First Aquatherm Series Installation And Application Manual

®
Aquatherm
INSTALLATION AND APPLICATION MANUAL
FOR
AQUATHERM
COMBO HEATERS
®
FIRST CO. - P.O. BOX 270969 - DALLAS, TEXAS 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.firstco.com
1
Page Introduction 3
Table of Contents
Sequence of Operation
General Description:
Air handler cabinet 3 Heating and cooling coils 3 Add-on hot water coil 3 Circulating pump 3 Flow control module 3 Check valve 3 Air purge valve 4 Blower door safety switch 4 Water heater 4 Boiler 4
Accessories: Thermostat 4
Freeze protector 4
Equipment Sizing:
Condensing unit 4 Air handler 4 Water heater 5
3
Installation:
Duct work 5 Electrical 5 Water piping 6
1. Material 6
2. Solder connections 6
3. Insulation 6
4. Length 6
5. Shut-off valves 6
6. Piping connections 6,8-10 Air handler 6 Flow control module 6 Water heater 6 Multiple water heaters 7 Anti-scald valve 7
Start-up Procedure (heating cycle)
Troubleshooting 12
7
2
The Aquatherm® is a First Co. air handler that converts a properly sized gas or oil-fired water heater into a highly efficient, dual - purpose appliance that can heat your home as well as provide hot water for domestic purposes.
Any properly sized water heater (for heating) and split system type condensing unit (for cooling) will work with First Co. Aquatherm® air handlers and are to be supplied by others. NO SPECIAL WATER
HEATER IS REQUIRED!
Aquatherm® air handlers are even compatible
with boiler systems.
Aquatherm® air handlers include a fan motor for
air circulation, hot water circulating pump, hot water heating coil, air purge valve, check valve, compo­nents for low voltage control and most include a cooling coil for air conditioning. All components in the water piping meet NSF61 and/or california AB1953 requirements.
SEQUENCE OF OPERATION
(Heating mode)
When space heating is needed, the wall thermostat energizes a small pump which circulates hot water (135 to 140 degrees ) from the water heater to the hot water coil in the air handler. As the fan motor forces the cool return air from the home over the hot water coil, the air absorbs heat from the hot water and this warm air (about 105 to 110 degrees) is then circulated throughout the duct system and into the home.
IMPORTANT. . . . . in most applications the water will
lose only 15 to 25 degrees in temperature while cir­culating through the hot water coil and will RETURN to the water heater at about 115 to 125 degrees to be reheated.
Add - on hot water coil: First Co. HWC series add-on hot water coils are designed to be installed in either existing or new duct work and operate in conjunction with the existing fan motor to provide complete or supplemental space heating from a gas or oil - fired water heater. These coils are completely cased and utilize the separate “flow control module” which can be installed at the water heater for easy access and service (see “flow control module”).
Circulating pump: All circulating pumps circulate water at a rate of 3 to 6 gallons per minute and are either factory installed or included as part of the field installed “flow control module”. These pumps are designed to circulate a precise amount of hot water between the water heater and air handler or add - on coil.
Flow control module: This U.L. Listed device con sists of the circulating pump, check valve, air purge valve, 6' plug - in line cord and pump relay. The module is sold & shipped separately with HWC add
- on hot water coils. The module can be field installed anywhere in the hot water heating loop between the water heater and hot water coil and offers the advan­tage of being able to install the pump assembly in the most appropriate location for service and main­tenance. Modules must be installed with the motor in a horizontal position. Junction box should not be located underneath the pump.
FLOW CONTROL MODULE - WIRING DIAGRAM
-
GENERAL DESCRIPTION
Air handler cabinet: Air handlers with cabinets are
made of galvanized steel and fully insulated to reduce noise and maximize efficiency. Throwaway filters are factory installed in most air handlers.
Heating and cooling coils: All heating and cooling coils are made of copper tubes with mechanically bonded aluminum fins for maximum heat transfer. Manual air vents are included on all hot water coils. Cooling coils have either piston - type metering de vices or field installed expansion valves. Primary and secondary condensate drain connections are provided on each cooling coil. All primary connections are 3/4 inch MPT.
-
Check valve: A check valve is factory installed in the hot water loop to eliminate any thermosyphoning (hot water circulating through the heating coil) while operating in the cooling mode. The check valve is installed within the air handler or as part of the “flow
3
control module”. Air purge valve: All air handlers and / or “flow control modules” include a large manual air purge valve to facilitate air removal from the heating loop prior to system start - up. When the air handler and water heater are piped according to First Co. instructions, the air in the hot water coil and piping will only need to be removed before initial start - up or after air has gotten into the system because of a plumbing leak or break in a water main. This can be accomplished by using the 2 - step process described under “start
-up procedure”.
Blower delay relay: FWA-HW,HBXB-HW,HBQB,UC­HW and UCQB series air handlers include a blower delay relay that allows the circulating pump to operate on a call for heat for 20 to 45 seconds motor comes on to deliver warm air quicker when the heating system starts. This relay also keeps the fan motor on for 20 to 45 seconds after the thermostat is satisfied in the heating cycle to maximize the ef­ficiency of the heating coil.
before the fan
All other air handlers require a 24 volt thermostat that energizes the fan motor on a requirement for cool ing and heating. This is commonly called an "electric
heat" thermostat. CAUTION . . . . . a gas furnace
thermostat will NOT work with these units because the fan motor will not come on when the thermostat calls for heat. Normal heat anticipator setting should be 0.3 to 0.4. If a set-back thermostat is used, allow extra time for recovery in the morning.
Freeze protector: Kit number 941-1 can be field installed on any Aquatherm® air handler or add -on coil and is highly recommended when the air handler or hot water coil is installed in a space that may be subjected to freezing temperatures such as in an attic or crawl space. The sensor attaches to the hot water coil and is wired to R and W in the low voltage circuit. If for any reason the temperature of the hot water coil falls below 38 degrees the sensor will bring on the pump to circulate hot water. This will occur even if the thermostat is in the "off" position.
-
Flue gas safety switch: All "Q" type air handlers, as well as FWA-xx series air handlers, include a factory installed flue gas safety switch (except 5 ton models). When the blower door is removed for any reason the air handler fan motor will not operate. This is especially important when the water heater is in the same closet as the air handler because products of combustion from the water heater flue pipe could be circulated throughout the duct system if the air handler were allowed to operate without the door in place.
Water Heater: Any properly sized gas or oil - fired water heater will work ( even direct vent or powered vent types ). Electric water heaters are not recom mended because of their slow recovery rate. Water heater warranties are not affected by this system since no modification of the water heater is necessary. Selection of higher efficiency water heaters will result in even greater savings.
Boiler: Most First Co. and add - on hot water coils are also compatible with boilers and instantaneous water heaters. Please con­tact the factory for assistance in selecting the proper equipment for these applications. (See Page 10 for wiring diagram of multiple air handlers.)
Aquatherm® air handlers
EQUIPMENT SIZING
Condensing unit: The condensing unit should be
sized to meet the calculated heat gain according to an approved heat gain formula. Air handler: Select an air handler with a heating BTUH that exceeds the structure's calculated heat loss and a cooling coil matched to the tonnage size of the outdoor condensing unit.
Special note . . . . . the actual heating output of the
air handler (BTUH) will not be greater than the heating output of the water heater (water heater BTUH input multiplied by it's recovery efficiency) regardless of the listed heating BTUH of the air handler.
-
ACCESSORIES
Thermostat: All "Q" type air handlers will operate
with any standard 24 volt heat / cool or heat pump thermostat.
Water heater: Add 10 to 20% to the structure's heat loss to obtain the minimum output of the required water heater (output = input x recovery efficiency). A minimum 40 gallon high recovery and / or high ef­ficiency gas or oil-fired water heater is recommended. In addition to the above formula, the following vol-
4
Loading...
+ 8 hidden pages