Fireye BLPS-25, BLPS-30, BLPS-15, BLPS-200, BLPS-300 User Manual

...
®
WARNING: The PPC4000 Fuel Air ratio Controller and BurnerLogix Control System must only be used with the approved pressure and temperature sensors. (e.g.: BLPS-15, TS350-4, etc.). Do not use with any other types of pressure or tem­perature sensors. UL approval requires these sensors.
TS350
TS752
BLPS
NOVEMBER 19, 2013
BLZPTS-1
PRESSURE AND
TEMPERATURE
SENSORS
for use with the
BURNERLOGIX
Burner Management
System and
PPC4000 Series
Fuel/Air Ratio
Controller
DESCRIPTION
The BLPS, TS350 and TS752 Series of pressure and temperature sensors are designed for use with the PPC4000 Fuel Air Ratio Controller and BurnerLogix Burner Management System with Integrated Boiler Control.
The pressure sensors (P/N BLPS-x) utilize a solid state pressure transducer to indicate steam pressure. The temperature sensors (P/N TS350-x and TS752-x) utilize a platinum, positive temperature coefficient sensing element to provide indication of water tempera­ture, stack temperature, boiler water temperature of a steam boiler, and outdoor air temper­ature. The pressure sensors have a maximum overpressure specification of 200% Full Scale Output and 800% Burst. The pressure sensors are equipped with a 1/4" NPT male fitting. The Immersion Style Temperature Sensors have a 1/2" NPT mounting for the 2", 4" and 8" thermowell probe.
The pressure and temperature sensors provide a 4-20 mA control signal over their respec­tive stated ranges to the PPC4000 and BurnerLogix Control systems. No setting or calibra­tion is required for either type of sensor.
The PPC4000 and BurnerLogix Control systems perform continuous safety checks on the operation of all pressure and temperature sensors to insure their safe and proper operation (e.g. under range, over range, open wiring, etc.).
1
Fireye P/N Description
BLPS-15 Pressure transducer, 0 to 15 psi (0 to 1030 mb), 4-20 mA output linear with pressure. ¼" NPT mount-
ing. Screw terminal connections and conduit adapter cover.
BLPS-25 Pressure transducer, -14.7 to 25 psi (-1013 to 1720 mb), 4-20 mA output linear with pressure. ¼" NPT
mounting. Screw terminal connections and conduit adapter cover.
BLPS-30 Pressure transducer, 0 to 30 psi (0 to 2070 mb), 4-20 mA output linear with pressure. ¼" NPT mount-
ing. Screw terminal connections and conduit adapter cover.
BLPS-200 Pressure transducer, 0 to 200 psi (0 to 13.8 Bar), 4-20 mA output linear with pressure. ¼" NPT mount-
ing. Screw terminal connections and conduit adapter cover.
BLPS-300 Pressure transducer, 0 to 300 psi (0 to 20.7 Bar), 4-20 mA output linear with pressure. ¼" NPT mount-
ing. Screw terminal connections and conduit adapter cover.
TS350-2 Temperature sensor, Range 32°F to 350°F (0°C to 176°C), 4-20 mA output, linear with temperature.
Insertion length is 2 inches. Stainless steel thermowell included with ½"-14 NPT mounting.
TS350-4 Temperature sensor, Range 32°F to 350°F (0°C to 176°C), 4-20 mA output, linear with temperature.
Insertion length is 4 inches. Stainless steel thermowell included with
TS350-8 Temperature sensor, Range 32°F to 350°F (0°C to 176°C), 4-20 mA output, linear with temperature.
Insertion length is 8 inches. Stainless steel thermowell included with ½"-14 NPT mounting.
TS752-2 Temperature sensor, Range 32°F to 752°F (0°C to 176°C), 4-20 mA output, linear with temperature.
Insertion length is 2 inches. Stainless steel thermowell included with
TS752-4 Temperature sensor, Range 32°F to 752°F (0°C to 176°C), 4-20 mA output, linear with temperature.
Insertion length is 4 inches. Stainless steel thermowell included with ½"-14 NPT mounting.
TS752-8 Temperature sensor, Range 32°F to 752°F (0°C to 176°C), 4-20 mA output, linear with temperature.
Insertion length is 8 inches. Stainless steel thermowell included with ½"-14 NPT mounting.
Note: BLPS-25 is not compatible with the Burnerlogix Control System
GENERAL SPECIFICATIONS
½"-14 NPT mounting.
½"-14 NPT mounting.
Temperature Sensors:
Temperature Measurement Range:
RTD Type: Platinum, 100 ohms +-0.1% @32°F (0°C) Temperature Coefficient: .00385 ohms/ohms/C Output: 4-20 mA, linear with temperature Operating Temperature Range: -13°F to 185°F (-25°C to 85°C) Accuracy: +/- 0.75% of span Thermowell Case: 300 Series stainless steel Mechanical Fittings: 1/2-14 NPT
Pressure Sensors:
Pressure Measurement Range: 0 to 15, -14.7 to 25, 0 to 30, 0 to 200, 0 to 300 psig Excitation Voltage: 9-30Vdc (supplied by BurnerLogix control) Accuracy: +/- 0.25% Full Scale (at constant temperature) Output: 4-20 mA, linear with pressure Maximum Over Pressure: 200% of full scale Maximum Burst Pressure: 800% of full scale Operating Temperature Range: -40°F to 185°F (-40°C to 85°C) Fitting: 1/4" NPT Male Electrical: 1/2" Conduit and Terminal Strip
TS350-X: 32°F to 350°F (0°C to 176°C) TS752-X: 32°F to 752°F (0°C to 400°C)
2
APPROVALS
Underwriters Laboratories Inc.:
MCCZ File MP1537 Controls, Primary Safety - Listed MCCZ2 File MP1537 Controls, Primary Safety - Component MCCZ7 File MP1537 Controls, Primary Safety Certified for Canada MCCZ8 File MP1537 Controls, Primary Safety Certified for Canada - Component
Factory Mutual: FM Class 7610 Acceptable by: Industrial Risk Insurers (I.R.I.)
FIGURE 1. Pressure Sensor - BLPS-15, -25, -30, -200, -300
®
GND
COM
OUT
EXC
3
FIGURE 2. Temperature Sensor - TS350-2, TS350-4, TS350-8
0.625”
X = 2”, 4” or 8”
11.0” [279]
7.5” [191]
WARNING:
1. Read these instructions carefully. Failure to follow them could result in a hazardous or
dangerous condition.
2. Insure that the range of the selected sensor is appropriate for the application. Note: A
general rule to follow when selecting the sensor range is that the expected value of the monitored pressure or sensor shoul d f all between 40-70% of the upper range of the sensor. For example, a steam boiler maintains 20 lbs. pressure, select the BLPS-30 Pressure Sensor, with a 0-30 PSIG range
3. The sensors must be located where the ambient temperature will not exceed the maximum
ambient operating temperature specified for the sensor.
4. Insure that the pressure range programmed on the BurnerLogix Boiler Room Control
matches the installed pressure sensor. Refer to Bulletin BLZ-1001.
5. Do not mount any of the sensors where they could be used as a footstep.
FIGURE 3. Temperature Sensor - TS752-2, TS752-4, TS752-8
4
6. Installation must be performed by a trained, experienced flame safeguard technician.
FIGURE 4.
WARNING: The electro-mechanical high steam limit and/or high hot water temperature limit MUST REMAIN in the running interlock circuit of the flame safeguard control.
STEAM PRESSURE
OR HOT WATER SENSOR
ELECTRO-MECHANICAL
HIGH LIMIT
(STEAM OR WATER)
®
MOUNTING PRESSURE SENSORS
Note: Refer to Figure 4.
1. The steam pressure sensors (BLPS-15, -25, -30, -200, -300) provide a 1/4” NPT male fitting for
connection to the steam header. Included is a 1/4” coupling.
2. Make sure the boiler is shut down and zero steam pressure exists in the boiler vessel.
3. Disconnect power to the boiler controller so the boiler cannot sequence during installation of the
steam pressure sensor.
4. Always mount the steam pressure sensor above the water line of the boiler.
5. Locate the pressure sensors where the ambient temperature will not exceed 185F
6.
Although the unit can withstand substantial vibration without damage or significant output effects, it is good practice to mount the pressure sensor where there is minimum vibration.
7. A steam trap (siphon loop) must be connected between the boiler and the pressure sensor to pre-
vent boiler scale and corrosive vapors from affecting the pressure sensor element.
8. Use only a small amount of pipe compound to seal the connection joints. Excess pipe compound
may clog the fitting and prevent proper operation of the sensor.
9. Make all pipe connections in accordance with approved standards.
10. When tightening the sensor, apply a wrench to the hex flats located just above the pressure fit-
ting.
DO NOT tighten by using a pipe wrench on the housing. Do not tighten the pressure sensor
by hand.
MOUNTING TEMPERATURE SENSORS
The immersion style temperature sensors have a ½" NPT mounting for the 2", 4" and 8" thermowell probes, and a ½" conduit fitting.
HOT WATER
Note: Refer to Figure 4
1. Disconnect power to the boiler controller so the boiler cannot sequence during installation of the
hot water temperature sensor.
2. The thermowell must be mounted where it is always exposed to the circulation of the hot water
3. If the water system is full, drain the system below the point where the thermowell will be
installed.
4. Tap an appropriate size fitting. (2", 4" and 8" thermowell have ½"NPT fitting).
5. Insert the appropriate thermowell (2", 4", or 8") and tighten.
6. Fill the system to check for leakage.
5
LEAD/LAG OPERATION: When two hot water boilers are set-up for lead/lag operation, a hot
WARNING: Location of the temperature sensor to monitor boiler water temperature of a steam boiler is critical. The sensor should be mounted where it is always exposed to the cir­culation of the boiler water, not too close to a hot or cold inlet or steam coil. Consult the boiler manufacturer for guidance on the sensor location.
water temperature sensor must be installed for each boiler.
STANDBY WATER TEMPERATURE
1. Disconnect power to the boiler controller so the boiler cannot sequence during installation of the
standby temperature sensor.
2. The thermowell must be mounted where it is always exposed to the circulation of the hot water.
3. If the water system is full, drain the system below the point where the thermowell will be
installed.
4. Tap an appropriate size fitting (2", 4" and 8" thermowells have 1/2" NPT fitting).
5. Insert the appropriate thermowell (2", 4", or 8") and tighten.
STACK TEMPERATURE
1. Use the existing well connection for the stack temperature sensor if provided by the boiler man-
ufacturer.
2. If no well connection is provided, select an appropriate lo cation for mounting the temperature
sensor. Preferably as close to the boiler outlet as possible.
OUTDOOR AIR TEMPERATURE
1. The outdoor air temperature sensor should be mounted on the outside of the building where it
will be exposed to representative air temperature, but not to direct sunlight. A sun shield may be required.
2. Mount the temperature sensor high enough so it cannot be covered with snow, leaves, or other
debris, or be tampered with. Vents from the building should be avoided.
6
WIRING SENSORS
CAUTION: Disconnect power supply from the BurnerLogix Control before connecting wires to prevent electrical shock and equipment damage.
For 4-20 mA output, use + EXC and - COM terminals
COM
OUT
GND
EXC
4
312
For 4-20 mA output,
use terminals 1 (+) and 2 (-)
MINCO
Measurement Specialties
Temperature Specialists Inc.
For 4-20 mA output,
For 4-20 mA output,
use terminals (+) and (-)
use terminals 6 and 7
®
PRESSURE SENSORS
1. All wiring must be in accordance with National Electrical Code and local codes, ordinances, and
regulations.
2. Sensor housing provides connection for 1/2" conduit.
3. The pressure sensors require 2 conductor, 18 gauge, shielded cable. Power limited, rated for
300V @105C. Use Belden 9318 or equivalent.
4. The shield should be connected to the earth ground terminal on the wiring base of the Burner-
Logix Control (Terminal #E) or to the common ground established in the cabinet. The shield should be taped at the sensor to avoid unintended contact with the sensor housing.
5. All sensor wiring should be in a separate conduit. DO NOT install sensor wiring in any conduit
or junction boxes with high voltage wiring.
6. Maximum wiring distance for sensor wiring is 100 feet.
7. See Table 1 for wiring terminations to the Burnerlo gix
8. See T able 2 for wiring connections to the PPC4000.
TEMPERATURE SENSORS
1. All wiring must be in accordance with National Electrical Code and local codes, ordinances, and
regulations.
2. Sensor housing provides connection for ½" conduit.
7
3. The temperature sensors require 2 conductor, 18 gauge, shielded cable. Power limited, rated for
CAUTION: PROGRAM AND SET-UP The proper operation of the BurnerLogix System and the pressure and temperature sen-
sors requires that the selected pressure ranges are appropriate for the application and must match the pressure range programmed on the BurnerLogix Control. Insure that the range of the selected sensor is correct for the application and the pressure range pro­grammed on the BurnerLogix Integrated Flame Safeguard and Boiler Controller matches the installed pressure sensor. Refer to Bulletin BLZ-1001.
FIREYE
BLZPTS-1 3 Manchester Road NOVEMBER 19, 2013 Derry, New Hampshire 03038 USA Supersedes November 6, 2013 www.fireye.com
300V @105C. Use Belden 9318 or equivalent.
4. The shield should be connected to the earth ground terminal on the wiring base of the Burner-
Logix Control (Terminal #E) or to the common ground established in the cabinet. The shield should be taped at the sensor to avoid unintended contact with the sensor housing.
5. All sensor wiring should be in a separate conduit. DO NOT install sensor wiring in any co nduit
or junction boxes with high voltage wiring.
6. Maximum wiring distance for sensor wiring is 100 feet.
7. SeeTable 1 and 2 for wiring terminations.
Table 1: Burnerlogix wiring connections
TS350/TS752 BLPS PCV AUX1 AUX2
Minco Meas Sp Temp Sp BurnerLogix Terminals
1+ 1+ 6+ + EXC X (WHT/BLU) X (WHT/BLU) X (WHT/BLU)
2- 2- 7- - COM 11 (WHT/GRN) 22 (WHT/VIO) 23 (BRN/WHT)
Table 2: PPC4000 wiring connections
TS350/TS752 BLPS PCV AUX1 AUX2 SENS4 SENS5
Minco Meas Sp Temp Sp PPC4000 Terminals
1+ 1+ 6+ + EXC P11.2 P11.2 P11.3 P11.3 P11.3
2- 2- 7- - COM P11.10 P11.9 P11.8 P11.7 P11.6
NOTICE
When Fireye products are combined with equipment manufactu red by others and/or integrated into systems designed or manufactured by others, the Fireye warranty, as stated in its General Terms and Conditions of Sale, pertains only to the Fireye products and not to any other equip ment or to the combined system or its overall performance.
WARRANTIES
FIREYE guarantees for one year from the date of installation or 18 months from date of manufactur e of its products to replace, or, at its option, to repair any product or part thereof (except lamps and photocells) which is found defective in material or workmanship or which otherwise fails to conform to the description of the product on the face of its sales order. THE FOREGOING IS IN LIEU OF
ALL OTHER WARRANTIES AND FIREYE MAKES NO WARRANTY OF MERCHANT­ABILITY OR ANY OTHER WARRANTY, EXPRESS OR IMPLIED. Except as specifically
stated in these general terms and conditions of sale, remedies with respect to any product or part number manufactured or sold by Fireye shall be limited exclusively to the right to replacement or repair as above provided. In no event shall Fireye be liable for consequential or special damages of any nature that may arise in connection with such product or part.