5. Junction Box
6. Neutral Wire (Wht)
7. Interconnect Wire
(Orange)
Hot Wir
8.
e (Blk)
3